HVDC cable accessories

Size: px
Start display at page:

Download "HVDC cable accessories"

Transcription

1 ^=r SVENSKA KRAFTNÄT SWEDISH NATIONAL GRID UNIT, BUSINESS AREA OUR REFERENCE TR E DATE CONSULTATIÖNS NT, NB TECHNICAL GUIDELINE EDITION 1 APPROVED TD HVDC cable accessories This technical guideline describes the principal design and construction requirements Svenska kraftnät applies to HV accessories to be used in HVDC cable systems for submarine and underground installations. The guideline shall be used when purchasing and designing extruded HVDC cable systems. SvK4005E. v4.0,

2 2 (13) Edition Change notes Date 1 First edition of this technical guideline

3 3 (13) Content 1 References Definitions and abbreviations General Manufacturer s prequalification Lifetime Materials Performance Joints Factory joint Field joint Termination Link box Surge arresters Earthing blade Discharge resistor Testing Documentation... 13

4 4 (13) 1 References The cable design of cable accessories shall comply with requirements in the following references. TR E TR E TR E TR01-12E TR01-13 TR IEC TS IEC IEC IEC SS SS-EN IEC IEC HVDC extruded cable HVDC mass-impregnated cable Earthing of HVAC and HVDC Cable Systems Self-Contained Surge Arresters kv Stamnätsstationer jordning Skyltar i ställverk Selection and dimensioning of high-voltage insulators intended for use in polluted conditions Part 4: Insulators for d.c. systems Hollow pressurized and unpressurized ceramic and glass insulators for use in electrical equipment with rated voltages greater than V Composite hollow insulators - Pressurized and unpressurized insulators for use in electrical equipment with rated voltage greater than V - Definitions, test methods, acceptance criteria and design recommendations Surge arresters Part 9: Metal-oxide surge arresters without gaps for HVDC converter stations Dimensionering av utomhusställverk Vind- och islaster Conductors of insulated cables. Power cables with extruded insulation and their accessories for rated voltages above 150 kv (Um = 170 kv) up to 500 kv (Um = 550 kv) Test methods and requirements Electric cables - Calculation of the current rating

5 5 (13) IEC Cigré TB No 623 Cigré Recommendation Cigré TB No 496 Cigré TB No 490 Cigré TB No 194 Calculation of the cyclic and emergency current rating of cables Recommendations for mechanical testing of submarine cables ÉLECTRA No 189 Recommendations for tests of power transmission DC cables for a rated voltage up to 800 kv. Recommendations for Testing DC Extruded Cable Systems for Power Transmission at a Rated Voltage up to 500 kv Recommendations for testing of long AC submarine cables with extruded insulation for system voltage above 30 (36) to 500 (550) kv Construction, laying and installation techniques for extruded and self contained fluid filled cable systems

6 6 (13) 2 Definitions and abbreviations Definitions and abbreviations used in this technical guideline, as well as in all other TR14 documents, can be found in a separate document in the TR14 series, TR E. 3 General 3.1 Manufacturer s prequalification Manufacturers shall have expertise in and substantial experience of designing, manufacturing and installing underground and submarine HVDC cables for the specified voltage level (or higher) and specified cable technology (extruded or MI). The manufacturer shall be able to present two reference projects as a basis for a prequalification. 3.2 Lifetime The design of cable accessories with respect to used materials, manufacturing techniques as well as electrical, thermal and mechanical stresses shall have the theoretical lifetime of at least 50 years. 3.3 Materials The materials used for delivery accessories must be of the same type and designation as for the qualification tests and type tests. The materials shall not be changed during the project. 3.4 Performance The cable accessories must fulfil the same electrical, mechanical and thermal performance requirements as the HVDC cable, including static and transient stresses and overloading. Requirements for HVDC cables are described in TR E and TR E. 4 Joints Sections of cables incorporating conductor joints must have the same mechanical robustness and handling characteristics as the cable. The cable conductors may not be joined by exothermic welding.

7 7 (13) The number of any type of joints in the final installed HVDC link must be minimised. 4.1 Factory joint A factory joint is defined as a joint made in the factory before armouring of the cable. The factory joints must be flexible and meet the same electrical performance requirements as for the cable. Sections of cables incorporating factory joints must have the same mechanical robustness and handling characteristics as the cable. This ability is to be proven in tests by the same mechanical and electrical performance and requirements as is valid for the cable. Sections of cable incorporating factory joints must have the same corrosion properties as the cable itself. Sections of cable incorporating factory joints must have the same water tightness properties as the cable itself, except that the joint itself does not need specific means for longitudinal water blocking. 4.2 Field joint Submarine cable A field joint is defined as a joint performed on an already wire-armoured cable and which is performed in the planned operation of jointing the consecutive cable loading lengths. Field joints may also be used for repairs, and are then referred to as repair joints. Field joints for extruded cables may be rigid. Rigid submarine joints may use parts from the pre-fabricated underground joints. Underground cable Field joints for extruded underground cables must be prefabricated. The earthed joints shall have screen separation. The remaining joints shall be used without screen separation. The design with screen separation must allow for sheath testing of cable sections after installation. Transition joint Transition joints are joints that connect cables with significant differences in design. For example, jointing an armoured submarine cable with underground cable is considered as a transition joint.

8 8 (13) Transition joint between submarine and underground cables requires a hang-off of the armour wires. 5 Termination The termination in this context is considered to consist of: the cable termination, support stands, foundation and all other necessary equipment including link box, earthing conductors and temporary grounding point, in order to have a complete operational installation. The design of the cable termination shall comply with the following conditions. Air temperature C Design wind velocity 34 m/s Ice layer thickness 20 mm Solar radiation 1000 W/m 2 The cable termination outer insulators must have a design and material appropriate and qualified for HVDC conditions (composite or porcelain). The colour must be uniform and coordinated with other insulators in the same yard. The insulators shall be maintenance free and shall not require regular cleaning. The design of porcelain insulators shall comply with IEC The design of composite insulators shall comply with IEC The profile of the insulators shall comply with IEC Section 10. The minimum Unified Specific Creepage Distance (USCD) for porcelain and composite insulators shall be according to Figure 1 and Table 1 below:

9 9 (13) Figure 1: USCD of insulators for HVDC cable terminations in different pollution areas in Sweden.

10 10 (13) Table 1: USCD of insulators for HVDC cable terminations in different pollution areas in Sweden. If a manufacturer presents positive service experience of similar cable termination in similar environment, lower creepage distance than proposed by technical guidelines could be considered. The termination shall be insulated from the support stand and shall be connected to earth by a separate earth conductor. All earthing connections including connections from the cable sheath and armouring shall have an electrical and mechanical design that meets any operation condition and failure conditions with respect to ohmic heating. Dimensioning of the earthing conductor shall be according to TR The top bolt of the terminations shall be equipped with a grounding ball-stud. It shall be mechanically robust to allow for connection of a grounding clamp with a grounding cable and allow for grounding using an insulated grounding stick from ground level. The grounding ball-stud shall be designed to withstand short circuit current of the link. The grounding ball-stud shall not disturb electric field distribution of corona rings. Corona rings shall be made of aluminium and shall not be covered/painted with any additional material. The cable termination is identified by the following data, which also shall be stated on the permanent rating plate: Rated continuous voltage pole-ground, U 0 (kv) Rated DC current, I 0 (A) Name of manufacturer Type designation and identification of the complete cable termination Year of manufacture

11 11 (13) Serial number The rating plate shall be made of corrosion resistant material; preferably stainless steel. The rating plate shall be attached at suitable location on the side of the metallic base of the termination insulation body. The cable terminations shall be marked with the signs according to TR Link box Link boxes shall be used for earthing purposes at earthed underground cable joint bays, transition joint bays and cable termination stands. The other joint bays shall have no link boxes. The link boxes shall allow for connecting the screens to local earth wires (insulated or not) from the permanent earthing system. The design of link boxes shall allow for screen separation in order to allow for sheath testing of cable sections. This shall allow for separation between the screens of the jointed cables, and separation between cable screens and the installed earth plane. It shall be possible to reassemble the initial earthing configuration in the link box after screen separation is no longer required. Earthed underground cable joint bays and transition joint bays shall be equipped with a buried link box. There shall be one link box for both cable poles in symmetrical monopole scheme. The link boxes for cable terminations shall be fitted on the termination steel stand. There shall be one link box for each cable termination. The underground link box shall have Intrusion Protection class of IP68. A stainless steel box with the bolted lid is required. The design of the underground link box shall allow reusing the gasket after opening the link box. The link box for installation on cable termination stand shall have Intrusion Protection class of IP54. The construction of the link-box shall prevent water condensation inside. A stainless steel box with the lockable lid on hinges is required. All incoming link cables into a link box shall be marked with nametags allowing identifying to which joint screens they are connected. The terminals in the link box shall be logically arranged and consistent in all link boxes (e.g. first link-cable is from positive joint west side, second link-cable from positive joint east side, etc.).

12 12 (13) A sign shall be attached on the outside of the underground link box lid. The sign shall be according to the example below and shall contain the following: Electric hazard sign Text Varning! Risk för farlig potential. Potentialjorda linkbox med närliggande delar av ledande material och omgivande mark innan arbetet påbörjas Svenska kraftnät s logo Svenska kraftnät s Littra designation of the cable link Joint pit designation The markings and signs shall have yellow background and black text. The markings shall be made from weather-proof material and shall have the life-length as the cable system. Figure 2: Example of a link-box sign. 7 Surge arresters Every cable termination shall be protected from Switching (SI) and Lightning (LI) impulses with surge arresters. In some cases, if it is found applicable, Svk may relieve from LI protection requirement. Surge arrester design shall follow TR01-12 in applicable parts and IEC

13 13 (13) The surge arrester Protection Level (PL) shall be calculated based on the cable system Withstand Voltage (WV). The relation between the cable system withstand voltage and surge arrester protection level for SI and LI shall be according to the following equations: SIWV = 1,15 SIPL LIWV = 1,15 LIPL 8 Earthing blade At each cable termination an earthing blade shall be installed enabling safe earthing before opening of the cable circuit. 9 Discharge resistor The cable manufacturer shall state if the cables at floating HVDC potential at SIPL can be discharged instantaneously by direct grounding or a discharge resistor is needed/preferred. In case discharge resistor is needed/preferred the cable manufacturer shall state the safe discharge duration. 10 Testing Testing of HVDC cable systems and accessories is covered in Svenska kraftnät technical guideline TR E. 11 Documentation The design of accessories, calculations, life-time estimations, testing etc. shall be documented according to document list described in TR Documentation shall comply with requirements in TR08-01 and TR08-02.

640 kv XLPE HVDC cable system

640 kv XLPE HVDC cable system 640 kv XLPE HVDC cable system World s most powerful extruded cable system enables utilization of renewable energy resources nkt.com Demand for higher voltages NKT s new 640 kv XLPE DC cable system is the

More information

640 kv extruded HVDC cable system

640 kv extruded HVDC cable system 640 kv extruded HVDC cable system World s most powerful extruded cable system Pehr Bergelin, Marc Jeroense, Tobias Quist, Hans Rapp NKT Summary In this paper, NKT s new 640 kv extruded DC cable system

More information

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITHOUT METALLIC SCREEN

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITHOUT METALLIC SCREEN Engineering Specification Electrical Networks MESP 030000-02 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED Version: 1 Issued: March 2014 Owner: Electrical

More information

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100 DATASHEET - NZMH2-A100 Circuit-breaker, 3p, 100A Part no. NZMH2-A100 Catalog No. 259099 Similar to illustration Delivery program Product range Circuit-breaker Protective function System and cable protection

More information

Revision of Qualification Procedures for High Voltage and Extra High Voltage AC Extruded Underground Cable Systems

Revision of Qualification Procedures for High Voltage and Extra High Voltage AC Extruded Underground Cable Systems Revision of Qualification Procedures for High Voltage and Extra High Voltage AC Extruded Underground Cable Systems Tutorial vor the ICC Educational Session on November 11 2009 in Scottsdale, AZ by Wim

More information

Protective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A

Protective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A DATASHEET - NZMN3-VE630 Circuit-breaker, 3p, 630A Part no. NZMN3-VE630 Catalog No. 259133 EL-Nummer (Norway) 0004358791 Similar to illustration Delivery program Product range Circuit-breaker Protective

More information

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100 DATASHEET - NZMC1-A160 Circuit-breaker, 3p, 160A Part no. NZMC1-A160 Catalog No. 283296 Similar to illustration Delivery program Product range Circuit-breaker Protective function System and cable protection

More information

Description Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100

Description Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100 DATASHEET - NZMN3-4-AE400 Circuit-breaker, 4p, 400A Part no. NZMN3-4-AE400 Catalog No. 265891 Similar to illustration EL-Nummer (Norway) 0004358857 Delivery program Product range Circuit-breaker Protective

More information

Description Set value in neutral conductor is synchronous with set value Ir of main pole. CSA 100. conductor. I r A 50-63

Description Set value in neutral conductor is synchronous with set value Ir of main pole. CSA 100. conductor. I r A 50-63 Circuit-breaker,4p,63A Partno. NZMH1-4-A63 Articleno. 284426 Similar to illustration Deliveryprogram Product range Circuit-breaker Protective function System and cable protection Standard/Approval IEC

More information

ECONOMICAL 36 kv CABLE SYSTEM FOR THE BELGIAN NETWORK

ECONOMICAL 36 kv CABLE SYSTEM FOR THE BELGIAN NETWORK ECONOMICAL 36 kv CABLE SYSTEM FOR THE BELGIAN NETWORK J. Becker NEXANS BENELUX S.A. F. Musique ELECTRABEL S.A. ABSTRACT In order to tackle the deregulated market with confidence and in a realistic way,

More information

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100 Circuit-breaker,3p,160A Partno. NZMN2-M160 CatalogNo. 265724 Similar to illustration Deliveryprogram Product range Circuit-breaker Protective function Motor protection Standard/Approval IEC Installation

More information

I r A Protection against direct contact Finger and back-of-hand proof to VDE 0106 part 100

I r A Protection against direct contact Finger and back-of-hand proof to VDE 0106 part 100 Circuit-breaker,3p,400A Partno. LZMC3-A400-I Articleno. 111955 Similar to illustration Deliveryprogramme Product range Circuit-breaker Protective function System and cable protection Standard/Approval

More information

TERMINATIONS AND JOINTS FOR XLPE-INSULATED kv MEDIUM VOLTAGE CABLES

TERMINATIONS AND JOINTS FOR XLPE-INSULATED kv MEDIUM VOLTAGE CABLES Accessories TERMINATIONS AND JOINTS FOR XLPE-INSULATED 12 36 kv MEDIUM VOLTAGE CABLES Cable Systems, Cables and Accessories Test values for terminations 1) Testing to DIN VDE 0278-629-1 (Testing methods

More information

Soft starter, 66 A, V AC, Us= 24 V DC, with control unit, Frame size N. Function Soft starter for three-phase loads, with control unit

Soft starter, 66 A, V AC, Us= 24 V DC, with control unit, Frame size N. Function Soft starter for three-phase loads, with control unit DATASHEET - S811+N66N3S Delivery program Soft starter, 66 A, 200-600 V AC, Us= 24 V DC, with control unit, Frame size N Part no. S811+N66N3S Catalog No. 168978 Eaton Catalog No. S811PLUSN66N3S EL-Nummer

More information

HIGH VOLTAGE CABLE ACCESSORIES - Application, Design, Installation, Testing - Ivan Jovanovic G&W Electric Company

HIGH VOLTAGE CABLE ACCESSORIES - Application, Design, Installation, Testing - Ivan Jovanovic G&W Electric Company HIGH VOLTAGE CABLE ACCESSORIES - Application, Design, Installation, Testing - Ivan Jovanovic G&W Electric Company 1 Year 1905 First detachable porcelain pothead for 4 kv systems Year 2015 Terminations

More information

CLP s first 400kV XLPE cable application

CLP s first 400kV XLPE cable application CLP s first 400kV XLPE cable application Chris Cheung CLP Power Hong Kong Limited 9 October 2017 Information Classification : PROPRIETARY Information Classification : PROPRIETARY Project Requirement Due

More information

KRF EMC Filters Installation, Operation and Maintenance Manual

KRF EMC Filters Installation, Operation and Maintenance Manual KRF EMC Filters Installation, Operation and Maintenance Manual KRF EMC Filters limit high frequency noise, as well as: Reduce interference Protect sensitive equipment Eliminate drive cross-talk Meet FCC

More information

Photovoltaic Module Installation Manual (IEC)

Photovoltaic Module Installation Manual (IEC) Phono Solar Technology Co., Ltd. Add: No. 1 Xinghuo Rd., Nanjing Hi-tech Zone, Nanjing, China Tel: +86 25 5863 8000 Fax: +86 25 5863 8009 E-mail: support@phonosolar.com Website: www.phonosolar.com PHONO

More information

Medium Voltage 12/20 (24)kV NF C cable system. Xavier Brosse Luanda May 2009

Medium Voltage 12/20 (24)kV NF C cable system. Xavier Brosse Luanda May 2009 Medium Voltage 12/20 (24)kV NF C 33-226 cable system Xavier Brosse Luanda May 2009 1 Evolution of French standard for MV cables Late 70 s : NF C 33-223 Cable Standard in France result of the move from

More information

LED MODULES READYLINE DL

LED MODULES READYLINE DL LED MODULES READYLINE DL BUILT-IN MODULE LED-MODULE READYLINE DOWNLIGHT DL WU-M-538 / WU-M-539 / WU-M-540 Typical Applications Downlights Replacement for CFL DIRECT MAINS CONNECTION REDUCED FLICKER HIGH

More information

Trends and Challenges of HV Cable Systems

Trends and Challenges of HV Cable Systems Trends and Challenges of HV Cable Systems Bruno Arnold Electrical Engineer FH Global Sales Far East, Latin America and India Pfisterer Business Unit PTS Cable Trends and Challenges of HV Cable Systems

More information

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES 1.0 SCOPE TABLE OF CONTENTS 2.0 CABLES SPLICES 2.1 Definitions 2.2 Scope of Specifications and Drawings 2.3 General Requirements 2.4 Routing Cables 2.5 Connectors 2.6 Conductor Connections 2.7 Heat Shrinkable

More information

Filters for Power Lines (Low Leakage Current)

Filters for Power Lines (Low Leakage Current) Filters for Power Lines (Low Leakage Current) 40 to 100 A, 100 db from 150 khz Series/Type: Date: January 2004 EPCOS AG 2015. Reproduction, publication and dissemination of this publication, enclosures

More information

Photovoltaic Module Installation Manual (IEC)

Photovoltaic Module Installation Manual (IEC) Phono Solar Technology Co., Ltd. Add: No. 1 Xinghuo Rd., Nanjing Hi-tech Zone, Nanjing, China Tel: +86 25 5863 8000 Fax: +86 25 5863 8009 E-mail: support@phonosolar.com Website: www.phonosolar.com PHONO

More information

Panel-mounting thermostats, type series EM

Panel-mounting thermostats, type series EM Data sheet 602025 Page /5 Panel-mounting thermostats, type series EM Particularities Operating temperature limiter Limit value range up to +650 C with temperature compensation Brief description Panel-mounting

More information

Bharat Heavy Electricals Limited HIGH PRESSURE BOILER PLANT, TIRUCHIRAPPALLI CONTROLS AND INSTRUMENTATION/FB

Bharat Heavy Electricals Limited HIGH PRESSURE BOILER PLANT, TIRUCHIRAPPALLI CONTROLS AND INSTRUMENTATION/FB Bharat Heavy Electricals Limited HIGH PRESSURE BOILER PLANT, TIRUCHIRAPPALLI 620 014. CONTROLS AND INSTRUMENTATION/FB DATA SHEET FOR MULTICORE, ARMOURED, CONTROL CABLE Project: Ennore Sez, 2 x 660 MW,

More information

INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 FIRE PREVENTION FOR CABLES, CABLE TRAYS AND CONDUITS

INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 FIRE PREVENTION FOR CABLES, CABLE TRAYS AND CONDUITS CERN INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 Edms 335813 TIS IS 48 Edited by: TIS/GS Publication Date: June 2001 Original: English FIRE PREVENTION FOR CABLES, CABLE

More information

Identification - electrical services

Identification - electrical services Identification - electrical services Aesthetic All live phase cable sheathing to be brown coloured and neutral phase cable sheathing to be blue coloured, all labelled L1, L2, L3 & N respectively in accordance

More information

CONTACT-DUO-PROFILE. Contact-Duo-Profile overview

CONTACT-DUO-PROFILE. Contact-Duo-Profile overview 13 6.3 13 6.3 4.7 20.7 24.6 +1/-0 24.6 +1/-0 2.5 24.6 +1/-0 20.7 4.3 +0.3-0.4 3.6 ±0.3 32.5 32.5 32.5 5 2 CONTACT-DUO-PROFILE Contact-Duo-Profile overview 13 6.3 13 6.3 4.7 2.5 16±0.8 4.7 2.5 4.7 2.5 2.6

More information

TeSys contactors. Model d. Type of contactor LC1- LC1- LC1- LC1- LC1-D115 & D09 D18 D25 D38 D40 D50 D95 LC1-D150 DT20 & DT25 DT32 & DT40

TeSys contactors. Model d. Type of contactor LC1- LC1- LC1- LC1- LC1-D115 & D09 D18 D25 D38 D40 D50 D95 LC1-D150 DT20 & DT25 DT32 & DT40 Characteristics Type of contactor LC- LC- LC- LC- LC-D & D09 D8 D2 D38 D40 D0 D9 LC-D0 DT20 & DT2 DT32 & DT40 Environment Rated insulation voltage (Ui) Conforming to IEC 947-4-, overvoltage category III,

More information

Joint paper: Feasibility and technical aspects of partial undergrounding of extra high voltage power transmission lines

Joint paper: Feasibility and technical aspects of partial undergrounding of extra high voltage power transmission lines Joint paper: Feasibility and technical aspects of partial undergrounding of extra high voltage power transmission lines Brussels, December 2010 1. Introduction Page 4 2. Executive Summary 5 3. Partial

More information

I r A I i = I n x. Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

I r A I i = I n x. Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100 Deliveryprogramme Circuitbr.,3pmotorprotection Partno. Articleno. 265784 NZMN4-ME875 Product range Circuit-breaker Protective function Motor protection Standard/Approval IEC Installation type Fixed Release

More information

220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX

220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX 220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX JAMNAGAR 220KV CABLE NETWORK: 2 2. DESIGN 2A. NETWORK: 220 KV NETWORK DESIGN IS DESIGNED WITH 100% REDUNDANCY FROM 220 KV BUS TO LOAD. THIS IS ACHIEVED

More information

7 Lighting Technology

7 Lighting Technology 7 Lighting Technology Floodlight 09676E00 explosion protected floodlight for use in explosive gas atmospheres of Zone 2 as well as in areas with combustibledust of Zone 21 and Zone 22. Explosion protection

More information

Indoor Linear 80W Driver SI-C215280N2KR

Indoor Linear 80W Driver SI-C215280N2KR Product Data Sheet Rev.00 2017. 2. 9 1# LED Driver Indoor Linear 80W Driver SI-C215280N2KR Constant Current LED Driver Features & Benefits Output Current Range: 1550mA Output Voltage Range: MAX 51 Vdc

More information

Emerging Subsea Networks

Emerging Subsea Networks NEW SUBSEA OPTICAL FIBRE JUNCTION BOX FOR REDUCED TENSILE LOAD APPLICATIONS Craig Beech (Global Marine Systems Ltd.), Peter Christian (Global Marine Systems Ltd.) Email: craig.beech@globalmarinesystems.com

More information

AS09..S 3-pole Contactors - Spring Terminals

AS09..S 3-pole Contactors - Spring Terminals 4 kw 5 hp AS09..S 3-pole Contactors - Spring AC Operated Description - 3-pole contactors with spring terminals, - N.C. or N.O. built-in auxiliary contact, - Rail-mounted, no tools required, - Additional

More information

INTERNATIONAL TELECOMMUNICATION UNION DIGITAL SECTIONS AND DIGITAL LINE SYSTEMS DEFINITION OF TERMS RELEVANT TO OPTICAL FIBRE SUBMARINE CABLE SYSTEMS

INTERNATIONAL TELECOMMUNICATION UNION DIGITAL SECTIONS AND DIGITAL LINE SYSTEMS DEFINITION OF TERMS RELEVANT TO OPTICAL FIBRE SUBMARINE CABLE SYSTEMS INTERNATIONAL TELECOMMUNICATION UNION ITU-T G.972 TELECOMMUNICATION (03/93) STANDARDIZATION SECTOR OF ITU DIGITAL SECTIONS AND DIGITAL LINE SYSTEMS DEFINITION OF TERMS RELEVANT TO OPTICAL FIBRE SUBMARINE

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker

Magnetic and Hydraulic-Magnetic Circuit Breaker Magnetic and Hydraulic-Magnetic Circuit Breaker 850-... Description Single, two, three and four pole magnetic and hydraulic-magnetic circuit breakers with trip-free-mechanism and toggle or rocker actuation.

More information

Pendant Light Fitting IEC Series 6470/2

Pendant Light Fitting IEC Series 6470/2 > Available light sources high-pressure sodium lamps (HSE) metal halide lamps (HIE) halogen lamps (QT) > Versatile mounting methods > Enclosure made of saltwater-resistant aluminium www.stahl.de 11435E

More information

Revision 2.0 Parts List Minor

Revision 2.0 Parts List Minor Revision.0 www.grindex.com Parts List 803.8 Minor Table of Contents Table of Contents Introduction... Specially approved products... Product Description...3 Products included... 3 The data plate...3 Exploded

More information

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 PURPOSE 2.0 SCOPE 3.0 CODES, STANDARDS AND REFERENCES

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 PURPOSE 2.0 SCOPE 3.0 CODES, STANDARDS AND REFERENCES TABLE OF CONTENTS 1.0 PURPOSE 2.0 SCOPE 3.0 CODES, STANDARDS AND REFERENCES 4.0 ORDER OF PRECEDENCE 5.0 SYSTEM PARAMETERS 5.1 Frequency 5.2 System Voltage 5.3 Short Circuit Rating 5.4 Insulation Levels

More information

An introduction to Kabeldon cable accessories kv

An introduction to Kabeldon cable accessories kv An introduction to Kabeldon cable accessories 1-420 kv 2009, Edition 1 Safe junctions for reliable cable networks Kabeldon cable accessories, safety by simplicity Making light work Modern society depends

More information

Revision 3.0 Parts List Salvador 1~, 3~

Revision 3.0 Parts List Salvador 1~, 3~ Revision 3.0 www.grindex.com Parts List 809.8 Salvador ~, 3~ Table of Contents Table of Contents Introduction... Specially approved products... Product Description...3 Products included... 3 The data

More information

sequenza 1000/1250 al manuale di istruzioni instruction manual 1^ edizione, ottobre st edition october 1996

sequenza 1000/1250 al manuale di istruzioni instruction manual 1^ edizione, ottobre st edition october 1996 manuale di istruzioni instruction manual 1^ edizione, ottobre 1996 1st edition october 1996 sequenza 1000/1250 al sequenza 1 1000/1250al cod. 5092 sequenza 1000/1250 al/s cod. 5093 sequenza 1000/1250 al/a

More information

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

02/11/2015

02/11/2015 DIN Rail Mount 17.5 mm MUS/MUSF 80 AC/DC Part number 84872141 Control relays monitoring their own power supply - MUS : Over/undervoltage control Selectable latching (memory) function - MUSF : Over/undervoltage

More information

Panel-Mounted Thermostat

Panel-Mounted Thermostat Data Sheet 602026 Page 1/7 Panel-Mounted Thermostat EM Series Special features Safety temperature monitor STW (STB) Safety temperature limiter STB Tested according to DIN EN 14597 and PED 2014/68/EU Brief

More information

LC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC

LC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC Product datasheet Characteristics LC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC Price* : 86.25 GBP Main Range Product name Product or component type Device short name Contactor application Utilisation category

More information

Revision 2.0 Parts List Minette 1~, 3~

Revision 2.0 Parts List Minette 1~, 3~ Revision.0 www.grindex.com Parts List 80.7 Minette ~, 3~ Table of Contents Table of Contents Introduction... Specially approved products... Product Description...3 Products included... 3 The data plate...3

More information

with handle LIMOGES Cedex 1. DESCRIPTION - USE 3. DIMENSIONS Symbol: Technology: Use:. For controlling a load remotely via a switch 2.

with handle LIMOGES Cedex 1. DESCRIPTION - USE 3. DIMENSIONS Symbol: Technology: Use:. For controlling a load remotely via a switch 2. 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 25A power contactors silent CONTENTS PAGES 1. Description, use... 1 2. Range... 1 3. Dimensions... 1 4. Positioning - Connection...

More information

JUMO extherm-at Type , Explosion-proof surface-mounted thermostat for zones 1, 2, 21, and 22

JUMO extherm-at Type , Explosion-proof surface-mounted thermostat for zones 1, 2, 21, and 22 Data Sheet 605055 Page 1/10 Type 605055, Explosion-proof surface-mounted thermostat for zones 1, 2, 21, and 22 Special features Single thermostat and double thermostat with capillary or rigid thermowell

More information

For Sales & Information, Call Toll Free: (888)

For Sales & Information, Call Toll Free: (888) PCR Outline Dimensions 2.75" (69.8 mm) 0.44" (11 mm) 0.25" (6.3 mm) (-) (+) 15.8" (401 mm) 9.3" (236 mm) Nameplate 1.25" (31.8 mm) 3.0" (76 mm) 7.40" (188 mm) 12.63" (321 mm) R 0.219" (R 5.56 mm) Serial

More information

GV3P80 TeSys GV3P thermal-magn motor circuit breaker 70-80A EverLink

GV3P80 TeSys GV3P thermal-magn motor circuit breaker 70-80A EverLink Characteristics TeSys GV3P thermal-magn motor circuit breaker 70-80A EverLink Main Range Product name Device short name Product or component type Device application Trip unit technology Complementary Poles

More information

Amphenol. Amphenol-Tuchel Electronics GmbH. C 112 Series M12 - Connectors

Amphenol. Amphenol-Tuchel Electronics GmbH. C 112 Series M12 - Connectors Amphenol Amphenol-Tuchel Electronics GmbH C 112 Series M12 - Connectors We connect con The company Amphenol-Tuchel Electronics is a worldwide leader in electrical connectors and contacting devices. Our

More information

ABB IEC International Pin and Sleeve

ABB IEC International Pin and Sleeve Approved According to IEC 60 309-1, -2, -4 Range from 16 up to 125 Amp, up to 600V, IP67 (Watertight) Safety Proven performance: With more than 30 years of experience, ABB IEC Pin and Sleeve Connectors

More information

High Voltage Cables kv. Handling and Operating Instructions

High Voltage Cables kv. Handling and Operating Instructions High Voltage Cables 52 145 kv Handling and Operating Instructions 1 (24) HANDLING AND OPERATING DRYREX High voltage cables 52 145 kv Contents Scope of application...3 General...3 Professional skills, tools

More information

EX-PROTECTED PORTABLE POWER SUPPLY UNITS

EX-PROTECTED PORTABLE POWER SUPPLY UNITS EX-PROTECTED PORTABLE POWER SUPPLY UNTS 125 A for Zone 1 Special requirements apply for power distributions for the use and operation of portable equipment in hazardous areas in Zones 1, 2, 21 and 22.

More information

LED Driver Compact fixed output

LED Driver Compact fixed output Driver LC 40W 900mA fixc C SNC ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 900 ma Max. output power 40 W Nominal life-time up to 50,000

More information

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS SINAMICS G130 Operating Instructions 03/2013 SINAMICS s dv/dt filter plus Voltage Peak Limiter Safety information 1 General 2 SINAMICS SINAMICS G130 Operating Instructions Mechanical installation 3 Electrical

More information

LC1D09FE7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A V AC coil

LC1D09FE7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A V AC coil Product datasheet Characteristics LC1D09FE7 TeSys D contactor - 3P(3 NO) - AC-3 -

More information

LIGHTING: ENCLOSED AND GASKETED AREA FLUORESCENT. Applications. Illustrated Feature. Certifications and Compliances

LIGHTING: ENCLOSED AND GASKETED AREA FLUORESCENT. Applications. Illustrated Feature. Certifications and Compliances Applications Enclosed and gasketed fixtures for use where vapors, moisture, dirt or corrosive atmospheres are encountered. For use in hazardous locations defined by the NEC as Class I, Division 2. Groups

More information

Modular pulse operated latching relay 16 A

Modular pulse operated latching relay 16 A 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 Modular pulse operated latc / 05 / 07 / 08 / 10 / 11 / 12 / 14 / 16 / 20 and 927 00 / 49 CONTENTS PAGES 1. Description,

More information

Connecting cables for valves, round plug connectors Product range overview

Connecting cables for valves, round plug connectors Product range overview Connecting cables for valves, round plug connectors Product range overview Version Type code Connection technology (Electrical connection 2) Electrical connection 1: socket M8x1 4-pin NEBV-M8W4L Plug M8x1,

More information

Slot-type Photomicrosensor with connector or pre-wired models (Non-modulated) *1. configuration. Dark-ON/Light-ON

Slot-type Photomicrosensor with connector or pre-wired models (Non-modulated) *1. configuration. Dark-ON/Light-ON Slot-type Photomicrosensor with connector or pre-wired models (Non-modulated) * EE-SX/6 Photomicrosensor with 0- to 00-mA direct switching capacity for built-in application. Series includes models that

More information

Guide for installers. METTLER TOLEDO MultiRange System solution analog Ex1. Hazardous area. Safe area

Guide for installers. METTLER TOLEDO MultiRange System solution analog Ex1. Hazardous area. Safe area Guide for installers METTLER TOLEDO MultiRange System solution analog Ex1 Hazardous area Safe area System solution analog Ex1 Contents Contents Page 1 Safety precautions... 2 2 System overview... 3 2.1

More information

PHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series

PHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 900 ma Max. output power 40 W Nominal life-time up to 30,000 h For luminaires of protection class I and protection

More information

Gamma instabus. Technical product information

Gamma instabus. Technical product information Gamma instabus Technical product information Universal dimmer N 554D31, 4 x 300 VA / 1x 1000 VA, AC 230 V Universal dimmer N 554D31 Control of dimmable lamps, including LED without minimum load Output

More information

Operating instructions

Operating instructions 108183 2017-05-17 Page 1 0359 Operating instructions TPPL-EX series Hazardous environments luminaires Please read the instructions carefully before starting any works! Content: 1. Safety instructions 2.

More information

Ordering details. Approval. Classification

Ordering details. Approval. Classification Datasheet - SRB 301MC-24V Guard door monitors and Safety control modules for Emergency Stop applications / General Purpose safety controllers (Series PROTECT SRB) / SRB 301MC Fit for signal evaluation

More information

Climatic proofing Damp heat, constant, to IEC Damp heat, cyclic, to IEC

Climatic proofing Damp heat, constant, to IEC Damp heat, cyclic, to IEC Deliveryprogramme Contactorrelay,3N/O+1N/C,AC Partno. DILER-31(230V50HZ,240V60HZ) Articleno. 051768 CatalogNo. XTRM10A31F Product range DILER Mini-contactors Application Contactor relays Description with

More information

Mechanical flow switch for On/Off control

Mechanical flow switch for On/Off control Mechanical flow switch for On/Off control Economic integration in pipe systems without any additional piping Magnetic measuring principle Mechanical adjustment of setpoint Type 8010 can be combined with...

More information

LED Driver Compact fixed output

LED Driver Compact fixed output Driver LC 45W 1050mA fixc C SNC ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 1,050 ma output power 45 W Nominal life-time up to 50,000

More information

ImproX (TRT) Twin Remote Terminal INSTALLATION MANUAL

ImproX (TRT) Twin Remote Terminal INSTALLATION MANUAL SPECIFICATIONS MODEL NUMBER: XRT910-0-0-GB-XX XRT911-0-0-GB-XX XTT911-0-0-NN-XX IMPROX TRT ImproX (TRT) Twin Remote Terminal INSTALLATION MANUAL Working Environment XRT910-0-0-GB-XX... (Aluminium Extruded

More information

Cable solutions for all environments. Scapa Cable Solutions

Cable solutions for all environments. Scapa Cable Solutions is the new name for the proven and well-regarded range of Cable Wrapping Tapes and Cable Components from Scapa. The continuing success of these ranges remain core to our future, and we are focused on developing

More information

LED Driver Linear / area fixed output

LED Driver Linear / area fixed output Driver LC 10W 350mA fixc lp SNC2 ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 350 ma Max. output power 10.2 W Up to 80 % efficiency For

More information

Protective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A

Protective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A Deliveryprogramme Circuitbreak.3pselect.protection Partno. Articleno. 265777 NZMH4-VE1600 Product range Circuit-breaker Protective function Systems, cable, selectivity and generator protection Standard/Approval

More information

USER MANUAL. WARNING Read the instructions before using the machine. EN (Original Instruction) / 1704

USER MANUAL. WARNING Read the instructions before using the machine. EN (Original Instruction) / 1704 USER MANUAL European Models American Models 60/100/120 3/4/5 24/40/48 3/4/5 Read the instructions before using the machine. EN (Original Instruction) 9124097 / 1704 KEEP THIS USER MANUAL FOR FUTURE USE

More information

ES-Mega MegaBeans. Access Control System. User Manual. People in Motion

ES-Mega MegaBeans. Access Control System. User Manual. People in Motion ES-Mega MegaBeans Access Control System User Manual / Order No. Device People in Motion Contents 1. General description..3 2. Installation Instructions..4 3. Start-up..4 4. Audible signals..4 5. Operating

More information

INSTRUCTION AND MAINTENANCE VIDEO MOTORE PROJECTION SCREEN

INSTRUCTION AND MAINTENANCE VIDEO MOTORE PROJECTION SCREEN INSTRUCTION AND MAINTENANCE VIDEO MOTORE PROJECTION SCREEN 1.1 TECHNICAL DATA PRODUCT DESCRIPTION Screens made with the following projection fabrics: SOFT WHITE, MATT WHITE SOFT, SOFT WHITE TRANSOUND,

More information

Illustrated Feature. Options

Illustrated Feature. Options Applications Enclosed and gasketed fixtures for use where vapors, moisture, dirt or corrosive atmospheres are encountered. For use in hazardous locations defined by the NEC as Class I, Division 2. Groups

More information

LED control gear Compact fixed output

LED control gear Compact fixed output Driver LC 40W 900mA fixc SR SNC ESSENCE series Product description Independent fixed output LED Driver Constant current LED Driver Output current 900 ma Max. output power 39 W Nominal life-time up to 50,000

More information

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver.   Product description. Benefits. Interfaces. Linear / area dimming Constant current LED driver DALI Dimmable Product description Dimmable built-in constant current LED Driver Adjustable output current between 1,050 and 1,750mA via DIP switch Max.

More information

EXPlora. Introduction

EXPlora. Introduction Introduction EXPlora The EXPlora range is most suited to manufacturers of ancillary electrical equipment such as motors, pumps, lighting equipment, process and control gear for use in factories and plant

More information

B1-00. SPECIAL REPORT FOR SC B1 (Insulated Cables) Walter Zenger. Special Reporter

B1-00. SPECIAL REPORT FOR SC B1 (Insulated Cables) Walter Zenger. Special Reporter CIGRE 2016 B1-00 SPECIAL REPORT FOR SC B1 (Insulated Cables) Walter Zenger Special Reporter 1. General Study Committee (SC) B1 is responsible for all aspects regarding land and submarine insulated cable

More information

Flygt Submersible Motor Cables

Flygt Submersible Motor Cables Flygt Submersible Motor Cables This brochure contains an overview of the Flygt motor cable assortment. The cables are especially designed for submersible use and made of carefully selected materials. The

More information

Cables for robot applications

Cables for robot applications Cables for robot applications 67 Primary cables Robot primary cable Cable design Internal conductor Special conductor Strand class VI (super-fine wire) Highly flexible Core insulation TPM or PUR Core identification

More information

with additional normally-open signalling contact l With integrated AS interface Safety at Work.

with additional normally-open signalling contact l With integrated AS interface Safety at Work. Safety Hinge Switch SHS3 In addition to the plug connection version, an SHS with fixed cable connection at the rear is also available Right and left hinged systems possible for optimum cable routing Mounting

More information

Safe, Accurate, and Repeatable

Safe, Accurate, and Repeatable Safe, Accurate, and Repeatable It is common for high-speed data cable to utilize two or more shielded twisted conductors. This type of cable is common in all digital electronic networks, and it requires

More information

IndyGo Facility Upgrades Project 35671EE

IndyGo Facility Upgrades Project 35671EE SECTION 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Identification for raceways. 2. Identification of power and control cables. 3. Identification for

More information

Hinges with built-in safety multiple switch SUPER CFSW. Hinges and connections. IP67 RoHS PA

Hinges with built-in safety multiple switch SUPER CFSW. Hinges and connections. IP67 RoHS PA Hinges with built-in safety multiple switch SUPER ECHNO POLYMER IP RoHS PA +0-0 MAERIAL Hinge body: self-extinguish high-rigidity SUPER-technopolymer, black or grey colour RAL 00 (C). Rotation pin: glass-fibre

More information

E2V Technologies CX2668A, CX2668AX Air-Cooled, Hollow Anode, Two-Gap Metal/Ceramic Thyratrons

E2V Technologies CX2668A, CX2668AX Air-Cooled, Hollow Anode, Two-Gap Metal/Ceramic Thyratrons E2V Technologies CX2668A, CX2668AX Air-Cooled, Hollow Anode, Two-Gap Metal/Ceramic Thyratrons The data to be read in conjunction with the Hydrogen Thyratron Preamble. ABRIDGED DATA Hollow anode, deuterium-filled

More information

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 872 LIGHT EMITTING DIODE TRAFFIC SIGNAL LAMP UNITS JULY 19, 2002

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 872 LIGHT EMITTING DIODE TRAFFIC SIGNAL LAMP UNITS JULY 19, 2002 STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 872 LIGHT EMITTING DIODE TRAFFIC SIGNAL LAMP UNITS JULY 19, 02 872.01 Description 872.02 Prequalification 872.03 Material Requirements

More information

Type: NZMN1 A100 Article No.: Sales text Circuit breaker3p systems/cable prot. Ordering information Number of poles

Type: NZMN1 A100 Article No.: Sales text Circuit breaker3p systems/cable prot. Ordering information Number of poles Type: NZMN1 A100 Article No.: 259085 Sales text Circuit breaker3p systems/cable prot. Ordering information Number of poles Description Rated current = rated uninterrupted current Setting range 3 pole I

More information

LED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series

LED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series Driver LC 200W 1050mA UNV ADV IND ADVANCED series Product description Independent constant current LED Driver For dry, damp and wet locations Max. output power 200 W Up to 93.7 % efficiency For luminaires

More information

PRINCIPLES AND APPLICATIONS

PRINCIPLES AND APPLICATIONS GENERATION & NETWORK Digital Automation Measuring and Control Devices AMS7000 PROCOM The optimum operation of an electrical network depends particularly on the reliability and the availability of the protection,

More information

Effective earthing of screened cables

Effective earthing of screened cables NOVEMBER 2006 Effective earthing of screened cables All metallic containment items, other extraneous metalwork and the screens of telecommunications cables in an information technology environment must

More information

3 Cleaning. 4 Technical data

3 Cleaning. 4 Technical data EXC+ EXC- Sig- SIG+ SEN- SEN+ 2.4 Attaching cable to the analog board Attaching cable of the weighing cell to the system solution Connect the cable to the appropriate terminal strip of the Ex1 system solution

More information

DOME OPTIC SPLICE CLOSURE

DOME OPTIC SPLICE CLOSURE FIBER OPTIC SPIICE CLOSURE GJS-JKDH1001-120 BOX DIMENSION: W=140mm H=340mm Weight = 1.80 kgs Outer Internal structure Fuse fiber disc Type sealing ring Plastic hoop base Pole Mount Pole Mount 1 1. product

More information

SWA Cable BS6724 Steel Wire Armoured LSZH Eland Product Group A9L

SWA Cable BS6724 Steel Wire Armoured LSZH Eland Product Group A9L SWA Cable BS6724 Steel Wire Armoured LSZH Eland Product Group A9L Application SWA Cable power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for

More information