Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

Size: px
Start display at page:

Download "Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017"

Transcription

1 Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017 Additional specification information for data communication to cameras and between Library and City Hall computer rooms GENERAL INFORMATION 1. Fiber optic cables will need to be provided, pulled, terminated and test by the selected vendor. The fiber optic cable will connect the library and City Hall computer rooms. 24-strand Corning multimode 50/125 OM4 cable is required. 2. New Category 6 Ethernet cables are required at the library for the cameras racks exist in both buildings with room for connections 4. Rack in City Hall currently has a Corning fiber optic housing that can be expanded by purchasing the correct Corning fiber optic spliced pigtails 5. A fiber optic housing must be purchased for the library. 6. A 4 conduit is between the two buildings is already in place. This conduit terminates on the outside of each building. It is the contractors responsibility to penetrate the wall, provided and install pull boxes, indoor conduit and other components necessary to complete the job. The conduit is new, empty except for a pull string. 7. The distance between the two computer rooms is approximate 450 feet vendor to validate prior to ordering any materials. 8. No copper cables are required between buildings. 9. There are a total of (28) camera s for the library, each location requires 2 drops for a total of Only camera will be connected at each location, the 2nd cable is for future use. 11. Label all NEMA boxes or junction boxes with ½ high characters indicating MDF/IDF origination/destination and other pertinent information. 12. Sealing of openings between floors, through rated fire and smoke walls, or created by the contractor for cable pass through shall be the responsibility of the contractor. Sealing material and application of this material shall be accomplished in such a manner that is acceptable to the local fire and building authorities having jurisdiction over this work. 13. Creation of such openings as are necessary for cable passage between locations shall be the responsibility of the contractor's work. Any openings created by or for the contractor and left unused shall also be sealed as part of this work. 14. Penetrations through fire-rated walls, partitions, floors, or ceilings shall be sealed with a material capable of preventing the passage of flames and hot gasses when subjected to requirements of the Test Standard specific of Fire Stops ASTM-E-814 UL1479 using approved methods. 15. Any damage must be reported immediately.

2 CATEGORY 6 CABLING SYSTEM 1. Approved Cabling Systems: Hitachi, Berk-Tek, Superior Essex Category 6, Structured Cabling System or approved equal. Acceptable connectivity manufacturers are ADC, Leviton or Ortronics and must remain consistent throughout. 2. Four pair, 23 AWG, Category 6, UTP, as defined by the EIA/TIA standards intended for use with transmission rates up to and including 155 Mbps. Cabling shall be tested up to 750 MHz. 3. The Contractor shall install cables and equipment as part of a Structured Cabling System (SCS). The various sections of this specification pertain to specific products and/or installation requirements that must conform to the warranty requirements of the Structured Cabling System manufacturer. 4. All horizontal building cabling shall be UL-Listed, Plenum-rated unshielded twisted pair (UTP), 4-pair, 23 AWG, Category 6 with solid crosscut spline for pair separation (600 Mhz). Colored cable sheath shall be utilized with one standard color for data (black). Category 6 and CMP identification marking shall be visible on the outside sheath. 5. Patch panels shall be Category 6 48-port patch panels (loaded) and consist of the panel, wiring blocks, rack mount strain relief bar, and port modules. 6. Patch panel shall mount to TIA-EIA compliant 19 rack mount bracket. It shall utilize standards compliant RJ45 jacks for station cable termination. 7. Jacks or inserts shall be RJ45, 6-port modules with individually replaceable jacks in accordance with TIA/EIA 568B wiring standard, FCC Part 68, UL listed, NEC Article 800. It shall accommodate 110- type jack of the 4-pair Category 6 cable. Jack shall support Gigabit Ethernet, 100 Base-T, 10 Base-T and analog connections. 8. Backside strain relief shall be provided for every row of ports. It shall be attached to the TIA/EIA compliant rack via rear mounting holes. Camera (Station) Outlets 1. BISCUIT OUTLETS: Biscuit-type outlets will be utilized for camera connections. 2. JACKS: Category 6 RJ45 unshielded modular jacks shall be utilized. The jacks shall meet or exceed TIA/EIA 568-B.2-1 and IEC requirements for Category 6 component performance. Jacks shall be capable of Gigabit Ethernet, 100 Base-T, 10 Base-T and analog connections. Wiring scheme label shall permit T568A or T568B wiring pattern. T568B wiring scheme will be utilized. 3. Modular jacks shall be terminated using 110-style pc board connectors. The 110style connectors shall be capable of terminating AWG solid core wire. 110 Contacts shall be paired (with additional space between pairs) to improve crosstalk performance. Each jack shall be provided with a bend-limiting strain relief. All jacks shall be terminated using manufacturerspecified jack termination tools and methods. 4. UTP Jacks will be color coded blue. 5. Cameras mounted on exterior of building will be connected to the biscuit-type jacks provided in #1. Camera s will not be hard wired back to main data frame. 6. There are a total of (28) camera s for the library, each location requires 2 drops for a total of Only 1 camera will be connected at each location, the 2nd cable is for future use. Label cables, outlets, patch panels, and punch blocks sequentially.

3 8. Label each outlet with permanent self-adhesive label or insert with minimum 3/16 in. high characters. 9. Label each cable with permanent self-adhesive label wrap with minimum, 1/8 in. 10. Labeling and marking shall be in accordance with TIA/EIA-606 the Administration Standard for Telecommunications Infrastructure of Commercial Buildings. Labeling will be done sequentially in accordance with current City standard labeling for horizontal and backbone cabling. Labeling in existing patch panels should conform to existing and continue in sequence. Contractor will confirm labeling scheme with the Owner s representative in advance. 11. Use labels on face of data patch panels and match existing where appropriate. 12. Mark up floor plans (if available) showing outlet locations, type, and cable ID. Turn these drawings over to the owner on completion in order to allow the owner's personnel to connect and test owner-provided equipment in a timely fashion. 13. All category 6 cabling must be Category 6 compliant in accordance with TIA/EIA-568-B-2.1 and ISO/IEC (and latest TSB s) MHz testing, bi-directional (NEXT) on all data drops using a TDR tester with current calibration (Fluke, Agilent or equivalent) independently certified for Category 6 testing. These shall include manufacturer-required tests for Category 6 cable (Attenuation, NEXT, PSNEXT, Return Loss, ELFEXT, and PSELFEXT data that indicate the worst case result, the frequency at which it occurs, the limit at that point, and the margin). Tests shall be performed on all data drops with swept frequency from 1 MHz to the highest frequency that is consistent with TIA standards. 15. Length, propagation delay and skew shall be included in Category 6 test results. Distances shall be noted in feet. 16. When repairs and re-tests are performed, the problem and corrective action taken shall be noted and both the failed and passed test data shall be collocated in the documented test results. All re-terminations after testing, regardless of cause, shall be re-tested. 17. The Owner reserves the right to require additional tests, as deemed appropriate. 18. All tests shall be documented electronically and transmitted to City s representative for review and retention. 19. The City s representative shall be provided a minimum of one week s notice of all acceptance and proof-of-performance testing to be conducted throughout the project.

4 FIBER OPTIC CABLING SYSTEM 1. Corning Cable Systems MIC MM 4 24-strand Corning Altos loose tube outdoor/underground fiber. The cable is constructed with a polyethylene outer sheath with is better suited for harsh conditions and has better tensile strength for long underground pulls. Corning Cable Systems cable and hardware No Substitutions. 2. Characteristics - Multimode 24 strand OM4 50/125 µm 3. Connectors: LC and ST fusion-spliced pigtails Corning Model number CCH-CS24-E4-P00QE - CCH SPLICE CASSETTE 24F OM4 LC 4. Rack mounted field patch panel Corning Model number WCH-02P 5. Approximately 450 feet of Corning Multi-mode OM4 fiber 024TU4-T4790D20 will be required Each end of the fiber run will terminate in to existing 19 Racks. 6. Vendor to validate distance 7. The City Hall computer room contains an existing CCH-04U (Corning Closet Connector Housing) Vendor can terminate the connections into this existing housing, but new cassettes and pigtails will be required for both City Hall and the Library. 8. Conduit path is in map below Red indicates existing conduit. INSPECTION AND TESTING PROCEDURES FIBER OPTIC CABLE 1. Fiber Optic Plenum (Building Backbone) Cable 2. Continuity of all Plenum fiber optic cables, regardless of length, shall be verified by emitting an intense light source at one end of the fiber and measuring the intensity of light using a power meter at the opposite end of the fiber. 3. The Contractor shall conduct a power meter (OLTS) test of each fiber optic segment in Plenum cables from patch panel to patch panel. Tests shall be conducted using ANSI/EIA/TIA A, for Multi-mode and for Singlemode. The Contractor shall provide a list reflecting cable ID and actual measured loss. ( Testing and Documentation from the Design Guide 2002 Corning Cable Systems provides an acceptable testing procedure for end-toend attenuation testing.) 4. Polished fiber ends shall be cleaned and inspected with a microscope for dirt or scratches before installing dust covers.

5 End of Document

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus PART 1: GENERAL REQUIREMENTS A. Contractor Work 1. Provide and install (except as noted in this document), cable,

More information

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards.

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards. 27 08 00 Certification and Commissioning of Communication Systems (Revision date: 7/3/12) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 - GENERAL 1.1 SECTION

More information

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project 1.1.0 GENERAL The purpose of this specification is to establish a requirement for the installation of a voice, video and data cable network. The cable (copper), wire, hardware, equipment racks, jumpers,

More information

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall obtain authorization from

More information

DESIGN!!GUIDELINES!!!!!

DESIGN!!GUIDELINES!!!!! DESIGNGUIDELINES 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 1. Testing General 1.1. For acceptance, 100% of the media

More information

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION PART 1 - GENERAL 1.1 SUMMARY SCOPE SECTION 25170 TESTING, IDENTIFICATION AND ADMINISTRATION 1. This section includes the minimum requirements for the testing, certification administration and identification

More information

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents PART 1 - GENERAL 1.1 SUMMARY SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors. 3. Cabling system identification products. 1.2

More information

RCIT Cable Certification Testing Revised 10/2017

RCIT Cable Certification Testing Revised 10/2017 RCIT Testing Revised 10/2017 General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall

More information

A. All communications equipment rooms shall be installed in a neat and workmanlike manner.

A. All communications equipment rooms shall be installed in a neat and workmanlike manner. SECTION 27 11 00 - COMMUNICATIONS EQUIPMENT ROOM FITTINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

The University of Texas at Austin September 30, 2011

The University of Texas at Austin September 30, 2011 SECTION 27 08 20 COPPER TESTING PART 1 - GENERAL 1.1 SUMMARY A. Test measurements shall be taken for all balanced-twisted pair cabling, including horizontal and backbone copper cables and wall-to-rack

More information

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE Prepared in cooperation and approval from BICSI Building Industry Consulting Services International and

More information

Frequency ASRL(db) Attenuation Max. NEXT Power Sum (MHz) Minimum db/100m db/1000ft Minimum db/100m Minimum db/100m

Frequency ASRL(db) Attenuation Max. NEXT Power Sum (MHz) Minimum db/100m db/1000ft Minimum db/100m Minimum db/100m Cat.5e 4 Pair UTP Cable Application: Voice ISDN 10Base T(IEEE 802.3) Fast Ethernet(IEEE802.3u) 100Vg-AnyLAN(IEEE 802.12) Token Ring(IEEE 802.5) TP-PMD(ANSI X3T9.5) 100Base-T Ethernet(IEEE 802.5) 155/622

More information

STRUCTURED CABLING SYSTEMS (SCS)

STRUCTURED CABLING SYSTEMS (SCS) STRUCTURED CABLING SYSTEMS (SCS) ModSecur - Structured Cabling Systems (SCS) A Structured Cabling System (SCS) is the backbone of any building, campus or site communication infrastructure. The sharp growth

More information

SECTION FIBER OPTIC STATION CABLES

SECTION FIBER OPTIC STATION CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications shall include all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

Follow The Leader In Shielded Technology

Follow The Leader In Shielded Technology 1970s Vampire Tap 1990s Shielded Modular Jack 190s 4 Position Data Connector Follow The Leader In Shielded Technology The new AMP-TWIST Jack is our latest shielded product evolution. It can be terminated

More information

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project 1.1.0 GENERAL MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project The purpose of this specification is to establish a requirement for the installation of

More information

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School BILOXI PUBLIC SCHOOL DISTRICT Biloxi Junior High School Request for Proposals E-Rate 2014-2015 - Internal Connections Submit Proposals To: Purchasing Department Attn: Traci Barnett 160 St. Peter Street

More information

Cable Installation Tips

Cable Installation Tips Cable Installation Tips Campus Network Design & Operations Workshop These materials are licensed under the Creative Commons Attribution-NonCommercial 4.0 International license (http://creativecommons.org/licenses/by-nc/4.0/)

More information

Telecommunication Infrastructure Project September 20, 2002

Telecommunication Infrastructure Project September 20, 2002 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Category rated UTP systems shall be provided and tested in accordance with the performance level established in Specification

More information

Description: Pair Color Code Chart: Pair Color Chart 1 Brown White Brown 2 Orange White Orange 3 Green White Green 4 Blue White Blue.

Description: Pair Color Code Chart: Pair Color Chart 1 Brown White Brown 2 Orange White Orange 3 Green White Green 4 Blue White Blue. Description: OZLINX CAT5e cable has a guaranteed performance; exceeds the Category 5e performance requirements and provides positive PSACR up to 155MHz for bandwidth requirement in the future. Product

More information

CATEGORY 6A CABLING SOLUTIONS

CATEGORY 6A CABLING SOLUTIONS 10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Premium Line Category 6A Cabling Solutions

More information

Cable Installation Tips

Cable Installation Tips Cable Installation Tips Campus Network Design & Operations Workshop These materials are licensed under the Creative Commons Attribution-NonCommercial 4.0 International license (http://creativecommons.org/licenses/by-nc/4.0/)

More information

Section Communications Optical Fiber Backbone Cabling

Section Communications Optical Fiber Backbone Cabling Part 1 1.1 Related Documents 1.1.1 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections apply to this Section. 1.2 Related

More information

CATEGORY 6A CABLING SOLUTIONS

CATEGORY 6A CABLING SOLUTIONS 10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Need of 10 Gigabit Service Application as

More information

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1. PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

3M Supported Applications Map 100,000 (2005) Single-mode. Fiber. Multimode. Fiber. Copper

3M Supported Applications Map 100,000 (2005) Single-mode. Fiber. Multimode. Fiber. Copper 3M Volition Network Solutions introduces Category 5e (Cat. 5e) copper cabling system to complement its leading fiber optic structured cabling system. Customers can now enjoy a single source of supply and

More information

Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab*

Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab* Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab* General Scope of Work: Supply and installation of Computer Laboratory setup in MIU Location of Installation:

More information

Request for Proposal (RFP)

Request for Proposal (RFP) Request for Proposal (RFP) Data Network for OCMS 017 Inquiries and requests regarding this RFP should be directed to: Michael Hale Technology Director Oconee County Schools PO Box 16 5-A School Street

More information

Delaware County Community College Project # Marple Campus Renovation - Phase % Construction Documents November 23, 2011

Delaware County Community College Project # Marple Campus Renovation - Phase % Construction Documents November 23, 2011 SECTION 271323 - COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 - GENERAL 1.1 DESCRIPTION A. This section provides the specifications for the work related to the optical fiber system in the project.

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors including patch panels. 3. Cabling identification

More information

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017 SECTION 27 15 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT Purchasing and Warehouse Services Department October 1, 2007 Addendum No. 1 INVITATION FOR BID No. 08-09 Temporary Faculty Offices, Chabot College All Prospective

More information

Project No. # Page 1

Project No. # Page 1 PART 1 - GENERAL This section of the has references, products, procedures, processes, and work descriptions/summaries that are common to many Washington State University Pullman (WSUP) campus telecommunications

More information

Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5

Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5 Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5 1.0 INTRODUCTION Customer to define background and introduction to the project based on

More information

SECTION 7 -- CROSS-CONNECT SYSTEMS

SECTION 7 -- CROSS-CONNECT SYSTEMS DETAIL ENGINEERING REQUIREMENTS AT&T March, 2016 Section 7, ATT-TP-76400 Revised NA SECTION 7 -- CROSS-CONNECT SYSTEMS CONTENTS PAGE 1. GENERAL... 7-2 1.1. Introduction... 7-2 1.2. Cable Holes... 7-2 1.3.

More information

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices Berk-Tek recommends installing a well-designed structured cabling channel per the TIA standards. This includes up to 100

More information

جامعة مؤتة العطاءات املركزية توريد وتركيب وتشغيل أجهزة شبكات/كلية الزراعة. Central Tenders Mu tah University

جامعة مؤتة العطاءات املركزية توريد وتركيب وتشغيل أجهزة شبكات/كلية الزراعة. Central Tenders Mu tah University عطاء رقم 3 /ل/ 2019 توريد وتركيب وتشغيل أجهزة شبكات/كلية الزراعة 1. 20U Network Rack: (QTY:- 1 pieces) 1. Wall Mounted Type. 2. Dimension (H x W x D): 20U x 600 x 600. 3. Material: Steel. 4. Front Door:

More information

CATEGORY 6 CABLING SOLUTIONS

CATEGORY 6 CABLING SOLUTIONS With over 20 years experience and know-how on communicating products design & developing, Premium Line has built maturity systems both in high tech develop and research center & complete structural quality

More information

CABLING STANDARDS FOR

CABLING STANDARDS FOR RFB for Wiring in the Outagamie County Courtrooms Attachment B September 1, 2016 CABLING STANDARDS FOR GENERAL The purpose of this document is to provide guidelines for all structured cable installations

More information

What really changes with Category 6

What really changes with Category 6 1 What really changes with Category 6 Category 6, the standard recently completed by TIA/EIA, represents an important accomplishment for the telecommunications industry. Find out which are the actual differences

More information

SMART CLASSix 48 UTP Patch Panels (with patching switches) -

SMART CLASSix 48 UTP Patch Panels (with patching switches) - Features Front-mounted Patching Switches connect ports internally, dramatically reducing the need for patch cords Compatible to Unshielded Twisted Pairs (UTP) cabling systems High performance panel that

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD, applicable TC -, and CEHNC Design Guide 0-- (Standard is single UTOs and Double UTOs) B. Roads-Service, Lanes Adequate access is provided to the and AAR D. Testing Results-provided

More information

STRUCTURED CABLE SYSTEM (SCS)

STRUCTURED CABLE SYSTEM (SCS) PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

SPECIAL SPECIFICATION 6559 Telecommunication Cable

SPECIAL SPECIFICATION 6559 Telecommunication Cable 2004 Specifications CSJ 0015-09-147, etc. SPECIAL SPECIFICATION 6559 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing, training,

More information

Robert Burén. Product Manager. Nexans Cabling Solutions. 10G Solutions

Robert Burén. Product Manager. Nexans Cabling Solutions. 10G Solutions Robert Burén Product Manager 10G Solutions Nexans Cabling Solutions 1 10 Gigabit Ethernet.Performance 30 GByte can be transmitted within 24 seconds Example: MRI-scan size is 30GB as average A memory device

More information

Special Specification 6242 Special Fiber Optic Cable

Special Specification 6242 Special Fiber Optic Cable Special Specification 6242 Special Fiber Optic Cable 1. DESCRIPTION 2. MATERIALS The contractor to install, splice, field terminate, test and document all fiber systems. A. General Requirements. Provide

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 27 15 00 COMMUNICATIONS HORIZONTAL CABLING PART 1 GENERAL 1.1 RELATED DOCUMENTS AND SECTIONS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

About Nexans 3. About Berk-Tek 4. LANmark-1000 Cat 6 UTP 5. LANmark-1000 Category 6 Plenum 6. LANmark-1000 Category 6 Riser 11

About Nexans 3. About Berk-Tek 4. LANmark-1000 Cat 6 UTP 5. LANmark-1000 Category 6 Plenum 6. LANmark-1000 Category 6 Riser 11 Table of contents About Nexans 3 About Berk-Tek 4 LANmark-1000 Cat 6 UTP 5 LANmark-1000 Category 6 Plenum 6 LANmark-1000 Category 6 Riser 11 LANmark-1000 Category 6 Patch 16 21 7/10/07 - http://www.berktek.com

More information

B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines.

B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines. PART 1 - GENERAL 1.1 SUMMARY A. This section includes: 1. Support Structures 2. Cable trays and ladder rack 3. Racks (including wire managers) 4. Cables (copper and optical fiber) 5. Jacks and faceplates

More information

SPECIAL SPECIFICATION 8540 Telecommunication Cable

SPECIAL SPECIFICATION 8540 Telecommunication Cable 2004 Specifications CSJ 0914-00-307 & CSJ 0914-25-003 SPECIAL SPECIFICATION 8540 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing,

More information

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008 Information & Communications Technology Group Standards June 2008 Appendix F UTP cabling Version 1.1 Appendix F UTP cabling 1. Introduction This Section details the required standards for Unshielded Twisted

More information

Preferred ordering guide for NETCONNECT

Preferred ordering guide for NETCONNECT Preferred ordering guide for NETCONNECT MEA Region Contents Copper solutions Category 6A products 3 Category 6A and Category 7 shielded copper cables 3 Category 6A modular shielded panels 3 Category 6A

More information

SMART CLASSix 24/48 UTP Patch Panels -

SMART CLASSix 24/48 UTP Patch Panels - Features Support 24 ports per 1U, 48 ports per 2U. Conform to ANSI/TIA/EIA-568-B.2-1, ISO/IEC 11801 2 nd edition (2002) and CENELEC EN50173 (2002) for Category 6/Class E. Simple labor-saving termination

More information

Liberty Mutual Structured Cabling Specification Bid and Build Structured Cabling Technical Specification for:

Liberty Mutual Structured Cabling Specification Bid and Build Structured Cabling Technical Specification for: Bid and Build Structured Cabling Technical Specification for: Horizontal & Backbone Requirements Page 1 of 30 PUBLICATION RECORD Document Version Publication Date Primary Author Description Revision 1.0

More information

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE)

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) PART 1: GENERAL 1.01 Telecommunications Engineer Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) B. Registered Communications Distribution Designer

More information

Gigabit Multi-mode SX to Single Mode LX Converter. User s Manual NGF-728 Series. Warning COPYRIGHT

Gigabit Multi-mode SX to Single Mode LX Converter. User s Manual NGF-728 Series. Warning COPYRIGHT COPYRIGHT Gigabit Multi-mode SX to Single Mode LX Converter User s Manual NGF-728 Series All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted

More information

Request for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling

Request for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling Request for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling Due Date: Allowable Contract Date from Posted 470 The Clarkdale- Jerome School District is requesting

More information

Connect with the industry s best CAT6 and CAT5e channel solutions!

Connect with the industry s best CAT6 and CAT5e channel solutions! Connect with the industry s best CAT6 and CAT5e channel solutions! Our CAT6 and CAT5e channel solutions far exceed the TIA/EIA specifications performance standards! To ensure consistent and continuing

More information

Project No. # Page 1

Project No. # Page 1 PART 1 - GENERAL This section of the has references, products, procedures, processes, and work descriptions/summaries that are common to many Washington State University Pullman (WSUP) campus telecommunications

More information

PREMIUM 5e F/UTP PRODUCTS

PREMIUM 5e F/UTP PRODUCTS Siemon s end-to-end cabling system is guaranteed to provide transmission performance margins in excess of industry standards for category 5e parameters, while featuring excellent EMI resistance. has been

More information

Table of Contents. Open Matrix System (OMS) 1-2

Table of Contents. Open Matrix System (OMS) 1-2 Company Profile Addison cabling system originated as a cabling solution produced and marketed by Caledonian Cables Ltd located at Sussex, England. Founded in 1978, Caledonian Cables originally entered

More information

FREEDM Loose Tube Interlocking Armored Cables

FREEDM Loose Tube Interlocking Armored Cables features and benefits Flexible, interlocking armor design Gel-free waterblocking technology Color-coded tubes and fibers UV-resistant, flameretardant jacket UV-Resistant Flame-Retardant Outer Jacket InterlockingArmor

More information

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables NEMA Standards Publication Performance Standard for Twisted Pair Premise Voice and Data Communications Cables Published by: National Electrical Manufacturers Association 1300 North 17th Street, Suite 1752

More information

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables NEMA Standards Publication WC 63.1-2005 Performance Standard for Twisted Pair Premise Voice and Data Communications Cables Published by: National Electrical Manufacturers Association 1300 North 17th Street,

More information

HI-DEX PRODUCT SET DATASHEET

HI-DEX PRODUCT SET DATASHEET APPLICATION HI-DEX is an ultra high-performance, pre-terminated and modular optical fibre cabling system based on MT ferrule connector technology. This product set is designed for installationn in the

More information

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk Paul Vanderlaan Product Development Engineer Belden Presented at BICSI January 20, 1999 Introduction New Parameters involving

More information

DINTEK LAN Cabling Systems

DINTEK LAN Cabling Systems 4 Pair UTP Cable Application: Voice Fast Ethernet(IEEE802.3) VgAnyLAN(IEEE 802.12) Token Ring(IEEE 802.5) TPPMD(ANSI X3T9.5) BaseT Ethernet(IEEE 802.3u) 155/622 Mbps 1.2/ 2.4 Gbps ATM 0BaseT Ethernet 550

More information

CATEGORY 5e CABLING SOLUTIONS

CATEGORY 5e CABLING SOLUTIONS With the high speed data transmission requirement in LAN, 1998 IEEE ratified standard 802.3z defined protocol 1000BASE-T over Category 5e and higher level Ethernet cabling system. After that, with the

More information

INFRASTONE BLACKSTONE 10G 6A(U/UTP) Europe, Middle East and Africa regions UNLIMITED USAGE 1

INFRASTONE BLACKSTONE 10G 6A(U/UTP) Europe, Middle East and Africa regions UNLIMITED USAGE 1 INFRASTONE BLACKSTONE 10G 6A(U/UTP) Europe, Middle East and Africa regions UNLIMITED USAGE 1 WWW.INFRASTONE.COM Contents BLACKSTONE CAT6A U/UTP channel performance Introduction BLACKSTONE CAT6A U/UTP channel

More information

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED.

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED. Beaverton School District Capital Program Purchasing 16550 SW Merlo Road, Beaverton, OR 97006 Phone: 503-591-4539 SOLICITATION ADDENDUM NO. 1 ITB 15-0012 THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION

More information

Premise Installation Guide

Premise Installation Guide Premise Installation Guide Table Of Contents Overview of Cabling Standards...1-2 Horizontal Cabling System Structure...3-5 Work Area... 6 Horizontal Distances of Copper Links (Open Office)... 7 Twisted

More information

IEEE 802.3af Power via MDI Standard Compliant Mid-Span Insertion Solution. Presented by PowerDsine: David Pincu -

IEEE 802.3af Power via MDI Standard Compliant Mid-Span Insertion Solution. Presented by PowerDsine: David Pincu - IEEE 802.3af Power via MDI Standard Compliant Mid-Span Insertion Solution Presented by PowerDsine: David Pincu - davidp@powerdsine.com Objectives! Investigate the Channel /Link options! Identify the requirements

More information

Lab - Build and Test Network Cables

Lab - Build and Test Network Cables Introduction In this lab, you will build and test straight-through and crossover Unshielded Twisted-Pair (UTP) Ethernet network cables. Note: With a straight-through cable, the color of wire used by pin

More information

Sumitomo Cable Specification SE-*RU. OFNP Rated Central Tube Cable with Optical Fibers. Issued: December 2014

Sumitomo Cable Specification SE-*RU. OFNP Rated Central Tube Cable with Optical Fibers. Issued: December 2014 Sumitomo Cable Specification SE-*RU Litepipe Ribbon Indoor Plenum Cable OFNP Rated Central Tube Cable with 12-432 Optical Fibers Issued: December 2014 78 Alexander Drive, Research Triangle Park, NC 27709

More information

TB806AUX Class E A / Cat.6A UTP Keystone Jack (Auto press-fit)

TB806AUX Class E A / Cat.6A UTP Keystone Jack (Auto press-fit) TB806AUX / Cat.6A UTP Keystone Jack (Auto press-fit) Cable holder with Strain Relief (SR) function: secure the cable with cable tie, and not wiggle to affect the termination and transmission. Cap: easy

More information

Cat.6 4 Pair UTP Cable

Cat.6 4 Pair UTP Cable 4 Pair UTP Cable Application: Voice Fast Ethernet(IEEE802.3u) VgAnyLAN(IEEE 802.12) Token Ring(IEEE 802.5) TPPMD(ANSI X3T9.5) BaseT Ethernet(IEEE 802.5) 155/622 Mbps 1.2/ 2.4 Gbps ATM 0BaseT Ethernet 550

More information

Mar11 Rev E

Mar11 Rev E Product Specification 108-1832 11Mar11 Rev E MT-RJ Patch Panel and Outlet Jacks (Standard, XG, SECURE and SECURE XG) 1. SCOPE 1.1. Content This specification, which meets the Optical Fiber Cabling Components

More information

TX COPPER CABLING SYSTEM

TX COPPER CABLING SYSTEM TX COPPER CABLING SYSTEM PERFORMANCE BEYOND PRODUCTS PANDUIT is the global leader in network connectivity, delivering end-to-end system solutions in support of your most demanding network requirements.

More information

Technical Specifications Florida Gulf Coast University

Technical Specifications Florida Gulf Coast University Technical Specifications Florida Gulf Coast University 9/19/2018 Page 1 of 21 Approved Vendors (alphabetical order) Aztek (CIP) Certified Installer Plus Mr. Scott Coyne 4730 Enterprise Avenue Suite #308

More information

Connected Solutions. April $ Post, 19 Rack ELERK1FR BK

Connected Solutions. April $ Post, 19 Rack ELERK1FR BK Connected Solutions April 2018 $30.97 Punch & Go Tool ONQAC3400 $139.97 per 305M Category 6 Riser, UTP, 23 AWG, Blue 305 Meter/1000 FT Pull Box CAB24/4PS6FT4BLUHYP $137.97 2 Post, 19 Rack ELERK1FR1194400BK

More information

SECTION 683 VIDEO OPTICAL TRANSCEIVER WITH BI-DIRECTIONAL DATA CHANNEL DESCRIPTION

SECTION 683 VIDEO OPTICAL TRANSCEIVER WITH BI-DIRECTIONAL DATA CHANNEL DESCRIPTION 683 SECTION 683 VIDEO OPTICAL TRANSCEIVER WITH BI-DIRECTIONAL DATA CHANNEL DESCRIPTION 683.01.01 GENERAL A. The Contractor shall furnish the designated quantity of Video Optical Transceiver (VOTR) pairs

More information

Brown University. Communications Standard Parts List

Brown University. Communications Standard Parts List CIS - NTG Brown University Communications Standard Parts List All data installations must receive the 25-year Mission Critical Warrantee from Hubbell Premise Wiring. All fiber installations must receive

More information

RJ45FC6-BLU. Base Data. Category 6 modular keystone jack - Blue - 1/bag. Article Number: Part No. RJ45FC6-BLU. Type RJ45FC6. Color.

RJ45FC6-BLU. Base Data. Category 6 modular keystone jack - Blue - 1/bag. Article Number: Part No. RJ45FC6-BLU. Type RJ45FC6. Color. insertions Contact set constructed of phosphor bronze Category 6 modular keystone jack - Blue - 1/bag Article Number: 852-25065 Part Number: Type: RJ45FC6 Base Data Part No. Type Color Features RJ45FC6

More information

Public Works Division Lighting District Fiber Optic Specifications April 2009

Public Works Division Lighting District Fiber Optic Specifications April 2009 Public Works Division Lighting District Fiber Optic Specifications April 2009 7000 Florida Street Punta Gorda, Florida 33950 Tele: 941.575.3600 Fax : 941.637.9265 www.charlottecountyfl.com/publicworks

More information

Category 5e F/UTP Euroclass D ca Cables

Category 5e F/UTP Euroclass D ca Cables Category 5e F/UTP Euroclass D ca Cables Datasheet: GD103437v2 APPLICATION The Brand-Rex GPF D ca cables are compliant with the European Construction Products Regulation, achieving Euroclass level D ca

More information

HighBand 25. TrueNet Category 6 Solutions

HighBand 25. TrueNet Category 6 Solutions HighBand 25 TrueNet Category 6 Solutions The highest performing cross-connect system in the world. A unique high-density solution with superior cable management. ADC KRONE s HighBand 25 cross connect solution

More information

INSTALLATION GUIDE. LANmark-OF Zone Distribution Box

INSTALLATION GUIDE. LANmark-OF Zone Distribution Box LANmark-OF Zone Distribution Box INSTALLATION GUIDE LANmark-OF Zone Distribution Box Document information Release November 2004 Published by Contact address Nexans Cabling Solutions Alsembergsesteenweg

More information

GenSPEED Category 5e Cables 3

GenSPEED Category 5e Cables 3 Datacom GenSPEED Category 5e Cables 3 GenSPEED Category 5e cables are available in a wide variety of performance levels and constructions. With many options to pick from, you can select the GenSPEED Category

More information

Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING

Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING Revision 05/01/2017 Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING PART 1 GENERAL 1.1 SECTION INCLUDES A. Voice, Data, and Fiber Cable Product materials B. Voice, Data, and Fiber Cable Execution

More information

Volition TM RJ45 K5e Jacks

Volition TM RJ45 K5e Jacks Volition TM RJ45 K5e Jacks Part of our 3M Volition Network Solutions, the new K5e range is our ultimate Category 5e hardware component (ISO/IEC 11801, EN 50173 and ANSI/TIA/EIA-568). The K5e jack is a

More information

How to Specify MTP Pre-terminated Optical Cabling. January White Paper. Published

How to Specify MTP Pre-terminated Optical Cabling. January White Paper. Published White Paper How to Specify MTP Pre-terminated Optical Cabling Published January 2009 The benefits of pre-terminated cabling The two principal advantages of pre- terminated cabling are reduced time on site

More information

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Telecommunciations Infrastructure Project September 20, A. Broadband radio frequency active and passive components

Telecommunciations Infrastructure Project September 20, A. Broadband radio frequency active and passive components PART 1 - GENERAL 1.1 SECTION INCLUDES A. Broadband radio frequency active and passive components B. Broadband optical active and passive components C. Coaxial cable and connectors D. Support and termination

More information

DATA/TELECOMMUNICATIONS REQUEST FOR PRICING

DATA/TELECOMMUNICATIONS REQUEST FOR PRICING Category 6A 10Gig DATA/TELECOMMUNICATIONS REQUEST FOR PRICING TABLE OF CONTENTS 1. GENERAL 3 1.1. Work Included... 3 1.2. Scope of Work... 3 1.3. Regulatory References... 4 1.4. Quality Assurance... 4

More information

TB876BSX-3WH Class E A / Cat.6A STP Keystone Jack (Auto press-fit)

TB876BSX-3WH Class E A / Cat.6A STP Keystone Jack (Auto press-fit) TB876BSX-3WH / Cat.6A STP Keystone Jack (Auto press-fit) Copper braid can be fully contacted and covered for 23-26 AWG solid wire. Press-fit process. 100% RoHS compliant, without soldering. Unique design

More information

LCS2 Cat. 6 RJ 45 Patch panels and units

LCS2 Cat. 6 RJ 45 Patch panels and units 87045 LIMOGES Cedex Telephone: 33 0 5 55 06 87 87 - Fax: 33 0 5 55 06 88 88 LCS2 Cat. 6 RJ 45 CONTENTS Page 1. General characteristics....1 2. Presentation...2 3. Installation...2 4. Technical characteristics...2

More information

Compact Module. Category 6 FTP Cabling System

Compact Module. Category 6 FTP Cabling System Compact Module Shielded design for improved EMI performance Suitable for Gigabit Ethernet applications and beyond Ultra-slimline design Colour coded for quick and accurate termination Interchangeable with

More information

MT-RJ SECURE Product Expansion Now 10 Variants of the MT-RJ SECURE Products

MT-RJ SECURE Product Expansion Now 10 Variants of the MT-RJ SECURE Products MT-RJ Product Expansion Now 0 Variants of the MT-RJ Products In response to several customers, the MT-RJ product line has been expanded with an additional six color/key versions. In addition to the original

More information

PATCH CORDS, PLUGS & CABLES

PATCH CORDS, PLUGS & CABLES PATCH CORDS, PLUGS & CABLES 3.1 SECTION CONTENTS Modular Cords...3.2 Cable Assemblies...3.3 Plugs & Connectors...3.4 Bundled Cable...3.5 Category 5e & 6 UTP Cable...3.6 Coax Cable...3.7 Fiber Optic Cable...3.8

More information