Instalaciones de fibra optica en entornos de centro de datos y campus para suportar 40, 100G y mas
|
|
- Grace Jackson
- 5 years ago
- Views:
Transcription
1 Instalaciones de fibra optica en entornos de centro de datos y campus para suportar 40, 100G y mas Jim Davis Regional Marketing Engineer Fluke Networks
2 Agenda Inspection and Cleaning Loss Budgets TIA (Cabling) vs IEEE (Application) Loss Testing Best practice to reduce uncertainty 3 jumper reference for MPO cable testing with OLTS OTDR Testing - Troubleshooting MPO Trunks Results management Cloud based services
3 INSPECTION, AND, IF NECESSARY, CLEANING (REPEAT AS NEEDED)
4 #1 Problem: Dirt! Contaminated connector end-faces: Leading cause of fiber link failures Particles of dust and debris trapped between fiber end faces cause signal loss, back reflection, and damaged equipment Many Sources of contamination: Equipment rooms & Telecommunication rooms in filthy environments Improper or insufficient cleaning tools, materials, procedures Debris and corrosion from poor quality adapter sleeves Hands of technicians Airborne 4
5 Video Microscopes for Inspection Protect your one good eye A variety of tips available Patch Cord and Bulkhead Auto Centering and Auto Focus options Ability to store images Can be used to compare against standard
6 Automated Analysis IEC IEC ED.2 MM Zone Name Scratches Defects A: Core (0-65µm) B: Cladding (65-115µm) No Limit 3 µm None > 3 µm No Limit 5 µm None > 5 µm 4 5 µm None > 5 µm No Limit < 5 µm 5 From 5-10 µm None > 10 µm C: Adhesive No Limit No Limit D: Contact ( µm) No Limit No Limit < 20 µm 5 30 µm None > 30 µm
7 Inspect Clean - Inspect
8 Inspect Clean - Inspect
9 Inspect Clean - Inspect
10 If Dry Clean fails, try Wet Clean
11 Pass!
12 MPO Inspection & cleaning Requires special adapter for microscope Two axis camera is easier even for 12 fiber connections Second knob on tip allows centering of fibers
13 MPO Inspection & cleaning Cleaning is more important than ever With large contact surface, any contaminants can cause and air gap and this leads to reflectance problems Example of a dirty MPO end face
14 The cover lifts to insert MPO connectors You may put a drop of solvent on the cleaning tape
15 MPO Inspection & cleaning That fiber from the earlier slide is clean now Example of a cleaned MPO end face
16 Tier I testing is loss, length, and polarity Is there enough light coming out of the fiber for the receiver to detect? Is the transmission on the right (left) fiber?
17 A Test Result! Yes! 17
18 A Test Result! What Test Limit was Passed? TIA Length Based Limit for Multimode Fiber 18
19 How Fiber Loss is Measured Set a reference Run a test Find the difference
20 First set a reference Then find the Difference Optical Loss Measured Direct connection (No bulkhead adapter!) All connections are included in the loss measurement
21 Why not 2 jumper reference? Sadly, most folks are setting a reference this way? db Issues You have no idea what the loss is in the adapter Whatever it is, it s subtracted from your measurement The uncertainty is horrendous negative loss
22 What is done today Let s take an example 0.75 db Issues You have no idea what the loss is in the adapter Whatever it is, it s subtracted from your measurement The uncertainty is horrendous negative loss
23 What is done today Let s take an example 0.3 db 0.1 db 0.3 db Measurement = = db Issues You have no idea what the loss is in the adapter Whatever it is, it s subtracted from your measurement The uncertainty is horrendous negative loss
24 Example of Negative Loss Bad test results do not accept!
25 Accurate test process and values will reduce uncertainty For less uncertainty in our fiber testing, especially of multimode fiber, there are 4 key ingredients to loss testing A one jumper reference An LED source Reference Grade Connectors Encircled Flux compliance 25
26 Accurate test process and values will reduce uncertainty For less uncertainty in our fiber testing, especially of multimode fiber, there are 4 key ingredients to loss testing A one jumper reference An LED source Reference Grade Connectors Encircled Flux compliance LED Source VCSEL Source 26
27 Accurate test process and values will reduce uncertainty For less uncertainty in our fiber testing, especially of multimode fiber, there are 4 key ingredients to loss testing A one jumper reference An LED source Reference Grade Connectors Encircled Flux compliance < 0.10 db of loss per mated pair <0.20 db for Single-Mode 27
28 Encircled Flux compliance The light source s launch condition determines how and where the light is distributed within the fiber Cladding Core Source 1 Over filled Source 2 Under filled Source 3 EF Compliant
29 Encircled Flux Improves Precision EF compliant = just enough light Measure the right loss Passes good links Fails bad links Overfilled = too much light near the edge Measures high loss Fails good links Underfilled = not enough light near the edge Measures low loss Passes everything
30 CALCULATING A LOSS BUDGET Difference between a TIA limit and an application limit The Loss Budget determines what Passes and Fails
31 There is no Cat 6A for fiber Which Limits to use? Does this link really pass? There is conflict between what the standard will support and what the application requires Installers should use Custom Limits to certify links Cabling Standards: TIA 568 ISO Application Standards: 1000BASE-T 10GBASE-T Application Standards: 1000BASE-T 10GBASE-T
32 There is no Cat 6A for fiber Which Limits to use? Does this link really pass? There is conflict between what the standard will support and what the application requires Installers should use Custom Limits to certify links Manufacturers may offer a custom link loss calculator for their components Cabling Standards: TIA 568 ISO Application Standards: 10GBaseSX 40GBase-SR4
33 IEEE 802.3ba (100 Gig) Fiber Channel Performance Requirements Per Table Maximum Channel Insertion Loss = 6.7 db at 1310 nm Maximum Length = 10 Km Per db at 1310 nm Maximum Discrete Reflectance shall be less than -26 db
34 TIA Limits Vs. IEEE limits 1 km Cabling Standards: TIA 568 ISO Per TIA: # Connectors * 0.75 db KM of fiber * 1 db/km (Tight Buffered) # Splices * 0.30 db In this example = 2.5 db Total Loss Budget Measured Loss = 2 db Pass for both TIA and IEEE Application Standards: 10GBaseLX 40GBase-LR4
35 TIA Limits Vs. IEEE limits 1 km Cabling Standards: TIA 568 ISO Per IEEE: Less than 6.7 db of loss, less than 10 KM of length In this example 6.7 db Total Loss Budget Measured Loss = 5 db Pass but only for IEEE Application Standards: 10GBaseLX 40GBase-LR4
36 Using a TIA limit without understanding the application Customer wants to run 10GBASE-SR on this multimode link 0.75 db 0.75 db 0.75 db nm (300 m) 0.75 db TIA (tester) Limit = 0.75 db db db db db = nm 10GBASE-SR Limit = nm This design will not support 10GBASE-SR
37 Which Limits to use? Does this link really pass? That 3.90 loss budget falls within the acceptable values for the cabling standard, but outside of the acceptable values for the application Cabling Standards: TIA 568 ISO Application Standards: 10GBaseSX 40GBase-SR4 X
38 Using a TIA limit without understanding the application Customer wants to run 10GBASE-SR on this multimode link 0.90 db (300 m) 0.75 db 0.75 db TIA (tester) Limit = 0.75 db db db = nm 10GBASE-SR Limit = nm This design will support 10GBASE-SR
39 Using a TIA limit without understanding the application Customer wants to run 10GBASE-SR on this multimode link 0.90 db (300 m) 0.75 db 0.75 db TIA (tester) Limit Confirm = 0.75 the db + performance 0.90 db of your db MPO cassettes Many manufacturers = 2.40 have 850 nm regular and High Performance or 10GBASE-SR Low Limit Loss = cassettes Regular 850 nmmay This have design > 1 will db of support loss for 10GBASE-SR the two connections
40 MPO/MTP Testing with OLTS
41 Multi-Fiber Connectors (MPO/MTP) 12 Fiber For plug and play cassettes in datacom environment 40 Gig 16 Fiber For SAN market, where switch & director blades come in eight fiber increments 24 Fiber High density for the data center server side 100 Gig
42 Two options for testing MPO to MPO cables Traditional duplex field tester Dedicated MPO field tester
43 MPO/MTP Testing with OLTS 3 Jumper Reference
44 How to tell 3 jumper reference is set properly Very important for end user Look for two TRC Verifications in test results
45 How to tell 3 jumper reference is set properly Very important for end user Second step check 2 nd TRC and reset reference
46 Testing MPO to MPO cables LC LC MPO MPO Loss reported Referenced out
47 OTDR testing of MPO/MTP connectors
48 OTDR Testing of MPO Connectors Ideally you will have at least 30 Meters of Launch and Receive fibers Provided that the link under test is short Use a fan out cord or cassette to convert from Single fiber Port on OTDR 30 Meters 30 Meters Launch Fiber Receive or Tail Fiber Don t forget your Pinned/Unpinned connections!
49 Port Protector/Sacrificial Cord in Action 30 Meter Launch Cord 30 meter Receive cord
50 MPO Launch Cord and Trace 30 Meters Fan-out to MPO Launch Fiber
51 MPO Launch Cord and Trace MPO
52 All 12 fibers stacked trace
53 Looks easy now let s try Single Mode MPO
54 First check launch/receive cords 50 Meter Launch Cord 50 meter Receive cord
55 Detail of launch fiber verification notice Gender Changing connector and tool
56 Example of Fiber Switch instead of Fan Out Switch 1 x 12
57 The Switch helps, but makes a large event
58 Launch and Receive Fibers Look Good
59 Here are Launch Link Receive Fibers
60 What is happening with the First Fiber?
61 Is the connector dirty?
62 Please be sure to Inspect ALL Connectors before installing, clean them if necessary, inspect again!! Video Microscope Brand new out of bag After Cleaning 62
63 Documenting Results Request your test results in Native Format, not.pdf Your tester only delivers results in Paper format? Consider using a cloud based results management service Check that the reference value is correct and recent Did they verify the known good leg? Deliver the results today, not in a month While your team still has access to the site
64 In Conclusion Inspect and clean if necessary Follow the right process to reduce uncertainty in your measurement MPO/MTP connectors are an accepted multi-lane solution Data Centers use them extensively Tier I testing can be done with OLTS and 3 jumper reference Tier II testing can be used for troubleshooting A 12/24 fiber launch fiber and tail fibers are required Leverage the benefits of cloud based results management
65 Thank you, Gracias, Obrigado Jim Davis Fluke Networks 6920 Seaway Blvd Everett, WA 98271
The Road to Single Mode: Direction for choosing, installing and testing single mode fiber
The Road to Single Mode: Direction for choosing, installing and testing single mode fiber Adrian Young Leviton Network Solutions Jim Davis Fluke Networks Adrian Young, Sr. Applications Engineer Leviton
More informationField Testing and Troubleshooting of PON LAN Networks per IEC Jim Davis Regional Marketing Engineer Fluke Networks
Field Testing and Troubleshooting of PON LAN Networks per IEC 61280-4 Jim Davis Regional Marketing Engineer Fluke Networks Agenda Inspection and Cleaning APC vs UPC PON basics Wavelengths Architecture
More informationThe need for Encircled Flux, real or imaginary?
Version 1.7 The need for Encircled Flux, real or imaginary? Harley Lang, RCDD Fluke Networks 14 March, 2013 Presentation agenda What s the issue Mandrels are they needed? Review of standards Coupled Power
More informationThe current state of multimode OTDR and Light Source and Power Meter (LSPM) Insertion Loss (IL) testing is as follows:
APPLICATION NOTE Meeting the Encircled Flux Launch Standard Scope: Guidance on how to test to the Encircled Flux (EF) multimode launch standard using existing optical test equipment and the Optronics Encircled
More informationUnderstanding Multimode Launching Conditions and TIA TSB-178
Understanding Multimode Launching Conditions and TIA TSB-178 What is EF? It is a new method to define the launch conditions of a light source EF measurement is based on the power distribution measurement
More informationDatasheet: MultiFiber Pro
Datasheet: MultiFiber Pro First MPO tester to support both Singlemode and Multimode MPO fiber testing Data centers are growing, fueled by the proliferation of media, virtualization and the need for more
More informationDatasheet: MultiFiber Pro Update
Datasheet: MultiFiber Pro Update Datasheet: MultiFiber Pro Update First MPO tester to support both Singlemode and Multimode MPO fiber testing Data centers are growing, fueled by the proliferation of media,
More informationAdvanced Test Equipment Rentals ATEC (2832)
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) Datasheet: MultiFiber Pro Optical Power Meter and Fiber Test Kits Data centers are growing, fueled by the proliferation
More informationConnectix Cabling Systems
Connectix Cabling Systems Cabling Standards and CPR Update Connectix CEP Fibre Optic Solutions Jason Holroyd CNID Director of Business Development Types of fibre Agenda Introduction Uses Construction Transmission
More informationRCIT Cable Certification Testing Revised 10/2017
RCIT Testing Revised 10/2017 General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall
More informationISO/IEC testing LC to LC (Duplex Multimode) DTX-MFM
Page 1 of 5 ISO/IEC 14763-3 testing LC to LC (Duplex Multimode) DTX-MFM ISO/IEC 11801 now refers fibre testing to ISO/IEC 14763-3. More importantly, the limits have changed and we'll show you how in this
More informationDatasheet: CertiFiber Pro Optical Loss Test Set
Datasheet: CertiFiber Pro Optical Loss Test Set The CertiFiber Pro is the Tier 1 (basic) fiber certification solution and part of the Versiv Cabling Certification product family. The Versiv line also includes
More informationVersiv makes you money every time you use it.
Datasheet: CertiFiber Pro Optical Loss Test Set The CertiFiber Pro is a Tier 1 (basic) fiber certification solution and part of the Versiv Cabling Certification product family. The Versiv line also includes
More informationHow to accelerate your cabling system approvals
How to accelerate your cabling system approvals Adrian Young Fluke Networks November, 2013 Singapore Objectives for this session Resolve field failures on the spot Look at real world examples of fault
More informationDatasheet: CertiFiber Pro Optical Loss Test Set
Datasheet: CertiFiber Pro Optical Loss Test Set The CertiFiber Pro is a Tier 1 (basic) fiber certification solution and part of the Versiv Cabling Certification product family. The Versiv line also includes
More informationDatasheet: CertiFiber Pro Optical Loss Test Set
Datasheet: CertiFiber Pro Optical Loss Test Set Datasheet: CertiFiber Pro Optical Loss Test Set The CertiFiber Pro is a Tier 1 (basic) fiber certification solution and part of the Versiv Cabling Certification
More informationFiber Optic Testing. The FOA Reference for Fiber Optics Fiber Optic Testing. Rev. 1/31/17 Page 1 of 12
Fiber Optic Testing Testing is used to evaluate the performance of fiber optic components, cable plants and systems. As the components like fiber, connectors, splices, LED or laser sources, detectors and
More informationMPO Technology Connectivity & Application
MPO Technology Connectivity & Application White paper White Paper MPO Technology Connectivity & Application v1.0 1 Introduction It has been proved that reducing cable diameters and increasing connection
More informationTECHN. Purpose. Background. to prepare the. A A Patch cord. horizontal infrastructure
Understanding the use of the PanMPO in 10GBASE SR and 40GBASE SR4 Channels Purpose The purpose of this document is to describe the usage and reasoning behind the development and characteristics of the
More informationTech Breakfast: Fibre Optic Cabling
Tech Breakfast: Fibre Optic Cabling An introduction phil.crawley@jigsaw24.com @IsItBroke on Twitter http://www.root6.com/author/phil Fibre optic cabling Applications within Film & TV Single mode vs. Multi
More informationArista 40G Cabling and Transceivers: Q&A
Arista 40G Cabling and Transceivers: Q&A 40G Cabling Technical Q&A Document 40Gigabit Cables and Transceivers Q. What 40G cables and transceivers are available from Arista? A. Arista supports a full range
More informationFiber Optics Redefined
Fiber Optics Redefined Questions and Answers on the basics of fiber optic installation TECHLOGIX NETWORX Questions & Answers Questions and Answers Q: What are the two main types of fiber? A: The two main
More informationOptical Design Manufacturing, Inc. Sprint 2.5. Alcatel-Lucent (ALU) Fiber Inspection and Testing Procedures. Technical Support Document
Optical Design Manufacturing, Inc. Sprint 2.5 Alcatel-Lucent (ALU) Fiber Inspection and Testing Procedures Technical Support Document 2 Table of Contents I. Introduction... 3 II. Test Site Overview...
More informationFIBER QUICKMAP. Users Manual. Multimode Troubleshooter
FIBER QUICKMAP Multimode Troubleshooter Users Manual January 2011, Rev. 1 7/11 2011 Fluke Corporation. All rights reserved. All product names are trademarks of their respective companies. LIMITED WARRANTY
More informationWe will look first at the cable, and then the transceivers (which act as both transmitter and receiver on each end of the fiber cable).
Nuclear Sensors & Process Instrumentation Fiber Cable Basics Fiber-optic communication is a method of transmitting information from one place to another by sending light through an optical fiber. The light
More information40G SWDM4 MSA Technical Specifications Optical Specifications
40G SWDM4 MSA Technical Specifications Specifications Participants Editor David Lewis, LUMENTUM The following companies were members of the SWDM MSA at the release of this specification: Company Commscope
More informationCategory 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards.
27 08 00 Certification and Commissioning of Communication Systems (Revision date: 7/3/12) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are
More informationHoW confident are You about Your connector cleanliness?
HoW confident are You about Your connector cleanliness? Gwennaël Amice, Senior Application Engineer Vincent Racine, Product Line Manager, Francis Audet, Advisor, CTO Offi ce, François Marcotte, Senior
More informationSSA Fibre-Optic Extender 160 Fibre Installation Guidelines Version 1.2
SSA Fibre-Optic Extender 160 Version 1.2 0.1 Introduction This document provides information on the specification and installation of optical fibre networks to support SSA optical extender products. SSA
More information40G SWDM4 MSA Technical Specifications Optical Specifications
40G SWDM4 MSA Technical Specifications Specifications Participants Editor David Lewis, LUMENTUM The following companies were members of the SWDM MSA at the release of this specification: Company Commscope
More informationOLS Series Light Sources, OPM Series Optical Power Meters, and Related Test Kits User s Guide
OLS Series Light Sources, OPM Series Optical Power Meters, and Related Test Kits User s Guide Limited Warranty One Year Limited Warranty All Noyes products are warranted against defective material and
More informationDESIGN!!GUIDELINES!!!!!
DESIGNGUIDELINES 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 1. Testing General 1.1. For acceptance, 100% of the media
More informationOPTICAL CHARACTERISTICS (applied to 12c MPO/MTP ) Item Parameter Reference
MPO/MTP TRUNK CABLE FEATURES MTP (US Conec) brand or MPO standard compliant multifiber connector Connector's design complies with IEC 61754-7 standards 4, 8, 12 and 24-fiber with single mode and multimode
More informationSidelighter TM Optical distance to fault measurement module
Sidelighter TM Optical distance to fault measurement module Available only at: Sidelighter TM Introducing the latest in optical fiber measurements and versatility Artisan Laboratories Corporation s hand
More informationFiber Optic Meter Fiber Optic Source
FOM/FOS Fiber Optic Meter Fiber Optic Source Warning To avoid injury: do not service the FOM or FOS unless you are qualified to do so. The service information provided in this document is for the use of
More information40GBASE-ER4 optical budget
40GBASE-ER4 optical budget Pete Anslow, Ciena SMF Ad Hoc, 21 August 2012 1 Introduction The Next Generation 40 Gb/s and 100 Gb/s Optical Ethernet Study Group has an adopted objective: Define a 40 Gb/s
More informationSMF Ad Hoc report. Pete Anslow, Ciena, SMF Ad Hoc Chair. IEEE P802.3bm, Geneva, September 2012
SMF Ad Hoc report Pete Anslow, Ciena, SMF Ad Hoc Chair IEEE P802.3bm, Geneva, September 2012 1 Introduction The Next Generation 40 Gb/s and 100 Gb/s Optical Ethernet Study Group SMF Ad Hoc has: Held two
More informationCC-Link IE Controller Network Compatible. CC-Link IE Controller Network Recommended Network Wiring Parts Test Specifications
Model Title CC-Link IE Controller Network Compatible CC-Link IE Controller Network Recommended Network Wiring Parts Specifications Management number: BAP-C0401-028-A CC-Link Partner Association (1/31)
More information100G-FR and 100G-LR Technical Specifications
100G-FR and 100G-LR Technical Specifications 100G Lambda MSA Rev 1.0 January 9, 2018 Chair Mark Nowell, Cisco Systems Co-Chair - Jeffery J. Maki, Juniper Networks Marketing Chair - Rang-Chen (Ryan) Yu,
More informationPre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017
Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM-2017-2 Date: 05/26/2017 Additional specification information for data communication to cameras and between Library
More informationT-BERD /MTS 5800 Network Tester Fiber Channel Layer 2 Traffic
Quick Card T-BERD /MTS 5800 Network Tester Fiber Channel Layer 2 Traffic This quick card outlines how to configure and run a Fiber Channel Layer 2 Traffic Test with a recommended test suite of Throughput,
More informationRFP LC Uniboot to RFP LC Uniboot Patch cord, 2 fibres, Interconnect tight-buffered cable, LSZH
1 1 9.41 115 0 Pretium EDGE 143 RFP LC Uniboot to RFP LC Uniboot Patch Pretium EDGE Solutions jumpers are integrated reverse -polarity uniboot duplex assemblies that meet the high -density space requirements
More informationIntel Ethernet SFP+ Optics
Product Brief Intel Ethernet SFP+ Optics Network Connectivity Intel Ethernet SFP+ Optics SR and LR Optics for the Intel Ethernet Server Adapter X520 Family Hot-pluggable SFP+ footprint Supports rate selectable
More informationSPECIAL SPECIFICATION 6559 Telecommunication Cable
2004 Specifications CSJ 0015-09-147, etc. SPECIAL SPECIFICATION 6559 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing, training,
More informationRFP LC Uniboot to RFP LC Uniboot Patch cord, 2 fibres, Interconnect tight-buffered cable, LSZH
1 1 9.41 115 0 Pretium EDGE 143 RFP LC Uniboot to RFP LC Uniboot Patch Pretium EDGE Solutions jumpers are integrated reverse -polarity uniboot duplex assemblies that meet the high -density space requirements
More informationInstallation. Step 1 Carefully unpack the package contents.
Installation Important: Please follow the installation procedure below. Improper operation may result if the start-up sequence is not correctly followed. Step 1 Carefully unpack the package contents. Step
More informationFTK200. Users Guide. Optical Fiber Test Kit
FTK200 Optical Fiber Test Kit Users Guide April 2000, Rev. 1 4/03 2000, 2003 Fluke Corporation. All rights reserved. Printed in USA. All product names are trademarks of their respective companies. LIMITED
More informationOPERATIONS GUIDE OWL
t T h Optical Wavelength Laboratories OPERATIONS GUIDE MICRO OWL 2 OPTICAL POWER METER Model Numbers: MO-2 MO-2V Opt ic l a a W v e le n g t h L a b o ra t o r ie s - - n e m ip u q E t s e T OWL r e ib
More informationSECTION TESTING, IDENTIFICATION AND ADMINISTRATION
PART 1 - GENERAL 1.1 SUMMARY SCOPE SECTION 25170 TESTING, IDENTIFICATION AND ADMINISTRATION 1. This section includes the minimum requirements for the testing, certification administration and identification
More information500 Business Center Drive Pittsburgh, PA USA CAGE 1BGJ7. June 2015 Part Numbers FIBER DRIVER
Market Central www.secureswitch.com 500 Business Center Drive Pittsburgh, PA 15205 USA 412.494.2800 CAGE 1BGJ7 June 2015 Part Numbers Fiber Driver ST Female (Lead Free) 61-00091 Fiber Driver - ST - Female
More informationSelection of a cable depends on functions such as The material Singlemode or multimode Step or graded index Wave length of the transmitter
Fibre Optic Communications The greatest advantage of fibre cable is that it is completely insensitive to electrical and magnetic disturbances. It is therefore ideal for harsh industrial environments. It
More informationEmpowering businesses through innovative network solutions.
Empowering businesses through innovative network solutions. We have been pushing boundaries and providing innovative products and solutions to clients around the world for nearly two decades. Our experience
More informationSPECIAL SPECIFICATION 8540 Telecommunication Cable
2004 Specifications CSJ 0914-00-307 & CSJ 0914-25-003 SPECIAL SPECIFICATION 8540 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing,
More informationRobert Burén. Product Manager. Nexans Cabling Solutions. 10G Solutions
Robert Burén Product Manager 10G Solutions Nexans Cabling Solutions 1 10 Gigabit Ethernet.Performance 30 GByte can be transmitted within 24 seconds Example: MRI-scan size is 30GB as average A memory device
More information40/100 Gb ETHERNET CABLING - A PERFECT STORM?
40/100 Gb ETHERNET CABLING - A PERFECT STORM? Mike Gilmore Mike Gilmore Mike Gilmore, Fellow IET Managing Director e-ready Building Standards Activities Member JTC1 SC25 WG3: Generic Cabling Convenor JTC1
More informationDTX. Users Manual. Fiber Test Kit
DTX Fiber Test Kit Users Manual PN 2411346 December 2004 2004 Fluke Corporation. All rights reserved. Printed in USA. All product names are trademarks of their respective companies. LIMITED WARRANTY AND
More informationCable Jacket - The outermost layer of the fiber cable. Application: Types Single mode Multi mode. Simplex or Duplex available
Fiber Optic Products FIBER OPTIC PRODUCTS FIBER OPTIC PATCH CORD CABLE The Construction of a Fiber-Optic Cable Cable Jacket - The outermost layer of the fiber cable. Strengthening fibers - The strengthening
More informationSECTION 4 TABLE OF CONTENTS
Contents Introduction LC, SC and ST Series...4-2 Markets and Applications...4-2 International Standard Documents Compliance...4-2 LC Series Features and Benefits...4-3 LC Standard... 4-4 to 4-5 LC for
More informationPluggable Transceivers Installation Guide
Pluggable Transceivers Installation Guide 121140-04 Published November 2017 Copyright 2017 Extreme Networks, Inc. All rights reserved. Legal Notice Extreme Networks, Inc. reserves the right to make changes
More informationCopper Cabling Troubleshooting Handbook
NETWORKSUPERVISION Copper Cabling Troubleshooting Handbook NETWORKSUPERVISION Table of Contents Introduction 2 Troubleshooting Basics 3 Link Models 4 The automated DTX Series diagnostics 5 Causes of Cabling
More informationTC3301. User's Manual
1000Base-T Ethernet Fiber Optic Converter User's Manual 1. Features p 1000Mbps for twisted pair, and 1000Mbps for fiber p Local Dry Contact Alarm Relay p Multimode (850nm) and Single Mode (1310nm/1550nm)
More informationLight Source. Specification & User Manual
Light Source Specification & User Manual Page 1 of 11 Copyright 2011 reserves the right to modify specifications without prior notice Table of Contents 1. Description and Features.......3 2. Specification......4
More informationMustang Series Fast Ethernet, TFOCA II, 100Base- TX / FX Media Converter, Multimode, 1310nM, USB Powered - 5.0VDC
Mustang Series Fast Ethernet, TFOCA II, 100Base- TX / FX Media Converter, Multimode, 1310nM, USB Powered - 5.0VDC Single Port, Jam Nut, USB Powered FEATURES Compliant with IEEE-802.3:2005 Fast Ethernet
More informationSpecial Specification 6242 Special Fiber Optic Cable
Special Specification 6242 Special Fiber Optic Cable 1. DESCRIPTION 2. MATERIALS The contractor to install, splice, field terminate, test and document all fiber systems. A. General Requirements. Provide
More information400G-FR4 Technical Specification
400G-FR4 Technical Specification 100G Lambda MSA Group Rev 1.0 January 9, 2018 Chair Mark Nowell, Cisco Systems Co-Chair - Jeffery J. Maki, Juniper Networks Marketing Chair - Rang-Chen (Ryan) Yu Editor
More informationDelaware County Community College Project # Marple Campus Renovation - Phase % Construction Documents November 23, 2011
SECTION 271323 - COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 - GENERAL 1.1 DESCRIPTION A. This section provides the specifications for the work related to the optical fiber system in the project.
More informationFiber Meter. Specification & User Manual
Specification & User Manual 2009 Copyright 2009, reserves the right to modify specifications without prior notice Page 1 of 8 Table of Contents 1. Description and Features.......3 2. Specification......4
More informationRFP LC Uniboot to RFP LC Uniboot Patch cord, 2 fibres, Interconnect tight-buffered cable, LSZH
1 1 9.41 115 0 Pretium EDGE 143 RFP LC Uniboot to RFP LC Uniboot Patch Pretium EDGE Solutions jumpers are integrated reverse -polarity uniboot duplex assemblies that meet the high -density space requirements
More informationD131x-apbpmslc TECHNICAL DATA. Fiber Optic Patch Cords Simplex LSZH. Description. Features & Benefits
Description DME PROLINK s patch cords are state-of-art product which are made through advanced polishing and assembly procedures. The multimode patch cords are offered with a Physical Contact (PC) polish
More informationPart 1: How to Avoid Confusion When Testing Insertion Loss According to TIA/EIA-568 B.1 and B.3
Fiber Optic Services And Products EYE ON FIBER Volume 1, Issue 2 August 2002 Part 1: How to Avoid Confusion When Testing Insertion Loss According to TIA/EIA-568 B.1 and B.3 I have been reviewing a Draft
More informationProduct information 19" 1U HD Patch Panel 48xRJ45/s, Cat. 6A, gray, fully populated
Product information 19" 1U HD Patch Panel 48xRJ45/s, Cat. 6A, gray, fully populated R512417 966740615 1 Pcs. 090.6102 Metal patch panel with integrated cable tie shelf. 19" 1U HD patch panel 4 12-port/s
More informationDisplayPort Extender over 2 LC Fibers
DisplayPort Extender over 2 LC Fibers Audio 3GSDI Embedder EXT-DP-CP-2FO User Manual Release A2 DisplayPort Extender over 2 LC Fibers Important Safety Instructions 1. Read these instructions. 2. Keep these
More informationOLP-87/87P. SmartClass Fiber PON Power Meter and Microscope
OLP-87/87P SmartClass Fiber PON Power Meter and Microscope The Viavi Solutions OLP-87 is an FTTx/PON power meter for use in qualifying, activating, and troubleshooting B-PON, E-PON, G-PON, and next-generation,
More informationCable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification
General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall obtain authorization from
More informationMar11 Rev E
Product Specification 108-1832 11Mar11 Rev E MT-RJ Patch Panel and Outlet Jacks (Standard, XG, SECURE and SECURE XG) 1. SCOPE 1.1. Content This specification, which meets the Optical Fiber Cabling Components
More informationHow to Specify MTP Pre-terminated Optical Cabling. January White Paper. Published
White Paper How to Specify MTP Pre-terminated Optical Cabling Published January 2009 The benefits of pre-terminated cabling The two principal advantages of pre- terminated cabling are reduced time on site
More informationU SER S G UIDE. TS2002A Fiber Optic Test Kit
U SER S G UIDE TS2002A Fiber Optic Test Kit TS2002A Test System Black Box TS2002A test system performs optical power loss measurement for both multimode and single-mode LAN/WAN fiber optic installations.
More informationDatasheet: SimpliFiber Pro
Datasheet: SimpliFiber Pro Datasheet: SimpliFiber Pro SimpliFiber Pro makes testing simple Fluke Networks' SimpliFiber Pro Optical Power Meter incorporates new and innovative features to give technicians
More informationScope: Using Wave Division Multiplexing (WDM) for the Protection Data Interface (PDI) of the 7SD5 / 7SD61.
Page 1 of 10 Using Technology for the PDI of the and 7SA522/7SA6 Scope: Using Wave Division Multiplexing () for the Protection Data Interface (PDI) of the 7SD5 /. Two important issues related to differential
More informationSimpliFiber Pro. Users Manual. Optical Power Meter and Fiber Test Kits
SimpliFiber Pro Optical Power Meter and Fiber Test Kits Users Manual September 2008, Rev. 2 6/12 2008, 2010, 2012 Fluke Corporation. All product names are trademarks of their respective companies. LIMITED
More informationDATA CENTER OPTICAL ASSEMBLIES TO SUPPORT QSFP, CFP AND CXP INDUSTRY STANDARD PINOUT CONFIGURATIONS
DATA CENTER OPTICAL ASSEMBLIES TO SUPPORT QSFP, CFP AND CXP INDUSTRY STANDARD PINOUT CONFIGURATIONS Data Center Optical Assemblies to Support QSFP, CFP and CXP Industry Standard Pinout Configurations QSFP,
More informationGigabit Multi-mode SX to Single Mode LX Converter. User s Manual NGF-728 Series. Warning COPYRIGHT
COPYRIGHT Gigabit Multi-mode SX to Single Mode LX Converter User s Manual NGF-728 Series All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted
More informationAerospace Fiber Optics
Aerospace Fiber Optics AFO 101, Session 2 Fiber Optic Assembly Everett Community College. All rights reserved. 1 Session Learning Objectives After completing this session you should be able to: Work safely
More informationHI-DEX PRODUCT SET DATASHEET
APPLICATION HI-DEX is an ultra high-performance, pre-terminated and modular optical fibre cabling system based on MT ferrule connector technology. This product set is designed for installationn in the
More informationfor FOSTEC INC. 1/ 15
TECHNICAL SPECIFICATION for OPTICAL FIBER PATCH CORD / PIGTAIL FOSTEC / 5 . Scope: This specification is applicable to optical fiber patch cord, pigtail and with w optical connectors. The pigtail is single
More informationVersiVision. FVTM4BCxA-CE / FVRM4BCxA-CE MULTIPLEXER SYSTEM 4-CHANNELS DIGITALLY ENCODED VIDEO 2-CHANNELS BI-DIRECTIONAL DATA
VersiVision FVTM4BCxA-CE / FVRM4BCxA-CE MULTIPLEXER SYSTEM 4-CHANNELS DIGITALLY ENCODED VIDEO 2-CHANNELS BI-DIRECTIONAL DATA 4-CHANNELS BI-DIRECTIONAL AUDIO 4-CHANNELS BI-DIRECTIONAL CONTACT CLOSURE 1-CHANNEL
More informationOPERATOR MANUAL OSD351 FIBRE OPTIC CCTV TRANSMITTER CARD
OPERATOR MANUAL OSD351 FIBRE OPTIC CCTV TRANSMITTER CARD OSD351 FIBRE OPTIC CCTV TRANSMITTER CARD Document No:10103701 PAGE 2 C O N T E N T S 1. TECHNICAL SUMMARY...4 1.1 BRIEF DESCRIPTION...4 1.2 TECHNICAL
More informationENGINEERING COMMITTEE Interface Practices Subcommittee SCTE STANDARD SCTE
ENGINEERING MITTEE Interface Practices Subcommittee SCTE STANDARD SCTE 240 2017 SCTE Test Procedures for Testing CWDM Systems in Cable Telecommunications Access Networks NOTICE The Society of Cable Telecommunications
More information40GBd QSFP+ SR4 Transceiver
Preliminary DATA SHEET CFORTH-QSFP-40G-SR4 40GBd QSFP+ SR4 Transceiver CFORTH-QSFP-40G-SR4 Overview CFORTH-QSFP-40G-SR4 QSFP+ SR4 optical transceiver are base on Ethernet IEEE P802.3ba standard and SFF
More informationVersiVision. FVTMHA0xA / FVRMHA0xA 16-CHANNEL DIGITALLY ENCODED VIDEO 1-CHANNEL BI-DIRECTIONAL DATA MULTIPLEXER USER S MANUAL.
VersiVision FVTMHA0xA / FVRMHA0xA 16-CHANNEL DIGITALLY ENCODED VIDEO 1-CHANNEL BI-DIRECTIONAL DATA MULTIPLEXER USER S MANUAL Revision B April 2013 VERSITRON, Inc. 83 Albe Drive / Suite C Newark, DE 19702
More informationPATCH CORDS, PLUGS & CABLES
PATCH CORDS, PLUGS & CABLES 3.1 SECTION CONTENTS Modular Cords...3.2 Cable Assemblies...3.3 Plugs & Connectors...3.4 Bundled Cable...3.5 Category 5e & 6 UTP Cable...3.6 Coax Cable...3.7 Fiber Optic Cable...3.8
More informationStructured Cabling. Product Line Brochure
Structured Cabling Product Line Brochure High Performance and Reliable Solution Infinique structured cabling products are manufactured to international standards and are certified for performance and
More informationStretch More Out of Your Data Centre s Multimode Cabling System
Stretch More Out of Your Data Centre s Multimode Cabling System 1. Introduction: Multimode fibre remains the preferred economic cabling media in the data centre due to its advantage of utilizing relatively
More informationUniprise Solution Brochure. North America/CALA.
Uniprise Solution Brochure North America/CALA Exceptional Value. Headroom to Standards. Simplicity by Design. Uniprise delivers quality, easy-to-use solutions that work from day one to support customer
More informationAXS-200/350 OPTICAL LOSS TEST SET. part of the SharpTESTER Line LAN Applications
OPTICAL LOSS TEST SET AXS-200/350 part of the SharpTESTER Line LAN Applications NETWORK TESTING OPTICAL Features/Benefits Straightforward step-by-step loss testing wizard Clear, LED-based pass/fail assessment
More informationExcel recommends Fluke Networks, this section is written around the use of this range of test equipment.
Testing Excel recommends Fluke Networks, this section is written around the use of this range of test equipment. Twisted Pair Copper This section describes and sets out the requirements for Class D (Cat
More informationINSTALLATION MANUAL FT-FOTR-1VDE-ST-S
INSTALLATION MANUAL FT-FOTR-1VDE-ST-S 1-Channel Digital Duplex Baseband Video Transmitter and Receiver With Reverse Data Transmission & Ethernet Transmission v1.0 4/5/11 1 PACKAGE CONTENTS This package
More informationInstallation Manual. Fiber Optic Transmission Systems. VOS-1VGA-LT/R series 1-Channel VGA Extender over Fiber VOSCOM TECHNOLOGIES CO.
TM Installation Manual Fiber Optic Transmission Systems VOS-1VGA-LT/R series 1-Channel VGA Extender over Fiber VOSCOM TECHNOLOGIES CO.,LIMITED WWW.VOSCOM.COM Important Safety Instructions EN_1 1. Read
More informationSC Connector. Fiber Optic Connectors. MDR Electronics
SC Connector Fiber Optic Connectors MDR Electronics www.mdrelectronics.com Table of contents 1. Introduction 3 2. Image and line drawing 4 3. Types of connector 5 4. Specifications 6 5. Ask for assistance
More informationMT-RJ SECURE Product Expansion Now 10 Variants of the MT-RJ SECURE Products
MT-RJ Product Expansion Now 0 Variants of the MT-RJ Products In response to several customers, the MT-RJ product line has been expanded with an additional six color/key versions. In addition to the original
More information