OPERATIVE GUIDE P.I.T. PILE INTEGRITY TEST

Size: px
Start display at page:

Download "OPERATIVE GUIDE P.I.T. PILE INTEGRITY TEST"

Transcription

1 OPERATIVE GUIDE P.I.T. PILE INTEGRITY TEST 1

2 Echotest procedure / PIT Pile Integrity test with MAE ETBT instrument Generals Theory notes Pile Integrity Test (PIT) is a simple non destructive test which can be performed in short time. Echotest, exploiting theory of propagation of elastic waves in a medium, is useful for detecting anomalies such as fractures, discontinuities, variations of pole section and to estimate length of the building. This method, born in Netherlands in the seventies, is well suited for precast concrete piles because of their regularity that will give more reliable measurements. It must be clear this test cannot provide information on bearing capacity of the work, but it can provide only information on quality of concrete. Methodology is essentially based on the physical principle of reflection, which means wave is generated with an impact on pole head and propagates up to pole base recording a signal by a receiver. More specifically, survey consists in generating at the top of the pole a compression wave through an instrumented hammer. Wave propagates with constant speed inside the pole (it is assumed that the medium is mostly homogeneous) until the opposite end where, because of change in density associated with discontinuities between background and concrete, it is reflected. Presence of any cavities, cracks, inclusions or poor quality concrete parts, generates anomalous reflections that overlap the original signal creating a returning signal which contains such information. Reflected signal is registered by a proper accelerometer, fixed at pole end. Analysis and correct interpretation of the signal called in technical terms "Reflectogram", allows to evaluate integrity of the pole. Length can be estimated from the known wave travel time (which travels at constant speed) from one end of the pole to the other. This test allows to investigate many poles in short time and with low cost. It is important to remember that test can be influenced by several factors which can affect the results. In this sense we want to underline that fractures or very large cavities do not allow to investigate the parts / units below them. In any case, strength points of this investigation are speed of execution and not particularly onerous data processing which require operators with a minimum of experience and 2

3 training. Reference regulation - ASTM D5882:2007 Standard Test Method for Low Strain Integrity Testing of Piles ; - Technical constructions regulations of 14 January 2008; - Ultrasonic speed through concrete is similar to that of ultrasonic test (UNI EN 9524). Data recording mode Present paragraph describes instrument functioning and the steps to be done in field for a correct execution of the test. Prepare with proper tools the surface (head of the pile) on which ETBT will be placed. Therefore it is recommended to bring gloves and brushes or iron spatula to remove debris, bentonite layers and angularity from the head of the pile. Without these precautions test can be altered. Test accuracy in determination of pole length directly depends on sonic pulse propagation speed within concrete, a factor that depends on the age and the strength of concrete, varies from pole to pole, and has an error margin of 10%. Travelling through the pile, wave loses energy due to internal frictions and whenever it encounters a change in pole section, a reflected wave that propagates upwards is generated, where it is detected by ETBT accelerometer. Impact point must be chosen close to pole center and the receiver (ETBT device) should be placed at cm from the edge within the armor. It is important to carefully check "coupling" between ETBT and concrete surface on which it is placed; it is recommended to use grout but also adhesive material such as plastic. It can be also used a mass of few kilos to increase adherence. When the head of the pile is hit in desired spot, impact starts signal acquisition coming from the accelerometer; this is shown immediately on Android device screen. To get an 3

4 average more reliable data, it is recommended to repeat test many times (from 5 to 10) so that during processing it is possible to delete any wrong measurement or any data different from average values. Resulting signal is then saved on Android device for later processing. Detailed operations to perform on device are described below. At Echotest Bt application start, screen as picture 1 appears on Android device. Picture 1 : Application home. By clicking on Connect button, list of instruments previously coupled will be displayed (see Pic.2), then scan peripherals detected by Bluetooth system; among that, the one named BT-232 must be searched. Once found and selected it, pairing code must be entered. Pairing-code is 1234 or Green written connected to: BT-232 indicates correct connection. Entering code procedure for connection is necessary only at application first start, then it will be necessary just to select device into the list. 4

5 Picture 2:Devices previously connected To proceed with echometric test, some information are required. For future reference to the investigated pile, it is recommended to identify it through site name and a brief description. These data will be used later, when saving recordings, to generate file name. To start a new test, press button New. Screen to enter pile identification data will be displayed as in picture 3. Picture 3:Pile identificative data entering. In addition, it is necessary to enter pile estimated length, in order to facilitate reading of 5

6 reflected pulse, and average propagation speed of compression waves into investigated concrete. It can be estimated according to concrete type and its maturity. If user has accessories for ultrasonic measures, it is recommended to measure speed directly through contact probes for a better characterization. Once entered and saved information, they will be displayed on main screen. Moreover, on graphic a vertical cursor will appear, in pink color and named P, which indicates entered pile length as in picture 4. If entered data are not correct, they can be changed through New button. Picture 4 : Entered data visualization. After entering identification values, speed and length, device must be configured; by clicking Setting button, configuration menu will be accessed (pic. 5). 6

7 Picture 5: Configuration window. Setting parameters are described below. Timebase, which indicates sampling interval of signal received by accelerometer, determines also observation time after hammering. Recommended setting is microseconds. It is recommended to set it so to have P cursor at 3 quarter of the screen. Trigger, which determines necessary intensity to start recording: instrument sensitivity decreases at this percentage increasing. It is recommended to set it at 30%, given seismic vibrations usually present on site. Compensation, which allows to apply an amplification, increasing exponentially in time. Signal generated by accelerometer at hammering is hundreds of time higher than signal reflecting few milliseconds later, it is clear that applied amplification cannot remain constant during recording. It is recommended to start with cursor placed between a quarter and middle of its travel (compensation 45%). Low-pass filter (LPF), which is necessary to remove high frequencies disturbing recording. In most cases it is recommended to activate low-pass filter to remove higher frequencies noise. Moving cursor towards right, a more and more low shear frequency is 7

8 selected. Gain varies recording wave amplitude. 2.5 gain is recommended. Invert which, if activated, allows to invert recording polarity, that is to say turn semi-wave from positive to negative and vice-versa. Once set necessary parameters detailed above it is possible to start recording by clicking Start button on the application, in order to arm trigger and prepare it to hammering. On device trigger led will brighten to confirm status. At each hammering device will receive an acquisition and related reflectogram will be displayed, confirming it through a beep and a vibration. Before proceeding with a second hammering, wait for trigger rearmament, which can be tested with a second vibration (if active), with trigger led lightening on ETBT and Start button in green color. At each hammering a reflectogram will be added in recording list, while that present in main screen is average of all recorded reflectograms. It is possible to include or exclude a reflectogram from average by clicking on it once opened the list (pic.6). Picture 6: Window displaying sequence of performed recordings. Reflectogram 4 is excluded so it won t be computed in average computing; to include it, just click again on it. 8

9 The estimated length of the pile can be acquired on field by touching the screen on graph in echo matching point. You will see a red vertical cursor with the distance in meters of its position. When test is finished, it is possible to immediately visualize on site test report containing all data of the survey. When it is possible to find return point (or points) with sufficient accuracy, save data acquired by pressing "Save" button on the Home and choose a name or leave the one set above. File will be saved in *.wav extension in the SD-card of Android device, in the folder Echotest (directory:/mnt/sdcard/echotest). Moreover it is possible to add descriptive notes to recording. By clicking on button Menu screen shown in picture 7 will be displayed. Pic.7 Menù Supplied software Echowin Net allows to elaborate survey and do proper evaluations about status and depth of investigated pile. 9

10 PILE PROFILE DESCRIPTION REFLECTOGRAM Pile: base Base: fixed Length: as estimated Pile: full Base: free Length: as estimated Pile: full Base: fixed Length: shorter Pile which broadens Pile which narrows Pile which broadens locally Pile which narrows locally Irregular profile 10

11 11

PulseCounter Neutron & Gamma Spectrometry Software Manual

PulseCounter Neutron & Gamma Spectrometry Software Manual PulseCounter Neutron & Gamma Spectrometry Software Manual MAXIMUS ENERGY CORPORATION Written by Dr. Max I. Fomitchev-Zamilov Web: maximus.energy TABLE OF CONTENTS 0. GENERAL INFORMATION 1. DEFAULT SCREEN

More information

Quick reference guide

Quick reference guide Quick reference guide Manufactured by: Esaote Europe B.V. Philipsweg 1 6227 AJ Maastricht The Netherlands Tel. +31 (43) 382 4600 Fax +31 (43) 382 4601 Internet: www.esaote.com Email: international.sales@esaote.com

More information

APP USE USER MANUAL 2017 VERSION BASED ON WAVE TRACKING TECHNIQUE

APP USE USER MANUAL 2017 VERSION BASED ON WAVE TRACKING TECHNIQUE APP USE USER MANUAL 2017 VERSION BASED ON WAVE TRACKING TECHNIQUE All rights reserved All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in

More information

The BAT WAVE ANALYZER project

The BAT WAVE ANALYZER project The BAT WAVE ANALYZER project Conditions of Use The Bat Wave Analyzer program is free for personal use and can be redistributed provided it is not changed in any way, and no fee is requested. The Bat Wave

More information

Source/Receiver (SR) Setup

Source/Receiver (SR) Setup PS User Guide Series 2015 Source/Receiver (SR) Setup For 1-D and 2-D Vs Profiling Prepared By Choon B. Park, Ph.D. January 2015 Table of Contents Page 1. Overview 2 2. Source/Receiver (SR) Setup Main Menu

More information

PHY221 Lab 1 Discovering Motion: Introduction to Logger Pro and the Motion Detector; Motion with Constant Velocity

PHY221 Lab 1 Discovering Motion: Introduction to Logger Pro and the Motion Detector; Motion with Constant Velocity PHY221 Lab 1 Discovering Motion: Introduction to Logger Pro and the Motion Detector; Motion with Constant Velocity Print Your Name Print Your Partners' Names Instructions August 31, 2016 Before lab, read

More information

ME EN 363 ELEMENTARY INSTRUMENTATION Lab: Basic Lab Instruments and Data Acquisition

ME EN 363 ELEMENTARY INSTRUMENTATION Lab: Basic Lab Instruments and Data Acquisition ME EN 363 ELEMENTARY INSTRUMENTATION Lab: Basic Lab Instruments and Data Acquisition INTRODUCTION Many sensors produce continuous voltage signals. In this lab, you will learn about some common methods

More information

X820S Seismic / accelerometric digitizer channels - 24 bit

X820S Seismic / accelerometric digitizer channels - 24 bit Seismic / accelerometric digitizer 24-96 channels - 24 bit DESCRIPTION Seismic/accelerometric digitizer equipped with 24-48-72-96 embedded channels for active and passive seismic surveys, dynamic investigations

More information

Pole Zero Correction using OBSPY and PSN Data

Pole Zero Correction using OBSPY and PSN Data Pole Zero Correction using OBSPY and PSN Data Obspy provides the possibility of instrument response correction. WinSDR and WinQuake already have capability to embed the required information into the event

More information

A Matlab toolbox for. Characterisation Of Recorded Underwater Sound (CHORUS) USER S GUIDE

A Matlab toolbox for. Characterisation Of Recorded Underwater Sound (CHORUS) USER S GUIDE Centre for Marine Science and Technology A Matlab toolbox for Characterisation Of Recorded Underwater Sound (CHORUS) USER S GUIDE Version 5.0b Prepared for: Centre for Marine Science and Technology Prepared

More information

EAN-Performance and Latency

EAN-Performance and Latency EAN-Performance and Latency PN: EAN-Performance-and-Latency 6/4/2018 SightLine Applications, Inc. Contact: Web: sightlineapplications.com Sales: sales@sightlineapplications.com Support: support@sightlineapplications.com

More information

1 Ver.mob Brief guide

1 Ver.mob Brief guide 1 Ver.mob 14.02.2017 Brief guide 2 Contents Introduction... 3 Main features... 3 Hardware and software requirements... 3 The installation of the program... 3 Description of the main Windows of the program...

More information

NOTICE: This document is for use only at UNSW. No copies can be made of this document without the permission of the authors.

NOTICE: This document is for use only at UNSW. No copies can be made of this document without the permission of the authors. Brüel & Kjær Pulse Primer University of New South Wales School of Mechanical and Manufacturing Engineering September 2005 Prepared by Michael Skeen and Geoff Lucas NOTICE: This document is for use only

More information

Patchmaster. Elektronik. The Pulse generator. February 2013

Patchmaster. Elektronik. The Pulse generator. February 2013 Patchmaster The Pulse generator Elektronik Telly Galiatsatos, BS 1987: Graduated at Queens College, NY Computer Science 1987-2007: Instrutech Corporation IT Engineering Support Software Engineer, Sales

More information

Logic Analyzer Auto Run / Stop Channels / trigger / Measuring Tools Axis control panel Status Display

Logic Analyzer Auto Run / Stop Channels / trigger / Measuring Tools Axis control panel Status Display Logic Analyzer The graphical user interface of the Logic Analyzer fits well into the overall design of the Red Pitaya applications providing the same operating concept. The Logic Analyzer user interface

More information

Machinery Diagnostic Plots Part 1 ORBIT Back-to-Basics: What does the data really tell us?

Machinery Diagnostic Plots Part 1 ORBIT Back-to-Basics: What does the data really tell us? Machinery Diagnostic Plots Part 1 ORBIT Back-to-Basics: What does the data really tell us? Gaston Desimone Latin America Technical Leader Bently Nevada* Machinery Diagnostic Services (MDS) Buenos Aires

More information

For the SIA. Applications of Propagation Delay & Skew tool. Introduction. Theory of Operation. Propagation Delay & Skew Tool

For the SIA. Applications of Propagation Delay & Skew tool. Introduction. Theory of Operation. Propagation Delay & Skew Tool For the SIA Applications of Propagation Delay & Skew tool Determine signal propagation delay time Detect skewing between channels on rising or falling edges Create histograms of different edge relationships

More information

MTI-2100 FOTONIC SENSOR. High resolution, non-contact. measurement of vibration. and displacement

MTI-2100 FOTONIC SENSOR. High resolution, non-contact. measurement of vibration. and displacement A worldwide leader in precision measurement solutions MTI-2100 FOTONIC SENSOR High resolution, non-contact measurement of vibration and displacement MTI-2100 Fotonic TM Sensor Unmatched Resolution and

More information

The Measurement Tools and What They Do

The Measurement Tools and What They Do 2 The Measurement Tools The Measurement Tools and What They Do JITTERWIZARD The JitterWizard is a unique capability of the JitterPro package that performs the requisite scope setup chores while simplifying

More information

127566, Россия, Москва, Алтуфьевское шоссе, дом 48, корпус 1 Телефон: +7 (499) (800) (бесплатно на территории России)

127566, Россия, Москва, Алтуфьевское шоссе, дом 48, корпус 1 Телефон: +7 (499) (800) (бесплатно на территории России) 127566, Россия, Москва, Алтуфьевское шоссе, дом 48, корпус 1 Телефон: +7 (499) 322-99-34 +7 (800) 200-74-93 (бесплатно на территории России) E-mail: info@awt.ru, web:www.awt.ru Contents 1 Introduction...2

More information

B2 Spice A/D Tutorial Author: B. Mealy revised: July 27, 2006

B2 Spice A/D Tutorial Author: B. Mealy revised: July 27, 2006 B2 Spice A/D Tutorial Author: B. Mealy revised: July 27, 2006 The B 2 Spice A/D software allows for the simulation of digital, analog, and hybrid circuits. CPE 169, however, is only concerned with the

More information

Noise. CHEM 411L Instrumental Analysis Laboratory Revision 2.0

Noise. CHEM 411L Instrumental Analysis Laboratory Revision 2.0 CHEM 411L Instrumental Analysis Laboratory Revision 2.0 Noise In this laboratory exercise we will determine the Signal-to-Noise (S/N) ratio for an IR spectrum of Air using a Thermo Nicolet Avatar 360 Fourier

More information

Audacity Tips and Tricks for Podcasters

Audacity Tips and Tricks for Podcasters Audacity Tips and Tricks for Podcasters Common Challenges in Podcast Recording Pops and Clicks Sometimes audio recordings contain pops or clicks caused by a too hard p, t, or k sound, by just a little

More information

Linrad On-Screen Controls K1JT

Linrad On-Screen Controls K1JT Linrad On-Screen Controls K1JT Main (Startup) Menu A = Weak signal CW B = Normal CW C = Meteor scatter CW D = SSB E = FM F = AM G = QRSS CW H = TX test I = Soundcard test mode J = Analog hardware tune

More information

Electrical and Electronic Laboratory Faculty of Engineering Chulalongkorn University. Cathode-Ray Oscilloscope (CRO)

Electrical and Electronic Laboratory Faculty of Engineering Chulalongkorn University. Cathode-Ray Oscilloscope (CRO) 2141274 Electrical and Electronic Laboratory Faculty of Engineering Chulalongkorn University Cathode-Ray Oscilloscope (CRO) Objectives You will be able to use an oscilloscope to measure voltage, frequency

More information

Experiment 9A: Magnetism/The Oscilloscope

Experiment 9A: Magnetism/The Oscilloscope Experiment 9A: Magnetism/The Oscilloscope (This lab s "write up" is integrated into the answer sheet. You don't need to attach a separate one.) Part I: Magnetism and Coils A. Obtain a neodymium magnet

More information

Standard Operating Procedure of nanoir2-s

Standard Operating Procedure of nanoir2-s Standard Operating Procedure of nanoir2-s The Anasys nanoir2 system is the AFM-based nanoscale infrared (IR) spectrometer, which has a patented technique based on photothermal induced resonance (PTIR),

More information

A COMPUTERIZED SYSTEM FOR THE ADVANCED INSPECTION OF REACTOR VESSEL STUDS AND NUTS BY COMBINED MULTI-FREQUENCY EDDY CURRENT AND ULTRASONIC TECHNIQUE

A COMPUTERIZED SYSTEM FOR THE ADVANCED INSPECTION OF REACTOR VESSEL STUDS AND NUTS BY COMBINED MULTI-FREQUENCY EDDY CURRENT AND ULTRASONIC TECHNIQUE More Info at Open Access Database www.ndt.net/?id=18566 A COMPUTERIZED SYSTEM FOR THE ADVANCED INSPECTION OF REACTOR VESSEL STUDS AND NUTS BY COMBINED MULTI-FREQUENCY EDDY CURRENT AND ULTRASONIC TECHNIQUE

More information

Getting Started with the LabVIEW Sound and Vibration Toolkit

Getting Started with the LabVIEW Sound and Vibration Toolkit 1 Getting Started with the LabVIEW Sound and Vibration Toolkit This tutorial is designed to introduce you to some of the sound and vibration analysis capabilities in the industry-leading software tool

More information

A HIGHLY INTERACTIVE SYSTEM FOR PROCESSING LARGE VOLUMES OF ULTRASONIC TESTING DATA. H. L. Grothues, R. H. Peterson, D. R. Hamlin, K. s.

A HIGHLY INTERACTIVE SYSTEM FOR PROCESSING LARGE VOLUMES OF ULTRASONIC TESTING DATA. H. L. Grothues, R. H. Peterson, D. R. Hamlin, K. s. A HIGHLY INTERACTIVE SYSTEM FOR PROCESSING LARGE VOLUMES OF ULTRASONIC TESTING DATA H. L. Grothues, R. H. Peterson, D. R. Hamlin, K. s. Pickens Southwest Research Institute San Antonio, Texas INTRODUCTION

More information

ULTRASONIC LOW-FREQUENCY FLAW DETERTOR A1220 ANKER USER MANUAL

ULTRASONIC LOW-FREQUENCY FLAW DETERTOR A1220 ANKER USER MANUAL ULTRASONIC LOW-FREQUENCY FLAW DETERTOR USER MANUAL Acoustic control systems Moscow 2006 CONTENTS 1 MAIN DATA... Ошибка! Закладка не определена. 1.1 List of abbreviations... Ошибка! Закладка не определена.

More information

Oscilloscope Guide Tektronix TDS3034B & TDS3052B

Oscilloscope Guide Tektronix TDS3034B & TDS3052B Tektronix TDS3034B & TDS3052B Version 2008-Jan-1 Dept. of Electrical & Computer Engineering Portland State University Copyright 2008 Portland State University 1 Basic Information This guide provides basic

More information

Ver.mob Quick start

Ver.mob Quick start Ver.mob 14.02.2017 Quick start Contents Introduction... 3 The parameters established by default... 3 The description of configuration H... 5 The top row of buttons... 5 Horizontal graphic bar... 5 A numerical

More information

Guided Wave Radar Level Meter

Guided Wave Radar Level Meter Guided Wave Radar Level Meter Guided Wave Radar Level Meter Instruction 1. Product Description 1.1 principle of measurement Guided Wave Radar is the measuring instruments that based on the time travel

More information

Reference. TDS7000 Series Digital Phosphor Oscilloscopes

Reference. TDS7000 Series Digital Phosphor Oscilloscopes Reference TDS7000 Series Digital Phosphor Oscilloscopes 07-070-00 0707000 To Use the Front Panel You can use the dedicated, front-panel knobs and buttons to do the most common operations. Turn INTENSITY

More information

Chapter 7. Scanner Controls

Chapter 7. Scanner Controls Chapter 7 Scanner Controls Gain Compensation Echoes created by similar acoustic mismatches at interfaces deeper in the body return to the transducer with weaker amplitude than those closer because of the

More information

OptoFidelity Video Multimeter User Manual Version 2017Q1.0

OptoFidelity Video Multimeter User Manual Version 2017Q1.0 OptoFidelity Video Multimeter User Manual Version 2017Q1.0 OptoFidelity Oy sales@optofidelity.com www.optofidelity.com OptoFidelity 2017 Microsoft and Excel are either registered trademarks or trademarks

More information

What s New in Raven May 2006 This document briefly summarizes the new features that have been added to Raven since the release of Raven

What s New in Raven May 2006 This document briefly summarizes the new features that have been added to Raven since the release of Raven What s New in Raven 1.3 16 May 2006 This document briefly summarizes the new features that have been added to Raven since the release of Raven 1.2.1. Extensible multi-channel audio input device support

More information

Practice, Practice, Practice Using Prototek Digital Receivers

Practice, Practice, Practice Using Prototek Digital Receivers Practice, Practice, Practice Using Prototek Digital Receivers You have purchased some of the finest locating tools in the business, but they don t do magic. Your skill at handling these tools and recognizing

More information

Operation Guide 3464

Operation Guide 3464 MA1810-EB 2018 CASIO COMPUTER CO., LTD. Contents Stopwatch Alarms and Hourly Time Signal Split Times and Lap Times Configuring Alarm Settings Before Getting Started... Indicators Graphic Display Area Navigating

More information

TECHNICAL PASSPORT OPERATION MANUAL

TECHNICAL PASSPORT OPERATION MANUAL «Acoustic Control Systems» Ltd. TECHNICAL PASSPORT OPERATION MANUAL LOW-FREQUENCY ULTRASONIC FLAW DETECTOR А1220 MONOLITH Москва, 2004 CONTENT: 1. General information 3 1.1 Operation principles 3 1.2 Application

More information

Common Spatial Patterns 2 class BCI V Copyright 2012 g.tec medical engineering GmbH

Common Spatial Patterns 2 class BCI V Copyright 2012 g.tec medical engineering GmbH g.tec medical engineering GmbH Sierningstrasse 14, A-4521 Schiedlberg Austria - Europe Tel.: (43)-7251-22240-0 Fax: (43)-7251-22240-39 office@gtec.at, http://www.gtec.at Common Spatial Patterns 2 class

More information

HOME GUARD USER MANUAL

HOME GUARD USER MANUAL HOME GUARD USER MANUAL CONTENTS 1. SAFETY PRECAUTIONS...2 2. INTRODUCTION...3 3. FEATURES...4 4. ACCESSORIES...5 5. INSTALLATION...6 6. NAME and FUNCTION of EACH PART...7 6.1 Front Pannel...7 6.2 Monitoring

More information

SPECIAL REPORT OF THE SUBCOMMITTEE ON POLARITY STANDARDS 1

SPECIAL REPORT OF THE SUBCOMMITTEE ON POLARITY STANDARDS 1 This document has been converted from the original publication: Thigpen, Ben B., Dalby, A. E. and Landrum, Ralph, 1975, Report on Subcommittee on Polarity Standards *: Geophysics, 40, no. 04, 694-699.

More information

Universal Mode. Survey Settings. The Universal Toolbar. First Run - Initial Configuration via the Setup Button

Universal Mode. Survey Settings. The Universal Toolbar. First Run - Initial Configuration via the Setup Button Universal Mode The Universal Toolbar The Universal Toolbar is the unified (and preferred) method of operating Revolution. From within the Universal Toobar, all functionality of the other 3 modes of Revolution

More information

The Cocktail Party Effect. Binaural Masking. The Precedence Effect. Music 175: Time and Space

The Cocktail Party Effect. Binaural Masking. The Precedence Effect. Music 175: Time and Space The Cocktail Party Effect Music 175: Time and Space Tamara Smyth, trsmyth@ucsd.edu Department of Music, University of California, San Diego (UCSD) April 20, 2017 Cocktail Party Effect: ability to follow

More information

Practicum 3, Fall 2010

Practicum 3, Fall 2010 A. F. Miller 2010 T1 Measurement 1 Practicum 3, Fall 2010 Measuring the longitudinal relaxation time: T1. Strychnine, dissolved CDCl3 The T1 is the characteristic time of relaxation of Z magnetization

More information

Diogen 24/24 two-regime seismograph

Diogen 24/24 two-regime seismograph Diogen 24/24 two-regime seismograph Moscow 2011 Diogen Diogen 24/24 Two-regime seismograph "Diogen-24/24" delivers high-quality seismic data to accurately assess geological conditions within engineering

More information

EDL8 Race Dash Manual Engine Management Systems

EDL8 Race Dash Manual Engine Management Systems Engine Management Systems EDL8 Race Dash Manual Engine Management Systems Page 1 EDL8 Race Dash Page 2 EMS Computers Pty Ltd Unit 9 / 171 Power St Glendenning NSW, 2761 Australia Phone.: +612 9675 1414

More information

ULTRA-TRAC APL INSTRUCTION MANUAL. Read and understand instructions before use. Patented. 851 Transport Drive Valparaiso, IN

ULTRA-TRAC APL INSTRUCTION MANUAL. Read and understand instructions before use. Patented. 851 Transport Drive Valparaiso, IN ULTRA-TRAC APL A C O U S T I C P I P E L O C A T O R INSTRUCTION MANUAL Read and understand instructions before use. Patented MADE IN USA 851 Transport Drive Valparaiso, IN 46383-8432 Phone: 888 4SENSIT

More information

A New "Duration-Adapted TR" Waveform Capture Method Eliminates Severe Limitations

A New Duration-Adapted TR Waveform Capture Method Eliminates Severe Limitations 31 st Conference of the European Working Group on Acoustic Emission (EWGAE) Th.3.B.4 More Info at Open Access Database www.ndt.net/?id=17567 A New "Duration-Adapted TR" Waveform Capture Method Eliminates

More information

WELDING CONTROL UNIT: TE 450 USER MANUAL

WELDING CONTROL UNIT: TE 450 USER MANUAL j WELDING CONTROL UNIT: TE 450 USER MANUAL RELEASE SOFTWARE No. 1.50 DOCUMENT NUMBER: MAN 4097 EDITION: MARCH 1998 This page is left blank intentionally. 2 / 34 TABLE OF CONTENTS SUBJECTS PAGE WELDING

More information

MIE 402: WORKSHOP ON DATA ACQUISITION AND SIGNAL PROCESSING Spring 2003

MIE 402: WORKSHOP ON DATA ACQUISITION AND SIGNAL PROCESSING Spring 2003 MIE 402: WORKSHOP ON DATA ACQUISITION AND SIGNAL PROCESSING Spring 2003 OBJECTIVE To become familiar with state-of-the-art digital data acquisition hardware and software. To explore common data acquisition

More information

Measurement of overtone frequencies of a toy piano and perception of its pitch

Measurement of overtone frequencies of a toy piano and perception of its pitch Measurement of overtone frequencies of a toy piano and perception of its pitch PACS: 43.75.Mn ABSTRACT Akira Nishimura Department of Media and Cultural Studies, Tokyo University of Information Sciences,

More information

Common Spatial Patterns 3 class BCI V Copyright 2012 g.tec medical engineering GmbH

Common Spatial Patterns 3 class BCI V Copyright 2012 g.tec medical engineering GmbH g.tec medical engineering GmbH Sierningstrasse 14, A-4521 Schiedlberg Austria - Europe Tel.: (43)-7251-22240-0 Fax: (43)-7251-22240-39 office@gtec.at, http://www.gtec.at Common Spatial Patterns 3 class

More information

Operating Instructions

Operating Instructions CNTX Contrast sensor Operating Instructions CAUTIONS AND WARNINGS SET-UP DISTANCE ADJUSTMENT: As a general rule, the sensor should be fixed at a 15 to 20 angle from directly perpendicular to the target

More information

IMIDTM. In Motion Identification. White Paper

IMIDTM. In Motion Identification. White Paper IMIDTM In Motion Identification Authorized Customer Use Legal Information No part of this document may be reproduced or transmitted in any form or by any means, electronic and printed, for any purpose,

More information

Digital Storage Oscilloscopes 2550 Series

Digital Storage Oscilloscopes 2550 Series Data Sheet Digital Storage Oscilloscopes 2550 Series The 2550 series digital storage oscilloscopes provide high performance and value in 2-channel and 4-channel configurations. With bandwidth from 70 MHz

More information

NanoGiant Oscilloscope/Function-Generator Program. Getting Started

NanoGiant Oscilloscope/Function-Generator Program. Getting Started Getting Started Page 1 of 17 NanoGiant Oscilloscope/Function-Generator Program Getting Started This NanoGiant Oscilloscope program gives you a small impression of the capabilities of the NanoGiant multi-purpose

More information

Working with a Tektronix TDS 3012B Oscilloscope EE 310: ELECTRONIC CIRCUIT DESIGN I

Working with a Tektronix TDS 3012B Oscilloscope EE 310: ELECTRONIC CIRCUIT DESIGN I Working with a Tektronix TDS 3012B Oscilloscope EE 310: ELECTRONIC CIRCUIT DESIGN I Prepared by: Kyle Botteon Questions? kyle.botteon@psu.edu 2 Background Information Recall that oscilloscopes (scopes)

More information

SLAB IMPULSE RESPONSE TEST NDE-360

SLAB IMPULSE RESPONSE TEST NDE-360 SYSTEM REFERENCE MANUAL 2008 SLAB IMPULSE RESPONSE TEST NDE-360 NOTICES Errors and Omissions This document is believed to be accurate, but Olson Instruments, Inc. will not be responsible for errors or

More information

Dave Jones Design Phone: (607) Lake St., Owego, NY USA

Dave Jones Design Phone: (607) Lake St., Owego, NY USA Manual v1.00a June 1, 2016 for firmware vers. 2.00 Dave Jones Design Phone: (607) 687-5740 34 Lake St., Owego, NY 13827 USA www.jonesvideo.com O Tool Plus - User Manual Main mode NOTE: New modules are

More information

DAC Express Release 3.4 (VT9801B)

DAC Express Release 3.4 (VT9801B) DAC Express Release 3.4 (VT9801B) DAC Express 3.4 Highlights n Display Wizard for fast test setups n 48-channel high performance remote strain measurement unit (EX1629) n Combine multi-channel analog,

More information

VivoSense. User Manual Galvanic Skin Response (GSR) Analysis Module. VivoSense, Inc. Newport Beach, CA, USA Tel. (858) , Fax.

VivoSense. User Manual Galvanic Skin Response (GSR) Analysis Module. VivoSense, Inc. Newport Beach, CA, USA Tel. (858) , Fax. VivoSense User Manual Galvanic Skin Response (GSR) Analysis VivoSense Version 3.1 VivoSense, Inc. Newport Beach, CA, USA Tel. (858) 876-8486, Fax. (248) 692-0980 Email: info@vivosense.com; Web: www.vivosense.com

More information

when it comes to quality! BMR GmbH 1

when it comes to quality! BMR GmbH 1 when it comes to quality! BMR GmbH 1 2 DressView Dressing systems Issue June 2016 1 Key functions 2 2 Menu structure 3 2.1 Main-menu 4 2.2 Terminal-menu 5 2.2.1 Adjusting the rotational speed in Terminal-menu

More information

PQ-Box 100 Quick Start Instructions

PQ-Box 100 Quick Start Instructions PQ-Box 100 Quick Start Instructions These instructions are provided for the purpose on providing a quick start to PQ-Box 100 installation and operation. Please refer to the user handbook for full details.

More information

PRACTICAL APPLICATION OF THE PHASED-ARRAY TECHNOLOGY WITH PAINT-BRUSH EVALUATION FOR SEAMLESS-TUBE TESTING

PRACTICAL APPLICATION OF THE PHASED-ARRAY TECHNOLOGY WITH PAINT-BRUSH EVALUATION FOR SEAMLESS-TUBE TESTING PRACTICAL APPLICATION OF THE PHASED-ARRAY TECHNOLOGY WITH PAINT-BRUSH EVALUATION FOR SEAMLESS-TUBE TESTING R.H. Pawelletz, E. Eufrasio, Vallourec & Mannesmann do Brazil, Belo Horizonte, Brazil; B. M. Bisiaux,

More information

Ultra 4K Tool Box. Version Release Note

Ultra 4K Tool Box. Version Release Note Ultra 4K Tool Box Version 2.1.43.0 Release Note This document summarises the enhancements introduced in Version 2.1 of the software for the Omnitek Ultra 4K Tool Box and related products. It also details

More information

Brain-Computer Interface (BCI)

Brain-Computer Interface (BCI) Brain-Computer Interface (BCI) Christoph Guger, Günter Edlinger, g.tec Guger Technologies OEG Herbersteinstr. 60, 8020 Graz, Austria, guger@gtec.at This tutorial shows HOW-TO find and extract proper signal

More information

RS232 Connection. Graphic LCD Screen. Power Button. Charger Adapter Input LNB Output. MagicFINDER Digital SatLock Operating Manual

RS232 Connection. Graphic LCD Screen. Power Button. Charger Adapter Input LNB Output. MagicFINDER Digital SatLock Operating Manual GENERAL FEATURES Easy-to-understand user-friendly menu and keypad. LNB short circuit protection. Display of Analog Signal Level, Digital Signal Quality with % and Bar, audible notification. Timer Lock,

More information

Real-time QC in HCHP seismic acquisition Ning Hongxiao, Wei Guowei and Wang Qiucheng, BGP, CNPC

Real-time QC in HCHP seismic acquisition Ning Hongxiao, Wei Guowei and Wang Qiucheng, BGP, CNPC Chengdu China Ning Hongxiao, Wei Guowei and Wang Qiucheng, BGP, CNPC Summary High channel count and high productivity bring huge challenges to the QC activities in the high-density and high-productivity

More information

Quick Start Bruker Dimension Icon AFM

Quick Start Bruker Dimension Icon AFM Do not remove Quick Start Bruker Dimension Icon AFM March 3, 2015 GLA Contacts Harold Fu (hfu@caltech.edu) Weilai Yu (wyyu@caltech.edu) Bruker Tech Support (AFMSupport@bruker-nano.com 800-873-9750) Watch

More information

The Syscal family of resistivity meters. Designed for the surveys you do.

The Syscal family of resistivity meters. Designed for the surveys you do. The Syscal family of resistivity meters. Designed for the surveys you do. Resistivity meters may conveniently be broken down into several categories according to their capabilities and applications. The

More information

WaveView. and. WaveCal

WaveView. and. WaveCal WaveView and WaveCal WaveView Introduction 1 Software Startup & Sample Acquisition 3 Startup WaveView 3 Configure Channels 5 Configure Acquisition 6 Collect and View Data 6 Store Data [and View File Data]

More information

TASTEPROBE Type DTP-1. Pre-amplifier for recording from contact chemosensilla INSTRUCTIONS

TASTEPROBE Type DTP-1. Pre-amplifier for recording from contact chemosensilla INSTRUCTIONS TASTEPROBE Type DTP-1 Pre-amplifier for recording from contact chemosensilla INSTRUCTIONS SYNTECH 2002 Hilversum, The Netherlands Reproduction of text and/or drawings is permitted for personal use. The

More information

Enhanced Diagnostics through Ultrasound Imaging

Enhanced Diagnostics through Ultrasound Imaging Enhanced Diagnostics through Ultrasound Imaging Mark Goodman, VP Engineering Presented by: Adrian Messer UE Systems, Inc. Ph: 914-592-1220 / 800-223-1325 Fax: 914-347-2181 Web: www.uesystems.com Email:

More information

BLUNIK II ACCESSORIES SPORT DRIVE SPORT CALCULATOR... 49

BLUNIK II ACCESSORIES SPORT DRIVE SPORT CALCULATOR... 49 USER GUIDE 12/2016 2 INDEX DESCRIPTION of BLUNIK II...6 DESCRIPTION of parameters...7 ADJUSTMENT OF PARAMETERS...7 Parameter: CLOCK SYNCHRO...8 Parameter: TIRES...9 Parameter: CALIBRATION... 10 Calibration

More information

Viavi ONX Ingress Mitigation and Troubleshooting Field Use Case using Ingress Expert

Viavi ONX Ingress Mitigation and Troubleshooting Field Use Case using Ingress Expert Viavi ONX Ingress Mitigation and Troubleshooting Field Use Case using Ingress Expert February 2018 Contents Purpose:... 2 Procedure:... 2 Real World Application and Use Case Findings:... 2 Consistent Noise

More information

Motion Video Compression

Motion Video Compression 7 Motion Video Compression 7.1 Motion video Motion video contains massive amounts of redundant information. This is because each image has redundant information and also because there are very few changes

More information

Immunity testing example using Tekbox TEM Cells

Immunity testing example using Tekbox TEM Cells 1 Introduction A customer asked us to solve an immunity issue of a corner light. The device failed BCI testing in the test house at frequencies in the 300 MHz to 400 MHz range. The failure mode was flickering

More information

Guide to Analysing Full Spectrum/Frequency Division Bat Calls with Audacity (v.2.0.5) by Thomas Foxley

Guide to Analysing Full Spectrum/Frequency Division Bat Calls with Audacity (v.2.0.5) by Thomas Foxley Guide to Analysing Full Spectrum/Frequency Division Bat Calls with Audacity (v.2.0.5) by Thomas Foxley Contents Getting Started Setting Up the Sound File Noise Removal Finding All the Bat Calls Call Analysis

More information

Activity P32: Variation of Light Intensity (Light Sensor)

Activity P32: Variation of Light Intensity (Light Sensor) Activity P32: Variation of Light Intensity (Light Sensor) Concept DataStudio ScienceWorkshop (Mac) ScienceWorkshop (Win) Illuminance P32 Vary Light.DS P54 Light Bulb Intensity P54_BULB.SWS Equipment Needed

More information

KNX Dimmer RGBW - User Manual

KNX Dimmer RGBW - User Manual KNX Dimmer RGBW - User Manual Item No.: LC-013-004 1. Product Description With the KNX Dimmer RGBW it is possible to control of RGBW, WW-CW LED or 4 independent channels with integrated KNX BCU. Simple

More information

System Requirements SA0314 Spectrum analyzer:

System Requirements SA0314 Spectrum analyzer: System Requirements SA0314 Spectrum analyzer: System requirements Windows XP, 7, Vista or 8: 1 GHz or faster 32-bit or 64-bit processor 1 GB RAM 10 MB hard disk space \ 1. Getting Started Insert DVD into

More information

#PS168 - Analysis of Intraventricular Pressure Wave Data (LVP Analysis)

#PS168 - Analysis of Intraventricular Pressure Wave Data (LVP Analysis) BIOPAC Systems, Inc. 42 Aero Camino Goleta, Ca 93117 Ph (805)685-0066 Fax (805)685-0067 www.biopac.com info@biopac.com #PS168 - Analysis of Intraventricular Pressure Wave Data (LVP Analysis) The Biopac

More information

Torsional vibration analysis in ArtemiS SUITE 1

Torsional vibration analysis in ArtemiS SUITE 1 02/18 in ArtemiS SUITE 1 Introduction 1 Revolution speed information as a separate analog channel 1 Revolution speed information as a digital pulse channel 2 Proceeding and general notes 3 Application

More information

Sources of Error in Time Interval Measurements

Sources of Error in Time Interval Measurements Sources of Error in Time Interval Measurements Application Note Some timer/counters available today offer resolution of below one nanosecond in their time interval measurements. Of course, high resolution

More information

FEASIBILITY STUDY OF USING EFLAWS ON QUALIFICATION OF NUCLEAR SPENT FUEL DISPOSAL CANISTER INSPECTION

FEASIBILITY STUDY OF USING EFLAWS ON QUALIFICATION OF NUCLEAR SPENT FUEL DISPOSAL CANISTER INSPECTION FEASIBILITY STUDY OF USING EFLAWS ON QUALIFICATION OF NUCLEAR SPENT FUEL DISPOSAL CANISTER INSPECTION More info about this article: http://www.ndt.net/?id=22532 Iikka Virkkunen 1, Ulf Ronneteg 2, Göran

More information

Expect to Make Waves.

Expect to Make Waves. Expect to Make Waves. The New Oscilloscope Large 10.4" LCD touch screen Long capture time Extensive communication capabilities www.lecroy.com The New Oscillos From its large 10.4" LCD touch screen to its

More information

Using AFM Phase Lag Data to Identify Microconstituents with Varying Values of Elastic Modulus

Using AFM Phase Lag Data to Identify Microconstituents with Varying Values of Elastic Modulus Using Data to Identify Microconstituents with Varying Values of Elastic Modulus D.N. Leonard*, A.D. Batchelor**, P.E. Russell*,** *Dept. of Material Science and Engineering, Box 7531, North Carolina State

More information

NI-DAQmx Device Considerations

NI-DAQmx Device Considerations NI-DAQmx Device Considerations January 2008, 370738M-01 This help file contains information specific to analog output (AO) Series devices, C Series, B Series, E Series devices, digital I/O (DIO) devices,

More information

Precise Digital Integration of Fast Analogue Signals using a 12-bit Oscilloscope

Precise Digital Integration of Fast Analogue Signals using a 12-bit Oscilloscope EUROPEAN ORGANIZATION FOR NUCLEAR RESEARCH CERN BEAMS DEPARTMENT CERN-BE-2014-002 BI Precise Digital Integration of Fast Analogue Signals using a 12-bit Oscilloscope M. Gasior; M. Krupa CERN Geneva/CH

More information

STX Stairs lighting controller.

STX Stairs lighting controller. Stairs lighting controller STX-1795 The STX-1795 controller serves for a dynamic control of the lighting of stairs. The lighting is switched on for consecutive steps, upwards or downwards, depending on

More information

BrainMaster tm System Type 2E Module & BMT Software for Windows tm. Display Screens for Master.exe

BrainMaster tm System Type 2E Module & BMT Software for Windows tm. Display Screens for Master.exe BrainMaster tm System Type 2E Module & BMT Software for Windows tm Display Screens for Master.exe 1995-2004 BrainMaster Technologies, Inc., All Rights Reserved BrainMaster and From the Decade of the Brain

More information

UPU 5000 Inline Delamination Detection and Process Trending with the Ultrasonic Measuring System

UPU 5000 Inline Delamination Detection and Process Trending with the Ultrasonic Measuring System UPU 5000 Inline Delamination Detection and Process Trending with the Ultrasonic Measuring System Delamination Detection and Process Trending with the GreCon Ultrasonic Measuring System Exploit all reserves

More information

ENGR 3030: Sound Demonstration Project. December 8, 2006 Western Michigan University. Steven Eick, Paul Fiero, and Andrew Sigler

ENGR 3030: Sound Demonstration Project. December 8, 2006 Western Michigan University. Steven Eick, Paul Fiero, and Andrew Sigler ENGR 00: Sound Demonstration Project December 8, 2006 Western Michigan University Steven Eick, Paul Fiero, and Andrew Sigler Introduction The goal of our project was to demonstrate the effects of sound

More information

Virtual Vibration Analyzer

Virtual Vibration Analyzer Virtual Vibration Analyzer Vibration/industrial systems LabVIEW DAQ by Ricardo Jaramillo, Manager, Ricardo Jaramillo y Cía; Daniel Jaramillo, Engineering Assistant, Ricardo Jaramillo y Cía The Challenge:

More information

Troubleshooting Your Design with the TDS3000C Series Oscilloscopes

Troubleshooting Your Design with the TDS3000C Series Oscilloscopes Troubleshooting Your Design with the 2 Table of Contents Getting Started........................................................... 4 Debug Digital Timing Problems...............................................

More information

Operation Guide 5554

Operation Guide 5554 MA1804-ED Contents Before Getting Started... Indicators Graphic Display Area Cycling Between Timekeeping Mode Digital Display Contents Navigating Between Modes Shifting the Hands Connecting with a Phone

More information

Flip-Flops. Because of this the state of the latch may keep changing in circuits with feedback as long as the clock pulse remains active.

Flip-Flops. Because of this the state of the latch may keep changing in circuits with feedback as long as the clock pulse remains active. Flip-Flops Objectives The objectives of this lesson are to study: 1. Latches versus Flip-Flops 2. Master-Slave Flip-Flops 3. Timing Analysis of Master-Slave Flip-Flops 4. Different Types of Master-Slave

More information