Model IQ4-PC User Manual Revision Date:

Size: px
Start display at page:

Download "Model IQ4-PC User Manual Revision Date:"

Transcription

1 Basic Specifications Supply Volts 230V 50/60Hz ±15% 115V 50/60Hz ±15% 24V DC (isolated) ±15% Power Consumption Max. 3VA (IQ4-PC-R0) Max. 6VA (IQ4-PC-R2-PSI24-RT) Operating Temperature -5 ~ +60 C Operating Humidity 0 ~ 90% Non condensing Relay Rating SPDT 5A 250VAC 1250VA Max. Mass 300gm (IQ4-PC-R0) 450gm (IQ4-PC-R2-PSI24-RT) Display Digit Height 14mm (0.56") Display Colour High Efficiency Red Display Reading 4 digit - Programmable from -999 to 9999 with programmable decimal point. Display Accuracy < ±0.25% of span ± 1 digit Repeatability (under constant conditions) < ±0.2% of span ± 1 digit Retransmit Accuracy < ±0.25% of span Current limit -PSI or -PSO 25mA Current limit -RT 25mA Dimensions Model IQ4-PC User Manual Revision Date: The IQ4-PC is a 4 digit microprocessor based indicator for process signal inputs. Three basic options are available IQ4-PC-R0 (no relays), IQ4-PC-R1 (1 relay), IQ4-PC-R2 (2 relays). Standard relay contacts are 5A SPDT with gold flashed contacts. This makes them suitable for both power switching or low level signalling. Supply voltage options are 230V 50/60Hz, 115V 50/60Hz, and 24V DC isolated (all ± 15%). Standard process inputs are 0/4-20mA, 0/1-5V, or 0/2-10V, although other input options are available to special order. Other options include an unregulated, current limited, 24VDC power supply for loop excitation, and an isolated 0/4-20mA retransmission signal. This manual describes a 0/4~20mA input however all the information is applicable to any other input. Please check the label on the instrument to see which options are fitted when using this manual

2 IQ4-PC Setting Notes Changing the settings (Programming Mode) In the centre of this manual is a table listing all the available options and how to select them. The key is used to enter the programming mode and accept changes. The and keys step up and down through the menu options and increase or decrease setting values. This instrument will exit programming mode automatically if no keys are pressed for 30 seconds. Any changes which have been made up till this point will be used as the new values. Factory/User Defaults There are two sets of default values, factory defaults and user defaults. Both sets of defaults are identical for a new instrument. After an instrument has been configured to a user s satisfaction all the selected values may be stored as user defaults. (See advanced settings). Most problems with the use of this unit arise from incorrect programming of the various options. Sometimes it is easier to start again rather than try to check every option. For this reason there is an option to reset to the user defaults. Press to enter programming mode - display will read Prog. Press until the display reads rest. Press and display will read ConF asking for confirmation of reset. To confirm reset press and simultaneously and hold. After a few seconds the decimal points will light and the display will return to normal. Release buttons. Any other action will abort the reset. The user defaults may be overwritten with the factory defaults at any time. (See advanced settings). Security Features To prevent unauthorised changes of settings, there are two levels of security options. These are low level security features only and are activated by a series of keystrokes which are difficult to guess or enter accidentally. Full/Reduced Menu This option can be used to restrict access to the important settings (such as calibration) but allows the user to change the relay set points. Menu Lock/Unlock This option allows access to the menu to view settings but not change them. This may be set with either full or reduced menu mode. Application Note 3 This diagram shows how a 4 wire transmitter may be powered from an indicator with the -PSO option. It is important to ensure that the transmitter supply current requirement is less than the rating of the indicator. In this diagram the retransmit option (-RT) is a voltage output instead of current. This is not a common option but is available to special order and is usually 0/1-5V or 0/2-10V

3 Application note 2 This diagram shows how the on-board power supply (-PSI) option is used to power a three wire transmitter. The 0/4-20mA retransmit (-RT option) is shown sinking from a 4-20mA instrument using the instrument s 24V supply. This could also be a separate power supply. The retransmit can drive a load up to 750 ohms from a 24V supply but this decreases if the power supply voltage is lower. Setting signal input range (CAL.0 and CAL.S) The input may be configured for 0-20mA or 4-20mA using the CAL.0 and CAL.S options from the menu. For 0-20mA the settings are CAL.0 = 0.00 and CAL.S = For 4-20mA the settings are CAL.0 = 4.00 and CAL.S =16.00 ( ) Setting display to match process variable (OFSt, SPAn, and deci) Process signals such as 4-20mA may be used to represent many different process values. This indicator may be programmed to display the process signal within the range -999 to 9999 with the decimal positioned where required. Example. To set the display to read to (Offset = -50.0, Span = 200.0) Set OFSt to -500 (will be 50.0 after the decimal is set) Set SPAn to 2000 (will be after the decimal is set) Set deci to Changing the OFSt or SPAn setting resets the relay high (Hi 1, Hi 2) and relay low (Lo 1, Lo 2) settings to disabled (disa). Set these options before setting the relays. Setting Retransmit Output (rt.os and rt.sp) The retransmit output can be programmed to operate over any part of the calibrated range of the instrument. Example. The instrument is calibrated to display 0~100.0 for a 4~20mA input but we wish to retransmit 4~20mA to represent 20.0 ~ (Offset = 20.0, Span = 60.0). Set rt.os to 20.0 Set rt.sp to 80.0 This setting uses the displayed value and cannot be adjusted outside the range of the instrument. This setting can therefore be used for scale expansion but not compression. Bear in mind that the output resolution is only as good as the input resolution. Making the span very small can cause the retransmission signal to respond in a jerky or uneven manner. Fault and error messages (indi) Depending on the status of the indi setting (see programming table), the instrument may display one or more of the following error messages from time to time. The display flashes between the error message and the signal level. The signal is higher than the relay 1 high setting. The signal is lower than the relay 1 low setting. The signal is higher than the relay 2 high setting. The signal is lower than the relay 2 low setting. The signal is above or below the relay 1 settings but the relay is being held(in or out depending on rea.1) by the start up delay. The signal is above or below the relay 2 settings but the relay is being held (in or out depending on rea.2) by the start up delay. The signal is more than 3% above the upper calibration point of the instrument. The signal is more than 3% below the lower calibration point of the instrument. is not disabled by the indi - off setting

4 Relay Operation In normal operation the IQ4-PC is designed to run with both relays energised. Relays de-energise on a fault condition. (This can be reversed using the rea option.) Hi 1, Hi 2 - High setting The relay high setting sets a point above which the relay is de-energised. This may be disabled by setting this option to disa. This is the setting normally used when turning something off when the measured signal is too high (eg. heating elements). Lo 1, Lo 2 - Low setting The relay low setting sets a point below which the relay is de-energised. This may be disabled by setting this option to disa. This is the setting normally used when turning something off when the measured signal is too low (eg. refrigeration). The use of both high and low settings allows a window to be set. Within the window limits the relay is energised. red.1, red.2 - Delay operation This setting delays relay operation when the measured signal changes from a normal to a fault condition. This is useful for the prevention of spurious alarms and trips when the measured signal is erratic eg. vibration monitoring. This value is the same for both Hi and Lo settings. HyS.1, Hys.2 - Hysteresis When the relay has de-energised because of a fault condition, relay hysteresis prevents the relay from energising again until the measured signal has returned to normal and has dropped by this amount below the set point. Setting this value greater than the Hi or Lo values prevents the relay from energising again once a fault has occurred unless the instrument is switched off and on again. This value is the same for both Hi and Lo settings. Hysteresis operates when going from a fault to a normal condition. rea.1, rea.2 - Relay action Changing the Relay Action setting from energised (EnEr) to de-energised (de.en) reverses the relay action. This is the recommended mode when things have to be switched on in a fault condition eg. chemical dosing. This setting affects all the previous relay options as well as the startup delay. Std.1, Std.2 - Startup Delay When the instrument is first switched on the relay is held energised for the period set in this register (0~100secs). Each relay is configured separately. The relay action may be more easily understood by referring to the diagrams below. The red bar indicates when the relay is energised. Application Note 1 The following diagram shows how the on-board 24V power supply (-PSI option) is used to power a two wire loop powered transmitter. The 0/4-20mA retransmit (-RT option) is shown sourcing into a 4-20mA instrument using the on-board 24V supply. The retransmit can drive a load up to 750 ohms. Special retransmit outputs like 0-1mA and 1-5mA are available to special order. Note that the retransmit is isolated from the input and the two 24V power supplies are totally independent of each other. Both 24V power supplies are smoothed but unregulated and are current limited at approximately 25mA

5 Advanced Settings Saving User Defaults Press to enter programming mode - display will read Prog. Press or until the display reads rest. Press and display will read ConF asking for confirmation of reset. Press and simultaneously and hold. After a few seconds the top segment bars will light and the display will return to normal. Release buttons. The current values will now become the user defaults and will be restored whenever a reset is performed. Overwriting User Defaults with Factory Defaults Press to enter programming mode - display will read Prog. Press or until the display reads rest. Press and display will read ConF asking for confirmation of reset. Press and simultaneously and hold. After a few seconds the bottom segment bars will light and the display will return to normal. Release buttons. The factory default values will now become the user defaults and will be restored whenever a reset is performed. Connections The diagrams below shows the rear view of the terminals for the IQ4-PC-R2 with PSI24 option (left) and PSO24 option (right) on pins 9 & 10 (otherwise 9 & 10 are not used). For the PSI option the negative side of the 24V is common to pin 2. Normal Relay Action (EnEr) Reversed Relay Action (de.en) Not all these options are fitted on every instrument. Check the connection diagram on the instrument to see which options are available. The latch is only available on units with relays. When pin 2 is connected to pin 10, both relays remain latched in a fault condition after the fault is removed. Breaking the link (use a N/C contact) returns the relays to normal (providing the fault condition no longer exists)

6 Programming table for Model IQ4-PC-R2 - Highlighted options are only available on the full menu. Relay 2 options are not available on model IQ4-PC-R1. Relay 1 & 2 options are not available on model IQ4-PC-R0. To enter programming mode press. Display will read Prog. Then use or to get to the option required. Key Display Function Key Function Key Function Key Function or Hi 1 Relay 1 high setting Show value or Increase or decrease value ( disa = disabled) Accept value or Lo 1 Relay 1 low setting Show value or Increase or decrease value ( disa = disabled) Accept value or HYS.1 Relay 1 hysteresis Show value or Increase or decrease value Accept value or Std1 Relay 1 startup delay Show value (seconds) or Increase or decrease value Accept value or red.1 Relay 1 operate delay Show value (seconds) or Increase or decrease value Accept value or rea.1 Relay 1 action Show options or EnEr./dE.En (Normal=energised/de-energised) Accept value or Hi 2 Relay 2 high setting Show value or Increase or decrease value ( disa = disabled) Accept value or Lo 2 Relay 2 low setting Show value or Increase or decrease value ( disa = disabled) Accept value or HYS.2 Relay 2 hysteresis Show value or Increase or decrease value Accept value or Std2 Relay 2 startup delay Show value (seconds) or Increase or decrease value Accept value or red.2 Relay 2 operate delay Show value (seconds) or Increase or decrease value Accept value or rea.2 Relay 2 action Show options or EnEr./dE.En (Normal=energised/de-energised) Accept value or indi Fault indication Show options or on/off Accept value or OFSt Display Offset Show value or Increase or decrease value Accept value or SPAn Display Span Show value or Increase or decrease value Accept value or deci Decimal Show position or 9999/999.9/99.99/9.999 Accept value or rt.os Retransmit Offset Show value or Increase or decrease value Accept value or rt.sp Retransmit Span Show value or Increase or decrease value Accept value or CAL.0 Calibrate zero Show value or Increase or decrease value Accept value or CAL.S Calibrate span Show value or Increase or decrease value Accept value or rest Reset to user defaults ConF (confirm) or End End Programming mode Return to monitoring Any of above End Programming mode and Return to monitoring Security Features - In the locked option, values may be viewed but not changed. and Confirm reset Do not confirm reset Key Display Function Key Display Key Display Key Function Prog Programming mode and hold process value then software revision number keep holding and hold. Then release Flash between FuLL/rEdu release at required option sets full or reduced menu keep holding and hold. Then release Flash between Loc/U.Loc release at required option sets lock/unlock

DCP100 Digital Control Programmer Specifications

DCP100 Digital Control Programmer Specifications DCP100 Digital Control Programmer Specifications EN01-6028 October 1996 Overview The DCP100 is a microprocessor based 1 /4 DIN programmer/controller for process variable versus time control of temperature,

More information

HS-509 VIBRATION TRIP MODULE

HS-509 VIBRATION TRIP MODULE HS-509 VIBRATION TRIP MODULE 1. Overview The HS-509 is a configurable trip amplifier capable of accepting a 4-20mA signal from a HS-420 sensor and providing two trip action relay outputs along with an

More information

ACT 10 Digital Keypad Operating & Installation Instructions This manual is found at

ACT 10 Digital Keypad Operating & Installation Instructions This manual is found at ACT 10 Digital Keypad Operating & Installation Instructions 18-00001 This manual is found at www.eaglesecuritysolutions.co.uk Installation Notes Always remember to factory default the controller before

More information

263 Series LED Bargraph Indicator and Controllers

263 Series LED Bargraph Indicator and Controllers 263 Series LED Bargraph Process Control Water Treatment High resolution 51 segment LED Bargraph for easy reading Accuracy 1% Red display Vertical or Horizontal mounting & stackable Connection Diagrams

More information

DPM 942-FPSI 4-20mA Loop Meter with Programmable Backlighting

DPM 942-FPSI 4-20mA Loop Meter with Programmable Backlighting 4-0mA Loop Meter with Programmable Backlighting ORDERING INFORMATION Standard Instrument (panel meter, fixing kit, data sheet) DPM 94-FPSI FEATURES 9mm (0.7 ) digit height Dual colour backlight with programmable

More information

ORM0022 EHPC210 Universal Controller Operation Manual Revision 1. EHPC210 Universal Controller. Operation Manual

ORM0022 EHPC210 Universal Controller Operation Manual Revision 1. EHPC210 Universal Controller. Operation Manual ORM0022 EHPC210 Universal Controller Operation Manual Revision 1 EHPC210 Universal Controller Operation Manual Associated Documentation... 4 Electrical Interface... 4 Power Supply... 4 Solenoid Outputs...

More information

Panel cutout required: 1.772" x 3.622" (45mm x 92mm) 1.76" (45mm) 2.45" (62mm) 3.20" (81mm) 3.60" (91mm) 0.59" (15mm) Special Features

Panel cutout required: 1.772 x 3.622 (45mm x 92mm) 1.76 (45mm) 2.45 (62mm) 3.20 (81mm) 3.60 (91mm) 0.59 (15mm) Special Features NEMA4X, IP65 Front Bezel Meter with Relays Option RELAY2 RELAY1 24V OUT POWER 4 3 2 1 6 5 2 1 2 1 NO NC COM NO NC COM RTD TC P P RTD 3 4 1 2 5 TC 6 SWITCH Rear View Gasket APM765 Panel Meter Description

More information

Installation and Setting up Instructions for the 990 Signal Conditioning Instrument

Installation and Setting up Instructions for the 990 Signal Conditioning Instrument Installation and Setting up Instructions for the 990 Signal Conditioning Instrument Contents Page 1.0 Overview... 3 2.0 Installation.. 4 2.1 Electrical connections... 4 2.2 Cable selection... 4 2.3 Electrical

More information

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV MG-XV operating instruction Measuring of norm signals, 4-8-digit Panel instrument type MG-BV Construction instrument type MG-AV Contents 1. Brief description... 3 2. Safety instructions... 3 2.1. Proper

More information

Figure 1: Standard 906 Sensor and Pulser Disc. Figure 2: Standard 906 Sensor and Pulser Wrap

Figure 1: Standard 906 Sensor and Pulser Disc. Figure 2: Standard 906 Sensor and Pulser Wrap Description: The TR5000 is a Full Logic Control Process ratemeter that can display up to three separate values of rate and compare them to programmable set points. Rates A & B can be programmed by the

More information

Description. Specifications and Ordering Information 1900/27 Vibration Monitor

Description. Specifications and Ordering Information 1900/27 Vibration Monitor R Specifications and Ordering Information 1900/27 Vibration Monitor Description The 1900/27 is a single-channel, stand-alone, locally mounted vibration monitor. It can be used as a stand-alone machinery

More information

Wall-/Pipe-Mount Level Indicator

Wall-/Pipe-Mount Level Indicator Data Sheet SS/_4 Wall-/Pipe-Mount Level Indicator High visibility 5-digit LED display clear multi-functional indication Analog and 2-relay outputs as standard high, low, latch and rate alarms, plus isolated

More information

UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load Cell

UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load Cell 99 Washington Street Melrose, MA 02176 Fax 781-665-0780 TestEquipmentDepot.com UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load

More information

UDC100 Universal Digital Controller. Specification. Overview. Features. Features, continued /99 Page 1 of 4

UDC100 Universal Digital Controller. Specification. Overview. Features. Features, continued /99 Page 1 of 4 UDC100 Universal Digital Controller 51-52-03-29 11/99 Page 1 of 4 Specification Overview The UDC100 Universal Digital Controller is a microprocessor-based 1/4 DIN low cost temperature controller. It combines

More information

Single Axis Position Controller

Single Axis Position Controller SERIES P9511 Single Axis Position Controller Compact Construction Simple Go-to operation Integrated Relay Output Integrated Mains Power Supply ELEKTRO-TRADING sp. Z o.o. 44-109 Gliwice, ul. Mechaników

More information

Standard signal metering in wall-mounting case

Standard signal metering in wall-mounting case User manual AKV-2VR4C Standard signal metering in wall-mounting case Technical features: Digit height: 20 mm Colour: red Range of display: -999 9999 Wall-mounting case: black, made of ABS-plastic Protection

More information

Vorne Industries. 87/719 Analog Input Module User's Manual Industrial Drive Itasca, IL (630) Telefax (630)

Vorne Industries. 87/719 Analog Input Module User's Manual Industrial Drive Itasca, IL (630) Telefax (630) Vorne Industries 87/719 Analog Input Module User's Manual 1445 Industrial Drive Itasca, IL 60143-1849 (630) 875-3600 Telefax (630) 875-3609 . 3 Chapter 1 Introduction... 1.1 Accessing Wiring Connections

More information

SCALE & WEIGHT DISPLAYS

SCALE & WEIGHT DISPLAYS The MICRO SERIES SCALE & WEIGHT DISPLAYS LARGE DIGIT MODELS Mighty-5S DPM MODELS Micro-S & Mighty-1S Mighty-1S Micro-S ELECTRO-NUMERICS, INC. Introduction The Electro-Numerics family of Digital Panel Meters

More information

TDEPD. Field-Programmable Pressure Switch/Transducer with Integrated LED Display. Programming Sequence Manual

TDEPD. Field-Programmable Pressure Switch/Transducer with Integrated LED Display. Programming Sequence Manual TDEPD Field-Programmable Pressure Switch/Transducer with Integrated LED Display Programming Sequence Manual Wiring Diagram Pin5 Maintenance Mode + Gray Vent Pin2 Digital Output 2 +/ Analog Output + White

More information

Intelligent Security and Fire Ltd

Intelligent Security and Fire Ltd User Manual Product ranges covered by this manual Vi-P14 Vi-P14A Document Reference Date Firmware Vi-Q4C1 Viq601a.doc 26/11/2009 From Viq001a21 Videoswitch Telephone 01252-851510 Ocean House, Redfields

More information

AK-PVE4 Operating Instructions. Measuring of norm signals in wall-type units. Performance:

AK-PVE4 Operating Instructions. Measuring of norm signals in wall-type units. Performance: AK-PVE4 Operating Instructions Measuring of norm signals in wall-type units 1 2 P Performance: Digit heights: 20 mm Colour: red Display range: -999 9999 Wall-type housing: light grey made of ABS-plastic

More information

ProVu PD6000 Process Meter

ProVu PD6000 Process Meter Congratulations on your purchase of the ProVu PD6000 process meter! This quick start guide will briefly describe some of the common setup procedures for this meter. This guide includes: Basic Wiring for

More information

2 CHANNEL RECEIVER DISPLAY POTENTIOMETER COM2 NC2 NO2

2 CHANNEL RECEIVER DISPLAY POTENTIOMETER COM2 NC2 NO2 2 CHANNEL RECEIVER RECTSHIVE915-DX Please read this manual carefully before installing the product. 1 DESCRIPTION Receiver Rolling Code, 2 channels with dry contact relay output 20A a 12 Vdc. Programming

More information

1900/25 Vibration Monitor

1900/25 Vibration Monitor 1900/25 Vibration Monitor BENTLY NEVADA MADE IN USA VIBRATION MONITOR OK ALERT DANGER BYPASS DISPLAY MOD E RESET NORMAL ALERT ALERT ADJUST LEVEL DANGER DANGER LEVEL ADJUST BUFFER ED TRANSDUCER 1 IN/SEC

More information

VLC-3 USER'S MANUAL. Light Program Controller. M rev. 04 K rev. 00 & ( ( 5, 352*5$0 1 : $ 2 ' 6(77,1*6 )81&7,216

VLC-3 USER'S MANUAL. Light Program Controller. M rev. 04 K rev. 00 & ( ( 5, 352*5$0 1 : $ 2 ' 6(77,1*6 )81&7,216 Light Program Controller VLC-3 USER'S MANUAL +50,1 +50,1 1 : $ ' 2 7. 6 8 ' 5, 7 6 6. $ ( 3 352*5$0 0,16(& )81&7,216 6(77,1*6 & 8 5 5 ( 1 7 3 ( 5, 2 ' M 890-00189 rev. 04 K 895-00406 rev. 00 GENERAL...

More information

Troubleshooting. 1. Symptom: Status indicator (Red LED) on SSR is constant on. 2. Symptom: Output indicator (Yellow LED) on SSR is flashing.

Troubleshooting. 1. Symptom: Status indicator (Red LED) on SSR is constant on. 2. Symptom: Output indicator (Yellow LED) on SSR is flashing. Product Data Electrical Data SST (Transmitter) SSR (Receiver) Supply voltage 18 30 V dc Max. Voltage ripple 15 % (within supply range) Current consumption 100 ma (RMS) 75 ma Digital - 100 ma Max. outputs

More information

Radio Thermostat Clock

Radio Thermostat Clock Radio Thermostat Clock Installation & User Instructions Part number: ZU0800009 80.10.1375.7_feeling_ks_fer_en.indd 1 18.04.2013 11:25:42 Table of contents Safety instructions... 3 Product details... 4

More information

F90 Series (Rate Indicators / Controllers) INSTRUCTION MANUAL

F90 Series (Rate Indicators / Controllers) INSTRUCTION MANUAL F90 Series (Rate Indicators / Controllers) INSTRUCTI MANUAL FEATURES DIN 48 9mm DIN 48 9mm Standard Panel Size Monitor & Preset Type 1 Monitor type with the large display 2 Preset Type can make the upper/lower

More information

LOW-COST, 3 1/2 DIGIT DC VOLTMETERS MODEL 201A & 201AN OPTION 201AN-AC / 301AN

LOW-COST, 3 1/2 DIGIT DC VOLTMETERS MODEL 201A & 201AN OPTION 201AN-AC / 301AN LOW-COST, 3 1/2 DIGIT DC VOLTMETERS MODEL 201A & 201AN OPTION 201AN-AC / 301AN STANDARD FEATURES ±1,999-count display span ±200 mv to ±200 Vdc ranges True-differential input with 80 db CMR 3-wire ratio

More information

COMPANY. MX 9000 Process Monitor. Installation, Operating & Maintenance Manual AW-Lake Company. All rights reserved. Doc ID:MXMAN082416

COMPANY. MX 9000 Process Monitor. Installation, Operating & Maintenance Manual AW-Lake Company. All rights reserved. Doc ID:MXMAN082416 COMPANY MX 9000 Process Monitor Installation, Operating & Maintenance Manual 2016 AW-Lake Company. All rights reserved. Doc ID:MXMAN082416 1 Table of Contents Unpacking...3 Quick Guide...3 Connect to Sensor...3

More information

LAUREL ELECTRONICS, INC.

LAUREL ELECTRONICS, INC. LAUREL ELECTRONICS, INC. Laureate Digital Panel Meter for Process, Strain & Potentiometer Follower Signals Features Selectable ±0.2, ±2, ±20, ±200, ±300 & ±600 Vdc voltage ranges Selectable ±2, ±20, ±200

More information

Electronic Panel Meters DIGEM Preference Program Process control, automation & laboratory uses Class 0.01 to 1 Current, Voltage, Frequency,

Electronic Panel Meters DIGEM Preference Program Process control, automation & laboratory uses Class 0.01 to 1 Current, Voltage, Frequency, Electronic Panel Meters DIGEM Preference Program Process control, automation & laboratory uses Class 0.01 to 1 Current, Voltage, Frequency, Temperature, RPM, Pressure, etc. LED/ LCD displays 1999 to 99999

More information

Standard RS232 RS ma

Standard RS232 RS ma 1 / 5 CONTROL AND VISUALIZATION OF AC CURRENT IN SINGLE PHASE LINES BY EXTERNAL SHUNT Function Operating mode Current control Frequency control DC component control Shunt Timer Resolution Current precision

More information

Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module

Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module Helvar Data is subject to change without notice. www.helvar.com i Contents Section Page Introduction 1 Installation 2 1. Attach

More information

MF-PFT. Programmable differential pressure transmitter for pressure or flow measurement and control. DIL1 Output/Utsignal

MF-PFT. Programmable differential pressure transmitter for pressure or flow measurement and control. DIL1 Output/Utsignal Operating and installation manual Programmable differential pressure transmitter for pressure or flow measurement and control. MF-PFT Instruction : Mi-202gb_060907 NOTE! Read the entire instruction carefully

More information

Micro-DCI 53ML5100 Manual Loader

Micro-DCI 53ML5100 Manual Loader Micro-DCI 53ML5100 Manual Loader Two process variable inputs Two manually controlled current outputs Multiple Display Formats: Dual Channel Manual Loader, Single Channel Manual Loader, Manual Loader with

More information

SINGLE ZONE CLIMATE ZONING SYSTEM. Technical Manual. Polyaire Pty Ltd

SINGLE ZONE CLIMATE ZONING SYSTEM. Technical Manual. Polyaire Pty Ltd SINGLE ZONE CLIMATE ZONING SYSTEM Technical Manual Polyaire Pty Ltd 11-13 White Road GEPPS CROSS South Australia, 5094 Tel: (08) 8349 8466 Fax: (08) 8349 8446 www.polyaire.com.au CONTENTS Features 1 Application

More information

FRQM-2 Frequency Counter & RF Multimeter

FRQM-2 Frequency Counter & RF Multimeter FRQM-2 Frequency Counter & RF Multimeter Usage Instructions Firmware v2.09 Copyright 2007-2011 by ASPiSYS Ltd. Distributed by: ASPiSYS Ltd. P.O.Box 14386, Athens 11510 (http://www.aspisys.com) Tel. (+30)

More information

Solid-State Digital Timer

Solid-State Digital Timer Solid-State Digital Timer 1/16 DIN, Digital-Set Timer with 0.1 Second to 9,990 Hours Range 8 field-selectable operation modes Universal AC/DC supply voltage timers available Operations include ON-delay,

More information

SIGNET 5500 Flow Monitor ENGLISH

SIGNET 5500 Flow Monitor ENGLISH ENGLISH 3.0901 H (6/01) English CAUTION! Remove power to unit before wiring input and connections. Follow instructions carefully to avoid personal injury. Contents 1. Power Connections 2. Compatible Sensor

More information

Veeder-Root brand Series C628 Dual Preset Counter (C628-8XXX) Technical Manual

Veeder-Root brand Series C628 Dual Preset Counter (C628-8XXX) Technical Manual Introduction Your Veeder-Root brand C628 Dual Preset Counter is one model in a family of 1/8 DIN units which offers breakthrough display technology as well as easy-to-program single-line parameters. Designed

More information

Thank you for purchasing this product. If installing for someone else, please ensure that the instructions are handed to the householder.

Thank you for purchasing this product. If installing for someone else, please ensure that the instructions are handed to the householder. Instruction Manual TPST501 (569568) - BOSS TM Universal mable Room Thermostat (Wired) (7 day, 5/2 day and 24 hour programme options) Thank you for purchasing this product. If installing for someone else,

More information

12months. on-site warranty. DZE ELECTRONIC PRESSURE SWITCH for detection of overload per EN 81 2 featuring two adjustable switching points

12months. on-site warranty. DZE ELECTRONIC PRESSURE SWITCH for detection of overload per EN 81 2 featuring two adjustable switching points BUCHER PRODUCTS AVAILABLE FROM HYDRATEC DZE ELECTRONIC PRESSURE SWITCH for detection of overload per EN 81 2 featuring two adjustable switching points 12months on-site warranty All our work comes with

More information

Operating Instructions

Operating Instructions CNTX Contrast sensor Operating Instructions CAUTIONS AND WARNINGS SET-UP DISTANCE ADJUSTMENT: As a general rule, the sensor should be fixed at a 15 to 20 angle from directly perpendicular to the target

More information

02/11/2015

02/11/2015 DIN Rail Mount 17.5 mm MUS/MUSF 80 AC/DC Part number 84872141 Control relays monitoring their own power supply - MUS : Over/undervoltage control Selectable latching (memory) function - MUSF : Over/undervoltage

More information

Process Transmitter RMA 422

Process Transmitter RMA 422 Technical Information TI 072R/24/ae Process Transmitter RMA 422 Multi-functional 1-2 channel top hat DIN rail unit with loop power supply, alarm set point monitoring, mathematics function and 1-2 analog

More information

Controllers, series CON Indicators, series IND. Controllers and indicators

Controllers, series CON Indicators, series IND. Controllers and indicators JJ Controllers, series CN JJ Indicators, series IND Controllers and indicators DS_Controllers_and_indicators 06/2016 161 Effective implementation of visualisation and control tasks Electronic indicating

More information

Thank you for purchasing this product. If installing for someone else, please ensure that the instructions are handed to the householder.

Thank you for purchasing this product. If installing for someone else, please ensure that the instructions are handed to the householder. Instruction Manual TPSE201 (181422) - BOSS TM Universal Programmer TPSE101 (569565) - BOSS TM Universal Timeswitch Thank you for purchasing this product. If installing for someone else, please ensure that

More information

Set Point Controller OC557. Operator s Manual

Set Point Controller OC557. Operator s Manual OC557_Manual_GB1206D Set Point Controller OC557 4 20mA Input Operator s Manual METRIX ELECTRONICS LTD. Tel: +44 (0)845 034 3234 Minchens Court, Minchens Lane Fax: +44 (0)845 034 3233 Bramley, Tadley, Hampshire

More information

INSTALLATION & OPERATING INSTRUCTIONS SINGLE/TWO CHANNEL 24HR/7 DAY TIMER. Cat No. TR671/TR672TOP

INSTALLATION & OPERATING INSTRUCTIONS SINGLE/TWO CHANNEL 24HR/7 DAY TIMER. Cat No. TR671/TR672TOP SINGLE/TWO CHANNEL 24HR/7 DAY TIMER Cat No. TR671/TR672TOP INSTALLATION & OPERATING INSTRUCTIONS TR671/TR672TOP 24Hr/7 Day 1/2 Channel Digital TOP Module (without Power Supply) Please read the instructions

More information

Instruction Manual. Universal Flow Controller Model 261 / 261-EC-01

Instruction Manual. Universal Flow Controller Model 261 / 261-EC-01 Universal Flow Controller Model 261 / 261-EC-01 Instruction Manual Type ARS 261-EC 01 Art.-no: 82212264 Table of Contents 1. Safety Instructions 2. Product ID - Dimensions 3. Function Description 4. Installation

More information

ED3. Digital Encoder Display Page 1 of 13. Description. Mechanical Drawing. Features

ED3. Digital Encoder Display Page 1 of 13. Description. Mechanical Drawing. Features Description Page 1 of 13 The ED3 is an LCD readout that serves as a position indicator or tachometer. The ED3 can display: Speed or position of a quadrature output incremental encoder Absolute position

More information

BE3-GPR GENERATOR PROTECTIVE RELAY

BE3-GPR GENERATOR PROTECTIVE RELAY BE3-GPR GENERATOR PROTECTIVE RELAY Behind-the-Panel Mounting Semi-flush Mounting Basler Electric s BE3-GPR generator protective relay offers multiple protective features in a single package. Its microprocessor-based

More information

TP7001 Range Electronic 7 Day Programmable Room Thermostat. Danfoss Heating. Installation Guide

TP7001 Range Electronic 7 Day Programmable Room Thermostat. Danfoss Heating. Installation Guide TP7001 Range Electronic 7 Day Programmable Room Thermostat Danfoss Heating Installation Guide For a large print version of these instructions please call Marketing on 0845 121 7400. Certification Mark

More information

ORDERING Page 6 BASLER RELAY STANDARDS, DIMENSIONS, ACCESSORIES Request bulletin SDA

ORDERING Page 6 BASLER RELAY STANDARDS, DIMENSIONS, ACCESSORIES Request bulletin SDA BE1-59NC CAPACITOR NEUTRAL OVERVOLTAGE RELAY The BE1-59NC Capacitor Neutral Overvoltage Relay provides sensitive protection for capacitor banks. ADDITIONAL INFORMATION INSTRUCTION MANUAL ADVANTAGES Helps

More information

User Manual M1. Direct current / Direct voltage signals 0-20 ma, 4-20 ma, 0-10 VDC. Technical features:

User Manual M1. Direct current / Direct voltage signals 0-20 ma, 4-20 ma, 0-10 VDC. Technical features: M1_61GB.pdf update: 17.09.2014 72x36 User Manual M1 Direct current / Direct voltage signals 0-20 ma, 4-20 ma, 0-10 VDC Technical features: red display of -1999 9999 digits (optional: green, orange or blue

More information

OPERATING AND SAFETY INSTRUCTIONS for DIGITAL TEMPERATURE CONTROLS (PLSM SERIES)

OPERATING AND SAFETY INSTRUCTIONS for DIGITAL TEMPERATURE CONTROLS (PLSM SERIES) user instructions 711 HULMAN STREET PO BOX 2128 TERRE HAUTE, IN 47802 812-235-6167 FAX 812-234-6975 OPERATING AND SAFETY INSTRUCTIONS for DIGITAL TEMPERATURE CONTROLS (PLSM SERIES) Models: 104A PLSM112;

More information

SI-510 DUAL TRIP AMPLIFIER

SI-510 DUAL TRIP AMPLIFIER SI-510 DUAL TRIP AMPLIFIER WITH ISOLATED RE-TRANSMITTED OUTPUT QM001 Issue 3 Page 1 CTENTS 1. OVERVIEW 3 1.1 Product Identification 3 1.2 Standard SI-510 Modules 4 2. SI-510 FUNCTIS 4 2.1 Display 4 2.2

More information

USER & ENGINEER INSTRUCTION MANUAL

USER & ENGINEER INSTRUCTION MANUAL USER & ENGINEER INSTRUCTION MANUAL BENSON CP4 USER INSTRUCTIONS CONTENTS PAGE SUBJECT PAGE No. Contents Page... 1 CP4 Basic Setting Guide... 2-3 Standard Terms... 4 Normal RUN Mode... 4 Override... 5

More information

SPA MICROPROCESSOR SPEEDOMETER INSTALLATION AND OPERATING MANUAL PAGE 2...INSTRUMENT FEATURES PAGE 3...OPERATING INSTRUCTIONS PAGE 3...

SPA MICROPROCESSOR SPEEDOMETER INSTALLATION AND OPERATING MANUAL PAGE 2...INSTRUMENT FEATURES PAGE 3...OPERATING INSTRUCTIONS PAGE 3... SPA MICROPROCESSOR SPEEDOMETER INSTALLATION AND OPERATING MANUAL PAGE 2...INSTRUMENT FEATURES PAGE 3...OPERATING INSTRUCTIONS PAGE 3...MENU SYSTEM PAGE 7...INSTALLATION DIAGRAMS PAGE 10...INSTALLATION

More information

SAUTER flexotron RDT405 Manual

SAUTER flexotron RDT405 Manual SAUTER flexotron 400 - RDT405 Manual P100012100 Table of contents DISCLAIMER The information in this manual has been carefully checked and is believed to be correct. Fr. Sauter AG however, makes no warranties

More information

Location. Electrical. Loads. 2-wire mains-rated, 0.5 mm² to 1.5 mm² Max. length: 300 m (with 1.5 mm² cable). Example: Belden 8471.

Location. Electrical. Loads. 2-wire mains-rated, 0.5 mm² to 1.5 mm² Max. length: 300 m (with 1.5 mm² cable). Example: Belden 8471. Product Description Installation and User Guide Transistor Dimmer (454) The DIN rail mounted 454 is a fourchannel transistor dimmer that can operate in one of two modes: leading edge or trailing edge.

More information

ALM-6813/6812 INSTALLATION AND PROGRAMMING MANUAL

ALM-6813/6812 INSTALLATION AND PROGRAMMING MANUAL ALM-6813/6812 INSTALLATION AND PROGRAMMING MANUAL Installation and programming Manual v2.2 1 MARSS Solar Defender SYSTEM This guidebook provides the essential instructions to install and configure the

More information

XTM72E & F Real-Time Clock Modules

XTM72E & F Real-Time Clock Modules Capricorn Controls Ltd Data & Application Notes Page 1 of 8 XTM72E & F Real-Time Clock Modules Originally designed to compliment our wide range of Gen-Set controls, these DC powered Real-Time-Clocks have

More information

2 WIRE - LOOP POWERED TRANSMITTER FOR PT100 AND NI100 PROBES

2 WIRE - LOOP POWERED TRANSMITTER FOR PT100 AND NI100 PROBES EN K20RTD 2 WIRE - LOOP POWERED TRANSMITTER FOR PT00 AND NI00 PROBES General Description The K20RTD instrument converts a temperature signal read by a PT00 (EN 60 75) or NI00 probe with connection by 2,

More information

Ocean Sensor Systems, Inc. Wave Staff, OSSI F, Water Level Sensor With 0-5V, RS232 & Alarm Outputs, 1 to 20 Meter Staff

Ocean Sensor Systems, Inc. Wave Staff, OSSI F, Water Level Sensor With 0-5V, RS232 & Alarm Outputs, 1 to 20 Meter Staff Ocean Sensor Systems, Inc. Wave Staff, OSSI-010-002F, Water Level Sensor With 0-5V, RS232 & Alarm Outputs, 1 to 20 Meter Staff General Description The OSSI-010-002E Wave Staff is a water level sensor that

More information

MENU EXECUTE Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free

MENU EXECUTE Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free Instruction Manual Model 2016-1250 Downconverter May 2009 Rev A F=2501.750 G=+25.0 MENU MODEL 2016 DOWNCONVERTER CROSS TECHNOLOGIES INC. ALARM REMOTE POWER EXECUTE Data, drawings, and other material contained

More information

Operating instructions Electronic preset counter Type series 717

Operating instructions Electronic preset counter Type series 717 Operating instructions Electronic preset counter Type series 717 1. Description 5.98.3_gb 6-digit adding/subtracting counter with two presets Very bright 8mm high LED display Counting and preset range

More information

DS 400 P. Intelligent Electronic Pressure Switch in Hygienic Stainless Steel Ball Housing. on hygienic process connections

DS 400 P. Intelligent Electronic Pressure Switch in Hygienic Stainless Steel Ball Housing. on hygienic process connections Intelligent Electronic Pressure Switch in Hygienic Stainless Steel Ball Housing Description The electronic pressure switch is the successful combination of hygienic process connections with flush welded

More information

48x24. Options ORDER NUMBER OF TYPE PFL B

48x24. Options ORDER NUMBER OF TYPE PFL B Frequency metering (0.01 Hz 9999 Hz) with 2 setpoints Free scalable indication and setpoints from 0 up to +9999 Standard: min/max memory - option: analogue output Allow to be placed side by side in grid

More information

800 Displaying Series Flowmeter

800 Displaying Series Flowmeter TECHNICAL PRODUCT INSTRUCTION SHEET 800 Displaying Series Flowmeter OVERVIEW The principle of operation is very simple. A jet of liquid is directed at a free running Pelton wheel turbine in a specially

More information

Model RM4-AI DIN Rail Process Monitor/Controller Inputs from 0 to 5 Amps True RMS display Operation and Instruction Manual

Model RM4-AI DIN Rail Process Monitor/Controller Inputs from 0 to 5 Amps True RMS display Operation and Instruction Manual Model RM4-AI DIN Rail Process Monitor/Controller Inputs from 0 to 5 Amps True RMS display Operation and Instruction Manual AMALGAMATED INSTRUMENT CO PTY LTD ACN: 001 589 439 Unit 5, 28 Leighton Place Hornsby

More information

Sequential and Combination Timer TK-415 with RS-232 communication

Sequential and Combination Timer TK-415 with RS-232 communication NOVATEK-ELECTRO LTD. Sequential and Combination Timer TK-415 with RS-232 communication OPERATION MANUAL WWW.NOVATEK-ELECTRO.COM/EN 2011 1. GENERAL PROVISIONS 1.1. BASIC FUNCTIONS - microprocessor controlled.

More information

FIELD MOUNTED RATE TOTALISER MODEL 202D

FIELD MOUNTED RATE TOTALISER MODEL 202D FIELD MOUNTED RATE TOTALISER MODEL 202D 16 June 2003 Introduction 1 1. INTRODUCTION The Model 202Di Rate Totaliser is a microprocessor based instrument which accepts a frequency or pulse input from

More information

C8000. sync interface. External sync auto format sensing : AES, Word Clock, Video Reference

C8000. sync interface. External sync auto format sensing : AES, Word Clock, Video Reference features Standard sync module for a frame Internal sync @ 44.1 / 48 / 88.2 / 96kHz External sync auto format sensing : AES, Word Clock, Video Reference Video Reference : Black Burst (NTSC or PAL) Composite

More information

Assembly. Front view. LEDs. Parametrization interface. Power Bus

Assembly. Front view. LEDs. Parametrization interface. Power Bus otation Speed Monitor Features Assembly 1-channel signal conditioner 2 V DC supply Input for 2- or -wire sensors Input frequency 10 mhz... 50 khz elay contact output Start-up override and restart inhibit

More information

T775U Series 2000 Electronic Stand-Alone Controller

T775U Series 2000 Electronic Stand-Alone Controller T775U Series 2000 Electronic Stand-Alone Controller INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The T775 electronic stand-alone controllers are the next generation of universal controls capable of remote

More information

LAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description

LAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description Description LAUREL ELECTRONICS, INC. Features Laureate Digital Panel Meter for Load Cell & Microvolt Input 20, 50, 100, 250 & 500 mv ranges Span adjust from 0 to ±99,999, zero adjust from -99,999 to +99,999

More information

Signet Chlorine Transmitter

Signet Chlorine Transmitter Signet 8630-3 Chlorine Transmitter English 3-8630.090-3 Rev. D 08/10 English Caution! Remove power to unit before wiring input or output connections. Follow instructions carefully to avoid personal injury

More information

RS Part No Instruction Manual Solid State DVR. (Single Chanel for Mobile) SSD01CA

RS Part No Instruction Manual Solid State DVR. (Single Chanel for Mobile) SSD01CA RS Part No. 696-1210 Instruction Manual Solid State DVR (Single Chanel for Mobile) RS PART NO.: 696-1210 MJPEG 1CH CAR DVR (Compact size 1ch Stand Alone DVR) Simple & Max Low cost but great guality MJPEG

More information

Triple RTD. On-board Digital Signal Processor. Linearization RTDs 20 Hz averaged outputs 16-bit precision comparator function.

Triple RTD. On-board Digital Signal Processor. Linearization RTDs 20 Hz averaged outputs 16-bit precision comparator function. Triple RTD SMART INPUT MODULE State-of-the-art Electromagnetic Noise Suppression Circuitry. Ensures signal integrity even in harsh EMC environments. On-board Digital Signal Processor. Linearization RTDs

More information

FREQUENCY CONVERTER. MULTIPLE OUTPUT WIDEBAND Ku AND Ka DOWNCONVERTERS. Narda-MITEQ FEATURES OPTIONS

FREQUENCY CONVERTER. MULTIPLE OUTPUT WIDEBAND Ku AND Ka DOWNCONVERTERS. Narda-MITEQ FEATURES OPTIONS MULTIPLE OUTPUT WIDEBAND Ku AND Ka DOWNCONVERTERS FEATURES Small weather resistant enclosure Automatic 5/10 MHz internal/external reference selection 10/100 Base-T Ethernet and RS-485/RS-422 remote control

More information

Electronic Timer Control Day Astronomic Electronic Control

Electronic Timer Control Day Astronomic Electronic Control Electronic Timer Control - 365-Day Astronomic Electronic Control Item ET90215CRE / EAN-Code PRODUCT DESCRIPTION The ET90000 Series combines powerful and intuitive scheduling with truly maintenance-free

More information

IMP+ INSTRUCTION MANUAL

IMP+ INSTRUCTION MANUAL IMP+ INSTRUCTION MANUAL IMP+ (FOURTH EDITION REV 2) June 2017 Part Number M-080-0-004-2P COPYRIGHT Pulsar Process Measurement Limited, 2005-17. All rights reserved. No part of this publication may be reproduced,

More information

OWNERS MANUAL. Revision /01/ Lightronics Inc. 509 Central Drive Virginia Beach, VA Tel

OWNERS MANUAL. Revision /01/ Lightronics Inc. 509 Central Drive Virginia Beach, VA Tel OWNERS MANUAL Revision 1.8 09/01/2002 OWNERS MANUAL Page 2 of 12 AR-1202 UNIT DESCRIPTION The AR-1202 consists of a processor and 12 dimmer channels of 2.4KW each. Each dimmer channel is protected by a

More information

T775U Series 2000 Electronic Stand-Alone Controller

T775U Series 2000 Electronic Stand-Alone Controller T775U Series 2000 Electronic Stand-Alone Controller INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The T775 electronic stand-alone controllers are the next generation of universal controls capable of remote

More information

Dragonfly Quad. User Manual V1.4. Order code: EQLED101

Dragonfly Quad. User Manual V1.4. Order code: EQLED101 Dragonfly Quad User Manual V1.4 Order code: EQLED101 Safety advice WARNING FOR YOUR OWN SAFETY, PLEASE READ THIS USER MANUAL CAREFULLY BEFORE YOUR INITIAL START-UP! Before your initial start-up, please

More information

Omega.com TM. DPS3100 & DPS3200 series Programmable Scanners

Omega.com TM.     DPS3100 & DPS3200 series Programmable Scanners Omega.com TM http://www.omega.com e-mail: info@omega.com DPS3100 & DPS3200 series Programmable Scanners TABLE OF CONTENTS SPECIFICATIONS... 3 DESCRIPTION... 4 DISPLAYING PARAMETERS... 5 Table 1. How to

More information

Installation Guide. HDMI 4x1 Switcher

Installation Guide. HDMI 4x1 Switcher Installation Guide HDMI 4x1 Switcher SY Electronics Ltd, Unit 7, Worrall Street, Salford, Greater Manchester, M5 4TH, United Kingdom Tel: +44 (0) 161 868 3450 Fax: +44 (0) 161 868 3459 The SY-HD-S41 is

More information

Noise Detector ND-1 Operating Manual

Noise Detector ND-1 Operating Manual Noise Detector ND-1 Operating Manual SPECTRADYNAMICS, INC 1849 Cherry St. Unit 2 Louisville, CO 80027 Phone: (303) 665-1852 Fax: (303) 604-6088 Table of Contents ND-1 Description...... 3 Safety and Preparation

More information

T775L Series 2000 Electronic Stand-Alone Staging Controller

T775L Series 2000 Electronic Stand-Alone Staging Controller T775L Series 2000 Electronic Stand-Alone Staging Controller INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The T775 electronic stand-alone controllers are the next generation of commercial and agricultural

More information

K3NX Process Meter OPERATION MANUAL

K3NX Process Meter OPERATION MANUAL Cat.No. N90 E1 1 K3NX Process Meter OPERATION MANUAL K3NX Process Meter Operation Manual Produced January 1998 Notice: OMRON products are manufactured for use according to proper procedures by a qualified

More information

MONITOR POWER Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free

MONITOR POWER Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free Instruction Manual Model 2099-10xx 10MHz Frequency Source April 2014, Rev. H MENU INTERNAL LEVEL = +10dBm MONITOR POWER 1 2 MODEL 2099 FREQUENCY SOURCE CROSS TECHNOLOGIES INC. ALARM OVEN REMOTE EXECUTE

More information

INT-X-P and INT-X-L Programming instructions

INT-X-P and INT-X-L Programming instructions London Electronics Limited Thorncote Green, Near Hatch, Sandy, Bedfordshire SG19 1PU Tel +44(0)1767 626444 Fax +44(0)1767 626446 www.london-electronics.com help@london-electronics.com Signal Conditioners,

More information

ST-4000D SIGNAL LEVEL METER

ST-4000D SIGNAL LEVEL METER ST-4000D SIGNAL LEVEL METER Rev 100606 Table of Contents Features / Specifications.... 1 Keypad Illustration....... 2 Keypad Controls.... 2 Getting Started: Powering the Meter...... 3 Quick Use Instructions.....

More information

Process transmitter RMA422

Process transmitter RMA422 Technical information TI072R/09/en Mat. No. 51001905 Process transmitter RMA422 Multifunctional 1-2 channel top hat DIN rail unit with intrinsically safe current input and loop power supply, alarm set

More information

ST-4000 SIGNAL LEVEL METER

ST-4000 SIGNAL LEVEL METER ST-4000 SIGNAL LEVEL METER Table of Contents Features / Specifications.... 1 Keypad Illustration....... 2 Keypad Controls.... 2 Getting Started: Powering the Meter.... 3 Quick Use Instructions.. 3 Main

More information

1 Output 1 operation. 3 Pressure unit display. 4 Main display Large 4-character LCD display. 5 Sub-display Small 4-character LCD display.

1 Output 1 operation. 3 Pressure unit display. 4 Main display Large 4-character LCD display. 5 Sub-display Small 4-character LCD display. ure Sensor DP-100 Series INSTRUCTI MANUAL High-performance Digital Display For use outside Japan MEUML-DP100 V1.1 Thank you for purchasing products from Panasonic Electric Works SUNX Co., Ltd. Please read

More information

TPHADA TRANSMITTER FOR HIGH PRESSURE WITH DIGITAL AUTO-ZERO & SPAN

TPHADA TRANSMITTER FOR HIGH PRESSURE WITH DIGITAL AUTO-ZERO & SPAN TPHADA TRANSMITTER FOR HIGH PRESSURE WITH DIGITAL AUTO-ZERO & SPAN Main features Ranges: from: 0...1000 to 0...5000 bar Output signal 4...20mA 2 wires / 0,1...5,1Vdc / 0.1...10.1Vdc / 0...5Vdc / 0...10Vdc

More information

ZN-PD. Smallest Air Particle Sensor in the Industry for In-line Measurement. Air Particle Sensor. Features

ZN-PD. Smallest Air Particle Sensor in the Industry for In-line Measurement. Air Particle Sensor. Features Air Particle Sensor Smallest Air Particle Sensor in the Industry for In-line Measurement Suitable for continuous measurement. With Realtime Clean Air Monitor. Be sure to read Safety Precautions on page

More information