1 UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE Prepared in cooperation and approval from BICSI Building Industry Consulting Services International and EIA/TIA Electronic Industries Association/Telecommunications Industry Association Revised 7/2015

2 INDEX SECTION CONTENTS PAGE 1. INTRODUCTION Responsibilities and Requirements 1.01 Contractor s experience Contractors Responsibilities Contractor s work with cable UND Telecommunications Responsibilities WORK AREA 2.01 Cable distance Cable raceway Outlet face plate Voice jacks Data jacks CATV jacks COMMUNICATIONS ROOMS 3.01 Size of communications room Lighting Cable management hardware Velcro ty-wraps ¾ plywood rack Electrical HVAC HORIZONTAL PATHWAY 4.01 Indoor Conduit Pull cord Distance between pull boxes Number of conduit bends Conduit bend radius Pull box placement Conduit Labeling Cable in ceiling Firestopping...3

3 5. HORIZONTAL CABLING 5.01 Cable distance Approved cable types Cable for wireless access points RISER CABLING 6.01 Topology Between communications rooms Approved cable types BACKBONE CABLING 7.01 Grounding Bonding through splice case Protectors NEC code for grounding CONNECTING HARDWARE 8.01 Patch Panels Copper termination at workstation jack Coax termination Multimode fiber termination Singlemode fiber termination ADMINISTRATION 9.01 Labeling...5 APPENDIX A Materials and Part Numbers 2 P a g e

4 1. INTRODUCTION - Responsibilities and Requirements 1.01 Any contractor that performs work involving communications at the UND must have a minimum of 5 years experience installing communications infrastructure Contractors will install: A. Conduit B. Cable tray C. Cabling D. Jacks E. Equipment mounting plywood F. Racks G. Termination panels and blocks H. Outside cable protectors 1.03 Contractor responsibilities regarding the installed cable are: A. Terminate both ends B. Label faceplates, blocks and/or patchpanels. D. Furnish as-builts when a project is completed E. Test cabling to Cat6 or Cat6a specifications 1.04 UND Responsibilities A. Connect the cable between the backbone, riser and horizontal cabling B. Installation of and/or moving telephone sets C. Activation of data ports D. Configuration and mounting switches E. Mounting wireless access points. 2. WORK AREA The work area is that area containing the outlet and equipment of the horizontal cabling system. Station equipment could be a telephone or a computer The maximum distance for communications cable is 295 ft All cabling installed from the communication room to the work area outlet must be installed above a ceiling or in a wall cavity. If not in either of these a conduit or metal raceway must be installed to enclose the cable Outlet Faceplate used in most locations is a three (3) position plate. Special installations may require a duplex (2) position faceplate or some may require a four (4) position plate Jacks used for voice are the same as used for data, and are mounted on the same outlet faceplate as the data jacks Data Jacks used by UND are specified in Appendix A and use the EIA/TIA T568B 8 pin termination configuration If coax cable is installed for CATV, it can be terminated into the same outlet box and faceplate using an F-81 type CATV connector. Instances where voice and/or data are installed in a different location than video, a separate outlet box using a faceplate with an F-81 barrel connector will be used. 1 P a g e

5 3. COMMUNICATIONS ROOMS The communications room is dedicated to communications functions and related support and should contain only communications equipment 3.01 The desired size of communication rooms is 90 sq feet, sized 9 x 10. The minimum width of a communications room is 5 feet Lighting shall be 50 foot candles measured 5 feet above finished floor. Lights must be at least 8 above the floor Communications room must have cable management hardware on the wall, between the wall and the rack and within the rack. Hardware must be provided and installed to facilitate neat/efficient jumper and patch cord routing Velcro Ty-raps must be used in the installation to avoid stressing the cable. When tightening the velcro ty-rap always ensure the cable is not pinched or crushed in any way, and never use mechanical tools to tighten. Cables shall not be compressed, crimped, crushed, or stretched and the outer jacket cut or damaged to expose the inside wires Install ¾ plywood coated with fire-retardant grey paint on three walls. Orientate 8 feet wide by 4 feet high, bottom to be 2 feet above floor A 19 two post rack, provided by contractor, must be secured to the floor. Mount rack perpendicular to a wall. Contact UND Telecommunications for which wall and exact placement Provide two double duplex 20 amp outlets near the rack location. Provide double duplex 20 amp outlets on each wall located below the plywood HVAC must be provided to maintain the temperature in the room between degrees Fahrenheit. 4. HORIZONTAL PATHWAY refers to the area where communications pathway extends from the communications room to the work area communications outlet EMT conduit for outlets will be ¾ and will either stub into the access ceiling above or below each work area communications outlet. If a cable tray exists, extend conduits to the overhead cable tray All conduits installed under the current project where cable is not installed shall have a pull cord capable of 200 pounds pulling tension installed in them by the contractor Maximum the distance between pull points or pull boxes in a conduit run is 100 feet Any one conduit section cannot contain more than 180 o total bends Sweeping bends with radius equal or greater than 6 time the inside diameter of the conduit. So in a ¾ conduit the minimum bend radius would be Pull boxes shall be used when the length of a run is over 100 feet or if there are bends totaling more than 180 o or if there is a reverse bend in the run. Pull boxes shall be positioned so that the conduit ends align with each other, and shall be so located where they will be readily accessible and indicated on the as-builts Conduit runs shall be clearly labeled at both ends. In the communications room the conduit shall be labeled with the destination work area room number and conduit number. At the work area outlet the conduit shall be labeled in the outlet box indicating the communications room number where the conduit ends Cabling installed in ceiling space is preferred to be in cable tray. Instances where cable tray is not available, cabling must be properly supported and may not lay on the ceiling tiles. When supporting communications cabling all NEC codes governing how cabling is to be supported must be followed. Cable support attachments must be no more than three feet apart. 2 P a g e

6 4.09 Firestopping shall comply with applicable codes. Information on firestopping can be obtained from the EIA/TIA or BICSI standards manual. 5. HORIZONTAL CABLING is that portion of the cabling system which extends from the communications work area outlet to the nearest communications room Cable distances shall follow the EIA/TIA and BICSI standards of 295 feet for installation of Category 6 or 6a cabling Approved cables to be used in the horizontal cabling system are: A. Systimax 1071/2071 Category 6 unshielded twisted pair (UTP) cable B. In special applications such as wireless access points, Systimax 1091/2091 Category 6a C. 50/125 micron OM3 laser optimized multimode fiber optic cable C. 8.3/125 micron singlemode fiber D. 75-ohm coaxial cable for video shall be RG-6 or RG-11, depending on distance and loss requirements and shall have a minimum of 95% braid 5.03 Cabling installed for wireless access points must be Systimax 1091/2091 Cat6a. 6. RISER CABLING connects communications room to communications room on the next floor or the main communications equipment room Topology of riser cabling shall use a star topology, radiating from the main equipment room to each communications room Cabled so that a home run will be made between the communications room on one floor and the main communications room. Cabling shall also be installed to allow access between each communications room Approved cables to be used in the riser cabling system are: A. Systimax 1071/2071 Category 6 unshielded twisted pair (UTP) cable B. In special applications Systimax 1091/2091 Category 6a C. 50/125 micron OM3 laser optimized multimode fiber optic cable C. 8.3/125 micron singlemode fiber D. 75-ohm coaxial cable for video shall be RG-6 or RG-11, depending on distance and loss requirements and shall have a minimum of 95% braid 7. BACKBONE CABLING provides interconnection between the main communications room of a building and the central point of demarcation on the campus Grounding of all backbone cables and protectors to NEC codes ( & ) unless local codes or the equipment manufacturer's requirements exceed the NEC's All cable shields shall be bonded through splice cases When installing copper cabling, building entrance protectors must be installed as close as possible to the cable entrance to the building. The maximum distance outside plant cable, either copper or fiber, may extend into a building is 50 feet. If the protectors are farther than 50 feet, the cable must either be installed in continuous EMT conduit or transitioned to cable designed for indoor cabling The NEC ( d) requires a #6 AWG copper wire be used for bonding the communications and power grounds. Acceptable grounding systems shall follow NEC through P a g e

7 8. CONNECTING HARDWARE 8.01 Patch panels are used to terminate UTP cabling in communications rooms. Must be Systimax Cat6 panels or if special application requires Cat 6a, Systimax Cat 6a patch panels will be installed. See appendix A for specification UTP cable termination at the work area outlet will be Systimax MGS400, Cat 6a installations use Systimax MGS600. A. Maintain twists to ½" from the termination point at the jack and at the communications room cable end to the patch panel. DO NOT PEEL BACK THE CABLE JACKET ANY MORE THAN ABSOLUTELY NECESSARY TO TERMINATE THE CABLES. PREFERABLY ½" AT BOTH THE PANEL AND AT THE OUTLET LOCATION ohm Coaxial Cable termination of 75 ohm coaxial cable shall follow standard procedures and practices. A. All 75-ohm coaxial cable shall be terminated with one piece, ½" shank, hexcrimp, male type "F" connectors. B. Care must be taken to not exceed a bend radius of 2 inches during installation or 3 inches once installed /125 Micron Fiber Optic Cable A. Terminate with LC type connectors B. The maximum optical attenuation each mated connector shall have is 0.5 db. The maximum attenuation for a cross-connect from one terminated fiber to another shall not exceed 1.0 db All splices will be done by fusion splicing. The maximum attenuation for a fusion splice shall not exceed 0.25 db /125 Singlemode Fiber Optic Cable A. Terminated with SC type connectors. B. The maximum optical attenuation each mated connector shall have is 0.5 db. C. The maximum attenuation for a fiber splice shall not exceed 0.25 db. All splices shall fusion spliced. 4 P a g e

8 9. Labeling horizontal cabling cables terminating in the communications room shall have the room number and outlet number from where it came. At the outlet end, the outlet itself shall be labeled with the circuit number that the cable has been assigned. The contractor shall request the Labeling Layout from UND Telecommunication prior to the need of this information. Room numbers shall be UND numbers and not the A/E plan drawing numbers All horizontal cabling faceplates and patchpanels shall be labeled with the room number, the alpha indicator, if used, the outlet number, and the jack position number. An example of a data drop in room 216, where the outlet is the third outlet in the room, and the jack is inserted in position 1 on the faceplate, the label will be 216R3-1. If this were for room 216A instead of 216 the label would read as 216AR3-1. The jack inserted in position two would be labeled, 216AR3-2. A. The outlet faceplate in the room or office would only be labeled with the room number, alpha character, and the outlet number. The faceplates are prestamped with the jack position number. B. The labeling format will be the same for phone or for data. The outlet and termination block will be labeled the same for either type of cable. C. Backbone cables would be labeled as cable Number and Count. Example; 1, is Cable Number 1 and Cable Count 1101 through This numbering system will be determined by the Telecommunications. 5 P a g e

9 APPENDIX A MATERIAL LIST & PART NUMBERS DESCRIPTION NAME Number 19"x 7 2 post Equipment Rack (either one) Newton Chatsworth Indoor 4pr Category 6 Systimax Indoor 4pr Category 6, plenum Systimax Indoor 4pr Category 6a Systimax Indoor 4pr Category 6a, plenum Systimax Cat6 4 pair 8 postion jack Systimax MGS Cat6a 4 pair 8 position jack Systimax MGS Duplex faceplate Systimax M12L number varies by color 3 position faceplate Systimax M13L number varies by color 4 position faceplate Systimax M14L number varies by color 48 port Cat6 angled patchpanel Systimax GS port Cat6a patchpanel Systimax GS block Siemens S210AB2-xxx 110/100 Pair block with legs Siemens S110AW /300 Pair block with legs Siemens S110AW Pair connecting block 110C Pair connecting block 110C block ID strip holder 188UT block Jumper trough 110A1 Indoor 8.3/125 Singlemode fiber Hitachi Indoor 8.3/125 Singlemode plenum fiber Hitachi Indoor, 50/125 OM3 Multimode fiber Hitachi Indoor, 50/125 OM3 Multimode plenum fiber Hitachi Indoor, 50/125 OM4 Multimode fiber Hitachi Indoor, 50/125 OM4 Multimode plenum fiber Hitachi port rack mount fiber dist panel Panduit FRME2 24 port wall mount fiber dist panel Panduit FWME2 25 pair indoor voice grade CommScope pair indoor voice grade CommScope Voice grade outside plant PIC filled cable Superior/Essex various Building Entrance Protector 489ACCI-xxx varies by cable size Gas Tube/Heat Coil Module 4B1-EW Outdoor 8.3/125 Singlemode fiber Hitachi strand fiber panel Panduit FRME4 SC 6 fiber panel Panduit FAP6WBUDSCZ LC 6 fiber panel Panduit FAP6WBUDLCZ Belden coax for TV distribution RG Belden coax for TV distribution, plenum RG-6 plenum 1695A Coax for TV backbone or riser RG Belden coax plenum for TV backbone or riser RG-11 plenum 89292

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1. PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

CABLING STANDARDS FOR

CABLING STANDARDS FOR RFB for Wiring in the Outagamie County Courtrooms Attachment B September 1, 2016 CABLING STANDARDS FOR GENERAL The purpose of this document is to provide guidelines for all structured cable installations

More information

APPENDIX A Verify All Part Numbers (Partial List of Approved Products)

APPENDIX A Verify All Part Numbers (Partial List of Approved Products) SECTION 16651 APPENDIX A Verify All Part Numbers (Partial List of Approved Products) SYSTIMAX SCS: OVER-VOLTAGE PROTECTION 1. Over-voltage Protection Device, 100-Pair with Enclosure, Product 489ACAI-100,

More information

A. All communications equipment rooms shall be installed in a neat and workmanlike manner.

A. All communications equipment rooms shall be installed in a neat and workmanlike manner. SECTION 27 11 00 - COMMUNICATIONS EQUIPMENT ROOM FITTINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

STRUCTURED CABLE SYSTEM (SCS)

STRUCTURED CABLE SYSTEM (SCS) PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus PART 1: GENERAL REQUIREMENTS A. Contractor Work 1. Provide and install (except as noted in this document), cable,

More information

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE)

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) PART 1: GENERAL 1.01 Telecommunications Engineer Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) B. Registered Communications Distribution Designer

More information

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School BILOXI PUBLIC SCHOOL DISTRICT Biloxi Junior High School Request for Proposals E-Rate 2014-2015 - Internal Connections Submit Proposals To: Purchasing Department Attn: Traci Barnett 160 St. Peter Street

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 - GENERAL 1.1 SECTION

More information

A. The requirements of Section govern the work specified in this section.

A. The requirements of Section govern the work specified in this section. SECTION 27 05 10 - COMMUNITY ANTENNA TELEVISION CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The requirements of Section 27 01 00 govern the work specified in this section. B. Refer to the following

More information

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017 Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM-2017-2 Date: 05/26/2017 Additional specification information for data communication to cameras and between Library

More information

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents PART 1 - GENERAL 1.1 SUMMARY SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors. 3. Cabling system identification products. 1.2

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors including patch panels. 3. Cabling identification

More information

Cable Installation Tips

Cable Installation Tips Cable Installation Tips Campus Network Design & Operations Workshop These materials are licensed under the Creative Commons Attribution-NonCommercial 4.0 International license (http://creativecommons.org/licenses/by-nc/4.0/)

More information

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT Purchasing and Warehouse Services Department October 1, 2007 Addendum No. 1 INVITATION FOR BID No. 08-09 Temporary Faculty Offices, Chabot College All Prospective

More information

SECTION 7 -- CROSS-CONNECT SYSTEMS

SECTION 7 -- CROSS-CONNECT SYSTEMS DETAIL ENGINEERING REQUIREMENTS AT&T March, 2016 Section 7, ATT-TP-76400 Revised NA SECTION 7 -- CROSS-CONNECT SYSTEMS CONTENTS PAGE 1. GENERAL... 7-2 1.1. Introduction... 7-2 1.2. Cable Holes... 7-2 1.3.

More information

Section Communications Optical Fiber Backbone Cabling

Section Communications Optical Fiber Backbone Cabling Part 1 1.1 Related Documents 1.1.1 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections apply to this Section. 1.2 Related

More information

B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines.

B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines. PART 1 - GENERAL 1.1 SUMMARY A. This section includes: 1. Support Structures 2. Cable trays and ladder rack 3. Racks (including wire managers) 4. Cables (copper and optical fiber) 5. Jacks and faceplates

More information

Cable Installation Tips

Cable Installation Tips Cable Installation Tips Campus Network Design & Operations Workshop These materials are licensed under the Creative Commons Attribution-NonCommercial 4.0 International license (http://creativecommons.org/licenses/by-nc/4.0/)

More information

Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5

Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5 Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5 1.0 INTRODUCTION Customer to define background and introduction to the project based on

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD, applicable TC -, and CEHNC Design Guide 0-- (Standard is single UTOs and Double UTOs) B. Roads-Service, Lanes Adequate access is provided to the and AAR D. Testing Results-provided

More information

SECTION FIBER OPTIC STATION CABLES

SECTION FIBER OPTIC STATION CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications shall include all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Mfgr. Berk Tek ea , Berk Tek ea , Berk Tek ea. Berk Tek ea ,350.

Mfgr. Berk Tek ea , Berk Tek ea , Berk Tek ea. Berk Tek ea ,350. 8. Pricing Schedule The undersigned has rd and understands all conditions and terms of RFP 336-, is authorized to submit this proposal on behalf of the company, and hereby offers to perform the services

More information

ADDENDUM NO. 2 This addendum consists of 8 pages. Kenai Peninsula Borough Purchasing & Contracting

ADDENDUM NO. 2 This addendum consists of 8 pages. Kenai Peninsula Borough Purchasing & Contracting KENAI PENINSULA BOROUGH Purchasing and Contracting 144 North Binkley Street Soldotna, Alaska 99669-7520 Toll-free within the Borough: 1-800-478-4441, Ext. 2260 PHONE: (907) 714-2260 FAX: (907) 714-2373

More information

Multi-Media Installation Guide

Multi-Media Installation Guide Multi-Media Installation Guide Coaxial Page 2 Data Plug Page 7 Data Jack Page 10 Telephone Page 13 Splicing Page 15 Cable Types Cable Types Two basic types of cable are used in multimedia installations.

More information

Request for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points

Request for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points Request for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points Due Date: Allowable Contract Date from Posted 470 The Palo Verde Elementary School District is requesting

More information

UNM IT/Telecommunications Guide Specification Labeling 11/07/

UNM IT/Telecommunications Guide Specification Labeling 11/07/ Labeling 1 PART 1: GENERAL 1.01 SCOPE OF WORK A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing

More information

Follow The Leader In Shielded Technology

Follow The Leader In Shielded Technology 1970s Vampire Tap 1990s Shielded Modular Jack 190s 4 Position Data Connector Follow The Leader In Shielded Technology The new AMP-TWIST Jack is our latest shielded product evolution. It can be terminated

More information

Information Technology Services DESIGN AND INSTALLATION STANDARDS

Information Technology Services DESIGN AND INSTALLATION STANDARDS Requirements and Guidelines for: New Construction, Renovations, Upgrades, and Retrofits. Revised: June 5, 2015 VIU ITS Network Services 2 TABLE OF CONTENTS 0 GENERAL... 5 1 FIBER OPTIC CABLING... 5 1.1

More information

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION PART 1 - GENERAL 1.1 SUMMARY SCOPE SECTION 25170 TESTING, IDENTIFICATION AND ADMINISTRATION 1. This section includes the minimum requirements for the testing, certification administration and identification

More information

Delaware County Community College Project # Marple Campus Renovation - Phase % Construction Documents November 23, 2011

Delaware County Community College Project # Marple Campus Renovation - Phase % Construction Documents November 23, 2011 SECTION 271323 - COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 - GENERAL 1.1 DESCRIPTION A. This section provides the specifications for the work related to the optical fiber system in the project.

More information

Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING

Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING Revision 05/01/2017 Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING PART 1 GENERAL 1.1 SECTION INCLUDES A. Voice, Data, and Fiber Cable Product materials B. Voice, Data, and Fiber Cable Execution

More information

Telecommunication Infrastructure Project September 20, 2002

Telecommunication Infrastructure Project September 20, 2002 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Category rated UTP systems shall be provided and tested in accordance with the performance level established in Specification

More information

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0553 Identification for Communications Systems

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0553 Identification for Communications Systems 1 General 1.1 Scope of work 1.1.1 The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the completion of

More information

STANDARDS SECTION (16651) COMMUNICATIONS DISTRIBUTION SYSTEM (Rev. Jun 2011)

STANDARDS SECTION (16651) COMMUNICATIONS DISTRIBUTION SYSTEM (Rev. Jun 2011) PART 1 GENERAL 1.00 DESCRIPTION STANDARDS SECTION 271000 (16651) COMMUNICATIONS DISTRIBUTION SYSTEM (Rev. Jun 2011) A. Furnish and install a complete Communications (Telephone/Data) Distribution System

More information

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Request for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling

Request for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling Request for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling Due Date: Allowable Contract Date from Posted 470 The Clarkdale- Jerome School District is requesting

More information

SECTION COMMUNICATIONS STRUCTURED CABLING

SECTION COMMUNICATIONS STRUCTURED CABLING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 27 15 00 COMMUNICATIONS STRUCTURED CABLING SPEC WRITER NOTES: 1. Edit this specification section between // //, to fit project, or delete if not applicable. 2.

More information

SPECIAL SPECIFICATION 6559 Telecommunication Cable

SPECIAL SPECIFICATION 6559 Telecommunication Cable 2004 Specifications CSJ 0015-09-147, etc. SPECIAL SPECIFICATION 6559 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing, training,

More information

SPECIAL SPECIFICATION 8540 Telecommunication Cable

SPECIAL SPECIFICATION 8540 Telecommunication Cable 2004 Specifications CSJ 0914-00-307 & CSJ 0914-25-003 SPECIAL SPECIFICATION 8540 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing,

More information

Data Network Wiring Standard. Part 1: General Section Includes Publications and Standards

Data Network Wiring Standard. Part 1: General Section Includes Publications and Standards Part 1: General 1.01 Section Includes A. Fiber Optic Cable B. Fiber Optic Distribution Cabinets C. Interbuilding Fiber Optic Cabling/Patch Cords D. Fiber Optic Connectors E. Interbuilding Distribution

More information

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED.

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED. Beaverton School District Capital Program Purchasing 16550 SW Merlo Road, Beaverton, OR 97006 Phone: 503-591-4539 SOLICITATION ADDENDUM NO. 1 ITB 15-0012 THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION

More information

THE OHIO STATE UNIVERSITY COMMUNICATIONS WIRING STANDARD

THE OHIO STATE UNIVERSITY COMMUNICATIONS WIRING STANDARD THE OHIO STATE UNIVERSITY COMMUNICATIONS WIRING STANDARD The objective of the standard wiring plan for the University is to provide an acceptable outlet for any communication device that requires connection

More information

Connected Solutions. April $ Post, 19 Rack ELERK1FR BK

Connected Solutions. April $ Post, 19 Rack ELERK1FR BK Connected Solutions April 2018 $30.97 Punch & Go Tool ONQAC3400 $139.97 per 305M Category 6 Riser, UTP, 23 AWG, Blue 305 Meter/1000 FT Pull Box CAB24/4PS6FT4BLUHYP $137.97 2 Post, 19 Rack ELERK1FR1194400BK

More information

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017 SECTION 27 15 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Fiber Optics Redefined

Fiber Optics Redefined Fiber Optics Redefined Questions and Answers on the basics of fiber optic installation TECHLOGIX NETWORX Questions & Answers Questions and Answers Q: What are the two main types of fiber? A: The two main

More information

C. Link offers a standard 1-year warranty on all parts and labor. Manufacturer's warranty is available for larger projects.

C. Link offers a standard 1-year warranty on all parts and labor. Manufacturer's warranty is available for larger projects. DIR-SDD-1898 Cabling Services and Related Products C. Link offers a standard 1-year warranty on all parts and labor. Manufacturer's warranty is available for larger projects. Please address all returns

More information

DESIGN!!GUIDELINES!!!!!

DESIGN!!GUIDELINES!!!!! DESIGNGUIDELINES 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 1. Testing General 1.1. For acceptance, 100% of the media

More information

Liberty Mutual Structured Cabling Specification Bid and Build Structured Cabling Technical Specification for:

Liberty Mutual Structured Cabling Specification Bid and Build Structured Cabling Technical Specification for: Bid and Build Structured Cabling Technical Specification for: Horizontal & Backbone Requirements Page 1 of 30 PUBLICATION RECORD Document Version Publication Date Primary Author Description Revision 1.0

More information

IT/Telecommunications Technical and Wiring Standards. Phillips Exeter Academy

IT/Telecommunications Technical and Wiring Standards. Phillips Exeter Academy IT/Telecommunications Technical and Wiring Standards FOR Phillips Exeter Academy Exeter, NH No deviations will be permitted from these specifications without the express written consent of Phillips Exeter

More information

384A Adapter Installation Instructions

384A Adapter Installation Instructions Instruction Sheet 860237684 Issue 9, October 2012 SYSTIMAX Solutions 384A Adapter Installation Instructions General The 384A adapter (Figure 1) is a broadband video adapter that provides connectivity to

More information

Technical Specifications Florida Gulf Coast University

Technical Specifications Florida Gulf Coast University Technical Specifications Florida Gulf Coast University 9/19/2018 Page 1 of 21 Approved Vendors (alphabetical order) Aztek (CIP) Certified Installer Plus Mr. Scott Coyne 4730 Enterprise Avenue Suite #308

More information

Preferred ordering guide for NETCONNECT

Preferred ordering guide for NETCONNECT Preferred ordering guide for NETCONNECT MEA Region Contents Copper solutions Category 6A products 3 Category 6A and Category 7 shielded copper cables 3 Category 6A modular shielded panels 3 Category 6A

More information

PLU-TV & AT&T CATV CLASSROOM/OFFICE BUILDING EQUIPMENT LISTS & DIAGRAMS CLT CATV.doc CENTER FOR LEARNING & TECHNOLOGY (CLT)

PLU-TV & AT&T CATV CLASSROOM/OFFICE BUILDING EQUIPMENT LISTS & DIAGRAMS CLT CATV.doc CENTER FOR LEARNING & TECHNOLOGY (CLT) Page 1 08-21-01 PLU-TV & AT&T CATV CLASSROOM/OFFICE BUILDING EQUIPMENT LISTS & DIAGRAMS CLT CATV.doc CENTER FOR LEARNING & TECHNOLOGY (CLT) The following is a list of equipment needed to cable and provide

More information

Project No. # Page 1

Project No. # Page 1 PART 1 - GENERAL This section of the has references, products, procedures, processes, and work descriptions/summaries that are common to many Washington State University Pullman (WSUP) campus telecommunications

More information

STRUCTURED CABLING SYSTEMS (SCS)

STRUCTURED CABLING SYSTEMS (SCS) STRUCTURED CABLING SYSTEMS (SCS) ModSecur - Structured Cabling Systems (SCS) A Structured Cabling System (SCS) is the backbone of any building, campus or site communication infrastructure. The sharp growth

More information

OCC Installation Conduit Guidelines Excerpt from Optical Cable Corporation s INSTALLATION GUIDE

OCC Installation Conduit Guidelines Excerpt from Optical Cable Corporation s INSTALLATION GUIDE Installation Conduit Guidelines Excerpt from Optical Cable Corporation s INSTALLATION GUIDE Conduit Installation A conduit cable installation involves placement of one or more optical cables inside a preinstalled

More information

DATA/TELECOMMUNICATIONS REQUEST FOR PRICING

DATA/TELECOMMUNICATIONS REQUEST FOR PRICING Category 6A 10Gig DATA/TELECOMMUNICATIONS REQUEST FOR PRICING TABLE OF CONTENTS 1. GENERAL 3 1.1. Work Included... 3 1.2. Scope of Work... 3 1.3. Regulatory References... 4 1.4. Quality Assurance... 4

More information

HighBand 25. TrueNet Category 6 Solutions

HighBand 25. TrueNet Category 6 Solutions HighBand 25 TrueNet Category 6 Solutions The highest performing cross-connect system in the world. A unique high-density solution with superior cable management. ADC KRONE s HighBand 25 cross connect solution

More information

Spec Sheet. InterReach Fusion Wideband 2.5 GHz WiMAX. In-Building Wireless Networking System. Product Highlights

Spec Sheet. InterReach Fusion Wideband 2.5 GHz WiMAX. In-Building Wireless Networking System. Product Highlights In-Building Wireless Networking System InterReach Fusion is the latest addition to ADC s portfolio of Distributed Antenna Systems. It offers the same superior performance as Unison in an easy-to-install,

More information

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection. SECTION 271300 - COMMUNICATIONS BACKBONE CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

Installation. SAPTF33xx-1xx in the Network. Standard Configuration

Installation. SAPTF33xx-1xx in the Network. Standard Configuration SAPTF33xx-1xx in the Network Standard Configuration One Unit A device (SAPTF33xx-100) and one device () are required for the standard configuration. The Unit A device is connected to the while the device

More information

SECTION O FIBER OPTICS

SECTION O FIBER OPTICS SECTION O FIBER OPTICS CONTENTS PAGE 1. GENERAL...O-2 1.1 Introduction...O-2 1.2 Definitions...O-2 1.3 Requirements...O-2 2. RUNNING, SECURING AND FIRESTOPPING FIBER OPTIC CABLE...O-3 2.1 Running Fiber

More information

Aldine ISD Structured Cabling System Installation Guidelines. Category 6 and OM1 Technical Specification

Aldine ISD Structured Cabling System Installation Guidelines. Category 6 and OM1 Technical Specification Aldine ISD Structured Cabling System Installation Guidelines Category 6 and OM1 Technical Specification Table of Contents PART 1 - GENERAL... 3 1.1 Summary of work... 3 1.2 Special requirements for cable

More information

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project 1.1.0 GENERAL The purpose of this specification is to establish a requirement for the installation of a voice, video and data cable network. The cable (copper), wire, hardware, equipment racks, jumpers,

More information

FTTH & FITH. Discreet optical fiber solutions from the network connection point to the set-top box.

FTTH & FITH. Discreet optical fiber solutions from the network connection point to the set-top box. FTTH & FITH Discreet optical fiber solutions from the network connection point to the set-top box www.omelcom.com FIBER: THE FUTURE IS HERE The past several years have seen major progress in the penetration

More information

Bravo AV s Structured or Whole-House Wiring Approach

Bravo AV s Structured or Whole-House Wiring Approach Custom Audio & Video Systems: Design and Installation Bravo AV s Structured or Whole-House Wiring Approach THE QUALITY OF THE CABLE YOU USE IS CRITICALLY IMPORT TO THE PERFORMANCE OF YOUR SYSTEM Introduction

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 27 15 00 COMMUNICATIONS HORIZONTAL CABLING PART 1 GENERAL 1.1 RELATED DOCUMENTS AND SECTIONS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab*

Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab* Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab* General Scope of Work: Supply and installation of Computer Laboratory setup in MIU Location of Installation:

More information

Project No. # Page 1

Project No. # Page 1 PART 1 - GENERAL This section of the has references, products, procedures, processes, and work descriptions/summaries that are common to many Washington State University Pullman (WSUP) campus telecommunications

More information

3M Fiber Optic Wall Mount Enclosure 8430 Series

3M Fiber Optic Wall Mount Enclosure 8430 Series 3M Fiber Optic Wall Mount Enclosure 8430 Series Installation Instructions January 2014 3 78-0013-9429-1-A Table of Contents 1.0 Description...3 2.0 Parts...4 3.0 Assembly...4 4.0 Mounting the Enclosure...6

More information

SPECIAL SPECIFICATION 6191 Fiber Optic Cable

SPECIAL SPECIFICATION 6191 Fiber Optic Cable 2004 Specifications CSJ 0014-02-014, etc SPECIAL SPECIFICATION 6191 Fiber Optic Cable 1. Description. Furnish, install, splice, field terminate, and test the fiber optic cables. 2. Materials. A. General

More information

Northwestern University Information Technology Building Infrastructure Requirements for Communication Facilities ( January 2010)

Northwestern University Information Technology Building Infrastructure Requirements for Communication Facilities ( January 2010) Northwestern University Information Technology Building Infrastructure Requirements for Communication Facilities ( January 2010) I. Introduction This document presents the current Northwestern University

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION TELECOMMUNICATIONS SYSTEM INFRASTRUCTURE

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION TELECOMMUNICATIONS SYSTEM INFRASTRUCTURE PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. The intent of this standard is to describe the requirements of the telecommunications system infrastructure. Part of this system is the responsibility

More information

Family Health Centers, Inc. Request for Proposal. for. Family Health Centers East Broadway Data and Communications Cabling Project

Family Health Centers, Inc. Request for Proposal. for. Family Health Centers East Broadway Data and Communications Cabling Project Family Health Centers, Inc. Request for Proposal for Family Health Centers East Broadway Data and Communications Cabling Project Date Issued: 06/07/2014 Date Due: 06/16/2014 Page 1 of 22 Table of Contents

More information

Cable Jacket - The outermost layer of the fiber cable. Application: Types Single mode Multi mode. Simplex or Duplex available

Cable Jacket - The outermost layer of the fiber cable. Application: Types Single mode Multi mode. Simplex or Duplex available Fiber Optic Products FIBER OPTIC PRODUCTS FIBER OPTIC PATCH CORD CABLE The Construction of a Fiber-Optic Cable Cable Jacket - The outermost layer of the fiber cable. Strengthening fibers - The strengthening

More information

RCIT Cable Certification Testing Revised 10/2017

RCIT Cable Certification Testing Revised 10/2017 RCIT Testing Revised 10/2017 General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall

More information

1.0 GENERAL. 1.2 SUMMARY.1 Section Includes:

1.0 GENERAL. 1.2 SUMMARY.1 Section Includes: 1.0 GENERAL 1.1 DOCUMENTS.1 This section of the Specification forms part of the Contract Documents and is to be read, interpreted, and coordinated with all other parts. 1.2 SUMMARY.1 Section Includes:

More information

Monash University. Communications Cabling Manual. (Sites running legacy PABXs)

Monash University. Communications Cabling Manual. (Sites running legacy PABXs) Monash University Communications Cabling Manual (Sites running legacy PABXs) Communications & Networks Information Technology Services Monash University Monash Cabling Specifications (PABX sites)doc Page

More information

Brown University. Communications Standard Parts List

Brown University. Communications Standard Parts List CIS - NTG Brown University Communications Standard Parts List All data installations must receive the 25-year Mission Critical Warrantee from Hubbell Premise Wiring. All fiber installations must receive

More information

SECTION TELECOMMUNICATIONS INFRASTRUCTURE

SECTION TELECOMMUNICATIONS INFRASTRUCTURE PART 1 - GENERAL 1.1 SUMMARY A. The telecommunications (telecom) infrastructure provides the basic infrastructure for the transport of voice and data signals throughout the facility. This is often regarded

More information

ANSI/TIA-PN D. Broadband Coaxial Cabling and Components Standard Draft 1, October 11, 2016 TABLE OF CONTENTS

ANSI/TIA-PN D. Broadband Coaxial Cabling and Components Standard Draft 1, October 11, 2016 TABLE OF CONTENTS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 Broadband Coaxial Cabling and Components Standard Draft 1, October 11, 2016

More information

SPECIAL SPECIFICATION 2284 Fiber Optic Cable (Self-Supporting)

SPECIAL SPECIFICATION 2284 Fiber Optic Cable (Self-Supporting) 2004 Specifications CSJ 0086-14-046 SPECIAL SPECIFICATION 2284 Fiber Optic Cable (Self-Supporting) 1. Description. Furnish, install, splice, field terminate, and test the fiber optic cables. 2. Materials.

More information

Request for Proposal (RFP)

Request for Proposal (RFP) Request for Proposal (RFP) Data Network for OCMS 017 Inquiries and requests regarding this RFP should be directed to: Michael Hale Technology Director Oconee County Schools PO Box 16 5-A School Street

More information

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008 Information & Communications Technology Group Standards June 2008 Appendix F UTP cabling Version 1.1 Appendix F UTP cabling 1. Introduction This Section details the required standards for Unshielded Twisted

More information

Effective earthing of screened cables

Effective earthing of screened cables NOVEMBER 2006 Effective earthing of screened cables All metallic containment items, other extraneous metalwork and the screens of telecommunications cables in an information technology environment must

More information

NETWORK INFRASTRUCTURE STANDARDS. Prepared by UIT Network Services

NETWORK INFRASTRUCTURE STANDARDS. Prepared by UIT Network Services NETWORK INFRASTRUCTURE STANDARDS Prepared by UIT Network Services Version 1.25 July 27, 2018 TABLE OF CONTENTS 1.0 REVISION NOTES 1 2.0 INTRODUCTION AND PURPOSE 2 2.0.1 Introduction... 2 2.0.2 Purpose...

More information

3M Supported Applications Map 100,000 (2005) Single-mode. Fiber. Multimode. Fiber. Copper

3M Supported Applications Map 100,000 (2005) Single-mode. Fiber. Multimode. Fiber. Copper 3M Volition Network Solutions introduces Category 5e (Cat. 5e) copper cabling system to complement its leading fiber optic structured cabling system. Customers can now enjoy a single source of supply and

More information

SUMITOMO PRODUCT SPECIFICATION. FutureFLEX. TCxxTP2-1 PLENUM RATED TUBE CABLE SERIES (NFPA 262) WITH GALVANIZED STEEL INTERLOCKED ARMORING

SUMITOMO PRODUCT SPECIFICATION. FutureFLEX. TCxxTP2-1 PLENUM RATED TUBE CABLE SERIES (NFPA 262) WITH GALVANIZED STEEL INTERLOCKED ARMORING SUMITOMO PRODUCT SPECIFICATION FutureFLEX TCxxTP2-1 PLENUM RATED TUBE CABLE SERIES (NFPA 262) WITH GALVANIZED STEEL INTERLOCKED ARMORING SUMITOMO ELECTRIC LIGHTWAVE CORP. 201 South Rogers Lane, Suite 100,

More information

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

1.0 REVISION NOTES INTRODUCTION AND PURPOSE Introduction Purpose CONTACT INFORMATION 3

1.0 REVISION NOTES INTRODUCTION AND PURPOSE Introduction Purpose CONTACT INFORMATION 3 NETWORK INFRASTRUCTURE STANDARDS Prepared by UIT Networkk Services Version 1.24 Februaryy 24, 2017 TABLE OF CONTENTS 1.0 REVISION NOTES 1 2.0 INTRODUCTION AND PURPOSE 1 2.0.1 Introduction... 1 2.0.2 Purpose...

More information

HI-DEX PRODUCT SET DATASHEET

HI-DEX PRODUCT SET DATASHEET APPLICATION HI-DEX is an ultra high-performance, pre-terminated and modular optical fibre cabling system based on MT ferrule connector technology. This product set is designed for installationn in the

More information

Special Specification 6242 Special Fiber Optic Cable

Special Specification 6242 Special Fiber Optic Cable Special Specification 6242 Special Fiber Optic Cable 1. DESCRIPTION 2. MATERIALS The contractor to install, splice, field terminate, test and document all fiber systems. A. General Requirements. Provide

More information

Introduction to Fibre Optics

Introduction to Fibre Optics Introduction to Fibre Optics White paper White Paper Introduction to Fibre Optics v1.0 EN 1 Introduction In today s networks, it is almost impossible to find a network professional who has never been in

More information

Content BULK CABLES VIDEO CABLES AUDIO CABLES EXTENDERS USB CABLES ETHERNET CABLES VIDEO BALUNS CONNECTORS ADAPTERS PATCH PANELS & WALLPLATES TOOLS

Content BULK CABLES VIDEO CABLES AUDIO CABLES EXTENDERS USB CABLES ETHERNET CABLES VIDEO BALUNS CONNECTORS ADAPTERS PATCH PANELS & WALLPLATES TOOLS Content BULK CABLES VIDEO CABLES AUDIO CABLES pages 2-8 pages 8-12 pages 12-13 EXTENDERS ETHERNET CABLES USB CABLES page 13 pages 14-15 pages 16-17 CONNECTORS ADAPTERS VIDEO BALUNS pages 17-23 pages 23-25

More information

Public Works Division Lighting District Fiber Optic Specifications April 2009

Public Works Division Lighting District Fiber Optic Specifications April 2009 Public Works Division Lighting District Fiber Optic Specifications April 2009 7000 Florida Street Punta Gorda, Florida 33950 Tele: 941.575.3600 Fax : 941.637.9265 www.charlottecountyfl.com/publicworks

More information

SECTION STRUCTURED CABLING SYSTEM

SECTION STRUCTURED CABLING SYSTEM SECTION 27 15 01 STRUCTURED CABLING SYSTEM GENERAL 1.1 SUMMARY A. The Section defines the requirements for the installation of the structured cabling system. As described elsewhere in these Documents the

More information

Telecommunciations Infrastructure Project September 20, A. Broadband radio frequency active and passive components

Telecommunciations Infrastructure Project September 20, A. Broadband radio frequency active and passive components PART 1 - GENERAL 1.1 SECTION INCLUDES A. Broadband radio frequency active and passive components B. Broadband optical active and passive components C. Coaxial cable and connectors D. Support and termination

More information

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices Berk-Tek recommends installing a well-designed structured cabling channel per the TIA standards. This includes up to 100

More information