www. ElectricalPartManuals. com l Basler Electric VOLTAGE REGULATOR FEATURES: CLASS 300 EQUIPMENT AVC63 4 FEATURES AND APPLICATIONS

Size: px
Start display at page:

Download "www. ElectricalPartManuals. com l Basler Electric VOLTAGE REGULATOR FEATURES: CLASS 300 EQUIPMENT AVC63 4 FEATURES AND APPLICATIONS"

Transcription

1 Using enhanced technology, the AVC63-4 voltage regulator is designed for use on 50/60 Hz brushless generators. This encapsulated regulator is economical, small in size, ruggedly constructed, and incorporates solid state technology with frequency compensation, automatic voltage buildup, overexcitation shutdown, and EM filtering as standard. FEATURES: ntegrated circuitry for compact size, simplicity, high reliability. Extremely rugged. Exciter field current 4A continuous, 7 A forcing. Regulation accuracy better than ± 1.0% no load to full load. Fast response. Frequency compensation. Overexcitation shutdown. EM suppression. Available from stock. CSA approved, File #LR l Basler Electric CLASS 300 EQUPMENT AVC63 4 VOLTAGE REGULATOR P. 0. BOX 269 HGHLAND, LLNOS 62249, U.S.A. PHONE FAX FEATURES AND APPLCATONS this page DESCRPTON AND SPECFCATONS page 2 & 3 NTERCONNECT page 3 DMENSONS page 4 NSTRUCTON MANUAL Reference Publication Number SVC

2 :::J DESCRPTON: The AVC63-4 model of voltage regulator maintains generator line voltage on brush less generators from 5 KW to over 100 KW in size. The voltage regulator senses generator average voltage to maintain a precise regulation band within ± 1 percent. This is accomplished by converting a 240 V AC single phase power input to a controlled DC signal to the generator's exciter field. The solid-state voltage build-up circuit will enable automatic generator line voltage build-up with a voltage input to the regulator of at least 6 V AC. Customer accessible stability, underfrequency and range adjusts enable fine tuning of the voltage regulator to the generator in use. <( z 0 z u => a.. => 0 a: 0!cc a: w z w CD SPECFCATONS: "CORNER FREQUENCY" --T _-[ -T.-- - The over-excitation feature assists in protecting the voltage regulator during an over-excitation fault condition. During this mode, a shutdown signal is sent to the power stage, turning the regulator off. This feature will reset when the voltage input is removed (less than 6 VAC for a minimum of 2 seconds) to the regulator. Figure 1 demonstrates the underfrequency characteristics of the voltage regulator during prime mover low speed conditions. Customer curve selection matches the voltage regulator to 50 or 60 Hz systems. --n. - J =r FGURE 1 - DC OUTPUT FREQUENCY (Hz) FREQUENCY COMPENSATON CHARACTERSTC MAX FORCNG MAX. 1 MN MN. CONT. (240 Vac NPUT) OHMS@ AMP VOLT AMP VOLT EXCTER FELD RESSTANCE 25 C MAX. OHMS SENSNG/POWER SNGLE PHASE VOLTAGE RANGE NPUT BURDEN Vac 500VA 2

3 SPECFCATONS (continued): DC OUTPUT POWER: 4 Adc at 63 Vdc maximum continuous, 7 Adc at 100 Vdc one minute forcing. (Forcing with 240 Vac nominal input). EXCTER FELD DC RESSTANCE: 15 ohms minimum; 100 ohms maximum. AC SENSNG/POWER NPUT: Operating range: Vac single phase, 50/60 Hz ±10%. Burden 500VA. VOLTAGE ADJUST RANGE: Vac. REGULATON ACCURACY: Better than ±1.0% no load to full load. RESPONSE TME: Less than 1.5 cycles for ±5% change in sensing voltage. EM SUPPRESSON: nternal electromagnetic interference filtering. OVEREXCTATON SHUTDOWN: Field voltage shuts down after time delay if exciter field voltage exceeds 1 00 Vdc ±5%. The time delay is inversely proportional to the magnitude of the detected overvoltage condition up to F+ F- 3 4 _,_.----A AVC63-4 Hz Hz the 135 Vdc point, thus allowing nominal forcing for approximately 1 minute. Beyond 135 Vdc, the field voltage is removed within 2.0 seconds. VOLTAGE BULDUP: nternal provisions for automatic voltage buildup from generator residual voltages as low as 6 Vac. TERMNATONS: 1/4" "Fast-On" Terminals. POWER DSSPATON: 15 Watts maximum. OPERATNG TEMPERATURE: -40 C (-13 F) to +60 C (+140 F). STORAGE TEMPERATURE: -40 C (-40 F) to +85 C (+ 185 F). VBRATON: Withstands 1.2 Gs at 5 to 26 Hz; 0.036" double amplitude at 27 to 52 Hz; and 5 Gs at 53 to 500 Hz. SHOCK: Withstands up to 15 Gs in each of three mutually perpendicular axes. WEGHT: 8 oz. (0.22 kg) Net. NOTES:.&. FOR 50HZ OPERATON, MOVE JUMPER TO 50HZ TERMNAL. &. FOR REMOTE VOLTAGE ADJUST, USE 1000 OHMS, 1/2 WATT (MN) POT FOR 10% ADJUSTMENT RANGE. ffi USE FAST-BLOW FUSE WTH HGH CURRENT NTERRUPT CAPABLTY. OR 7t-----' nterconnection Diagram, 208/240Vac Nominal. FGURE 2 - TYPCAL NTERCONNECTON DAGRAM 3

4 4.187 DA. (2 PL) NOTES:.350 (9) VOLTAGE ADJUST 0 STABLTY ADJUST t ===== _l 3.935MAX (100) MAX (68) Analog Voltage Controller Model AVC63 4 PN: nput Vac, 50/60Hz, 500 VA Output 63 Vdc, 4 A U r;::;) Basler 9 Highland, llinois USA ---..J 1) DMENSONS ARE N NCHES (MLLMETERS). 2) TERMNALS ARE QUCK-CONNECT TABS.250" x.032". (6.35 x 0.8mm) ON.400" (10.16mm) CENTERS (except 60Hz). ffi DMENSONS TO TERMNALS ARE APPROXMATE. 4) NET WEGHT= 8 OZ (0.22 KG) 5) RECOMMENDED TORQUE LMT ON MOUNTNG HARDWARE: a. #8 screw 8-10 ln-lbs b. M4 screw.9 N-m 6) USE OF LOCKNG NUT WTH NYLON NSERT RECOMMENDED WHEN NSTALLNG AVC WTH LOOSE HARDWARE. UNDERFREQUENCY ADJUST MAX (56).181 (TYP.) (5).169 (TYP.) (4) ROUTE 143, BOX 269, HGHLAND, LLNOS U.S.A P.A.E. Les Pins, Wasselonne Cedex FRANCE PHONE FAX PHONE ( ) FAX ( ) info@basler.com Printed in U.S.A.

5 Using enhanced technology, the AVC full wave voltage regulator is designed for use on 50/60 Hz brushless generators. This encapsulated regulator is small in size, ruggedly constructed, and incorporates solid state technology with frequency compensation, a build-up circuit, overexcitation shutdown, droop input, accessory input, and EM filtering as standard. FEATURES ntegrated circuitry for compact size, simplicity, high reliability. Extremely rugged. Exciter field current 6A continuous, 1 OA forcing. Regulation accuracy better than ±0.5% no load to full load. Fast response. Frequency compensation. Overexcitation shutdown. EM suppression. Accessory input. ADDTONAL NFORMATON NSTRUCTON MANUAL Request Publication l Basler Electric AVC110-6 VOLTAGE REGULATOR c N EXCTATON ON/OFF SWTCH (F USED) Figure 1 -Typical nterconnection Diagram 277/480V nominal, 3-phase, 4-wire wye connection P. 0. BOX 269 HGHLAND, LLNOS 62249, U.S.A. PHONE FAX SVE

6 AVC11Q-6 SPECFCATONS EXCTER SENSNG DC OUTPUT F ELD RESSTANCE POWER NPUT NPUT MAX FORCNG SNGLE MAX. 10 SEC MN. MAX PHASE VOLTAGE CONT. (240Vac NPUT) OHMS@ OHMS VOLTAGE BURDEN ADJUST AMP VOLT AMP VOLT 25oC DC OUTPUT POWER: 6 Adc at 110 Vdc maximum continuous, 10 Adc at 200 Vdc 10 seconds forcing. (Forcing with 240 Vac nominal input). EXCTER FELD DC RESSTANCE: 18.3 ohms minimum; 100 ohms maximum. AC POWER NPUT: Operating range: Vac single phase, 50/60 Hz or 125Hz PMG ±10%. Burden 800VA. SENSNG NPUT: Vac single phase, 50/60 Hz ±10% <5VA. VOLTAGE ADJUST RANGE: Vac. REGULATON ACCURACY: Better than ±0.5% no load to full load. RESPONSE TME: Less than 1.5 cycles for ±5% change in sensing voltage. EM SUPPRESSON: nternal electromagnetic interference filtering. PARALLEL COMPENSATON: SA <10VA. Adjustable up to 6% droop for 0.8PF. ACCESSORY NPUT: ±3Vdc signal causes a ±30% change in the regulation set point. OVEREXCTATON SHUTDOWN: Field voltage shuts down after time delay if exciter field voltage exceeds a set point adjustable approx Vdc. The time delay is inversely proportional to the magnitude of the detected overvoltage condition up to the 240 Vdc point, thus allowing nominal forcing for approximately 10 seconds. Beyond 240 Vdc, the field voltage is removed instantaneously RANGE Vac ±10% 50/60Hz 125Hz PMG 800VA RANGE Vac 50/60Hz VOLTAGE BULDUP: nternal provisions for automatic voltage buildup from generator residual voltages as low as 5 Vac. TERMNATONS: Screw type. POWER DSSPATON: 35 Watts maximum. OPERATNG TEMPERATURE: -40 C (-40 F) to +60 C (+ 140 F). STORAGE TEMPERATURE: -40 C ( -40 F) to + 70 C ( F). VBRATON: Withstands 1.5 Gs at 5 to 29 Hz; 0.036" double amplitude at 29 to 52 Hz; and 5 Gs at 52 to 500 Hz. SHOCK: Withstands up to15 Gs in each of three mutually perpendicular axes. WEGHT: oz. (0.38 kg) Net (1248) ( ( 12.5) ) (140 0) Figure 3 - Outline Drawing (Top view) Basler Electric ROUTE 143, BOX 269, HGHLAND, LLNOS U.S.A P.A.E. Les Pins, Wasselonne Cedex FRANCE PHONE FAX PHONE ( ) FAX ( ) DA HOLE (58) (4 PLACES) basler. com, i nfo@basler.com 02BJQ.) Printed in U.S.A.

www. ElectricalPartManuals. com l Basler Electric P. 0. BOX 269 HIGHLAND, ILLINOIS 62249, U.S.A. PHONE FAX

www. ElectricalPartManuals. com l Basler Electric P. 0. BOX 269 HIGHLAND, ILLINOIS 62249, U.S.A. PHONE FAX - L M limn The BE1- Ground Fault Overvoltage Relay provides sensitive protection for ungrounded and high resistance grounded systems. ADVANTAGES Provides 1 00% stator ground fault protection. 100/120 Vac

More information

ORDERING Page 6 BASLER RELAY STANDARDS, DIMENSIONS, ACCESSORIES Request bulletin SDA

ORDERING Page 6 BASLER RELAY STANDARDS, DIMENSIONS, ACCESSORIES Request bulletin SDA BE1-59NC CAPACITOR NEUTRAL OVERVOLTAGE RELAY The BE1-59NC Capacitor Neutral Overvoltage Relay provides sensitive protection for capacitor banks. ADDITIONAL INFORMATION INSTRUCTION MANUAL ADVANTAGES Helps

More information

ORDERING Page 6 STANDARDS, DIMENSIONS and ACCESSORIES Request bulletin SDA

ORDERING Page 6 STANDARDS, DIMENSIONS and ACCESSORIES Request bulletin SDA BE1-59NC CAPACITOR NEUTRAL OVERVOLTAGE RELAY The BE1-59NC Capacitor Neutral Overvoltage Relay provides sensitive protection for capacitor banks. ADVANTAGES Helps avoid cascading capacitor failures. Sensing

More information

CLASS 300 EQUIPMENT BE3-25A AUTO-SYNCHRONIZER (Single Phase)

CLASS 300 EQUIPMENT BE3-25A AUTO-SYNCHRONIZER (Single Phase) CLASS 300 EQUIPMENT BE3-25A AUTO-SYNCHRONIZER (Single Phase) In applications requiring parallel operation of multiple generators or a single generator to an energized station bus, the BE3-25A automatically

More information

EA63-7D. Generator Automatic Voltage Regulator Operation Manual. Self Excited Automatic Voltage Regulator

EA63-7D. Generator Automatic Voltage Regulator Operation Manual. Self Excited Automatic Voltage Regulator EA63-7D Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator SP POWERWORLD LTD Willows, Waterside, Ryhall, Stamford, Lincs, PE9 4EY, UK Tel: +44 1780 756872 -

More information

Self Excited Automatic Voltage Regulator For Generator Compatible with Marathon SE350* Operation Manual

Self Excited Automatic Voltage Regulator For Generator Compatible with Marathon SE350* Operation Manual Self Excited Automatic Voltage Regulator For Generator Compatible with Marathon SE350* Operation Manual s * Use for reference purpose only and not a genuine Marathon product. 1. INTRODUCTION Sensing Input

More information

EA350. Generator Automatic Voltage Regulator Operation Manual

EA350. Generator Automatic Voltage Regulator Operation Manual Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator For General Generators Compatible with Marathon SE350* * Use for reference purpose only and not a genuine

More information

EVC300i. Generator Automatic Voltage Regulator Operation Manual

EVC300i. Generator Automatic Voltage Regulator Operation Manual EVC300i Generator Automatic Voltage Regulator Operation Manual 1. INTRODUCTION The EVC300i Voltage Regulator is thyristor base to control the DC exciter field power of conventional 50 or 60 Hz brushless

More information

EVC600i. Generator Automatic Voltage Regulator Operation Manual

EVC600i. Generator Automatic Voltage Regulator Operation Manual EVC600i Generator Automatic Voltage Regulator Operation Manual 1. INTRODUCTION The EVC600i Voltage Regulator is thyristor base to control the DC exciter field power of conventional 50 or 60 Hz brushless

More information

BE3-GPR GENERATOR PROTECTIVE RELAY

BE3-GPR GENERATOR PROTECTIVE RELAY BE3-GPR GENERATOR PROTECTIVE RELAY Behind-the-Panel Mounting Semi-flush Mounting Basler Electric s BE3-GPR generator protective relay offers multiple protective features in a single package. Its microprocessor-based

More information

PBC series. RoHS. Ready. IEC-Type Contactors & Accessories 9-80 Amp AC-3, Amp AC-1 AC Coils. P&B PBC Series IEC Type Contactors & Accessories

PBC series. RoHS. Ready. IEC-Type Contactors & Accessories 9-80 Amp AC-3, Amp AC-1 AC Coils. P&B PBC Series IEC Type Contactors & Accessories PBC series IEC-Type Contactors & Accessories 9-80 Amp AC-3, 25-125 Amp AC-1 AC Coils File E38802 (PBC) RoHS Ready Users should thoroughly review the technical data before selecting a product part number.

More information

RMX-44 & RMX-62 MIXING MATRIX. Installation & Operation Manual

RMX-44 & RMX-62 MIXING MATRIX. Installation & Operation Manual RMX-44 & RMX-6 MIXING MATRIX Installation & Operation Manual TABLE OF CONTENTS RMX-44 & RMX-6 INTRODUCTION... RMX-44 CALLOUTS... RMX-44 BLOCK DIAGRAM... RMX-6 CALLOUTS... 4 RMX-6 BLOCK DIAGRAM... 5 RMX-44

More information

MAP110 AC-DC Series Data Sheet

MAP110 AC-DC Series Data Sheet Description Single-Output Model Selection VOLTAGE RANGE OUTPUT CURRENT OUTPUT CURRENT REGULATION REGULATION %p-p (NOTE 1) ACCURACY MAP110-1005 5V 4.95V to 5.50 16A 2 0.2% 1% 1% 5.09V to 5.11V MAP110-1012

More information

BE1-81O/U Frequency Protection. Washington State University Hands-On Relay School.

BE1-81O/U Frequency Protection. Washington State University Hands-On Relay School. Frequency Protection Washington State University Hands-On Relay School www.basler.com Relay Benefits As many as four independent, adjustable frequency setpoints and time delays Each setpoint has output

More information

Single output models feature wide-range output adjustability to meet a wide variety of standard and user-specific output voltage requirements.

Single output models feature wide-range output adjustability to meet a wide variety of standard and user-specific output voltage requirements. RoHS Lead-Solder-Exemption Compliant New 3.3 V and 5 V Output Models Universal Input 85-264 VAC Industry-Standard Footprint: 7.0" x 4.3" x 1.97" (177.8 x 109.2 x 50.0 mm) Input Transient & ESD Compliance

More information

EG4015. Digital Generator Governor Controller User Manual

EG4015. Digital Generator Governor Controller User Manual EG4015 Digital Generator Governor Controller User Manual Digital Governor for use in Gas and Diesel Generators with smoke and idle controls. Senses generator frequency, no magnetic pickup unit (MPU) is

More information

02/11/2015

02/11/2015 DIN Rail Mount 17.5 mm MUS/MUSF 80 AC/DC Part number 84872141 Control relays monitoring their own power supply - MUS : Over/undervoltage control Selectable latching (memory) function - MUSF : Over/undervoltage

More information

AF-300 E11 Adjustable Frequency Drive

AF-300 E11 Adjustable Frequency Drive AF-300 E11 Adjustable Frequency Drive The AF-300 E11 adjustable frequency drive is GE s new generation of micro drives. GE recognized your need for a high-performance, full-featured compact drive and designed

More information

3.5. Control Relays and Timers. Contents. 9575H Series 3000 Type AA, AC and DC. General Purpose Relays Type AA

3.5. Control Relays and Timers. Contents. 9575H Series 3000 Type AA, AC and DC. General Purpose Relays Type AA .5 9575H Series 000 Relay Contents 9575H Series 000 Type AA, AC and DC Product Selection....................... Accessories............................ Technical Data and Specifications........... Dimensions............................

More information

Solid-State Digital Timer

Solid-State Digital Timer Solid-State Digital Timer 1/16 DIN, Digital-Set Timer with 0.1 Second to 9,990 Hours Range 8 field-selectable operation modes Universal AC/DC supply voltage timers available Operations include ON-delay,

More information

ADVR-053. Universal Hybrid Analog-Digital Voltage Regulator Operation Manual

ADVR-053. Universal Hybrid Analog-Digital Voltage Regulator Operation Manual ADV-053 Universal Hybrid Analog-Digital Voltage egulator Operation Manual elf Excited 5 Amp Analog / Digital Voltage egulator For shunt and auxiliary windings generators With over-excitation and lost of

More information

Datasheet - SRB301LC 24VAC/DC

Datasheet - SRB301LC 24VAC/DC 25.02.2016-18:05:23h Datasheet - SRB301LC 24VAC/DC Guard door monitors and Safety control modules for Emergency Stop applications / General Purpose safety controllers (Series PROTECT SRB) / SRB301LC Preferred

More information

Series CT7N Bimetallic Overload Relays

Series CT7N Bimetallic Overload Relays Series CT7N imetallic Overload Relays Choose CT7N overloads in DC applications and when monitoring Variable Frequency Drives Sprecher + Schuh has always paid particular attention to the subject of motor

More information

VAT 20 Adjustable Frequency Drive

VAT 20 Adjustable Frequency Drive VAT 0 Adjustable Frequency Drive VAT 0 Adjustable Frequency Drive The VAT 0 is a small, flexible, low cost, well performing AC drive designed for use in small machines such as fans and conveyors. The drive

More information

Magnecraft Power Relays

Magnecraft Power Relays Description DPST-NO, 30 A; DPDT, 30 A (NO) / 3 A (NC) Description The series power relays offer a small package size and features Class F insulation for a maximum coil temperature of 55 C (3 F). These

More information

ADVR-08. Universal Hybrid Analog-Digital Voltage Regulator Operation Manual

ADVR-08. Universal Hybrid Analog-Digital Voltage Regulator Operation Manual Universal Hybrid Analog-Digital Voltage egulator Operation Manual Universal Hybrid Analog/Digital 2 lines sensing 8 Amp AV with multiple power input capability such as Full Harmonic (Compound Windings),

More information

Modular Lube Lubrication Systems System Controls

Modular Lube Lubrication Systems System Controls Model 84501 Program Timer Solid State Designed to control the lubrication cycle frequency of air-operated single-stroke pumps. Timer turns pump on/off at programmed intervals via a 3-way or 4-way air solenoid

More information

multi-function meters

multi-function meters multi-function meters eclipse 2 eclipse 7 installation and operating manual 1 GENERAL DESCRIPTION 2 INSTALLATION 3 WIRING INFORMATION 4 2 ECLIPSE 2 METERS 2.1 PROGRAMMING THE METER 5 2.2 INFORMATION 6

More information

Panel-mounting thermostats, type series EM

Panel-mounting thermostats, type series EM Data sheet 602025 Page /5 Panel-mounting thermostats, type series EM Particularities Operating temperature limiter Limit value range up to +650 C with temperature compensation Brief description Panel-mounting

More information

UDC100 Universal Digital Controller. Specification. Overview. Features. Features, continued /99 Page 1 of 4

UDC100 Universal Digital Controller. Specification. Overview. Features. Features, continued /99 Page 1 of 4 UDC100 Universal Digital Controller 51-52-03-29 11/99 Page 1 of 4 Specification Overview The UDC100 Universal Digital Controller is a microprocessor-based 1/4 DIN low cost temperature controller. It combines

More information

UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load Cell

UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load Cell 99 Washington Street Melrose, MA 02176 Fax 781-665-0780 TestEquipmentDepot.com UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load

More information

Soft starter, 66 A, V AC, Us= 24 V DC, with control unit, Frame size N. Function Soft starter for three-phase loads, with control unit

Soft starter, 66 A, V AC, Us= 24 V DC, with control unit, Frame size N. Function Soft starter for three-phase loads, with control unit DATASHEET - S811+N66N3S Delivery program Soft starter, 66 A, 200-600 V AC, Us= 24 V DC, with control unit, Frame size N Part no. S811+N66N3S Catalog No. 168978 Eaton Catalog No. S811PLUSN66N3S EL-Nummer

More information

Process Transmitter RMA 422

Process Transmitter RMA 422 Technical Information TI 072R/24/ae Process Transmitter RMA 422 Multi-functional 1-2 channel top hat DIN rail unit with loop power supply, alarm set point monitoring, mathematics function and 1-2 analog

More information

DPS-250AB-18 E. 電氣規格 (Electrical Specification) REV. Description Date DESCRIPTION : MODEL NO. : Date Drawn Desing(EE) Design(ME) DOCUMENT NO. : REV.

DPS-250AB-18 E. 電氣規格 (Electrical Specification) REV. Description Date DESCRIPTION : MODEL NO. : Date Drawn Desing(EE) Design(ME) DOCUMENT NO. : REV. Description Date 07/18/ 08 敖孌鳳孫占蠃杜連軍 ES-250AB-18 E S1 File Name DF-PSLA4V-2R00.DOC SHEET 1 OF 6 1. Input characteristics: 1.1 Input voltage range: 90Vac to 135Vac; 180Vac to 265Vac,single phase. switch

More information

Type Contact form Model

Type Contact form Model Low Signal Relay G6A High sensitivity can be driven by digital circuits. Low-profile design allows use in.70 mm (0.50 in) PC board rack. Surge withstand meets FCC Part 68 regulation. Units can be mounted

More information

High Performance Outdoor Test Translators

High Performance Outdoor Test Translators Input Output LO Frequency Frequency Frequency Model (GHz) (GHz) (GHz) Number RF Transmit-Band to RF Receive-Band 5.85 6.425 3.625 4.2 2.225 DN-WS-6.1/3.9 5.85 6.65 3.4 4.2 2.45 DN-WS-6.25/3.8 6.725 7.025

More information

Type: NZMN1 A100 Article No.: Sales text Circuit breaker3p systems/cable prot. Ordering information Number of poles

Type: NZMN1 A100 Article No.: Sales text Circuit breaker3p systems/cable prot. Ordering information Number of poles Type: NZMN1 A100 Article No.: 259085 Sales text Circuit breaker3p systems/cable prot. Ordering information Number of poles Description Rated current = rated uninterrupted current Setting range 3 pole I

More information

Standard RS232 RS ma

Standard RS232 RS ma 1 / 5 CONTROL AND VISUALIZATION OF AC CURRENT IN SINGLE PHASE LINES BY EXTERNAL SHUNT Function Operating mode Current control Frequency control DC component control Shunt Timer Resolution Current precision

More information

Generator protection relay

Generator protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Off-the-shelf generator protection relay for small and medium sized power generators Three-phase time overcurrent and

More information

Weekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N

Weekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N Weekly Timer 1/4 DIN Size Timer Features Prompted Programming and Large LCD Display 24 hours x 7 days programming using just 5 switches 16 program steps and cycle operation Two independent 15 A control

More information

MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz

MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz Mobile Communications MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz CAUTION THESE SERVICING INSTRUCTIONS ARE FOR USE BY QUALI- FIED PERSONNEL ONLY. TO

More information

Universal Hybrid Analog-Digital Voltage Regulator Operation Manual

Universal Hybrid Analog-Digital Voltage Regulator Operation Manual Universal Hybrid Analog-Digital Voltage egulator Operation Manual elf Excited Analog/Digital 5Amp AV For use in shunt and generators with auxiliary windings Warning! 1. Only qualified technicians should

More information

Absolute Rotary Encoder E6CP

Absolute Rotary Encoder E6CP Absolute Rotary Encoder Absolute Rotary Encoders with Gray Code Output Gray code output decreases output errors Lightweight plastic housing Used with Omron s H8PS Cam Positioner, this encoder detects the

More information

Ordering details. Approval. Classification

Ordering details. Approval. Classification Datasheet - SRB 301MC-24V Guard door monitors and Safety control modules for Emergency Stop applications / General Purpose safety controllers (Series PROTECT SRB) / SRB 301MC Fit for signal evaluation

More information

GP-500 SERIES - Low Voltage

GP-500 SERIES - Low Voltage M O T O R & G E N E R A T O R P R O T E C T I O N AUTOMATIC INSULATION RESISTANCE TESTERS Meg-Alert is an automatic, in-line insulation resistance tester and monitor with test capabilities from 500 to

More information

Panel cutout required: 1.772" x 3.622" (45mm x 92mm) 1.76" (45mm) 2.45" (62mm) 3.20" (81mm) 3.60" (91mm) 0.59" (15mm) Special Features

Panel cutout required: 1.772 x 3.622 (45mm x 92mm) 1.76 (45mm) 2.45 (62mm) 3.20 (81mm) 3.60 (91mm) 0.59 (15mm) Special Features NEMA4X, IP65 Front Bezel Meter with Relays Option RELAY2 RELAY1 24V OUT POWER 4 3 2 1 6 5 2 1 2 1 NO NC COM NO NC COM RTD TC P P RTD 3 4 1 2 5 TC 6 SWITCH Rear View Gasket APM765 Panel Meter Description

More information

Flat-Bed Module Recorders

Flat-Bed Module Recorders Flat-Bed Module Recorders Model No. 08376-50 08376-55 08376-60 0115-0192 4/28/00 Table of Contents Introduction...3 Power Requirements...3 Chart Paper Installation...3 Pen Installation...5 Grounding...5

More information

Specifications. Reference Documentation. Performance Conditions

Specifications. Reference Documentation. Performance Conditions The material in this section is organized into two main groupings: the specification tables and the supporting figures. The specification tables include: 1. PAL general and test signal specifications 2.

More information

TOSHIBA Industrial Magnetron E3328

TOSHIBA Industrial Magnetron E3328 TOSHIBA E3328 is a fixed frequency continuous wave magnetron intended for use in the industrial microwave heating applications. The average output power is 3kW in the frequency range from 2450 to 2470

More information

Bulletin 190 IEC Modular Starter System

Bulletin 190 IEC Modular Starter System Bulletin 90 Table of Contents Selection Guide Description Page Bulletin 90....................................... Accessories....................................... 7 Specifications.....................................

More information

Multifunction Digital Timer

Multifunction Digital Timer Multifunction Digital Timer 72 x72 mm Timer with Easy-to-use Functions Nine output modes accommodate a wide variety of applications. All parameters set by scroll-through menus accessed from the front panel.

More information

Catalogue Ignitors and power switches for HID

Catalogue Ignitors and power switches for HID Catalogue 2012 Ignitors and power switches for HID Overview Product overview Ignitor matrix Standards Page 6 Page 7 Page 8 Product information Ignitors and power switches for HID Page 9 Superimposed-pulse

More information

Model Number Structure

Model Number Structure Cycle Control Units CSM DS_E_7_1 Refer to Safety Precautions for All Power Controllers. Used in Combination with the to Enable High-precision Temperature Control Use cycle control to achieve power control

More information

LC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC

LC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC Product datasheet Characteristics LC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC Price* : 86.25 GBP Main Range Product name Product or component type Device short name Contactor application Utilisation category

More information

14 GHz, 2.2 kw KLYSTRON GENERATOR GKP 22KP 14GHz WR62 3x400V

14 GHz, 2.2 kw KLYSTRON GENERATOR GKP 22KP 14GHz WR62 3x400V 14 GHz, 2.2 kw KLYSTRON GENERATOR GKP 22KP 14GHz WR62 3x400V With its characteristics of power stability independent of the load, very fast response time when pulsed (via external modulated signal), low

More information

Process transmitter RMA422

Process transmitter RMA422 Technical information TI072R/09/en Mat. No. 51001905 Process transmitter RMA422 Multifunctional 1-2 channel top hat DIN rail unit with intrinsically safe current input and loop power supply, alarm set

More information

HYL-035D0850G103. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

HYL-035D0850G103. Constant current LED driver DALI Dimmable. LED Driver.   Product description. Benefits. Interfaces. Constant current LED driver DALI Dimmable Product description Dimmable Independent constant current Adjustable output current between 350 and 1,050mA via DIP switch Max. output power 35 W Up to 88 % efficiency

More information

Magnecraft General Purpose Relays 750R Series DPDT and 3DPT, 10 A

Magnecraft General Purpose Relays 750R Series DPDT and 3DPT, 10 A and 3DPT, 10 A UL Listed when used with proper Magnecraft s The 750R series octal base, plug-in relays offer clear or full-feature covers with multiple mounting options and accessories. 750R 750R Full-Feature

More information

Type Contact form Model PCB SPDT G6E-134P-ST-US G6E-134PL-ST-US. Type Contact form Model

Type Contact form Model PCB SPDT G6E-134P-ST-US G6E-134PL-ST-US. Type Contact form Model Low Signal Relay G6E Subminiature 7.87 H x.1 W x 16 L mm (0.31 H x 0.3 W x 0.63 L in). High sensitivity with pick-up coil power of 8 mw. Surge withstand meets FCC Part 68 rule and Telcordia 2.5 kv Specifications.

More information

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV MG-XV operating instruction Measuring of norm signals, 4-8-digit Panel instrument type MG-BV Construction instrument type MG-AV Contents 1. Brief description... 3 2. Safety instructions... 3 2.1. Proper

More information

SITOP power supply. Technical data, April SITOP Power Supply. Answers for industry.

SITOP power supply. Technical data, April SITOP Power Supply. Answers for industry. SITOP power supply Technical data, April 2010 SITOP Power Supply Answers for industry. SITOP reliable power supply Efficient operation of a machine or plant requires a reliable, constant power supply.

More information

XT-17M-B relay - Delay-off, 1 C/O, 16 A

XT-17M-B relay - Delay-off, 1 C/O, 16 A - Delay-off, 1 C/O, 16 A Datasheet Features Delay-off Single function Time ranges: XT-17M-B1 0.1...1 s XT-17M-B2 1...10 s XT-17M-B3 6...60 s XT-17M-B4 1...10 min XT-17M-B5 6...60 min XT-17M-B6 1...10 h

More information

MATE3 Owner s Manual Addendum

MATE3 Owner s Manual Addendum Purpose MATE3 Owner s Manual Addendum This document is an addendum to 900-0117-01-00, Revision C of the MATE3 System Display and Controller Owner s Manual. It provides descriptions of changes to the MATE3

More information

TRIPLETT. PairMaster. Lan Cable Test Set. Instruction Manual

TRIPLETT. PairMaster. Lan Cable Test Set. Instruction Manual TRIPLETT PairMaster Lan Cable Test Set Instruction Manual The PairMaster LAN CABLE TEST SET INSTRUCTION MANUAL IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS Before using the PairMaster, read all

More information

Passive UTP Transceiver Hub with Integral Camera Power Installation Guide

Passive UTP Transceiver Hub with Integral Camera Power Installation Guide Passive UTP Transceiver Hub with Integral Installation Guide Models Include: HubSat4D - Four (4) Channel Passive UTP Transceiver Hub with Integral HubSat42D - Four (4) Channel Passive UTP Transceiver includes

More information

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver.   Product description. Benefits. Interfaces. Linear / area dimming Constant current LED driver DALI Dimmable Product description Dimmable built-in constant current LED Driver Adjustable output current between 1,050 and 1,750mA via DIP switch Max.

More information

clipping; yellow LED lights when limiting action occurs. Input Section Features

clipping; yellow LED lights when limiting action occurs. Input Section Features ELX-1A Rack-Mount Mic/Line Mixer Four inputs, one output in a single rack space Very-highery-high-quality audio performance High reliability Extensive filtering circuitry and shielding protect against

More information

Type: DILM12 10(24VDC) Article No.:

Type: DILM12 10(24VDC) Article No.: Type: DILM12 10(24VDC) Article No.: 276845 Ordering information Rated operational current AC 3 400 V I e A 12 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,

More information

Modular DAA with 2/4 Wire Convertor. XE0002D Block Diagram

Modular DAA with 2/4 Wire Convertor. XE0002D Block Diagram XE0002D August 2005 Modular DAA with 2/4 Wire Convertor Description The XE0002D is a compact DAA module designed for applications requiring voice, data or fax transfer. It complies with FCC Part 68 rules

More information

E6CP-A. An Absolute Encoder at About the Same Price as an Incremental Encoder. Ideal for robot limit signals. Low-cost Encoder with Diameter of 50 mm

E6CP-A. An Absolute Encoder at About the Same Price as an Incremental Encoder. Ideal for robot limit signals. Low-cost Encoder with Diameter of 50 mm Low-cost Encoder with Diameter of 50 mm CSM DS_E An Absolute Encoder at About the Same Price as an Incremental Encoder. Ideal for robot limit signals. High-precision detection of automatic machine timing.

More information

LEVEL ADJUST POWER Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free

LEVEL ADJUST POWER Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free Instruction Manual Model 1200-07 Amplifier September 2010 Rev A MONITOR J1 LEVEL ADJUST POWER MODEL 1200 AMPLIER CROSS TECHNOLOGIES, INC. Data, drawings, and other material contained herein are proprietary

More information

Kuhnke Technical Data. Contact Details

Kuhnke Technical Data. Contact Details Kuhnke Technical Data The following page(s) are extracted from multi-page Kuhnke product catalogues or CDROMs and any page number shown is relevant to the original document. The PDF sheets here may have

More information

ALLEN BRADLEY TIMING RELAY

ALLEN BRADLEY TIMING RELAY ALLEN BRADLEY TIMING RELAY Configuration Details Product: 700-HS12BA1 Description: 700-HS General Purpose Square Base Timing Relay, On Delay Timer, 1.0 to 180 seconds, DPDT, 120V AC 50/60Hz CONTROL RELAY

More information

Luminaire installation box Surface-mounted box Ceiling installation box

Luminaire installation box Surface-mounted box Ceiling installation box -Smart PTM Ambient light sensor and motion detector for constant lighting control uminaire installation box Surface-mounted box Ceiling installation box Overview: -SMART PTM i is an ambient light sensor,

More information

45 Hz to 500 Hz 1.0% Hz to 1 khz 2.0% + 3. Accuracy 0.09% + 2. Range / resolution. Range / resolution. Accuracy 1% + 2

45 Hz to 500 Hz 1.0% Hz to 1 khz 2.0% + 3. Accuracy 0.09% + 2. Range / resolution. Range / resolution. Accuracy 1% + 2 AC Voltage Range¹ / resolution 2 3 4 45 Hz to 500 Hz 1.0% + 3 500 Hz to 1 khz 2.0% + 3 600.0 mv / 0.1 mv 6.000 V / 0.001 V 60.00 V / 0.01 V 600.0 V / 0.1 V 1000 V / 1 V 1. All AC voltage ranges are specified

More information

Instruction Manual Model # Block Upconverter

Instruction Manual Model # Block Upconverter Instruction Manual Model 2115-278# Block Upconverter August 2018, Rev. A MODEL 2115 UPCONVERTER CROSS TECHNOLOGIES INC. EXT 10MHZ ALARM POWER Data, drawings, and other material contained herein are proprietary

More information

KRF EMC Filters Installation, Operation and Maintenance Manual

KRF EMC Filters Installation, Operation and Maintenance Manual KRF EMC Filters Installation, Operation and Maintenance Manual KRF EMC Filters limit high frequency noise, as well as: Reduce interference Protect sensitive equipment Eliminate drive cross-talk Meet FCC

More information

1900/25 Vibration Monitor

1900/25 Vibration Monitor 1900/25 Vibration Monitor BENTLY NEVADA MADE IN USA VIBRATION MONITOR OK ALERT DANGER BYPASS DISPLAY MOD E RESET NORMAL ALERT ALERT ADJUST LEVEL DANGER DANGER LEVEL ADJUST BUFFER ED TRANSDUCER 1 IN/SEC

More information

AS09..S 3-pole Contactors - Spring Terminals

AS09..S 3-pole Contactors - Spring Terminals 4 kw 5 hp AS09..S 3-pole Contactors - Spring AC Operated Description - 3-pole contactors with spring terminals, - N.C. or N.O. built-in auxiliary contact, - Rail-mounted, no tools required, - Additional

More information

LC1D50AF7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 50 A V AC 50/60 Hz coil

LC1D50AF7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 50 A V AC 50/60 Hz coil Product data sheet Characteristics LC1D50AF7 TeSys D contactor - 3P(3 NO) - AC-3 -

More information

FREQUENCY CONVERTER HIGH-PERFORMANCE OUTDOOR BLOCK UP AND DOWNCONVERTERS. Narda-MITEQ 1 FEATURES OPTIONS

FREQUENCY CONVERTER HIGH-PERFORMANCE OUTDOOR BLOCK UP AND DOWNCONVERTERS. Narda-MITEQ 1 FEATURES OPTIONS FREQUENCY CONVERTER HIGH-PERFORMANCE OUTDOOR BLOCK UP AND DOWNCONVERTERS Standard Configuration Vertical Mount Option FEATURES Antenna mount, weatherproof to IP-65 Automatic 5/10 MHz internal/external

More information

TeSys contactors. Model d. Type of contactor LC1- LC1- LC1- LC1- LC1-D115 & D09 D18 D25 D38 D40 D50 D95 LC1-D150 DT20 & DT25 DT32 & DT40

TeSys contactors. Model d. Type of contactor LC1- LC1- LC1- LC1- LC1-D115 & D09 D18 D25 D38 D40 D50 D95 LC1-D150 DT20 & DT25 DT32 & DT40 Characteristics Type of contactor LC- LC- LC- LC- LC-D & D09 D8 D2 D38 D40 D0 D9 LC-D0 DT20 & DT2 DT32 & DT40 Environment Rated insulation voltage (Ui) Conforming to IEC 947-4-, overvoltage category III,

More information

SM-1100/SM-1500/SM-1600 ROTARY ACTUATORS

SM-1100/SM-1500/SM-1600 ROTARY ACTUATORS SM-1100/SM-1500/SM-1600 ROTARY ACTUATORS GENERAL DESCRIPTION The SM-1100, SM-1500 and SM-1600 Series are multi-turn, rotary actuators, designed to meet the exacting requirements for closed-loop modulating

More information

Technical data. General specifications. Indicators/operating means

Technical data. General specifications. Indicators/operating means Model Number Single head system Features Sensor head bidirectional and rotatable Function indicators visible from all directions Quick mounting bracket Selectable sound lobe width Programmable Diagrams

More information

Level Measurement silometer FMC 420, FMC 423

Level Measurement silometer FMC 420, FMC 423 Technical Information TI 077F/00/en Level Measurement silometer FMC 420, FMC 423 For connecting to capacitance probes or Deltapilot S hydrostatic probes Main applications The is used for continuous level

More information

SECTION 8. Counters & Timers. Laurel Hecon Simpson Yokogawa (YCA)

SECTION 8. Counters & Timers. Laurel Hecon Simpson Yokogawa (YCA) SECTION Counters & Timers (Analog / Digital) Laurel Hecon Simpson Yokogawa (YCA) Counters and Timers from the following manufacuturers are also available but not shown in catalog: Texmate Triplett (LFE)

More information

DC Motors & Controls. DC2 DC Drives for 1/4 thru 2 Hp PMDC and Shunt Wound Motors. 1/4-2 Hp 115/230 VAC 1 Phase 50/60 Hz.

DC Motors & Controls. DC2 DC Drives for 1/4 thru 2 Hp PMDC and Shunt Wound Motors. 1/4-2 Hp 115/230 VAC 1 Phase 50/60 Hz. HVAC Farm Duty Brake 200 & 575 Volt & Controls DC 310 DC2 DC Drives for 1/4 thru 2 Hp PMDC and Shunt Wound DC & Controls 1/4-2 Hp 115/ 1 Phase 50/60 Hz. Applications: General purpose industrial use with

More information

Figure 1: Device components

Figure 1: Device components Order No. : 2860 10 Order No. : 2830 10 Operation- and Assembly Instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically skilled persons. Failure to observe

More information

Type Contact form Model Ag (Au clad) Standard DPDT G6A-274P-ST-US Low-sensitivity DPDT G6A-274P-ST40-US

Type Contact form Model Ag (Au clad) Standard DPDT G6A-274P-ST-US Low-sensitivity DPDT G6A-274P-ST40-US Low Signal Relay G6A Fullly Sealed Relay with High Impulse Withstand High sensitivity can be driven by digital circuits. Low-profile design allows use in 12.70 mm PC board rack. Surge withstand meets FCC

More information

Datasheet - SRB-E-201ST

Datasheet - SRB-E-201ST 27.04.2016-16:36:21h Datasheet - SRB-E-201ST Multi-function safety modules / SRB-E-201ST STOP 0 Function 1 oder 2-channel control Start button / Auto-start Monitoring two-hand control panels to EN 574

More information

Contactless Encoder Incremental: ppr RI360P0-QR24M0- INCRX2-H1181

Contactless Encoder Incremental: ppr RI360P0-QR24M0- INCRX2-H1181 Compact, rugged housing Many mounting possibilities Status displayed via LED Immune to electromagnetic interference 1024 pulses per revolution (default) 360, 512, 1000, 1024, 2048, 2500, 3600, 4096, parametr.

More information

Passive UTP Transceiver Hub with Integral Camera Power Installation Guide

Passive UTP Transceiver Hub with Integral Camera Power Installation Guide Passive UTP Transceiver Hub with Integral Installation Guide Models Include: HubSat8D - Eight (8) Channels HubSat82D - HubSat8D w/eight (8) HubWayAv Balun/s for s HubSat83D - HubSat8D w/eight (8) HubWayDv

More information

Advantys STB DATA SHEET. Advantys STB Output Module. Description. Features

Advantys STB DATA SHEET. Advantys STB Output Module. Description. Features Advantys STB Advantys STB Output Module DATA SHEET Description The Advantys model STBDAO5260 Digital Output Module provides 2 isolated discrete output points that operate on a 115 VAC power source. The

More information

Programmable Power Supplies 188 W 384 W R&S HMP Series

Programmable Power Supplies 188 W 384 W R&S HMP Series Programmable Power Supplies 188 W 384 W R&S HMP Series Test & Measurement Product Brochure 02.01 R&S HMP Series The R&S HMP Series Key facts Low residual ripple due to linear post-regulators Real-time

More information

Junior Max (JR Max ) Controller

Junior Max (JR Max ) Controller Get more done TM Junior Max (JR Max ) Controller stations Operating Instructions Thank you for purchasing this advanced, highly featured Irritrol Junior MAX controller. The Junior MAX is the latest addition

More information

SECU-16. Specifications Power: Input Voltage 9-12V DC or AC Input Current Max 200mA. 8 2-wire inputs, Analog (0 5VDC) or Supervised

SECU-16. Specifications Power: Input Voltage 9-12V DC or AC Input Current Max 200mA. 8 2-wire inputs, Analog (0 5VDC) or Supervised SECU-16 Introduction The SECU-16 module allows 8 inputs and 8 low-current relay outputs to be added to an ADICON control system. The inputs may be supervised (switch closure), analog, or 4-20mA. Specifications

More information

COHERENCE ONE PREAMPLIFIER

COHERENCE ONE PREAMPLIFIER COHERENCE ONE PREAMPLIFIER OWNER S MANUAL TABLE OF CONTENTS Introduction Features Unpacking Instructions Installation Phono Cartridge Loading Basic Troubleshooting Technical Specifications Introduction

More information