Guide for installers. METTLER TOLEDO MultiRange System solution analog Ex1. Hazardous area. Safe area
|
|
- Dina Harvey
- 5 years ago
- Views:
Transcription
1 Guide for installers METTLER TOLEDO MultiRange System solution analog Ex1 Hazardous area Safe area
2
3 System solution analog Ex1 Contents Contents Page 1 Safety precautions System overview Using the System solution analog Ex Typical configurations Description of components Installation Setting up System solution analog Ex Equipotential bonding Connecting power supply Configuration Corner adjustment Replacing connection cables Making connection cables Installing new connection cable Technical data General technical data Intrinsically safe characteristic values Dimensional drawing Accessories Guide for installers /09 1
4 Safety precautions System solution analog Ex1 1 Safety precautions The System solution analog Ex1 is approved for operation in Zone 1 and 21 hazardous areas. Particular care is required when using weighing systems with the System solution analog Ex1 in hazardous areas. The code of practice is oriented to the "Safe Distribution" concept drawn up by METTLER TOLEDO. Competence Ex approval Operation Installation The System solution analog Ex1 may only be installed, maintained and repaired by authorised METTLER TOLEDO service personnel. No modifications may be made to the device and no repair work may be performed on the modules. Any weighing cells or system modules that are used must comply with the specifications contained in the installation instructions. Non-compliant equipment jeopardises the intrinsic safety of the system, cancels the "Ex" approval and renders any warranty or product liability claims null and void. The safety of the weighing system is only guaranteed when the weighing system is operated, installed and maintained in accordance with the respective instructions. Also comply with the following: the instructions for the system modules and weighing cells, the regulations and standards in the respective country, the statutory requirement for electrical equipment installed in hazardous areas in the respective country, all instructions related to safety issued by the owner. The explosion-protected weighing system must be checked to ensure compliance with the requirements for safety before being put into service for the first time, following any service work and every 3 years, at least. Prevent the build-up of static electricity. Always wear suitable working clothes when operating or performing service work in an hazardous area. Do not use protective coverings for the devices. Avoid damage to the system components. Only install or perform maintenance work on the weighing system in the hazardous areas if the following conditions are fulfilled: the intrinsically safe characteristic values and zone approval of the individual components are in accord with one another, the owner has issued a permit ("spark permit" or "fire permit"), the area has been rendered safe and the owner's safety co-ordinator has confirmed that there is no danger, the necessary tools and any required protective clothing are provided (danger of the build-up of static electricity). The certification papers (certificates, manufacturer s declarations) must be present. Lay cabling securely so that it does not move and effectively protect it against damage. Only route cables into the housing of the system modules via the suitable cable gland and ensure proper seating of the seals. 2 Guide for installers /09
5 System solution analog Ex1 System overview 2 System overview 2.1 Using the System solution analog Ex1 The System solution analog Ex1 is used to connect intrinsically safe analog weighing cells to a weighing terminal with an integrated A/D converter. Here, the System solution analog Ex1 adds up the analog voltage signals of the individual weighing cells. With the System solution analog Ex1, it is possible to construct special scales, e.g. container scales consisting of several DMS weighing cells with a container placed on top. 2.2 Typical configurations System solution analog Ex1, intrinsically safe weighing terminal and DMS weighing cells Hazardous area Safe area Weighing terminal Weighing cell 1* Ex-i, max. 20 m Weighing cell 2* Weighing cell 3* System solution analog Ex1 Weighing cell 4* * Weighing cells must be approved for the hazardous area. The intrinsically safe characteristic values must be in accord with those of the A/D converter of the weighing terminal. System solution analog Ex1 2.3 Description of components Ignition protection type EN II 2G EEx ia IIC T4 II 2D IP68 T75 C Temperature range 20 C to +60 C Protection type IP68 Connection cable 5 m Guide for installers /09 3
6 Installation System solution analog Ex1 3 Installation 3.1 Setting up System solution analog Ex Preparing System solution analog Ex1 1. Open cover of the System solution analog Ex1 by loosening the 12 screws. 2. Remove blind plugs for connection of the weighing cell cables Connecting DMS weighing cells CAUTION Weighing cell cables may not be shortened! Attaching cable gland to cell cable Preparing cell cable 1. Strip cable end approx. 180 mm. 2. Shorten cable shielding to 6 mm. 3. Strip the wire ends approx. 6 mm and twist them. 4. Push on the wire end ferrules and press them on firmly with a pair of crimping pliers. Note Measures for shielding against incoming and outgoing interference are especially important with longer cell cables. The maximum interference immunity classes will only be achieved with careful and proper installation and wiring of all connected peripherals and weighing platforms. For this purpose, it is extremely important to connect the shielding on both sides in a professional manner. The CE-conformity of the entire system is the responsibility of the person commissioning the device. Union nut Molded seal Metal housing Shield Seal Counter nut 1. Slide the union nut and moulded seal over the prepared cable. 2. Place cable shielding over the contact. 3. Screw in metal housing with union nut. 4 Guide for installers /09
7 System solution analog Ex1 Installation Connecting cell cables to System solution analog Ex1 1. Screw cable to the housing. Ensure proper seating of seal when doing so! 2. Identify weighing cells (1 to 4). 3. Connect weighing cell cables in accordance with the drawing to the System solution analog Ex1. For 6-lead weighing cells with a Sense connection, lead the Sense connections from each of two weighing cells to one terminal and open the two hook switches (1) if necessary. 4. Close the cover of the System solution analog Ex1 again. Ensure correct position of cover seal when doing so. EXC SEN SIG SIG+ SEN+ EXC+ 1 Sense connection Weighing cell 4 Weighing cell 3 Weighing cell 2 Weighing cell Sense Sense Power Signal + + Connecting System solution analog Ex1 to weighing terminal 1. Lay connection cable to weighing terminal and pull it into the housing. 2. Screw cable to the housing. Ensure proper seating of seal when doing so. 3. Connect wires. See terminal diagram of the intrinsically safe weighing terminal. 3.2 Equipotential bonding Equipotential bonding must be installed by an electrician authorised by the owner. METTLER TOLEDO Service only has a monitoring and consulting function here. Connect equipotential bonding (PA) of all devices (power supply unit, weighing terminal and weighing platform) in accordance with the terminal diagram and the country-specific regulations and standards. In the process it must be ensured that all device housings are connected to the same potential via the PA terminals, no circulating current flows via the cable shielding for intrinsically safe circuits, the neutral point for equipotential bonding is as close to the scale as possible. Guide for installers /09 5
8 Installation System solution analog Ex1 3.3 Connecting power supply See guide for installers of the intrinsically safe weighing terminal or power supply. 3.4 Configuration Configuration of the weighing system occurs via service mode of the A/D converter of the connected weighing terminal. See operating instructions of the weighing terminal. 3.5 Corner adjustment Corner compensation must be performed after configuration and calibration of the weighing system Checking cornerload Checking of a multi-sensor weighing platform with four weighing cells is described in the following. 1. Place the test weight (1/3 of maximum load) in the centre of the load plate and tare. 2. Load test weights in succession in the middle of each of the four quadrants, and note absolute value with sign. Adjustment is required for deviations greater than the permissible verification error limit Adjusting corners Notes Begin the adjustment at the corner with the greatest deviation. The adjustment of weighing cell 1 occurs at the potentiometer pair 1, cell 2 at pair 2, etc. Potentiometer pair 4 Potentiometer pair 3 Hook switches Potentiometer pair 2 Potentiometer pair 1 Weighing cell 4 Weighing cell 3 Weighing cell 2 Weighing cell 1 6 Guide for installers /09
9 System solution analog Ex1 Installation 1. Switch off weighing system. 2. Open all hook switches. 3. Move all potentiometers to the middle position. 4. With a positive deviation: Turn both potentiometers the same number of rotations to the right. With a negative deviation: Turn both potentiometers the same number of rotations to the left. 5. After completing corner adjustment, screw the cover of the system solution back on. Ensure proper seating of seal when doing so. Notes The following work must be performed after a weighing cell has been replaced: Recalibrate weighing system with maximum load. Check cornerload and adjust if need be. Guide for installers /09 7
10 Replacing connection cables System solution analog Ex1 4 Replacing connection cables 4.1 Making connection cables EXPLOSION HAZARD Take the parameters of the cable used into consideration when checking the intrinsically safe parameters. Use only cables approved for use in the hazardous area. Customer-specific weighing platform cables for intrinsically safe circuits must be fabricated as follows: Cable Dimension A (system solution) Dimension B (terminal) Max. length System solution analog Ex1 weighing terminal 3 x 2 x 0.75 mm 2 80 mm mm m 1 Wire end ferrules with plastic collar, crimp connection Earthing cable gland A As per country-specific regulations for intrinsically-safe circuits Push sleeve over wires and shielding Cable shielding B 1. Cut cable to length and strip cable ends according to dimension A/B. 2. Shorten shielding on both sides to 10 mm. 3. Strip wire ends. 4. Crimp wire end ferrules onto wire ends with a crimping tool. 5. Push second rear section of earthing cable gland onto cable. Do not damage the insulation of the wires here. 6. Push sleeve over wires and shield. Fold over cable shielding. 7. Push on front section of cable gland and screw onto rear section. 8 Guide for installers /09
11 System solution analog Ex1 Replacing connection cables 4.2 Installing new connection cable 1. Open System solution analog Ex1 and detach preinstalled connection cable from the junction PCB. 2. Disconnect earthing cable gland and pull out cable. 3. Pull newly made connection cable into the terminal box and secure with the earthing cable gland. Ensure correct position of seal when doing so. 4. Attach wires according to labelling at the junction PCB. 5. Close housing cover of the System solution analog Ex1. Ensure correct position of seal when doing so. 6. Lay connection cable securely to weighing terminal and connect according to the guide for installers. Guide for installers /09 9
12 Technical data System solution analog Ex1 5 Technical data 5.1 General technical data Explosion protection Ignition protection type EN Metric terminal box II 2 G EEx ia IIC T4 II 2 D IP68 T75 C Temperature range 20 C to +60 C Preinstalled cable Number of weighing cells Permissible platform resistance 5 m max. four (connect only one weighing cell per connection terminal!) 87.5 Ω Housing Housing protection type IP68 Housing type Chrome-nickel-steel (1.4301) 10 Guide for installers /09
13 System solution analog Ex1 Technical data 5.2 Intrinsically safe characteristic values Power supply and measurement circuit U i max I i max P i max KL5, KL6, KL7 20 V 350 ma 1.2 W CAUTION The following conditions must be fulfilled before you connect the System solution analog Ex1 to the A/D converter of the weighing terminal: U i, cell > U 0, A/D converter I i, cell > I 0, A/D converter P i, cell > P 0, A/D converter n x C i, cell + C cable < C 0, A/D converter (n = number of connected cells) L i, cell + L cable < L 0, A/D converter U i max, system solution > U 0, A/D converter I i max, system solution > I 0, A/D converter P i max, system solution > P 0, A/D converter The weighing cell cable and connection cable of the System solution analog Ex1 must be taken into account here when calculating the inductivities and capacitances. 5.3 Dimensional drawing Metric terminal box Dim. in mm Guide for installers /09 11
14 Accessories System solution analog Ex1 6 Accessories Graphic Designation Order No. Cable For intrinsically safe circuits, Ex-i 3 x 2 x 0.75 mm 2, shielded, 100 m Wire end ferrules H 0.75 / 13, with plastic collar, 100 pcs Cable gland M16 x 1.5 EEx e II, 6 pcs Guide for installers /09
15
16 Subject to technical changes Mettler-Toledo (Albstadt) GmbH 04/09 Printed in Germany Mettler-Toledo (Albstadt) GmbH D Albstadt Tel , Fax Internet:
Guide for installers. METTLER TOLEDO MultiRange System solution Point Ex.
Guide for installers METTLER TOLEDO MultiRange System solution Point Ex www.mt.com/support System solution Point Ex Contents Contents Page 1 Safety precautions... 4 2 System overview... 5 2.1 Using the
More information3 Cleaning. 4 Technical data
EXC+ EXC- Sig- SIG+ SEN- SEN+ 2.4 Attaching cable to the analog board Attaching cable of the weighing cell to the system solution Connect the cable to the appropriate terminal strip of the Ex1 system solution
More informationGuide for installers. METTLER TOLEDO MultiRange Explosion proof weighing system with IND226x weighing terminal.
Guide for installers METTLER TOLEDO MultiRange Explosion proof weighing system with weighing terminal www.mt.com/support Contents Contents Page 1 Safety instructions... 4 2 System overview... 6 2.1 Typical
More informationInductive sensor. 2-wire, analog output BI8-M18-LI-EXI
ATEX category II 1 G, Ex-zone 0 ATEX category II 2 D, Ex-zone 21 Threaded barrel, M18 x 1 Chrome-plated brass 2-wire, 14 30 VDC Analog output 4 20 ma Cable connection Wiring diagram Type code Ident no.
More informationDMP 335. Industrial Pressure Transmitter. Welded, Dry Stainless Steel Sensor. accuracy according to IEC 60770: 0.5 % FSO.
DMP 5 Industrial Pressure Transmitter Welded, Dry Stainless Steel Sensor accuracy according to IEC 60770: 0.5 % FSO Nominal pressure from 0... 6 bar up to 0... 600 bar Output signals -wire: 4... 0 ma -wire:
More informationDMP 335 DMP 335. Industrial Pressure Transmitter. Welded, Dry Stainless Steel Sensor. Pressure Transmitter. Industrial
DMP 5 Industrial Pressure Transmitter Welded, Dry Stainless Steel Sensor accuracy according to IEC 60770: 0.5 % FSO Industrial Pressure Transmitter Nominal pressure from 0... 6 bar up to 0... 600 bar Output
More informationDMP 331 DMP 331. Industrial Pressure Transmitter. for Low Pressure. Stainless Steel Sensor. Pressure Transmitter. Industrial. tri-matic.
DMP Industrial Pressure Transmitter for Low Pressure Stainless Steel Sensor accuracy according to IEC 60770: standard: 0.5 % FSO option: 0.5 / 0. % FSO Industrial Pressure Transmitter from 0... 00 mbar
More informationDMP 339. Pressure Transmitter. with G ¼" flush diaphragm. Pressure Transmitter. Industrial. accuracy according to IEC 60770: 0.
DMP 9 Industrial Pressure Transmitter with G ¼" flush diaphragm accuracy according to IEC 60770: 0.5 % FSO Industrial Pressure Transmitter DMP 9 Nominal pressure from 0... 60 bar up to 0... 600 bar Output
More informationMB 204/MB 204-Ex. Multi-Barrier for PROFIBUS PA and FOUNDATION Fieldbus 10/ EN
Multi-Barrier for PROFIBUS PA and FOUNDAION Fieldbus 10/63-6.11 EN P R O F I PROCESS FIELD BUS B U S Intrinsically safe power supply of up to 31 stations on the bus, cascadable multi-barrier Intrinsically
More informationInductive sensor With analog output BI15-M30-LI-EXI
ATEX category II 1 G, Ex-zone 0 ATEX category II 2 D, Ex-zone 21 Threaded barrel, M30 x 1.5 Chrome-plated brass 2-wire, 14 30 VDC Analog output 4 20 ma Cable connection Wiring Diagram Type designation
More informationInductive sensor NI3-EG08K-Y1-H1341
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationInductive sensor BI1.5-EG08K-Y1
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationViper Ex the hazard free way to precise weighing results. Ex ia. The intrinsically safe compact scales combine leadingedge
The intrinsically safe compact scales combine leadingedge technology, user friendliness, and measurement certainty in rugged industrial design. APPROVED Ex ia 2 sensor technologies 5 weighing ranges 3
More informationInductive sensor NI10-M18-Y1X-H1141
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More information- special pressure ranges - variety of electrical and mechanical. Characteristics. - other versions on request
DMP Industrial Pressure Transmitter for Low Pressure piezoresistive stainless steel sensor O p t i o n : f l u s h v e r s i o n accuracy: 0.75 %, 0.5 %, 0.0 %, 0.05 % FSO BFSL (0.5 %, 0.5 %, 0. %, 0.
More informationDMP 343. Industrial Pressure Transmitter. Without Media Isolation. accuracy according to IEC 60770: 0,35 % FSO. Nominal pressure
DMP 4 Industrial Pressure Transmitter Without Media Isolation accuracy according to IEC 60770: 0,5 % FSO Nominal pressure from 0... 0 mbar up to 0... 000 mbar Product characteristics excellent linearity
More informationUser manual Version Ex Remote station XGA 15" family type 17-71KB-45../... Ex Remote station SXGA 18" family type 17-71KB-55../...
User manual Version 3.00 Ex Remote station XGA 15" family type 17-71KB-45../... Ex Remote station SXGA 18" family type 17-71KB-55../... User manual Remote station XGA 15'' family Remote station SXGA 18''
More informationDMP 331i DMP 333i. Precision Pressure Transmitter. Stainless Steel Sensor. accuracy according to IEC 60770: 0.1 % FSO
DMP i DMP i Precision Pressure Transmitter Stainless Steel Sensor accuracy according to IEC 600: 0. % FSO from 0... 00 mbar up to 0... 600 bar Output signal wire:... 0 ma wire: 0 0 V others on request
More informationMagnetic field sensor for pneumatic cylinders BIM-IKT-Y1X
ATEX category II 2 G, Ex zone 1 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Rectangular, height 17 mm Metal, GD-Zn Magnetic-inductive sensor DC 2-wire, nom. 8.2 VDC Output acc. to DIN EN 60947-5-6
More informationDS 400 P. Intelligent Electronic Pressure Switch in Hygienic Stainless Steel Ball Housing. on hygienic process connections
Intelligent Electronic Pressure Switch in Hygienic Stainless Steel Ball Housing Description The electronic pressure switch is the successful combination of hygienic process connections with flush welded
More informationLMP 331 LMP 331. Screw-In Transmitter with piezoresistive Stainless Steel Sensor
LMP Screw-In Transmitter with piezoresistive Stainless Steel Sensor flush diaphragm hydrostatic level measurement of clean, thin fluid media nominal pressure ranges from 0... 40 mbar up to 0... 40 bar
More informationDS 200 P DS 200 P. Electronic Pressure Switch with Flush Process Connection
with Flush Process Connection piezoresistive pressure sensor up to independent contacts, configurable optional: analogue output Exprotection (for wire) cooling element up to 00 C nominal pressure ranges
More informationLMP 305. Slimline Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO.
Slimline Probe Stainless Steel Sensor accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO Nominal pressure from 0... mh 2 O up to 0... 250 mh 2 O Output signals 2-wire: 4... 20 ma
More informationRSCC. Load cells. Special features. Data sheet
RSCC Load cells Special features - Load cell with SG measurement system - aximum capacities: 50 kg to 5 t - Hermetically sealed (IP68) - Rust resistant materials - Legal for trade to 3000 divisions, test
More informationDMP 331Pi. Precision. Pressure Ports And Process Connections With Flush Welded Stainless Steel Diaphragm. Pressure Transmitter.
Precision Pressure Transmitter Pressure Ports And Process Connections With Flush Welded Stainless Steel Diaphragm Version with cooling element accuracy according to IEC 0770: 0. % FSO Precision Pressure
More informationCapacitance Level Measurement Electronic insert FEC 12
Technical Information TI 50F/00/en Capacitance Level Measurement Electronic insert FEC Smart electronic inserts for Multicap probes DC..TE/TA and DC..E/A with HART protocol and integrated linearisation
More informationMagnetic Field Sensor for pneumatic cylinders BIM-IKT-Y1X
ATEX category II 2 G, Ex zone 1 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationOperating instructions
108183 2017-05-17 Page 1 0359 Operating instructions TPPL-EX series Hazardous environments luminaires Please read the instructions carefully before starting any works! Content: 1. Safety instructions 2.
More informationProcess transmitter RMA422
Technical information TI072R/09/en Mat. No. 51001905 Process transmitter RMA422 Multifunctional 1-2 channel top hat DIN rail unit with intrinsically safe current input and loop power supply, alarm set
More informationAnalog Input Module HART Ex i / I.S. Inputs, 8 Channels Type 9461/
> 8 channels for 2-wire HART transmitters > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit monitoring for each field circuit > Module
More informationDS 210. Electronic Pressure Switch. Without Media Isolation. accuracy according to IEC 60770: 0.35 % FSO. Nominal pressure
Without Media Isolation accuracy according to IEC 60770: 0. % FSO Nominal pressure from 0... 0 mbar up to 0... 000 mbar Contacts, or independent contacts freely configurable Analogue output wire:... 0
More informationEx td A21 IP66 T58 C. max. 3 x 4 mm 2 or 1 x 10 mm 2 with pin cable lug + 1 x 2.5 mm 2 fine wire. max. 4 x M20 metal thread
I Ex-junction box I GHG 791 001 R0001 GHG 791 001 R0006 GHG 791 0101 R000 GHG 791 0101 R0001 Technical data GHG 791 01 up to 6 terminals / GHG 791 0 up to 8 terminals Marking accd. to 94/9/EC II G Ex dem
More informationDMP 331i / DMP 333i LMP 331 i
DMP i / DMP i LMP i Precision Pressure Transmitter / Screwin transmitter Stainless Steel Sensor accuracy according to IEC 60770: 0. % FSO from 0... 00 mbar up to 0... 600 bar Output signal wire:... 0 ma
More informationIndustriefunkuhren. Technical Manual. IRIG-B Generator-Module for analogue / digital Signals of Type: IRIG-B / IEEE C / AFNOR NF S87-500
Industriefunkuhren Technical Manual IRIG-B Generator-Module for analogue / digital Signals of Type: IRIG-B / IEEE C37.118 / AFNOR NF S87-500 Module 7628 ENGLISH Version: 02.01-06.03.2013 2 / 20 7628 IRIG-B
More informationAnalog Input Module HART Ex n Inputs, 8 Channels Series 9461/15
> 8 channels for 2-wire HART transmitters > Inputs for Ex nl, Ex na and Nonincendive > Galvanic separation between inputs and system > Open-circuit and short-circuit monitoring for each field circuit >
More informationGE Interlogix Fiber Options S700V & S702V. Instruction Manual FIBER-OPTIC VIDEO TRANSMISSION SYSTEM
g GE Interlogix Fiber Options Instruction Manual S700V & S702V FIBER-OPTIC VIDEO TRANSMISSION SYSTEM Federal Communications Commission and Industry Canada Radio Frequency Interference Statements This equipment
More informationDMK 457 DMK 457. Pressure Transmitter for Shipbuilding and Offshore
GmbH Postal address: House address Fon (+49) 0 22 42-8703-0 Postbox 26 Löhestr. 37 Fax (+49) 0 22 42-8703-20 http: // www.tematec.de 53759 Hennef 53773 Hennef e-mail: team@tematec.de Data Sheet Page /5
More informationDMK 457 DMK 457. Pressure Transmitter for Shipbuilding and Offshore
Pressure Transmitter for Shipbuilding and Offshore ceramic sensor accuracy: 0.25 % FSO BFSL (0.50 % FSO IEC 60770) nominal pressure ranges from 0... 0.6 bar up to 0... 600 bar The pressure transmitter
More informationSINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS
SINAMICS G130 Operating Instructions 03/2013 SINAMICS s dv/dt filter plus Voltage Peak Limiter Safety information 1 General 2 SINAMICS SINAMICS G130 Operating Instructions Mechanical installation 3 Electrical
More informationActuators IC 20, IC 40
Actuators IC 20, IC 40 IC 20 for basic applications with three-point step control and automatic/manual mode changeover for easy commissioning IC 40 for complex applications with programmable functions
More informationLevel Switch. LS Ex KS Ex RS Ex. Manual. AQ Elteknik AB
Level Switch LS Ex KS Ex RS Ex Manual Level Switch Ex Manual version 3.0 March 2013 2 1. Table of contents 1. Table of contents...3 2. Manufacturer information...4 Manufacturer Declaration of Conformity...4
More information9 Control Equipment. Measurement- and Control Equipment Series 8214, 8218
9 Control Equipment Measurement- and Control Equipment Series, Explosion protection to CENELEC IEC Can be used in Zone 1 and Zone 2 Designed for panel mounting Enclosure material : Polyester resin : Aluminium,
More informationPressure transmitter For applications in hazardous areas Model IS-3
Pressure Pressure transmitter For applications in hazardous areas Model IS-3 WIKA data sheet PE 81.58 for further approvals see page 10 Applications Chemical, petrochemical industry Oil, natural gas Machine
More information2 Hour Electronic Boost Timer
2 Hour Electronic Boost Timer Model No. TGBT4 Installation & Operating Instructions 1. General Information These instructions should be read carefully and retained for further reference and maintenance.
More informationColour Explosion Proof Video Camera USER MANUAL VID-C
Colour Explosion Proof Video Camera USER MANUAL VID-C Part Number: MAN-0036-00 Rev 4 Copyright 2002 Net Safety Monitoring Inc. Printed in Canada This manual is provided for informational purposes only.
More informationQuality products from a single source
Velocity sensors Quality products from a single source For more than 50 years Brüel & Kjær Vibro has been a leading manufacturer of vibration measuring instruments and machine condition monitoring systems.
More informationSINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS
SINAMICS G130 / G150 Line harmonics filter Operating Instructions 05/2010 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 / G150 Operating Instructions Mechanical installation 3 Electrical
More information(1) (2) (3) Bedienungs- und Montageanleitung. Safety instructions. Structure of the device
3 x cinch/s-video socket Order no. 33 1532 xx USB/3.5 mm audio socket Order no. 33 1539 xx VGA socket Order no. 33 1540 xx VGA socket with screw-in lift terminals Order no. 33 1541 xx High definition socket
More informationTRANSCENSION 6-CHANNEL DMX DIMMER PACK (order code: BOTE40) USER MANUAL
www.prolight.co.uk TRANSCENSION 6-CHANNEL PACK (order code: BOTE40) USER MANUAL SAFETY WARNING FOR YOUR OWN SAFETY, PLEASE READ THIS USER MANUAL CAREFULLY BEFORE YOUR INITIAL START-UP! CAUTION! Keep this
More informationInstallation Manual IPT Installation of skillet systems with 125 A track current. MV a-E.
www.wampfler.com Page 1 of 27 Index Page 1 Basics...4 2 Basic understanding of an IPT -system...5 3 General rules regarding metal parts in close proximity...6 3.1 Envelope free of ferromagnetic material...6
More informationCAPACITIVE SENSORS KAS. Series 26. Level Control Food Industry Pharmaceutical Industry Semiconductor Industry Chemical Industry
CAPACITIVE SENSORS KAS Series 26 Level Control Food Industry Pharmaceutical Industry Semiconductor Industry Chemical Industry Registrier-Nr.: 1327-01 Testing laboratory accredited according to DIN EN 45001
More informationLevel instruments. Point level measurement - Capacitance switches. Pointek CLS100. 5/10 Siemens FI Overview.
Siemens G 2009 Overview Configuration is a compact 2-wire inverse frequency shift capacitance switch for level detection in constricted spaces, interfaces, solids, liquids, slurries and foam. Benefits
More informationSIWAREX FTA Weighing Module for High Accuracy Requirements Calibrating SIWAREX FTA with SIWATOOL FTA
SIWAREX FTA Weighing Module for High Accuracy Requirements Calibrating SIWAREX FTA with SIWATOOL FTA Quick Guide For modules with order number 7MH4900-2AA01 Contents 1 2 3 4 5 6 Hardware-Requirements..
More informationOperating Instructions
CNTX Contrast sensor Operating Instructions CAUTIONS AND WARNINGS SET-UP DISTANCE ADJUSTMENT: As a general rule, the sensor should be fixed at a 15 to 20 angle from directly perpendicular to the target
More information7 Lighting Technology
7 Lighting Technology Floodlight 09676E00 explosion protected floodlight for use in explosive gas atmospheres of Zone 2 as well as in areas with combustibledust of Zone 21 and Zone 22. Explosion protection
More informationInstallation instructions Ex frames
General information Installation and maintenance: For European member countries of GENELEC shall standard EN 60079-14 and EN 60079-17 be considered. For countries members of IECEx shall standard IEC 60079-14
More informationOperating Instructions 07/2007 Edition. SINAMICS G130/G150 Line harmonics filter. sinamics
Operating Instructions 07/2007 Edition SINAMICS G130/G150 Line harmonics filter sinamics s Safety information 1 General 2 SINAMICS SINAMICS G130/G150 Operating Instructions Mechanical installation 3 Electrical
More informationSITRANS F flowmeters SITRANS F M. Transmitter MAG 6000 I/6000 I Ex d e 4/43
Overview The MAG 6000 I/I Ex d transmitter is designed for the demands in the process industry. The robust die cast aluminium housing provides superb protection, even in the most harsh industrial environments.
More informationLong Range Ethernet Extender
CopperLink Model 2160 Series Long Range Ethernet Extender Quick Start Guide Part Number: 07M2160-QS, Rev. B Revised: February 24, 2012 Sales Office: +1 (301) 975-1000 Technical Support: +1 (301) 975-1007
More informationMKH 8060 Directional studio microphone
MKH 8060 Directional studio microphone Instruction manual Contents Contents Important safety information... 2 The MKH 8060... 3 Delivery includes... 4 Product overview... 5 Putting the MKH 8060 into operation...
More informationXW3D. Simple Wiring of Sensor Actuators. Connector Terminal Boxes. Specifications. Materials and Finish. Connection Combinations
Terminal Boxes XWD CSM_XWD_DS_E Simple Wiring of Sensor Actuators Greatly reduce wiring in combination with the Smartclick XS. Insert the connector and turn / of a turn to lock the connectors. Higher rated
More informationFigure 1: Device components
Order No. : 2860 10 Order No. : 2830 10 Operation- and Assembly Instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically skilled persons. Failure to observe
More informationDCT 532. Industrial Pressure Transmitter with i²c interface. Stainless Steel Sensor
Industrial Pressure Transmitter with i²c interface Stainless Steel Sensor Accuracy according to IEC 60770: standard: ± 0. % FSO option: ± 0. % FSO Nominal pressure from 0... 00 mbar up to 0... 00 bar Digital
More informationERbic Bus Interface Connector System. Catalog E /06 Edition 4
ERbic Bus Interface Connector System www.erni.com Catalog E 074441 01/06 Edition 4 www.erni.com 2 Catalog Katalog D E 074441 074440 01/06 Edition Ausgabe 4 3 www.erni.com Table of Contents ERNI bus interface
More informationElectronic MICROSTAT-T Temperature controller with digital indication for use with resistance thermometers and thermocouples Series 8650
M. K. JUCHHEIM GmbH & Co Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.de
More informationOperating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130
Operating Manual (Edition 04/2004) sinamics Line Reactors SINAMICS G130 Contents 1. Safety Information 2 2. General 5 3. Mechanical Installation 6 4. Electrical Installation 8 5. Technical Specifications
More informationLevel Measurement Point level measurement - RF Capacitance switches
Overview Configuration Installation Standpipes 50 (2) 20 (0.79) max. is a compact, 2-wire, inverse frequency shift capacitance switch for level and material detection in constricted spaces, interfaces,
More informationDS 201. Electronic Pressure Switch. Ceramic Sensor. accuracy according to IEC 60770: 0.5 % FSO
Ceramic Sensor accuracy according to IEC 600: 0. % FSO Nominal pressure from 0... 00 mbar up to 0... 600 bar Contacts, or independent PNP contacts, freely configurable Analogue output wire:... 0 ma wire:
More informationAK-PVE4 Operating Instructions. Measuring of norm signals in wall-type units. Performance:
AK-PVE4 Operating Instructions Measuring of norm signals in wall-type units 1 2 P Performance: Digit heights: 20 mm Colour: red Display range: -999 9999 Wall-type housing: light grey made of ABS-plastic
More informationEddy Current Probe System
CMSS 785 Eddy Current Probe System API-670 Proximity transducer system, 5 mm and 8 mm Eddy Current Probe System The CMSS 785 system is an eddy current type non-contact displacement/ vibration system, used
More informationR87B. Box Fan. Comprehensive Lineup of Single, Double, and Triple Axial Fans with Easy One-step Mounting. Model Number Structure. Ordering Information
Box Fan R87B CSM_R87B_DS_E_4_4 Comprehensive Lineup of Single, Double, and Triple Axial Fans with Easy One-step Mounting Mounts in a square cutout and conceals the hole-cut to simplify installation work.
More informationR87B. Box Fan. Comprehensive Lineup of Single, Double, and Triple Axial Fans with Easy One-step Mounting. Ordering Information. Model Number Structure
Box Fan R87B CSM_R87B_DS_E_4_2 Comprehensive Lineup of Single, Double, and Triple Axial Fans with Easy One-step Mounting Mounts in a square cutout and conceals the hole-cut to simplify installation work.
More informationOM2000N INSTALLATION MANUAL
OM2000N INSTALLATION MANUAL 2 1 Figure A 1 2 Laser Beam Output Window Power Cable 821001342 (Rev. B) DESCRIPTION The OM2000N oscillating mirror is an accessory for the 2000N family laser scanners: DS2100N,
More informationSQM40/41 Actuators for air and gas dampers
SQM40/41 Actuators for air and gas dampers Description SQM40/41 actuators are used for the positioning of flow control valves, butterfly valves, dampers or any application requiring rotary motion. The
More informationQuality products from a single source
Velocity sensors Quality products from a single source For more than 50 years, Brüel & Kjær Vibro has been a leading manufacturer of vibration measuring instruments and machine condition monitoring systems.
More informationR&S AMU-Z7 Analog I/Q Combiner Technical Information
R&S AMU-Z7 Analog I/Q Combiner Technical Information 1415.7335.92 01 Test & Measurement Technical Information 2009 Rohde & Schwarz GmbH & Co. KG 81671 Munich, Germany Printed in Germany Subject to change
More informationFX-4AD-TC SPECIAL FUNCTION BLOCK USER'S GUIDE
FX-4AD-TC SPECIAL FUNCTION BLOCK USER'S GUIDE JY992D55901A This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX-4AD-TC special
More informationOPERATING MANUAL. DMX Demultiplexer 3012B Mk2
last updated: 2007-03-08 OPERATING MANUAL DMX Demultiplexer 3012B Mk2 (C) SOUNDLIGHT 1995-2007 * ALL RIGHTS RESERVED * NO PART OF THIS MANUAL MAY BE REPRODUCED, DUPLICATED OR USED COMMERCIALLY WITHOUT
More informationInductive linear position sensor LI300P0-Q25LM0-LIU5X3-H1151
Rectangular, aluminium / plastic Versatile mounting possibilities LED indicates measuring range Immune to electromagnetic interferences Extremely short blind zones 12 bit resolution 4-wire, 15 30 VDC Analog
More informationEXPlora. Introduction
Introduction EXPlora The EXPlora range is most suited to manufacturers of ancillary electrical equipment such as motors, pumps, lighting equipment, process and control gear for use in factories and plant
More information3.3. Ex-Escape sign luminaires. Ex-Lite Metal version with LED technology for Zone 1 and Zone 21 / NEC applications
. Ex-Escape sign luminaires Ex-Lite Metal version with LED technology for Zone 1 and Zone 21 / NEC applications The robust escape sign luminaire The Ex-Lite series of explosion-protected escape sign luminaire
More informationHeating thermostat Series AMHs B Operating Instructions 11.06/
Heating thermostat Series AMHs-1-80 B 60.3045.0 Operating Instructions 11.06/ 00367556 Typographical conventions Warning signs The signs for Danger and Warning are used in this manual under the following
More informationS6-R READER. Installation and Operating Instructions
Installation and Operating Instructions The information provided in these installation instructions may be modified without prior notification. All previous versions cease to be valid with the publication
More informationKRF EMC Filters Installation, Operation and Maintenance Manual
KRF EMC Filters Installation, Operation and Maintenance Manual KRF EMC Filters limit high frequency noise, as well as: Reduce interference Protect sensitive equipment Eliminate drive cross-talk Meet FCC
More informationMODEL HS35 DRAWWORKS OPTICAL ENCODER
MODEL HS35 DRAWWORKS OPTICAL ENCODER Product Description This specially configured DrawWorks Model HS35 encoder combines rugged, heavy-duty features into a unique through-shaft style for use as a winchturns
More information4 Wiring Brochure Wiring and installation of specific control
- Wiring Brochure tekmarnet 4 User Switch 480 W 480 09/09 1 Information Brochure Choose controls to match application 2 Application Brochure Design your mechanical applications 3 Rough In Wiring Rough-in
More informationIndustrial Monitor Update Kit
Industrial Monitor Update Kit (Bulletin Number 6157) Installation Instructions 2 Table of Contents Table of Contents Industrial Monitor Update Kit... 3 Overview... 3 Part 1 - Initial Preparation... 5 Part
More informationMINI MCR-SL-F-UI-NC. Frequency transducers. Data sheet. 1 Description
Frequency transducers Data sheet 105_en_01 PHOENIX CONTACT 01-08-19 1 Description Configurable -way isolated frequency transducer. The device is suitable for the connection of NAMUR proximity sensors (IEC
More informationSentronic PLUS Electronic Pressure Regulator. Installation Manual
Sentronic PLUS Electronic Pressure Regulator Installation Manual Sentronic PLUS ASCO NUMATICS Sentronic PLUS Electronic Pressure Regulator Electrical Characteristics * Max. ripple: 10 % Specifications
More informationProcess Transmitter RMA 422
Technical Information TI 072R/24/ae Process Transmitter RMA 422 Multi-functional 1-2 channel top hat DIN rail unit with loop power supply, alarm set point monitoring, mathematics function and 1-2 analog
More informationLinear flow control with actuator IFC
Linear flow control with actuator Product brochure GB 3 Edition 01.14 Linear relationship between adjustment angle and flow rate Large control ratio of 25:1 EC type-tested and certified Actuators IC 20
More informationMax. temp. of sensor C. Capillary tube mm. Switching difference K. Sensor cartridge mm
21.610/1 RAK: Universal thermostat How energy efficiency is improved Demand-led controlling, monitoring and limiting, without auxiliary energy. Areas of application For controlling and monitoring the temperature
More informationSpeed sensor MiniCoder GEL 2471
Speed sensor MiniCoder GEL 2471 for electrically conducting toothed-wheels Technical information version 10.02 The MiniCoder family from Lenord + Bauer offers spacesaving solutions for the contactless
More informationMG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV
MG-XV operating instruction Measuring of norm signals, 4-8-digit Panel instrument type MG-BV Construction instrument type MG-AV Contents 1. Brief description... 3 2. Safety instructions... 3 2.1. Proper
More informationCHECK LINE. Model LS-36-LED. Stationary Stroboscope. Operating Manual BY ELECTROMATIC
CHECK LINE BY ELECTROMATIC Stationary Stroboscope Model LS-36-LED Operating Manual Table of Contents 1.0 Introduction... 02 1.1 Unpacking 1.2 Optional Accessories 2.0 Safety Information... 3 3.0 Controls...
More informationUser s Manual Model WF100 Extension Cable for EXA100
User s Manual Model WF100 Extension Cable for EXA100 1st Edition User s Manual Model WF100 Extension Cable for EXA100 1st Edition Safety Precautions Introduction This instruction manual covers the Extension
More informationLt DELTA USA, Inc
Infrared LOOP SCANNER Rota-Sonde TS2006 Infrared - high sensitivity 480 F or 750 F Quick and easy commissioning Self-monitoring and alarm functions Lt 1037 1 Applications R o t a - S o n d e TS2 0 0 6
More informationSensor module. Safety instructions. Function Correct use. Product characteristics. Structure of the device. Operation. Ref.No.
Sensor module Ref.No.: SM 1608 V03 Safety instructions Caution! Electrical devices may only be installed and fitted by electrically skilled persons. Non-compliance with the installation information could
More informationCirculating Feed Delivery System Installation Instructions for Model 55, 75, 90, & HMC FLEX-AUGER Feed Delivery Systems
Circulating Feed Delivery System Installation Instructions for Model 55, 75, 90, & HMC FLEX-AUGER Feed Delivery Systems MA773-06 5/99 May 1999 Chore-Time Warranty Chore-Time Equipment warrants each new
More informationTrusted TMR I/O SmartSlot Slot Cables
PD-TC500 Trusted Trusted TMR I/O SmartSlot Slot Cables Product Overview This document provides detailed information for the types of Trusted input/output (I/O) Cables available within the SmartSlot group.
More information