Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5

Size: px
Start display at page:

Download "Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5"

Transcription

1 Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category INTRODUCTION Customer to define background and introduction to the project based on their specific requirements. 1.1 PURPOSE The intent of this document is to provide a standard specification that will be used for all K-12 educational facilities requiring cabling installation. This document provides the minimum performance criteria for the components and sub-systems comprising a complete cabling system that shall accommodate District infrastructure requirements in excess of ten years. Product specifications, general design considerations and installation guidelines are provided in this written document. Quantities of telecommunications outlets, typical installation details, cable routing and outlet types for the specific educational facility(ies) will be provided as an attachment to this document (provided by design firm). If the bid documents are in conflict, the written specification shall take precedence. The successful vendor shall meet or exceed all requirements for the cabling system described in this document. The District s cable infrastructure project requires an AMP NECTCONNECT structured cabling system, or equivalent single-manufacturer solution. If all requirements are complied with, the cabling system shall be backed by a Tyco Electronics 25-Year System Warranty. The System Warranty shall be facilitated by the Contractor and be established between Tyco Electronics and the District. The successful contractor is required to furnish all labor, supervision, tooling, and miscellaneous mounting hardware and consumables for the cabling system installed. The contractor shall maintain current status as an AMP NETCONNECT Design and Installation (ND&I) contractor, including all training requirements, for the duration of the project. The Contractor shall staff each installation crew with the appropriate number of trained personnel, in accordance with their AMP ND&I contract agreement, to support the 25-Year System Warranty requirements. After installation, the Contractor shall submit all documentation to support the warranty requirements in accordance with the warranty requirements, and to apply for said warranty on behalf of the District. The warranty will cover the components and labor associated with the repair/replacement of any defective link within the warranty period, when the defect is a valid warranty claim. 1

2 1.2 SCOPE This document defines the cabling system and subsystem components to include cable, termination hardware, supporting hardware, and miscellany required to furnish and install a complete cabling infrastructure supporting voice, data and video. The intent of this document is to provide pertinent information to allow the vendor to bid the labor, supervision, tooling, materials, and miscellaneous mounting hardware and consumables to install a complete system. However, it is the responsibility of the vendor to propose any and all items required for a complete system whether or not it is identified in the specification, drawings and bill of materials attached to this specification. 1.3 APPLICABLE DOCUMENTS: The cabling system described in this specification is derived in part from the recommendations made in industry standard documents. The list of documents below have bearing on the desired cabling infrastructure are incorporated into this specification by reference: 1) This Technical Specification and Associated Drawings 2) TIA/EIA-568-B Commercial Building Telecommunications Cabling Standard April, ) TIA/EIA-569-A Commercial Building Standard for Telecommunications Pathways and Spaces - February, ) TIA/EIA-606 Administration Standard for the Telecommunications Infrastructure of Commercial Buildings - February, ) TIA/EIA-607 Commercial Building Grounding and Bonding Requirements for Telecommunications - August, ) Building Industries Consulting Services, International (BICSI) Telecommunications Distribution Methods Manual (TDMM) 9 th edition 7) National Fire Protection Agency (NFPA) - 70, National Electrical Code (NEC) ) AMP NETCONNECT Design and Installation Contractor Agreement (current) If a conflict exists between applicable documents, then the order in the list above shall dictate the order of precedence in resolving conflicts. This order of precedence shall be maintained unless a lesser order document has been adopted as code by a local, state or federal entity. If a conflict exists, documents adopted as code shall take precedence. If this document and any of the documents listed above are in conflict, then the more stringent requirement shall apply. All documents listed are believed to be the most current releases of the documents, the vendor is responsible to determine and adhere to the most recent release when developing the proposal for installation. 2.0 CABLING INFRASTRUCTURE OBJECTIVES The District has three primary classifications of users that each have different requirements in how they will access the infrastructure and utilize the telecommunications services provided across the infrastructure. The three classifications of users include students, instructors and administrative staff, each with distinct goals for how the telecommunications system will enhance their ability to perform. 2

3 Student Use - The primary focus of the telecommunications system for students is to learn, and learn by using. Students will utilize the telecommunications system in three primary locations to include the classroom, the media center and computer labs. Instructor Use - The primary focus of the telecommunications system for the instructor is to broaden their informational and curriculum resources, and enhance the delivery of educational data in the classroom. Instructors will utilize the telecommunications system in two primary locations to include the classroom and teacher work areas. Administrative Staff - The primary focus of the telecommunications system for the administrative staff is to utilize common business applications to help them more efficiently manage the business of running a school or district. Administrative staff will utilize the telecommunications system in office areas, comparable to a commercial business environment. To meet the District s telecommunications objectives the cabling infrastructure needs to support the transmission of voice, video and data to all user work areas which include: Classroom Computer Labs Media Center Teacher Work Areas Staff Offices 2.1 CABLING INFRASTRUCTURE OVERVIEW Voice Subsystem - The voice subsystem will be comprised of 110Connect XC connecting hardware, Category 3 high pair count backbone cable, and Enhanced Category 5 UTP horizontal cable. From the Main Cross-connect (MC) within each facility, high pair count Category 3 cable will be installed to each Telecommunications Closet (TC) in a star configuration. Risers will be comprised of individual runs or combinations of 25-, 50, 100-, 200-, or 300-pair cables to meet the pair count requirement in each TC. Riser pair count sizing will be calculated at 2-pair per horizontal voice jack served from each TC plus (10%-25%) spare to allow for growth. At both MC and TC ends, all voice pair terminations for both riser and horizontal pairs will be performed on wall mount 110Connect XC cross-connect frames. Voice frames will be constructed with ample horizontal and vertical wire management to facilitate the proper termination of Category 3 cable, and allow neat and orderly cross-connect administration, labeling, and Move, Add, and Change (MAC) management. At the station end horizontal voice cables will be terminated on 8-conductor, 8-position IDC jacks. Video Subsystem - The video subsystem will be comprised of coaxial and fiber optic cable and termination hardware in the backbone, and Enhanced Category 5 UTP cable and termination hardware in the horizontal. From the MC, two runs of RG-11 will be installed in a star configuration to each TC. At the MC, the coaxial cable will be terminated on rack mount patch panels. Horizontal Enhanced Category 5 video cable will be terminated on rack mount 110Connect XC blocks in the TC, and on 8-conductor, 3

4 8-position Enhanced Category 5 110Connect jacks at the station end. Video frames will be constructed with ample horizontal and vertical wire management to facilitate the proper termination of coaxial, fiber optic, and Enhanced Category 5 cable, and allow neat and orderly cross-connect administration, labeling, and Move, Add, and Change (MAC) management. Data Subsystem - The data subsystem will be comprised of fiber optic cable and termination hardware in the backbone, and both Enhanced Category 5 UTP cable and termination hardware, and fiber optic cable and termination hardware in the horizontal. Whether the District intends to implement a centralized or distributed LAN architecture, fiber shall be installed in the horizontal in addition to an Enhanced Category 5 cabling system to support growth to future high bandwidth systems. Distributed Implementation - From the MC, a minimum of (12 to 24)-strand multimode fiber optic cable will be installed in a star configuration to each TC to support backbone data connectivity to hub equipment operating over the Enhanced Category 5 and fiber optic horizontal cable. Fiber optic backbone cable shall be terminated on rack mount fiber termination panels. Termination panels shall provide adequate features to dress, strain relief, provide slack storage, and protect fiber strands to the termination point. Enhanced Category 5 UTP cable and duplex fiber optic zipcord cable will be used for horizontal data connectivity. Horizontal fiber cable shall be terminated on rack mount fiber termination panels. Termination panels shall provide adequate features to dress, strain relief, provide slack storage, and protect fiber strands to the termination point. Horizontal Enhanced Category 5 UTP cable shall be terminated on rack mount 48-port Enhanced Category 5 patch panels. At the outlet end, fiber optic cable shall be terminated with SC-style fiber optic connectors, mounted with a duplex SC adapter insert, and Enhanced Category 5 UTP cable shall be terminated to an Enhanced Category 5 8-conductor, 8-position 110Connect jack. Centralized Optical Fiber Implementation - From the MC, appropriately sized multimode fiber optic cables will be installed in a star configuration to each TC. The strand count to each TC will be sized at a 1:1 ratio to the horizontal strands present in each TC plus 25% spare to allow for growth. Fiber optic backbone cable shall be terminated on rack mount fiber termination panels in the MC, and in rack mount splice closures in the TC. Termination panels and splice closures shall provide adequate features to dress, strain relief, provide slack storage, and protect fiber strands to the termination or splice point. At the outlet end, fiber optic cable shall be terminated with SC-style fiber optic connectors and mounted with a duplex SC adapter insert. 2.2 FACILITIES ENVIRONMENT Customer to define facilities that the infrastructure is to support, whether existing or new, and convey the size of the facility(ies) involved and the scope of the supporting infrastructure needed. Square footage, outlet totals, quantity and locations of closets, equipment room(s), description of riser, and general age and building environmental information should be provided here. 4

5 5 K-12 Educational Environment

6 3.0 HORIZONTAL DISTRIBUTION SUBSYSTEM 3.1 TELECOMMUNICATIONS OUTLETS As described in Section 2.0 above, outlets will be located in the following primary user work areas: Classroom Computer Labs Media Center Teacher Work Areas Staff Offices In order to support the connectivity requirements for voice, video, and data within the primary user work areas, the following outlet configurations/designation will be used: Outlet Description Designation Outlet Composition Video Outlet V The Video outlet will be composed of a single gang faceplate loaded with one 8-position 8-conductor Enhanced Category 5 jack. Video outlets will be supported by one Enhanced Category 5 UTP cable. Data Outlet D The Data outlet will be composed of a single gang faceplate loaded with one 8-position 8-conductor Enhanced Category 5 jack and one duplex SC insert. Data outlets will be supported by one Enhanced Category 5 UTP cable, and one duplex 62.5/125 micron fiber optic zipcord. Wall Mount Voice Outlet WmV The Voice outlet will be composed of a single gang stainless steel wall mount phone faceplate loaded with one 8-position 8-conductor Category 3 jack. Voice outlets will be supported by one Enhanced Category 5 UTP cable. Voice/Data Outlet VD The Voice/Data outlet will be composed of a single gang faceplate loaded with two 8-position 8-conductor Enhanced Category 5 jacks, one designated as voice and one designated as data. Voice/Data outlets will be supported by two Enhanced Category 5 UTP cables and one duplex 62.5/125 micron fiber optic zipcord. Voice/Data/Video Outlet VDV The Voice/Data/Video outlet will be composed of a double gang faceplate loaded with three 8-position 8- conductor Enhanced Category 5 jacks and one duplex SC insert. One jack will be designated as voice, one as data, and one as video. Voice/Data/Video outlets will be supported by three Enhanced Category 5 UTP cables and one duplex 62.5/125 micron fiber optic zipcord. 6

7 3.1.1 PRODUCT SPECIFICATIONS Note: Jacks, faceplates, and icons are available in various colors. The colors specified below are the most common. As well, the use of icons is optional. Modular Jacks All modular jacks shall be wired to the [T568A or T568B] wiring pattern. Modular jacks shall be constructed with a housing of polyphenylene oxide, 94V-0 rated. Modular jacks shall be terminated using a 110-style pc board connector (made of 94V-0 rated polycarbonate), color-coded for both T568A and T568B wiring. The 110 connector shall terminate AWG solid or AWG stranded conductors with a maximum insulation diameter of.050 inches. The modular jack contacts shall be plated with a minimum of 50 microinches of gold in the contact area and a minimum of 150 microinches of tin-lead in the solder area over a 50 microinch minimum nickel underplate. Modular jacks shall be compatible with panel thicknesses of Modular jacks shall snap into a.790" X.582" opening. Modular jacks shall be UL Listed under file number E Category 3 (voice/modem/fax) modular jacks shall be non-keyed, 4-pair and shall meet TIA Category 3 performance requirements. Category 3 modular jacks shall be AMP NETCONNECT part number X (X indicates color). Enhanced Category 5 modular (data) jacks shall be unkeyed 4-pair and shall meet the performance requirements listed in the table below in addition to all other standard Category 5 performance requirements. Modular jacks shall fit in a.790" X.582" opening. Modular jacks shall be terminated using a 110-style pc board connector, color-coded for both T568A and T568B wiring. Each jack shall be wired to [T568A or T568B]. Modular jacks shall be UL Listed under file number E Modular jacks shall be AMP NETCONNECT part number X [(X indicates color)]. Enhanced Category 5 Jack Typical Worst-Case Performance Characteristics Frequency, Attenuation, Return Loss, NEXT, db PS NEXT, db FEXT, db MHz db db Video Outlets shall mount in a single gang box and provide two angled communications ports, capable of accepting front-loaded, individual modular jacks or inserts. Video outlets shall contain one almond Enhanced Category 5 jack and one blank insert. Outlets shall also be capable of providing one duplex fiber port (ST or SC) with fiber cable assemblies exiting parallel to the wall. Each port shall be provided with an icon to 7

8 indicate its function. Outlets shall provide a means of supporting modular jacks during termination. Outlets shall be light almond in color. Video outlets shall be AMP NETCONNECT HideAway part number or approved equivalent. Video outlets shall be mounted to an in-wall or surface mount single gang box as required. Data Outlets shall mount in a single gang box and provide two angled communications ports, capable of accepting front-loaded, individual modular jacks or inserts. Data outlets shall also be capable of providing one duplex fiber port (ST or SC) with fiber cable assemblies exiting parallel to the wall. Each port shall be provided with an icon to indicate its function. Outlets shall provide a means of supporting modular jacks during termination. Outlets shall be light almond in color. Data outlets shall contain one blue Enhanced Category 5 jack, one blank insert, and one duplex SC Insert. There shall be one Enhanced Category 5 cable and one fiber optic zipcord cable terminated to the outlet as noted in 3.1 above. Data outlets shall be AMP NETCONNECT HideAway part number or approved equivalent. Data outlets shall be mounted to an in-wall or surface mount single gang box as required. Wall Mount Voice Outlet- Use single gang stainless steel faceplate with mounting posts. This outlet shall be serviced by one Enhanced Category 5 cable to be terminated with a single Category 3 jack. The faceplate shall be mounted to an in-wall single gang box. Voice/Data Outlets shall mount in a single gang box and provide two angled communications ports, capable of accepting front-loaded, individual modular jacks or inserts. Voice/Data outlets shall also be capable of providing one duplex fiber port (ST or SC) with fiber cable assemblies exiting parallel to the wall. Each port shall be provided with an icon to indicate its function. Outlets shall provide a means of supporting modular jacks during termination. Outlets shall be light almond in color. This outlet shall contain one blue Enhanced Category 5 jack, one green Enhanced Category 5 jack, and one duplex SC Insert. There shall be one Enhanced Category 5 cable, one Enhanced Category 5 cable, and one fiber optic zipcord cable terminated to the outlet as noted in 3.1 above. Voice/Data outlets shall be AMP NETCONNECT HideAway part number or approved equivalent. Voice/Data outlets shall be mounted to an inwall or surface mount single gang box as required. Voice/Data/Video Outlets shall mount in a double gang box and provide four angled communications ports, capable of accepting front-loaded, individual modular jacks or inserts. Outlets shall also be capable of providing two duplex fiber ports (ST or SC) with fiber cable assemblies exiting parallel to the wall. Each port shall be provided with an icon to indicate its function. Outlets shall provide a means of supporting modular jacks during termination. Outlets shall be light almond in color. This outlet shall contain one blue Enhanced Category 5 jack, one green Enhanced Category 5 jack, one almond Enhanced Category 5 jack, one duplex SC Insert and one blank. There shall be three Enhanced Category 5 cables and one fiber optic zipcord cable terminated to the outlet as noted in 3.1 above. Voice/Data/Video outlets shall be AMP NETCONNECT HideAway part number or approved equivalent. The outlet shall be mounted to an in-wall or surface mount double gang box as required OUTLET PLACEMENT 8

9 All outlet locations will be noted on the attached floor plan drawings, and designated by outlet type. In classrooms, outlet placement must accommodate teacher and student needs for instructional delivery and student use. Outlets in the computer lab areas, and in the media center have different requirements than normal wallmount outlets. Details and suggestions for placement are provided herein. Classrooms - The typical classroom will contain two video outlets, one wall mount voice outlet and usually between two and five data outlets. One data outlet will be for use by the instructor, and two to four data outlets will be for use by the students. Blackboard Area Wall Mount Video Outlet & Instructor Data Outlet Wall Phone Outlet As shown in the typical classroom diagram, the front wall of the classroom is usually filled with blackboard. The instructor desk is generally placed in the front of the room near the corner of the blackboard area. The wall opposite the entrance to the classroom is generally an external wall composed of windows and HVAC equipment, and is unsuitable for routing cable and placing outlets. Window Wall Typical Classroom Wall Mount Video Outlet Student PC Area Video support needs to be provided at two ends of the classroom to provide the instructor some flexibility in where video information is displayed. Video outlets should be mounted at a height to correspond with and support the connection of a wall mounted TV. In some cases the wall mount video location and the instructor s desk are co-located in a front or rear corner of the room. Video and instructor data outlets can be combined in a single raceway to facilitate both outlets within a limited space. If the classroom s do not have wall mounted TVs, but utilize AV equipment on roller carts, the video outlet locations and mounting height should be revised to support the common location where moveable AV equipment is used in the classroom. Student PC Area Video Outlet Voice/Data Outlet A minimum of one data outlet should be provided for the instructor, however, two instructor outlets on opposite sides of the classroom may be desired to allow the instructor the rearrange the room and place his/her desk in the front or rear of the room. 9

10 Generally PCs in the classroom designated for student use are clustered against an exterior wall or side of the classroom. If surface mount raceway is required to support classroom outlets, when more than one data outlet is required for student PCs, multiple outlets can be fed Raceway from False Ceiling through a single vertical raceway. The raceway and surface mount boxes must be sized to accommodate the total quantities of cables routed through the raceway within NEC and ANSI/EIA/TIA maximum fill ratios, and allow proper bend radius and dress/termination of the cables. Computer Labs - Computer Labs have a high density of PCs in a small area, requiring a high density of connectivity. As opposed to installing 12 to 20 outlets within a single room to support the typical computer lab, it is recommended that a single outlet per wall be installed, and stackable hubs be utilized to provide connectivity to the student PCs in the lab. The instructor will still require video and data outlets placed strategically in the room as described for the typical classroom above. Depending on how the lab room is arranged, and what facilities are provided for routing patch cords, computer lab connectivity to all student PCs can be supported by a single data outlet and wall mount rack or shelves equipped with the appropriate stackable hubs. A distribution method for connection of the PCs to the hub ports via patch cords should be designed which keeps walkways and student work areas free of connecting cables and electrical extension cords. Adjacent to the data outlet that will support the lab hub(s), a wall mount swing gate, or fixed rack or wall-mount shelves should be installed to house the hub equipment. Surface mount raceway can be used to route patch cords between the hub ports and student lab PCs. Media Center - The media center generally has kiosk type areas throughout the room, which are set up for specific educational uses. Areas such as language arts, Internet access and interactive tutorial type instruction are typically found. Concentrations of outlets for a specific application can be routed and installed as shown above for student PC areas in the classroom TELECOMMUNICATIONS OUTLET INSTALLATION All outlets shall be installed in the following manner: Cables shall be coiled in the in-wall or surface-mount boxes if adequate space is present to house the cable coil without exceeding the manufacturer s bend radius. In hollow wall installations where box-eliminators are used, excess wire can be stored in the wall. No more than 12 of slack shall be stored in an in-wall box, modular furniture raceway, or insulated walls. Excess slack may be neatly coiled and stored in the ceiling above each drop location when there is not enough space present in the outlet box to store slack cable. In addition, each cable type shall be terminated as indicated below: 10

11 Cables shall be dressed and terminated in accordance with the recommendations made in the TIA/EIA-568-B document, the manufacturer s recommendations and best industry practices. Pair untwist of UTP cable at the termination shall not exceed one-half an inch. Bend radius of the cable in the termination area shall not be less than 4 times the outside diameter of the cable. The cable jacket of UTP cables shall be maintained as close as possible to the termination point. Voice jacks, unless otherwise noted in drawings, shall be located in the bottom position(s) of each faceplate. Voice jacks in horizontally oriented faceplates shall occupy the right-most position(s). Data jacks shall occupy the top position(s) on the faceplate. Data jacks in horizontally oriented faceplates shall occupy the left-most position(s). Fiber feedthrough inserts shall exit the faceplate parallel to the mounting surface and the bottom of the faceplate in a vertical orientation, on the right hand side in a horizontal orientation. Frequency, MHz 3.2 HORIZONTAL DISTRIBUTION CABLE Enhanced Category 5 Cabling plenum Horizontal cabling shall be 24 AWG, 4-pair UTP, UL/NEC CMP rated, with a [white, gray, blue or yellow] plenum-rated PVC jacket. Individual conductors shall be FEP insulated. Cable jacketing shall be lead-free. Cable shall meet the performance requirements listed in the table below in addition to all other standard Category 5 performance requirements. Cable shall be supplied [on wooden reels or in reel-in-box]. Cable shall be UL listed under file number E Horizontal cable shall be AMP NETCONNECT part number X. Enhanced Cat 5 Cable Performance Characteristics Attenuation, db/100m Max. PSNEXT, db Min./Typical PSELFEXT, db Min./Typical Return Loss, db Min. NEXT, db Min./Typical ELFEXT, db Min./Typical ACR, db Typical, 90m /81 69/77 66/73 63/ /79 67/75 64/71 61/ /70 58/66 52/59 49/ /66 54/62 46/53 43/ /64 52/60 44/51 41/ /61 49/57 40/47 37/ /60 48/56 38/45 35/ /58 46/54 36/43 33/ /57 45/53 34/41 31/ /52 40/48 28/35 25/ /49 37/45 24/31 21/ /46 34/42 20/27 17/ /45 33/41 18/25 15/ /42 30/38 14/21 11/ /41 29/37 13/20 10/ The horizontal optical fiber cable shall be 62.5/125 2-fiber multimode with a UL rating of OFNP. The cable jacket shall be orange and have a dual jacket zipcord construction. External diameter of cable shall be 2.9 x 5.9 mm. The cable shall provide a maximum attenuation of nm and nm. The bandwidth of the cable shall be nm and nm. The optical fiber PS ACR, db Typical, 90m 11

12 cable shall be AMP/Pirelli part number 02LBHNTAHHPZN. Quantities of cables to each outlet type shall be in accordance with the definitions provided in Section above. Note: The cables specified above are available in various colors, and the above paragraph and part numbers below should be adjusted to reflect the colors desired HORIZONTAL DISTRIBUTION CABLE INSTALLATION Cable shall be installed in accordance with manufacturer s recommendations and best industry practices. Cable raceways shall not be filled greater than the NEC maximum fill for the particular raceway type. Cables shall be installed in continuous lengths from origin to destination with no splices unless specifically addressed in this document as a transition from horizontal to backbone fiber strands within the TC. Where cable splices are allowed, they shall be in accessible locations and housed in an enclosure intended and suitable for the purpose. The cable s minimum bend radius and maximum pulling tension shall not be exceeded. If a J-hook or trapeze system is used to support cable bundles all horizontal cables shall be supported at a maximum of four-foot intervals. At no point shall cable(s) rest on acoustic ceiling grids or panels. Horizontal distribution cables shall be bundled in groups not greater than 40 cables. Cable bundle quantities in excess of 40 cables may cause deformation of the bottom cables within the bundle. Cable shall be installed above fire-sprinkler and systems and shall not be attached to the system or any ancillary equipment or hardware. The cabling system and support hardware shall be installed so that it does not obscure any valves, fire alarm conduit, boxes, or other control devices. Cables shall not be attached to ceiling grid or lighting support wires. Where light weight support for drop cable legs are required, the contractor shall install clips to support the cabling. Any cable damaged or exceeding recommended installation parameters during installation shall be replaced by the contractor prior to final acceptance at no cost to the Owner. Cables shall be identified by a self-adhesive label in accordance with the System Documentation Section of this specification. The cable label shall be applied to the cable behind the faceplate on a section of cable that can be accessed by removing the cover plate. Unshielded twisted pair cable shall be install so that there are no bends less than four times the cables outside diameter (4 X cable O.D.) at any point in the run and at the termination field. Pulling tension on 4-pair UTP cables shall not exceed 25-pounds for a single cable or cable bundle. 12

13 3.3 HORIZONTAL CROSS-CONNECT TERMINATION HARDWARE HORIZONTAL DATA CROSS-CONNECT The horizontal data cross-connect shall be a passive transition from the horizontal termination hardware to the network equipment within the same or adjacent racks. Racks housing cable termination hardware and/or network equipment shall be augmented with horizontal and vertical management hardware, both front and rear. The management shall allow proper dress and termination of horizontal cables to the rear of the termination hardware, and allow patch cords to be properly dressed from the termination field to network equipment on the front of the rack(s). The horizontal crossconnect shall be contained in AMP NETCONNECT 19 x 7 rack(s) with horizontal cable troughs and wire minders, and vertical management on the mounting rails of the rack. Patch panels shall be 3.5 inches high and provide 48 modular jack ports, wired to [T568A or T568B]. Patch panel modular jacks shall be configured as 6-port, replaceable modules. The front of each module shall be capable of accepting 9mm to 12mm labels. Each port shall be capable of accepting an icon to indicate its function. Patch panels shall terminate the building cabling on 110-style insulation displacement connectors. Patch panels shall comply with the performance characteristics listed in the following table in addition to all other standard Category 5 requirements. Patch panels must be UL Listed under file number E Patch panels shall be AMP NETCONNECT part number or an approved equivalent. Enhanced Category 5 Patch Panel Typical Worst-Case Performance Characteristics Frequency, Attenuation, Return Loss, NEXT, db PS NEXT, db FEXT, db MHz db db (Distributed) Twenty-four port (48-strand) duplex SC patch panels will be rack mounted to support the termination of horizontal fiber cables. Duplex SC patch panels will be augmented with horizontal and vertical wire management to allow the proper dress and termination of fiber cables to the rear of the panel, and to dress patch cords in the front of the panel. (Centralized) WIMs enclosures will be utilized as the splice closure to transition horizontal fiber strands to vertical fiber strands. The WIMs closure may either be rack or wall mounted, and has built in wire management for dressing horizontal and backbone fiber strands to the splice trays. Either fusion or mechanical splices may be used. 48 Port Enhanced Category 5 Patch Panel AMP Part No

14 Rear Cable Support Bar AMP Part No WIMs Chassis AMP Part No WIMs Rack Mounting Angles AMP Part No Splice Module AMP Part No Splice Tray, Fusion AMP Part No Fusion Splice Holder AMP Part No Splice Tray, Corelink AMP Part No Corelink Splice, package of 12 AMP Part No port Duplex SC Panel AMP Part No VOICE CROSS-CONNECT The cross-connect for voice connectivity shall be a passive cross-connect between horizontal wall mount 110Connect XC frames and backbone wall mount 110Connect XC frames. Wall mount voice frames shall be composed of field terminated 110 blocks, horizontal wire troughs, connecting blocks, and designation holders and strips. Vertical management rings shall be mounted between adjacent vertical frames to provide wire management of the cross-connect wire. Combinations of 100 and/or 300 pair blocks and associated wire management accessories shall be used as required by the horizontal and backbone pair counts to be terminated in a given closet. Backbone blocks shall employ 5-pair connecting blocks, and horizontal blocks shall employ five 4- pair and one 5-pair connecting block on each 25-pair row. Frames should be constructed on ¾ fire retardant plywood backboards, and oriented so that backbone frames are located on the left and horizontal frames are located on the right of the termination field. Frame orientation may need to be adjusted to accommodate the available TC space. 110XC 100 Pair Block Kit, C4 & C5s AMP Part No XC 100 Pair Block Kit, C5s AMP Part No XC 300 Pair Block Kit, C4 & C5s AMP Part No XC 300 Pair Block Kit, C5s AMP Part No Horizontal Wire Trough AMP Part No Vertical Cross-connect Ring, Large AMP Part No Vertical Cross-connect Ring, Small AMP Part No VIDEO CROSS-CONNECT The cross-connect for video connectivity shall be a passive cross-connect between horizontal rack mount 110-style blocks and active video equipment. Rack mount frames shall be field terminated, and shall employ six 4-pair connecting blocks on each 25-pair row. Racks shall be augmented with horizontal management hardware at the front, to properly dress patch cords and field terminations. 110XC 100 Pair Block, Rack Mount AMP Part No XC Connecting Block, 4-pair AMP Part No HORIZONTAL CROSS-CONNECT INSTALLATION 14

15 Copper termination and management hardware shall be installed in the following manner: Cables shall be dressed and terminated in accordance with the recommendations made in the TIA/EIA-568-B document, manufacturers recommendations and/or best industry practices. Pair untwist at the termination shall not exceed one-half an inch. Bend radius of the cable in the termination area shall not exceed 4 times the outside diameter of the cable. Cables shall be neatly bundled and dressed to their respective panels or blocks. Each panel or block shall be fed by an individual bundle separated and dressed back to the point of cable entrance into the rack or frame. The cable jacket shall be maintained as close as possible to the termination point. Fiber optic termination hardware shall be installed in the following manner: Fiber slack shall be neatly coiled within the fiber termination panel. No slack loops shall be allowed external to the fiber panel(s). Each cable shall be individually attached to the respective termination panel by mechanical means. The cables strength member(s) shall be securely attached the cable strain relief bracket in the panel. Each fiber cable shall be stripped upon entering the termination panel and the individual fibers routed in the termination panel. Each cable shall be clearly labeled at the entrance to the termination panel. Cables labeled within the bundle shall not be acceptable. Dust caps shall be kept on fiber connectors and couplings at all times unless they are in use and physically connected. 4.0 BACKBONE CABLE Voice Backbone - High pair count, 24 AWG twisted pair cable shall be utilized to provide voice backbone connectivity between the MC each TC. Voice backbone cable will be sized according to the pair requirements of each closet, based on a ratio of 2-pair per station plus (10% to 25%) spare. Single or multiple runs of 25-, 50-, 100-, 200-, and 300-pair cables will be provided as required, and will be jacketed as appropriate for use in riser or plenum areas. A coupled bonding conductor will be installed within the high pair count riser bundle and bonded and grounded at each end. If plenum jacketed voice backbone cables are required, multiples of 100-pair will be utilized. Video Backbone - RG-6 or RG-11 quad shield coaxial cable shall be utilized to provide video backbone connectivity between the MC and each TC. Two runs of coaxial cable shall be installed between the MC and each TC to facilitate forward and return paths for the video signal. If the MC to TC distance is equal to or less than 400-feet, RG-6 coaxial cable shall be used. If the MC to TC distance is between 400-feet and 685-feet, RG-11 coaxial cable shall be used. Data Backbone - (Distributed) Twenty four strand fiber optic cable shall be utilized to provide data backbone connectivity between the MC and each TC. One (12 to 24)- strand fiber optic backbone cable shall be installed from the MC to each of the TCs, and 15

16 will be jacketed as appropriate for use in a riser or plenum environment. Backbone fiber optic cable shall be colored orange to denote multimode fiber. (Centralized) Combinations of 24- through 72 strand multimode fiber cables will be used between the MC and each TC to support the number of strands required to splice horizontal fiber strands through to the centralized cross-connect location. Plenum cable is generally required in the K-12 environment as backbone cables are typically routed horizontally between through ceiling between the Main Cross-connect and the Telecommunications Closet. If non-plenum cable is used through a plenum environment, the conduit shall be installed in appropriately sized conduit. 12-Strand, 62.5/125, Tight Buffer, MM OFNR 12-Strand, 62.5/125, Tight Buffer, MM OFNP 24-Strand, 62.5/125, Tight Buffer, MM OFNR 24-Strand, 62.5/125, Tight Buffer, MM OFNP 48-Strand, 62.5/125, Tight Buffer, MM OFNR 48-Strand, 62.5/125, Tight Buffer, MM OFNP 72-Strand, 62.5/125, Tight Buffer, MM OFNR 72-Strand, 62.5/125, Tight Buffer, MM OFNP RG-6 Quad Shield Coaxial Cable, CATVR RG-6 Quad Shield Coaxial Cable, CATVP RG-11 Quad Shield Coaxial Cable, CATVP AMP Part No. 12LBHNTATJRNN AMP Part No. 12LBHNTATJPNN AMP Part No. 24LB2TTATJRNN AMP Part No. 24LB2TTATJPNN AMP Part No. 48LB4TTATJRNN AMP Part No. 48LB4TTATJPNN AMP Part No. 72LB6TTATJRNN AMP Part No. 72LB6TTATJPNN ComScope Part No. F2-660BVR ComScope Part No. 2227V ComScope Part No. 2287V 4.1 BACKBONE CABLE INSTALLATION All backbone cables shall be installed in the following manner: Backbone cables shall be installed separately from horizontal distribution cables. Where cables are housed in conduits, the backbone and horizontal cables shall be installed in separate conduits or in separate innerducts within conduits. Where cables are installed in an air return plenum, the cable shall be installed in conduit, or plenum cable shall be installed in a plenum innerduct to provide protection to the cable Where backbone cables and distribution cables are installed in a cable tray or wireway, backbone cables shall be installed first and bundled separately from the horizontal distribution cables. 4.2 BACKBONE TERMINATION HARDWARE. Each fiber optic cable shall be terminated in the MC in 24-, 48- or 72-port rack mount enclosures providing protection to the terminated fibers. The enclosures shall provide duplex MM SC-Style inserts. If a distributed approach to LAN implementation is used, the same rack mount termination enclosures in the MC shall be utilized in the TC. If a centralized approach to LAN implementation is used, WIMs splice closures shall be utilized to transition from horizontal to backbone fiber strands at the TC. Fiber optic splice enclosures will fully enclose the splices and provide adequate cable management accessories to strain relief, dress, provide slack storage, and protect fiber cable and fiber 16

17 strands to the splice. Fiber optic patch panels, used in a distributed approach to LAN implementation, shall provide adequate cable management accessories to properly strain relief, dress, provide slack storage, and protect fiber cable and fiber strands to the termination. Voice backbone cables shall be terminated in wall mount 110-style frames. Wall mount voice frames shall be composed of field terminated 110 blocks, horizontal wire troughs, connecting blocks, and designation holders and strips. Vertical management rings shall be mounted between adjacent vertical frames to provide wire management of the crossconnect wire. Combinations of 100 and/or 300 pair blocks and associated wire management accessories shall be used as required by the backbone pair counts to be terminated in the MC. Backbone blocks shall employ 5-pair connecting blocks on each 25-pair row. Frames should be constructed on ¾ fire retardant plywood backboards, and oriented so that PBX frames and the MPOP are located on the left, and backbone riser frames are located on the right of the termination field. Frame orientation may need to be adjusted to accommodate the available MC space. 24-port Optical Fiber Enclosure AMP Part No port Optical Fiber Enclosure AMP Part No port Optical Fiber Enclosure AMP Part No Duplex SC Adapter Insert 3-port (6-strand) AMP Part No LightCrimp SC-Style Simplex Connector, MM AMP Part No Video Patch Panel AMP Part No F-Connector Insert Adapter AMP Part No F Connector for RG-6, CATVP LRC Part No. PL56QS F Connector for RG-6, CATVR LRC Part No. F56CH F Connector for RG-11, CATVP LRC Part No. PL11QS 110XC 100 Pair Block Kit, C4 & C5s AMP Part No XC 100 Pair Block Kit, C5s AMP Part No XC 300 Pair Block Kit, C4 & C5s AMP Part No XC 300 Pair Block Kit, C5s AMP Part No Horizontal Wire Trough AMP Part No Vertical Cross-connect Ring, Large AMP Part No Vertical Cross-connect Ring, Small AMP Part No TERMINATION HARDWARE INSTALLATION Copper termination and management hardware shall be installed in the following manner: Cables shall be dressed and terminated in accordance with the recommendations made in the TIA/EIA-568-B document, manufacturers' recommendations and/or best industry practices. Pair untwist at the termination shall not exceed one-half an inch. Bend radius of the cable in the termination area shall not exceed 4 times the outside diameter of the cable. 17

18 Cables shall be neatly bundled and dressed to their respective panels or blocks. Each panel or block shall be fed by an individual bundle separated and dressed back to the point of cable entrance into the rack or frame. The cable jacket shall be maintained as close as possible to the termination point. Each cable shall be clearly labeled on the cable jacket behind the patch panel at a location that can be viewed without removing the bundle support ties. Cables labeled within the bundle, where the label is obscured from view shall not be acceptable. Fiber optic termination hardware shall be installed in the following manner: Fiber slack shall be neatly coiled within the fiber termination panel. No slack loops shall be allowed external to the fiber panel(s). Each cable shall be individually attached to the respective termination panel by mechanical means. The cables strength member(s) shall be securely attached the cable strain relief bracket in the panel. Each fiber cable shall be stripped upon entering the termination panel and the individual fibers routed in the termination panel. Each cable shall be clearly labeled at the entrance to the termination panel. Cables labeled within the bundle shall not be acceptable. Dust caps shall be kept on fiber connectors and couplings at all times unless they are in use and physically connected. 5.0 TELECOMMUNICATIONS SPACES The telecommunication closets shall house racks, voice termination fields and required cable routing hardware. Racks shall be placed in a manner that will allow a minimum of 3 feet of clearance from the front and rear mounting surfaces and on one side. If one mounting rail of the rack is placed against a wall, the mounting rail shall be no closer than 6 to the wall to allow room for vertical management. Where there is more than one rack, the racks shall be ganged with vertical management hardware to provide interbay management. Ganged rack frames will be placed in a manner that will allow a minimum of 3 feet of clearance from the front and rear mounting surfaces and on one side of the ganged assembly. Voice termination fields shall be mounted on 4 x 8 x.75 virgin fire retardant plywood, unless otherwise noted in the drawings. Backbone termination fields shall be mounted to the left of the horizontal voice fields where possible. Contractor shall provide required ladder and wall mount management rings to properly support and dress cables from entrance conduits to racks and frames. 5.1 INSTALLATION SPECIFICATIONS Racks shall be installed in the following manner: Racks shall be securely attached to the concrete floor using 3/8 hardware 18

19 All racks shall be grounded to the telecommunications ground bus bar in accordance with Section 9.0 of this document. Rack mount screws (#12-24) not used for installing fiber panels and other hardware shall be bagged and left with the rack upon completion of the installation. Voice termination fields shall be mounted on 4 x 8 x.75 virgin plywood. The plywood shall be mounted vertically at 12 A.F.F (Above Finished Floor). 6.0 WORK AREA AND PATCH CORD CABLE ASSEMBLIES Data patch cords used at the telecommunication rack and at the workstation shall be Enhanced Category 5, 4-pair, 8-position 8-conductor assemblies. Each workstation shall require one 10 foot Enhanced Category 5 patch cord. Phone line cords are typically provided with end user station equipment, and are not included in this specification. At the TC in a distributed approach to LAN implementation, appropriate length Enhanced Category 5 patch cords shall be provided to cross-connect between the data patch panels and network equipment. One patch cord per user outlet shall be provided. Optical patch cords shall be provided to patch the network equipment to the backbone fiber and shall be 1 or 2 meters in length. If a centralized approach to LAN implementation is installed, no patch cords are required in the TC for data connectivity as the data circuits are splice through to the MC. For voice connectivity cross-connect wire is utilized to connect backbone to horizontal pairs. Patch Cords for video applications, both end equipment and TC patch cords will be determined at a later date. Enhanced Cat 5 Patch Cable, 8ft, Black AMP Part No Enhanced Cat 5 Patch Cable, 10ft, Black AMP Part No Enhanced Cat 5 Patch Cable, 12ft, Black AMP Part No Optical Fiber Patch Cord, Duplex SC/SC, 1M AMP Part No Optical Fiber Patch Cord, Duplex SC/SC, 2M AMP Part No CABLING SYSTEM TESTING All cables and termination hardware shall be 100% tested by the installation contractor for defects in installation and to verify cable performance under installed conditions. All conductors of each installed cable shall be verified useable by the contractor prior to system acceptance. Any defect in the cabling system installation including but not limited to cable, connectors, feedthrough couplers, patch panels, and connector blocks shall be repaired or replaced in order to ensure 100% useable conductors in all cables installed. All cables shall be tested in accordance with this document, the ND&I Contract agreement, and best industry practices. If any of these are in conflict, the Contractor 19

20 shall be responsible to bring any discrepancies to the attention of the project team for clarification and/or resolution. 7.1 COPPER Each cable shall be tested for continuity on all pairs and/or conductors. Twisted-pair voice cables shall be tested for continuity, pair reversals, shorts, and opens using a continuity type test set. Twisted-pair data cables shall be tested for the all of the above requirements, plus tests that indicate installed cable performance. These data cables shall be tested using a Class II cable analyzer CONTINUITY Each pair of each installed cable shall be tested using a continuity test set that shows opens, shorts, polarity and pair-reversals. Shielded/screened cables shall be tested with a device that verifies shield continuity in addition to the above stated tests. The test shall be recorded as pass/fail as indicated by the test set in accordance with the manufacturers recommended procedures, and referenced to the appropriate cable identification number and circuit or pair number. Any faults in the wiring shall be corrected and the cable re-tested prior to final acceptance LENGTH Each installed cable shall be tested for installed length using a TDR type device. The cables shall be tested from patch panel to patch panel, block to block, patch panel to outlet or block to outlet as appropriate. The cable length shall conform to the maximum distances set forth in the TIA/EIA-568-B Standard. Cable lengths shall be recorded, referencing the cable identification number and circuit or pair number PERFORMANCE VERIFICATION High speed unshielded twisted pair (UTP) data cable shall be performance verified using an automated test set. This test set shall be capable of testing for the continuity and length parameters defined above, and provide results for the following tests: Near End Cross-Talk (NEXT) Attenuation Ambient Noise Attenuation to Cross-Talk Ratio (ACR) Test results shall be automatically evaluated by the equipment, using the most up-todate criteria from the TIA/EIA-568-B Standard, and the result shown as pass/fail. Test results shall be printed directly from the test unit or from a download file using an application from the test equipment manufacturer. The printed test results shall include all tests performed, the expected test result and the actual test result achieved. 20

Follow The Leader In Shielded Technology

Follow The Leader In Shielded Technology 1970s Vampire Tap 1990s Shielded Modular Jack 190s 4 Position Data Connector Follow The Leader In Shielded Technology The new AMP-TWIST Jack is our latest shielded product evolution. It can be terminated

More information

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents PART 1 - GENERAL 1.1 SUMMARY SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors. 3. Cabling system identification products. 1.2

More information

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus PART 1: GENERAL REQUIREMENTS A. Contractor Work 1. Provide and install (except as noted in this document), cable,

More information

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE Prepared in cooperation and approval from BICSI Building Industry Consulting Services International and

More information

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017 Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM-2017-2 Date: 05/26/2017 Additional specification information for data communication to cameras and between Library

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 - GENERAL 1.1 SECTION

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors including patch panels. 3. Cabling identification

More information

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1. PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE)

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) PART 1: GENERAL 1.01 Telecommunications Engineer Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) B. Registered Communications Distribution Designer

More information

Section Communications Optical Fiber Backbone Cabling

Section Communications Optical Fiber Backbone Cabling Part 1 1.1 Related Documents 1.1.1 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections apply to this Section. 1.2 Related

More information

SPECIAL SPECIFICATION 6559 Telecommunication Cable

SPECIAL SPECIFICATION 6559 Telecommunication Cable 2004 Specifications CSJ 0015-09-147, etc. SPECIAL SPECIFICATION 6559 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing, training,

More information

SPECIAL SPECIFICATION 8540 Telecommunication Cable

SPECIAL SPECIFICATION 8540 Telecommunication Cable 2004 Specifications CSJ 0914-00-307 & CSJ 0914-25-003 SPECIAL SPECIFICATION 8540 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing,

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School BILOXI PUBLIC SCHOOL DISTRICT Biloxi Junior High School Request for Proposals E-Rate 2014-2015 - Internal Connections Submit Proposals To: Purchasing Department Attn: Traci Barnett 160 St. Peter Street

More information

PREMIUM 5e F/UTP PRODUCTS

PREMIUM 5e F/UTP PRODUCTS Siemon s end-to-end cabling system is guaranteed to provide transmission performance margins in excess of industry standards for category 5e parameters, while featuring excellent EMI resistance. has been

More information

A. All communications equipment rooms shall be installed in a neat and workmanlike manner.

A. All communications equipment rooms shall be installed in a neat and workmanlike manner. SECTION 27 11 00 - COMMUNICATIONS EQUIPMENT ROOM FITTINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

STRUCTURED CABLE SYSTEM (SCS)

STRUCTURED CABLE SYSTEM (SCS) PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

Description: Pair Color Code Chart: Pair Color Chart 1 Brown White Brown 2 Orange White Orange 3 Green White Green 4 Blue White Blue.

Description: Pair Color Code Chart: Pair Color Chart 1 Brown White Brown 2 Orange White Orange 3 Green White Green 4 Blue White Blue. Description: OZLINX CAT5e cable has a guaranteed performance; exceeds the Category 5e performance requirements and provides positive PSACR up to 155MHz for bandwidth requirement in the future. Product

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD, applicable TC -, and CEHNC Design Guide 0-- (Standard is single UTOs and Double UTOs) B. Roads-Service, Lanes Adequate access is provided to the and AAR D. Testing Results-provided

More information

CABLING STANDARDS FOR

CABLING STANDARDS FOR RFB for Wiring in the Outagamie County Courtrooms Attachment B September 1, 2016 CABLING STANDARDS FOR GENERAL The purpose of this document is to provide guidelines for all structured cable installations

More information

APPENDIX A Verify All Part Numbers (Partial List of Approved Products)

APPENDIX A Verify All Part Numbers (Partial List of Approved Products) SECTION 16651 APPENDIX A Verify All Part Numbers (Partial List of Approved Products) SYSTIMAX SCS: OVER-VOLTAGE PROTECTION 1. Over-voltage Protection Device, 100-Pair with Enclosure, Product 489ACAI-100,

More information

CATEGORY 6A CABLING SOLUTIONS

CATEGORY 6A CABLING SOLUTIONS 10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Need of 10 Gigabit Service Application as

More information

CATEGORY 6A CABLING SOLUTIONS

CATEGORY 6A CABLING SOLUTIONS 10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Premium Line Category 6A Cabling Solutions

More information

CATEGORY 6 CABLING SOLUTIONS

CATEGORY 6 CABLING SOLUTIONS With over 20 years experience and know-how on communicating products design & developing, Premium Line has built maturity systems both in high tech develop and research center & complete structural quality

More information

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION PART 1 - GENERAL 1.1 SUMMARY SCOPE SECTION 25170 TESTING, IDENTIFICATION AND ADMINISTRATION 1. This section includes the minimum requirements for the testing, certification administration and identification

More information

Liberty Mutual Structured Cabling Specification Bid and Build Structured Cabling Technical Specification for:

Liberty Mutual Structured Cabling Specification Bid and Build Structured Cabling Technical Specification for: Bid and Build Structured Cabling Technical Specification for: Horizontal & Backbone Requirements Page 1 of 30 PUBLICATION RECORD Document Version Publication Date Primary Author Description Revision 1.0

More information

Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab*

Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab* Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab* General Scope of Work: Supply and installation of Computer Laboratory setup in MIU Location of Installation:

More information

Information Technology Services DESIGN AND INSTALLATION STANDARDS

Information Technology Services DESIGN AND INSTALLATION STANDARDS Requirements and Guidelines for: New Construction, Renovations, Upgrades, and Retrofits. Revised: June 5, 2015 VIU ITS Network Services 2 TABLE OF CONTENTS 0 GENERAL... 5 1 FIBER OPTIC CABLING... 5 1.1

More information

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017 SECTION 27 15 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 27 15 00 COMMUNICATIONS HORIZONTAL CABLING PART 1 GENERAL 1.1 RELATED DOCUMENTS AND SECTIONS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

3M Supported Applications Map 100,000 (2005) Single-mode. Fiber. Multimode. Fiber. Copper

3M Supported Applications Map 100,000 (2005) Single-mode. Fiber. Multimode. Fiber. Copper 3M Volition Network Solutions introduces Category 5e (Cat. 5e) copper cabling system to complement its leading fiber optic structured cabling system. Customers can now enjoy a single source of supply and

More information

A. The requirements of Section govern the work specified in this section.

A. The requirements of Section govern the work specified in this section. SECTION 27 05 10 - COMMUNITY ANTENNA TELEVISION CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The requirements of Section 27 01 00 govern the work specified in this section. B. Refer to the following

More information

SECTION 7 -- CROSS-CONNECT SYSTEMS

SECTION 7 -- CROSS-CONNECT SYSTEMS DETAIL ENGINEERING REQUIREMENTS AT&T March, 2016 Section 7, ATT-TP-76400 Revised NA SECTION 7 -- CROSS-CONNECT SYSTEMS CONTENTS PAGE 1. GENERAL... 7-2 1.1. Introduction... 7-2 1.2. Cable Holes... 7-2 1.3.

More information

Belden IBDN System 10GX 10GX Modules and 10GX Patch Panels

Belden IBDN System 10GX 10GX Modules and 10GX Patch Panels C O M M E R C I A L N E T W O R K I N G C O P P E R 5.6 Belden IBDN System GX GX Modules and GX Patch Panels AX2272 GX Module, Black GX Module The GX Module is a revolutionary punch down UTP connector

More information

DESIGN!!GUIDELINES!!!!!

DESIGN!!GUIDELINES!!!!! DESIGNGUIDELINES 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 1. Testing General 1.1. For acceptance, 100% of the media

More information

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

CATEGORY 5e CABLING SOLUTIONS

CATEGORY 5e CABLING SOLUTIONS With the high speed data transmission requirement in LAN, 1998 IEEE ratified standard 802.3z defined protocol 1000BASE-T over Category 5e and higher level Ethernet cabling system. After that, with the

More information

STRUCTURED CABLING SYSTEMS (SCS)

STRUCTURED CABLING SYSTEMS (SCS) STRUCTURED CABLING SYSTEMS (SCS) ModSecur - Structured Cabling Systems (SCS) A Structured Cabling System (SCS) is the backbone of any building, campus or site communication infrastructure. The sharp growth

More information

ADDENDUM NO. 2 This addendum consists of 8 pages. Kenai Peninsula Borough Purchasing & Contracting

ADDENDUM NO. 2 This addendum consists of 8 pages. Kenai Peninsula Borough Purchasing & Contracting KENAI PENINSULA BOROUGH Purchasing and Contracting 144 North Binkley Street Soldotna, Alaska 99669-7520 Toll-free within the Borough: 1-800-478-4441, Ext. 2260 PHONE: (907) 714-2260 FAX: (907) 714-2373

More information

SECTION FIBER OPTIC STATION CABLES

SECTION FIBER OPTIC STATION CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications shall include all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project 1.1.0 GENERAL The purpose of this specification is to establish a requirement for the installation of a voice, video and data cable network. The cable (copper), wire, hardware, equipment racks, jumpers,

More information

Public Works Division Lighting District Fiber Optic Specifications April 2009

Public Works Division Lighting District Fiber Optic Specifications April 2009 Public Works Division Lighting District Fiber Optic Specifications April 2009 7000 Florida Street Punta Gorda, Florida 33950 Tele: 941.575.3600 Fax : 941.637.9265 www.charlottecountyfl.com/publicworks

More information

B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines.

B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines. PART 1 - GENERAL 1.1 SUMMARY A. This section includes: 1. Support Structures 2. Cable trays and ladder rack 3. Racks (including wire managers) 4. Cables (copper and optical fiber) 5. Jacks and faceplates

More information

Multi-Media Installation Guide

Multi-Media Installation Guide Multi-Media Installation Guide Coaxial Page 2 Data Plug Page 7 Data Jack Page 10 Telephone Page 13 Splicing Page 15 Cable Types Cable Types Two basic types of cable are used in multimedia installations.

More information

PATCH CORDS, PLUGS & CABLES

PATCH CORDS, PLUGS & CABLES PATCH CORDS, PLUGS & CABLES 3.1 SECTION CONTENTS Modular Cords...3.2 Cable Assemblies...3.3 Plugs & Connectors...3.4 Bundled Cable...3.5 Category 5e & 6 UTP Cable...3.6 Coax Cable...3.7 Fiber Optic Cable...3.8

More information

MT-RJ SECURE Product Expansion Now 10 Variants of the MT-RJ SECURE Products

MT-RJ SECURE Product Expansion Now 10 Variants of the MT-RJ SECURE Products MT-RJ Product Expansion Now 0 Variants of the MT-RJ Products In response to several customers, the MT-RJ product line has been expanded with an additional six color/key versions. In addition to the original

More information

HighBand 25. TrueNet Category 6 Solutions

HighBand 25. TrueNet Category 6 Solutions HighBand 25 TrueNet Category 6 Solutions The highest performing cross-connect system in the world. A unique high-density solution with superior cable management. ADC KRONE s HighBand 25 cross connect solution

More information

10G 6A UTP SYSTEM PRODUCTS 10G 6A UTP

10G 6A UTP SYSTEM PRODUCTS 10G 6A UTP 0G A is Siemon s advanced, end-to-end augmented category UTP structured cabling system, designed to meet or exceed all 0GBASE-T performance requirements, including alien crosstalk. Siemon s full channel

More information

Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING

Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING Revision 05/01/2017 Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING PART 1 GENERAL 1.1 SECTION INCLUDES A. Voice, Data, and Fiber Cable Product materials B. Voice, Data, and Fiber Cable Execution

More information

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED.

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED. Beaverton School District Capital Program Purchasing 16550 SW Merlo Road, Beaverton, OR 97006 Phone: 503-591-4539 SOLICITATION ADDENDUM NO. 1 ITB 15-0012 THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION

More information

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT Purchasing and Warehouse Services Department October 1, 2007 Addendum No. 1 INVITATION FOR BID No. 08-09 Temporary Faculty Offices, Chabot College All Prospective

More information

DATA/TELECOMMUNICATIONS REQUEST FOR PRICING

DATA/TELECOMMUNICATIONS REQUEST FOR PRICING Category 6A 10Gig DATA/TELECOMMUNICATIONS REQUEST FOR PRICING TABLE OF CONTENTS 1. GENERAL 3 1.1. Work Included... 3 1.2. Scope of Work... 3 1.3. Regulatory References... 4 1.4. Quality Assurance... 4

More information

TX COPPER CABLING SYSTEM

TX COPPER CABLING SYSTEM TX COPPER CABLING SYSTEM PERFORMANCE BEYOND PRODUCTS PANDUIT is the global leader in network connectivity, delivering end-to-end system solutions in support of your most demanding network requirements.

More information

Telecommunciations Infrastructure Project September 20, A. Broadband radio frequency active and passive components

Telecommunciations Infrastructure Project September 20, A. Broadband radio frequency active and passive components PART 1 - GENERAL 1.1 SECTION INCLUDES A. Broadband radio frequency active and passive components B. Broadband optical active and passive components C. Coaxial cable and connectors D. Support and termination

More information

Preferred ordering guide for NETCONNECT

Preferred ordering guide for NETCONNECT Preferred ordering guide for NETCONNECT MEA Region Contents Copper solutions Category 6A products 3 Category 6A and Category 7 shielded copper cables 3 Category 6A modular shielded panels 3 Category 6A

More information

Compact Module. Category 6 FTP Cabling System

Compact Module. Category 6 FTP Cabling System Compact Module Shielded design for improved EMI performance Suitable for Gigabit Ethernet applications and beyond Ultra-slimline design Colour coded for quick and accurate termination Interchangeable with

More information

SPECIAL SPECIFICATION 6191 Fiber Optic Cable

SPECIAL SPECIFICATION 6191 Fiber Optic Cable 2004 Specifications CSJ 0014-02-014, etc SPECIAL SPECIFICATION 6191 Fiber Optic Cable 1. Description. Furnish, install, splice, field terminate, and test the fiber optic cables. 2. Materials. A. General

More information

10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System

10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System 10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System Next-Generation Category 6A UTP Cabling System Drivers for 10 GbE Aggregation of Gigabit Links Server Consolidation and

More information

Connect with the industry s best CAT6 and CAT5e channel solutions!

Connect with the industry s best CAT6 and CAT5e channel solutions! Connect with the industry s best CAT6 and CAT5e channel solutions! Our CAT6 and CAT5e channel solutions far exceed the TIA/EIA specifications performance standards! To ensure consistent and continuing

More information

IT/Telecommunications Technical and Wiring Standards. Phillips Exeter Academy

IT/Telecommunications Technical and Wiring Standards. Phillips Exeter Academy IT/Telecommunications Technical and Wiring Standards FOR Phillips Exeter Academy Exeter, NH No deviations will be permitted from these specifications without the express written consent of Phillips Exeter

More information

The Uniduct Nonmetallic Latching Raceway

The Uniduct Nonmetallic Latching Raceway Uniduct One-Piece Latching Raceway The Uniduct Nonmetallic Latching Raceway System is a one-piece single channel design, ideally suited to route and protect fiber optic, UTP, and and other low-voltage

More information

Michigan State University Construction Standards EXTERIOR FIBER OPTIC CABLE SYSTEM PAGE

Michigan State University Construction Standards EXTERIOR FIBER OPTIC CABLE SYSTEM PAGE PAGE 271800-1 SECTION 271800 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

DINTEK LAN Cabling Systems

DINTEK LAN Cabling Systems 4 Pair UTP Cable Application: Voice Fast Ethernet(IEEE802.3) VgAnyLAN(IEEE 802.12) Token Ring(IEEE 802.5) TPPMD(ANSI X3T9.5) BaseT Ethernet(IEEE 802.3u) 155/622 Mbps 1.2/ 2.4 Gbps ATM 0BaseT Ethernet 550

More information

MX5-F(XX)... Flat MAX module, T568A/B, rear strain relief cap

MX5-F(XX)... Flat MAX module, T568A/B, rear strain relief cap MAX 5e UTP Modules MAX 5e modules exceed category 5e performance with component and channel performance to 60 MHz. These modules offer all the functional advantages of our MAX 6 modules in a variety of

More information

Volition TM RJ45 K5e Jacks

Volition TM RJ45 K5e Jacks Volition TM RJ45 K5e Jacks Part of our 3M Volition Network Solutions, the new K5e range is our ultimate Category 5e hardware component (ISO/IEC 11801, EN 50173 and ANSI/TIA/EIA-568). The K5e jack is a

More information

DS1 Cross-Aisle Panel

DS1 Cross-Aisle Panel DS1 Cross-Aisle Panel Model 005-0005-0100 Installation Guide 1.1 Overview 1.1.1 Inspection Compare the contents of the DS1 Cross-Aisle Panel shipping container with the packing list. Call Telect if anything

More information

ADDENDUM #3. SPECIAL NOTE: Addendum #3 information shall supersede the information contained in the Contract Documents

ADDENDUM #3. SPECIAL NOTE: Addendum #3 information shall supersede the information contained in the Contract Documents WESLEYAN U N I V E R S I T Y Facilities 170 Long Lane Middletown, Connecticut 06457 (860) 685-3476 FAX (860) 685-3101 ADDENDUM #3 Date: March 4, 2013 Project: To: CFA A Rehearsal Hall AHU Replacement Annual

More information

Cable Installation Tips

Cable Installation Tips Cable Installation Tips Campus Network Design & Operations Workshop These materials are licensed under the Creative Commons Attribution-NonCommercial 4.0 International license (http://creativecommons.org/licenses/by-nc/4.0/)

More information

SPECIAL SPECIFICATION 2284 Fiber Optic Cable (Self-Supporting)

SPECIAL SPECIFICATION 2284 Fiber Optic Cable (Self-Supporting) 2004 Specifications CSJ 0086-14-046 SPECIAL SPECIFICATION 2284 Fiber Optic Cable (Self-Supporting) 1. Description. Furnish, install, splice, field terminate, and test the fiber optic cables. 2. Materials.

More information

Frequency ASRL(db) Attenuation Max. NEXT Power Sum (MHz) Minimum db/100m db/1000ft Minimum db/100m Minimum db/100m

Frequency ASRL(db) Attenuation Max. NEXT Power Sum (MHz) Minimum db/100m db/1000ft Minimum db/100m Minimum db/100m Cat.5e 4 Pair UTP Cable Application: Voice ISDN 10Base T(IEEE 802.3) Fast Ethernet(IEEE802.3u) 100Vg-AnyLAN(IEEE 802.12) Token Ring(IEEE 802.5) TP-PMD(ANSI X3T9.5) 100Base-T Ethernet(IEEE 802.5) 155/622

More information

SECTION COMMUNICATIONS STRUCTURED CABLING

SECTION COMMUNICATIONS STRUCTURED CABLING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 27 15 00 COMMUNICATIONS STRUCTURED CABLING SPEC WRITER NOTES: 1. Edit this specification section between // //, to fit project, or delete if not applicable. 2.

More information

Project No. # Page 1

Project No. # Page 1 PART 1 - GENERAL This section of the has references, products, procedures, processes, and work descriptions/summaries that are common to many Washington State University Pullman (WSUP) campus telecommunications

More information

Connected Solutions. April $ Post, 19 Rack ELERK1FR BK

Connected Solutions. April $ Post, 19 Rack ELERK1FR BK Connected Solutions April 2018 $30.97 Punch & Go Tool ONQAC3400 $139.97 per 305M Category 6 Riser, UTP, 23 AWG, Blue 305 Meter/1000 FT Pull Box CAB24/4PS6FT4BLUHYP $137.97 2 Post, 19 Rack ELERK1FR1194400BK

More information

blackbox.com/connect The smart choice when price matters most. Need help? Talk to a Black Box cable expert 24/7 at

blackbox.com/connect The smart choice when price matters most. Need help? Talk to a Black Box cable expert 24/7 at blackbox.com/connect The smart choice when price matters most. Need help? Talk to a Black Box cable expert 24/7 at 877-877-2269 The Black Box quality you've come to expect. In stock. Ships today. The smart

More information

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices Berk-Tek recommends installing a well-designed structured cabling channel per the TIA standards. This includes up to 100

More information

INFRASTONE BLACKSTONE 10G 6A(U/UTP) Europe, Middle East and Africa regions UNLIMITED USAGE 1

INFRASTONE BLACKSTONE 10G 6A(U/UTP) Europe, Middle East and Africa regions UNLIMITED USAGE 1 INFRASTONE BLACKSTONE 10G 6A(U/UTP) Europe, Middle East and Africa regions UNLIMITED USAGE 1 WWW.INFRASTONE.COM Contents BLACKSTONE CAT6A U/UTP channel performance Introduction BLACKSTONE CAT6A U/UTP channel

More information

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008 Information & Communications Technology Group Standards June 2008 Appendix F UTP cabling Version 1.1 Appendix F UTP cabling 1. Introduction This Section details the required standards for Unshielded Twisted

More information

Cable Installation Tips

Cable Installation Tips Cable Installation Tips Campus Network Design & Operations Workshop These materials are licensed under the Creative Commons Attribution-NonCommercial 4.0 International license (http://creativecommons.org/licenses/by-nc/4.0/)

More information

Robert Burén. Product Manager. Nexans Cabling Solutions. 10G Solutions

Robert Burén. Product Manager. Nexans Cabling Solutions. 10G Solutions Robert Burén Product Manager 10G Solutions Nexans Cabling Solutions 1 10 Gigabit Ethernet.Performance 30 GByte can be transmitted within 24 seconds Example: MRI-scan size is 30GB as average A memory device

More information

Clarity. Advanced solutions for 10 Gig, Category 6 and 5e copper connectivity PRODUCT SOLUTION GUIDE EXPERTISE. TECHNOLOGY. SOLUTIONS.

Clarity. Advanced solutions for 10 Gig, Category 6 and 5e copper connectivity PRODUCT SOLUTION GUIDE EXPERTISE. TECHNOLOGY. SOLUTIONS. Clarity Advanced solutions for 10 Gig, Category 6 and 5e copper connectivity PRODUCT SOLUTION GUIDE EXPERTISE. TECHNOLOGY. SOLUTIONS. Center Tuned Components Higher Signal-to- Noise Ratio Optimal Mated

More information

10G 6A F/UTP SYSTEM PRODUCTS 10G 6A F/UTP

10G 6A F/UTP SYSTEM PRODUCTS 10G 6A F/UTP 0G A Combining 0 Gb/s performance with the security, noise immunity and pathway space maximisation of a screened cabling system, Siemon s end-to-end solution represents the cutting edge of augmented category

More information

HI-DEX PRODUCT SET DATASHEET

HI-DEX PRODUCT SET DATASHEET APPLICATION HI-DEX is an ultra high-performance, pre-terminated and modular optical fibre cabling system based on MT ferrule connector technology. This product set is designed for installationn in the

More information

Brown University. Communications Standard Parts List

Brown University. Communications Standard Parts List CIS - NTG Brown University Communications Standard Parts List All data installations must receive the 25-year Mission Critical Warrantee from Hubbell Premise Wiring. All fiber installations must receive

More information

About Nexans 3. About Berk-Tek 4. LANmark-1000 Cat 6 UTP 5. LANmark-1000 Category 6 Plenum 6. LANmark-1000 Category 6 Riser 11

About Nexans 3. About Berk-Tek 4. LANmark-1000 Cat 6 UTP 5. LANmark-1000 Category 6 Plenum 6. LANmark-1000 Category 6 Riser 11 Table of contents About Nexans 3 About Berk-Tek 4 LANmark-1000 Cat 6 UTP 5 LANmark-1000 Category 6 Plenum 6 LANmark-1000 Category 6 Riser 11 LANmark-1000 Category 6 Patch 16 21 7/10/07 - http://www.berktek.com

More information

Aldine ISD Structured Cabling System Installation Guidelines. Category 6 and OM1 Technical Specification

Aldine ISD Structured Cabling System Installation Guidelines. Category 6 and OM1 Technical Specification Aldine ISD Structured Cabling System Installation Guidelines Category 6 and OM1 Technical Specification Table of Contents PART 1 - GENERAL... 3 1.1 Summary of work... 3 1.2 Special requirements for cable

More information

Project No. # Page 1

Project No. # Page 1 PART 1 - GENERAL This section of the has references, products, procedures, processes, and work descriptions/summaries that are common to many Washington State University Pullman (WSUP) campus telecommunications

More information

Telecommunication Infrastructure Project September 20, 2002

Telecommunication Infrastructure Project September 20, 2002 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Category rated UTP systems shall be provided and tested in accordance with the performance level established in Specification

More information

Technical Specifications Florida Gulf Coast University

Technical Specifications Florida Gulf Coast University Technical Specifications Florida Gulf Coast University 9/19/2018 Page 1 of 21 Approved Vendors (alphabetical order) Aztek (CIP) Certified Installer Plus Mr. Scott Coyne 4730 Enterprise Avenue Suite #308

More information

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards.

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards. 27 08 00 Certification and Commissioning of Communication Systems (Revision date: 7/3/12) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are

More information

Product information 19" 1U HD Patch Panel 48xRJ45/s, Cat. 6A, gray, fully populated

Product information 19 1U HD Patch Panel 48xRJ45/s, Cat. 6A, gray, fully populated Product information 19" 1U HD Patch Panel 48xRJ45/s, Cat. 6A, gray, fully populated R512417 966740615 1 Pcs. 090.6102 Metal patch panel with integrated cable tie shelf. 19" 1U HD patch panel 4 12-port/s

More information

Copper Solution Contents Cabinets Fiber Optic Solution

Copper Solution Contents Cabinets Fiber Optic Solution Contents Copper Solution Category 6A + Cabling Solutions Cat.6A + 1000MHz S/FTP Installation Cable A1 Cat.6A + S/FTP Patch Cord A2 Cat.6A + 90 Fully Shielded Die-casting Keystone Jack A3 Modular German

More information

Mfgr. Berk Tek ea , Berk Tek ea , Berk Tek ea. Berk Tek ea ,350.

Mfgr. Berk Tek ea , Berk Tek ea , Berk Tek ea. Berk Tek ea ,350. 8. Pricing Schedule The undersigned has rd and understands all conditions and terms of RFP 336-, is authorized to submit this proposal on behalf of the company, and hereby offers to perform the services

More information

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Fiber Optic Cable System

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Fiber Optic Cable System 1993 Specifications CSJ 0008-12-071 SPECIAL SPECIFICATION ITEM 6540 Fiber Optic Cable System 1.0 Description. This item shall govern for the furnishing and installation of fiber optic cables in designated

More information

UNM IT/Telecommunications Guide Specification Labeling 11/07/

UNM IT/Telecommunications Guide Specification Labeling 11/07/ Labeling 1 PART 1: GENERAL 1.01 SCOPE OF WORK A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing

More information

SECTION 683 VIDEO OPTICAL TRANSCEIVER WITH BI-DIRECTIONAL DATA CHANNEL DESCRIPTION

SECTION 683 VIDEO OPTICAL TRANSCEIVER WITH BI-DIRECTIONAL DATA CHANNEL DESCRIPTION 683 SECTION 683 VIDEO OPTICAL TRANSCEIVER WITH BI-DIRECTIONAL DATA CHANNEL DESCRIPTION 683.01.01 GENERAL A. The Contractor shall furnish the designated quantity of Video Optical Transceiver (VOTR) pairs

More information

Special Specification 6242 Special Fiber Optic Cable

Special Specification 6242 Special Fiber Optic Cable Special Specification 6242 Special Fiber Optic Cable 1. DESCRIPTION 2. MATERIALS The contractor to install, splice, field terminate, test and document all fiber systems. A. General Requirements. Provide

More information

What really changes with Category 6

What really changes with Category 6 1 What really changes with Category 6 Category 6, the standard recently completed by TIA/EIA, represents an important accomplishment for the telecommunications industry. Find out which are the actual differences

More information

CABLE MANAGEMENT PRODUCTS Cable Managers & Accessories

CABLE MANAGEMENT PRODUCTS Cable Managers & Accessories CABLE MANAGEMENT PRODUCTS Cable Managers & Accessories Evolution Cable Management Page 5-3 Velocity Cable Management Page 5-8 Velocity Standard Pack Page 5-12 Vertical Cable Management Page 5-13 Global

More information

March 4 th, Addendum No. 1. Brooklyn College Systems Integrator Broadcast Television Equipment Project No: BY019/

March 4 th, Addendum No. 1. Brooklyn College Systems Integrator Broadcast Television Equipment Project No: BY019/ Facilities Planning, Construction, and Management Office of Financial Management Procurement Services 555 West 57 th Street 11 th Floor New York, New York 10019 CUNY.Builds@mail.cuny.edu March 4 th, 2013

More information

btnet new products Modular and preloaded patch panels btnet

btnet new products Modular and preloaded patch panels btnet btnet new products Modular and preloaded patch panels 128 btnet content 130 General characteristics Catalogue 132 UTP and FTP cable 134 Patch panel and cord 135 Pop-up and floor box 136 Fiber optic BTNET

More information