1 SURGE PROTECTIVE DEVICES
2 COMPANY INTRODUCTION Bridex Singapore Pte Ltd is founded in 1978 as a manufacturer of instruments transformer for the Asian market. We are the first local electrical switchgear components manufacturer that launches our own Asian identity Today we aim to become a knowledge-based, technology driven engineering organization, with emphasis on providing solution for electrical distribution and control. We specialize in the area of instruments, distribution & protection and power quality solution. With our present headquarter in Singapore and subsidiaries that are located in Australia, Malaysia, Philippines and representative office in Vietnam, we are well equipped to service both local market and countries in the Asia Pacific. PRODUCTION INTRODUCTION Rudolf Surge Protective Devices Transient over-voltage is characterized with high peak values, rapid amplitude growth and a short duration. Surge voltages can be caused by: - Lightning - Switching of electrical loads by the power utilities - Switching of high power machines - Electro-static discharges When a surge voltage is produced in an electrical conductor, an over-current with a magnitude of several ka is lead to earth, it can reach installation through low voltage network, data lines (voice & data), high frequency lines (antennas) or conductors of earth terminations. In order to avoid the over-current destroying the equipment connected to the electrical system, surge protective device is installed in front of the equipment to derive the current generated by the surge voltage directly to earth. This action by-pass the surge voltage from the equipment and lead it to earth. Surge Protection Devices are needed in any kind of electrical installation, in order to protect and provide the following benefits: - Protect against lightning, its destructive consequences, and the costly repairs and downtimes that they originate; - Avoid downtimes caused by random logic failures (that require to restart electronic equipment to get it back into operation); - Increase operative life of electronics, by providing to it always a clean and disturbancefree power supply; surge protective devices the brand that add values to your solution.
3 BASIC FEATURES In order to select the most appropriate SPD, we need to understand the selection criteria: Maximum discharge current (Imax) : The maximum current through the SPD having an 8/20 wave-shape and magnitude to derive the over-current to earth for one time without suffering damage. Nominal discharge current (In) Voltage protection level (Up) : The current through the SPD having a 8/20 wave-shape and magnitude to derive the over-current to earth for 15 times without suffering damage. : The performance of the SPD in limiting the voltage across its terminals when the nominal discharge current passes through it. Maximum continuous operating voltage/ : The maximum r.m.s. voltage which may be continuously rated voltage (Uc) applies to the SPD mode of protection. Location of the protector in accordance to international standard recommendation is classify into 3 classes. - Class I : High protection level, 10/350 wave-shape to be assemble at the entry connection - Class II : Medium protection level, 8/20 wave-shape to be assemble downstream from Class I protection for example: at the LV Main Switchboard. - Class III : Fine protection level, 8/20 wave-shape to be assemble at the load end or downstream from Class II protection. SPDs are parallel units hence its installation is easy and fast. General Installation Rules Selection of RUDOLF s SPD to be installed, this is done by verify the specifications of the electrical installation with the specifications of your selected RUDOLF s SPD. (Voltage,nr. of phases, protection level); Read the installation manual before installing any RUDOLF s SPD; Measure voltage between L-N and L-L in your system. Check if the voltage is correct in respect to the Uc of the selected RUDOLF s SPD; Check if PE is correct (according to the standards); Select MCB if needed; Switch-off the power supply on the line or panels where the RUDOLF s SPD must be connected; Connection of RUDOLF s SPD in parallel; Check the wire distance between the RUDOLF s SPD and the connection point to the Line. - Very important: the wire distance between the RUDOLF s SPD and the AC Line should be kept as short as possible, ideally at no more than 1 meter. - Above 1 meter of connecting wire length, the Up will increase at 20 V per every additional 20 cm. (decreasing performance due to larger impedance). Keep the connecting wire as straight as possible. Do not coil it. Ground properly the RUDOLF s SPD. If RUDOLF s SPD is connected in a cabinet or in combination with an RCB, install the RUDOLF s SPD prior to the RCB. When turning power on, check if diagnostics are OK. If out of order switch off the power, check connections and try again.
4 SELECTION GUIDE Product Code No. of Poles Imax (ka) Un (VAC) Configuration Modes Protected R-SPD Monoblock 1 R-SPD202 1P+N Monoblock 3 R-SPD204S 3P+N (L-L) / 230 (L-N) Monoblock+signal 7 R-SPD Monoblock 1 R-SPD452 1P+N Monoblock 3 R-SPD454S 3P+N (L-L) / 230 (L-N) Monoblock+signal 7 R-SPD Monoblock 1 R-SPD652 1P+N Monoblock 3 R-SPD654S 3P+N (L-L) / 230 (L-N) Monoblock+signal 7 R-SPD10011S Monoblock+signal 1 R-SPD10013S Monoblock+signal 1 WIRING DIAGRAM TN-C Networks TT Networks TNS Networks TT Networks TN Networks
5 SPECIFICATION Class II : 20 ka, 40 ka Medium Protection Level Description R-SPD2011 R-SPD202 R-SPD204S R-SPD4511 R-SPD452 R-SPD454S Nominal Voltage (Un) 230 V 230 V 400 V (L-L) / 230 V 230 V 400 V (L-L) / 230 V (L-N) 230 V (L-N) Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz Maximum Continuous 275 V 275 V 440 V (L-L) / 275 V 275 V 440 V (L-L) / Voltage (Uc) 275 V (L-N) 275 V (L-N) I max (1x) 8/20 KA 20 ka 20 ka 20 ka 40 ka 40 ka 40 ka I nom (15x) 8/20 KA 8 ka 5 ka 5 ka 15 ka 15 ka 15 ka Circuit Type MOV MOV MOV MOV MOV MOV Time Response <25 ns <25 ns <25 ns <25 ns <25 ns <25 ns Protection L-G, L-N, L-G, L-L, L-G, L-N, L-G, L-L, N-G L-N, N-G N-G L-N, N-G Diagnostics Optical Optical (LED) Optical (LED) Optical, Optical (LED) Optical (LED) + Signal + Signal Thermal fuse Yes Yes Yes Yes Yes Yes No. Of Poles Connection Parallel Parallel Parallel Parallel Parallel Parallel Box DIN DIN DIN DIN DIN DIN Width Of Housing 18 mm 36 mm 90 mm 18 mm 36 mm 90 mm Maximum Cable Section 6 mm mm mm mm mm mm 2 Ground Connections 6 mm mm mm mm mm mm 2 Operating Temperature -30 C, 75 C -30 C, 75 C -30 C, 75 C -30 C, 75 C -30 C, 75 C -30 C, 75 C Voltage Protecting 1.2 kv 1.2 kv 1.2 kv 1.3 kv 1.3 kv 1.3 kv Level In
6 SPECIFICATION Class II : 65 ka High Protection Description R-SPD6511 R-SPD652 R-SPD654S Nominal Voltage (Un) 230 V 230 V 400 V (L-L) / 230 V (L-N) Frequency 50/60 Hz 50/60 Hz 50/60 Hz Maximum Continuous 275 V 275 V 440 V (L-L) / 275 V (L-N) Voltage (Uc) I max (1x) 8/20 KA 65 ka 65 ka 65 ka I nom (15x) 8/20 KA 20 ka 20 ka 20 ka Circuit Type MOV MOV MOV Time Response <25 ns <25 ns <25 ns Protection L-G, L-N, N-G L-G, L-L, L-N, N-G Diagnostics Optical Optical (LED) Optical (LED) + Signal Thermal fuse Yes Yes Yes Nr. Of Poles Connection Parallel Parallel Parallel Box DIN DIN DIN Width Of Housing 18 mm 36 mm 90 mm Maximum Cable Section mm mm mm 2 Ground Connections mm mm mm 2 Operating Temperature -30 C, 75 C -30 C, 75 C -30 C, 75 C Voltage Protecting 1.5 kv 1.5 kv 1.5 kv Level In * Optical : With local flag display Optical + Signal : With local flag display & remote auxiliary contact
7 SPECIFICATION Class I : 100 ka High Protection Description R-SPD10011R R-SPD10013IR Nominal Voltage (Un) 230 V 400 V Frequency 50/60 Hz 50/60 Hz Maximum Continuous 270 V 440 V Voltage (Uc) I max (1x) 8/20 KA 100 ka 100 ka I nom (15x) 8/20 KA 30 ka 30 ka Circuit Type MOV MOV Time Response <25 ns <25 ns Protection L-G L-G Diagnostics Optical (LED) + Signal Optical (LED) + Signal Thermal fuse Yes Yes Nr. Of Poles 1 1 Connection Parallel Parallel Box DIN DIN Width Of Housing 36 mm 36 mm Maximum Cable Section 50 mm 2 50 mm 2 Ground Connections 50 mm 2 50 mm 2 Operating Temperature -30 C, 75 C -30 C, 75 C Voltage Protecting 1200 V 1800 V Level In * Optical : With local flag display Optical + Signal : With local flag display & remote auxiliary contact
SURGE PROTECTIVE DEVICES
SURGE PROTECTIVE DEVICES COMPANY INTRODUCTION Bridex Singapore Pte Ltd is founded in 1978 as a manufacturer of instruments transformer for the Asian market. We are the first local electrical switchgear
More informationEMC Solutions Noise filtering
Power & Signal Quality TRABTECH EMC Solutions Noise filtering Interference-free power supply and signal transmission A permanent supply and safe data link are essential for the operational reliability
More informationProtective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A
DATASHEET - NZMN3-VE630 Circuit-breaker, 3p, 630A Part no. NZMN3-VE630 Catalog No. 259133 EL-Nummer (Norway) 0004358791 Similar to illustration Delivery program Product range Circuit-breaker Protective
More informationDescription Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100
DATASHEET - NZMN3-4-AE400 Circuit-breaker, 4p, 400A Part no. NZMN3-4-AE400 Catalog No. 265891 Similar to illustration EL-Nummer (Norway) 0004358857 Delivery program Product range Circuit-breaker Protective
More informationContactors and Contactor Assemblies
Terminal designations according to EN 50 012 3RT10 1 contactors Ident. no. 10E 01 Sizes S0 to S12 Terminal designations according to EN 50 012 3RT10 2 to 3RT10 7, 3RT12, 3RT14 contactors 3RT10 1 contactors
More informationI r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
DATASHEET - NZMC1-A160 Circuit-breaker, 3p, 160A Part no. NZMC1-A160 Catalog No. 283296 Similar to illustration Delivery program Product range Circuit-breaker Protective function System and cable protection
More information3M Sensored Termination (15 kv) QX-T15I-vi1-E
3M Sensored Termination () QX-T15I-vi1-E Data Sheet May 2016 Kit Contents: Each kit contains sufficient quantities of the following materials to make three single-phase terminations. 31" (REF) One piece
More informationI r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
DATASHEET - NZMH2-A100 Circuit-breaker, 3p, 100A Part no. NZMH2-A100 Catalog No. 259099 Similar to illustration Delivery program Product range Circuit-breaker Protective function System and cable protection
More informationDescription Set value in neutral conductor is synchronous with set value Ir of main pole. CSA 100. conductor. I r A 50-63
Circuit-breaker,4p,63A Partno. NZMH1-4-A63 Articleno. 284426 Similar to illustration Deliveryprogram Product range Circuit-breaker Protective function System and cable protection Standard/Approval IEC
More informationI r A Protection against direct contact Finger and back-of-hand proof to VDE 0106 part 100
Circuit-breaker,3p,400A Partno. LZMC3-A400-I Articleno. 111955 Similar to illustration Deliveryprogramme Product range Circuit-breaker Protective function System and cable protection Standard/Approval
More informationHigh performance circuit breakers
Series High performance Description The high performance MCB offers a compact solution to circuit protection. The devices are DIN rail mounted. The is available with application-specific trip characteristics
More informationProtective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A
Deliveryprogramme Circuitbreak.3pselect.protection Partno. Articleno. 265777 NZMH4-VE1600 Product range Circuit-breaker Protective function Systems, cable, selectivity and generator protection Standard/Approval
More informationI r A I i = I n x. Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
Deliveryprogramme Circuitbr.,3pmotorprotection Partno. Articleno. 265784 NZMN4-ME875 Product range Circuit-breaker Protective function Motor protection Standard/Approval IEC Installation type Fixed Release
More informationI r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
Circuit-breaker,3p,160A Partno. NZMN2-M160 CatalogNo. 265724 Similar to illustration Deliveryprogram Product range Circuit-breaker Protective function Motor protection Standard/Approval IEC Installation
More informationHYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.
Linear / area dimming Constant current LED driver DALI Dimmable Product description Dimmable built-in constant current LED Driver Adjustable output current between 1,050 and 1,750mA via DIP switch Max.
More informationLED Driver Linear / area fixed output
Driver LC 10W 350mA fixc lp SNC2 ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 350 ma Max. output power 10.2 W Up to 80 % efficiency For
More information1 Power Protection and Conditioning
Power Protection and Conditioning MCR Hardwired Series Power Line Conditioning with Voltage Regulation The MCR Hardwired Series provides excellent noise filtering and surge protection to safeguard connected
More informationPRINCIPLES AND APPLICATIONS
GENERATION & NETWORK Digital Automation Measuring and Control Devices AMS7000 PROCOM The optimum operation of an electrical network depends particularly on the reliability and the availability of the protection,
More informationHYL-035D0850G103. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.
Constant current LED driver DALI Dimmable Product description Dimmable Independent constant current Adjustable output current between 350 and 1,050mA via DIP switch Max. output power 35 W Up to 88 % efficiency
More informationI/A Series Hardware Fiber Optic LAN Converter
I/A Series Hardware PSS 21H-7F3 B4 The provides bidirectional conversion between coaxial and fiber optic media. The converter is compatible with existing I/A Series system hardware, utilizes industry standard
More informationModular Power System acc. VG MoFess Module for Military Ground Vehicles
This new modular Power System for Military Ground Vehicles based on a standard box incorporating up to three different power modules. The power inlet module (230 V AC) includes line filter, lightning protection
More informationSPECIAL SPECIFICATION 6735 Video Optical Transceiver
2004 Specifications CSJ 0924-06-244 SPECIAL SPECIFICATION 6735 Video Optical Transceiver 1. Description. This Item governs the furnishing and installation of Video optical transceiver (VOTR) in field location(s)
More informationTOSHIBA Industrial Magnetron E3328
TOSHIBA E3328 is a fixed frequency continuous wave magnetron intended for use in the industrial microwave heating applications. The average output power is 3kW in the frequency range from 2450 to 2470
More informationLED Driver Compact fixed output
Driver LC 40W 900mA fixc C SNC ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 900 ma Max. output power 40 W Nominal life-time up to 50,000
More informationDimmers SЕRIES. Kitchen light control. Bedroom light control. Living room light control
Kitchen light control Bedroom light control 15 SЕRES iving room light control ighting control in corridors (for hotels, offices and hospitals) FDER reserves the right to alter characteristics at any time
More informationEA63-7D. Generator Automatic Voltage Regulator Operation Manual. Self Excited Automatic Voltage Regulator
EA63-7D Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator SP POWERWORLD LTD Willows, Waterside, Ryhall, Stamford, Lincs, PE9 4EY, UK Tel: +44 1780 756872 -
More informationMILLITARY SPECIFICATION SHEET
INCH-POUND MILLITARY SPECIFICATION SHEET 10 November 2000 SUPERSEDING MIL-R-6106/14B 10 March 1989 RELAY, ELECTRIC, PERMANENT DRIVE, 50 AMP, SPDT (DB) DOUBLE MAKE DOUBLE BREAK AUXILIARY CONTACTS (5 AMP),
More informationPHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series
Product description Fixed output built-in LED Driver Constant current LED Driver Output current 900 ma Max. output power 40 W Nominal life-time up to 30,000 h For luminaires of protection class I and protection
More informationLED Driver Compact fixed output
Driver LC 45W 1050mA fixc C SNC ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 1,050 ma output power 45 W Nominal life-time up to 50,000
More informationMapletree Audio Design
Ultra 4C Preamplifier Mapletree Audio Design Ultra 4C Stereo Phono/Line Preamplifier PS 2D Power Supply User s Manual Rev. Mar. 22, 2019 Mapletree Audio Design R. R. 1, Seeley's Bay, Ontario, Canada, K0H
More informationAS09..S 3-pole Contactors - Spring Terminals
4 kw 5 hp AS09..S 3-pole Contactors - Spring AC Operated Description - 3-pole contactors with spring terminals, - N.C. or N.O. built-in auxiliary contact, - Rail-mounted, no tools required, - Additional
More informationMASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz
Mobile Communications MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz CAUTION THESE SERVICING INSTRUCTIONS ARE FOR USE BY QUALI- FIED PERSONNEL ONLY. TO
More informationTelemetry Receiver Installation Guide
BBV Telemetry Receiver Installation Guide Models covered Rx200 Building Block Video Ltd., Unit 1, Avocet Way, Diplocks Industrial Estate, Hailsham, East Sussex, UK. Tel: +44 (0)1323 842727 Fax: +44 (0)1323
More information15 Series - Dimmer
Features Master slave system for multiple load dimming Suitable for incandescent and halogen lighting loads (with or without transformer or electronic supply) Compatible with energy saving (CF or ED) dimmable
More informationUsing Ultrasound and Infrared Technologies for Metal-Clad Switchgear Inspections
Using Ultrasound and Infrared Technologies for Metal-Clad Switchgear Inspections Adrian Messer, Manager of US Operations UE Systems, Inc. Ph: 864-224-4517 Cell: 914-282-3504 Web: www.uesystems.com Email:
More informationCURRENT INJECTION RELAY TESTER CR-100. ( Code P60212 (770081) ) INSTRUCTIONS MANUAL ( M / 05A ) (c) CIRCUTOR S.A.
CURRENT INJECTION RELAY TESTER CR-100 ( Code P60212 (770081) ) INSTRUCTIONS MANUAL ( M 981 329 / 05A ) (c) CIRCUTOR S.A. ---- CURRENT- TIME TRIP TESTER CR-100 --------------- Page. 2 CURRENT INJECTION
More informationGP-500 SERIES - Low Voltage
M O T O R & G E N E R A T O R P R O T E C T I O N AUTOMATIC INSULATION RESISTANCE TESTERS Meg-Alert is an automatic, in-line insulation resistance tester and monitor with test capabilities from 500 to
More informationBulletin 190 IEC Modular Starter System
Bulletin 90 Table of Contents Selection Guide Description Page Bulletin 90....................................... Accessories....................................... 7 Specifications.....................................
More information1995 Metric CSJ SPECIAL SPECIFICATION ITEM 6031 SINGLE MODE FIBER OPTIC VIDEO TRANSMISSION EQUIPMENT
1995 Metric CSJ 0508-01-258 SPECIAL SPECIFICATION ITEM 6031 SINGLE MODE FIBER OPTIC VIDEO TRANSMISSION EQUIPMENT 1.0 Description This Item shall govern for the furnishing and installation of color Single
More informationwith handle LIMOGES Cedex 1. DESCRIPTION - USE 3. DIMENSIONS Symbol: Technology: Use:. For controlling a load remotely via a switch 2.
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 25A power contactors silent CONTENTS PAGES 1. Description, use... 1 2. Range... 1 3. Dimensions... 1 4. Positioning - Connection...
More informationTeSys contactors. Model d. Type of contactor LC1- LC1- LC1- LC1- LC1-D115 & D09 D18 D25 D38 D40 D50 D95 LC1-D150 DT20 & DT25 DT32 & DT40
Characteristics Type of contactor LC- LC- LC- LC- LC-D & D09 D8 D2 D38 D40 D0 D9 LC-D0 DT20 & DT2 DT32 & DT40 Environment Rated insulation voltage (Ui) Conforming to IEC 947-4-, overvoltage category III,
More informationLED Driver Compact fixed output
Driver LC 10W 250mA fixc R ADV ADV series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 250 ma For luminaires of protection class II For ambient temperatures
More informationORDERING Page 6 BASLER RELAY STANDARDS, DIMENSIONS, ACCESSORIES Request bulletin SDA
BE1-59NC CAPACITOR NEUTRAL OVERVOLTAGE RELAY The BE1-59NC Capacitor Neutral Overvoltage Relay provides sensitive protection for capacitor banks. ADDITIONAL INFORMATION INSTRUCTION MANUAL ADVANTAGES Helps
More informationMCR3 POWER EQUIPMENT. Microprocessor Controlled Constant Current Regulator. Compliance with Standards. Uses. Features
Microprocessor Controlled Constant Current Regulator Compliance with Standards FAA: ICAO: IEC: 61822 CENELEC: AC 150/5345-10 (current edition), L-828, L-829. Aerodrome Design Manual Part 5, para. 3.2 (current
More informationSPECIAL SPECIFICATION 1987 Single Mode Fiber Optic Video Transmission Equipment
1993 Specifications CSJ 0027-12-086, etc. SPECIAL SPECIFICATION 1987 Single Mode Fiber Optic Video Transmission Equipment 1. Description. This Item shall govern for the furnishing and installation of color
More informationLow-Cost, Single-CT, Automatic Power Factor Controller for Balanced Three-Phase Reactive Power Compensation User Manual
Low-Cost, Single-CT, Automatic Power Factor Controller for Balanced Three-Phase Reactive Power Compensation User Manual Firmware Version: 1.0.1.8 Page 1 of 24 Dated: 23 rd June 2016 CAUTIONS: NOTE These
More informationProtection against direct contact Finger and back of hand proof to VDE 0106 Part 100
Circuit-breaker3psystems/cableprot. Partno. NZMB2-A250 Articleno. 259090 Deliveryprogramme Range Circuit-breaker Protective function System and cable protection Standard/Approval IEC Installation type
More informationDimming actuators GDA-4K KNX GDA-8K KNX
Dimming actuators GDA-4K KNX GDA-8K KNX GDA-4K KNX 108394 GDA-8K KNX 108395 Updated: May-17 (Subject to changes) Page 1 of 67 Contents 1 FUNCTIONAL CHARACTERISTICS... 4 1.1 OPERATION... 5 2 TECHNICAL DATA...
More informationMAXTECH, Inc. BRC-1000 Series. C-Band Redundant LNB Systems. Technology for Communications. System Block Diagrams
MAXTECH, Inc. Technology for Communications BRC-1000 Series C-Band Redundant LNB Systems Introduction Redundant LNB systems minimize system downtime due to LNB failure by providing a spare LNB and an automatic
More informationPAM-1840 Preamplifier Operation Manual
PAM-1840 Preamplifier Operation Manual 1 TABLE OF CONTENTS INTRODUCTION 3 GENERAL INFORMATION 4 SPECIFICATIONS 4 OPERATING INSTRUCTIONS 5 MAINTENANCE 6 2 INTRODUCTION BEFORE APPLYING POWER Review this
More informationmulti-function meters
multi-function meters eclipse 2 eclipse 7 installation and operating manual 1 GENERAL DESCRIPTION 2 INSTALLATION 3 WIRING INFORMATION 4 2 ECLIPSE 2 METERS 2.1 PROGRAMMING THE METER 5 2.2 INFORMATION 6
More informationAgilent N9355/6 Power Limiters 0.01 to 18, 26.5 and 50 GHz
Agilent N9355/6 Power Limiters 0.01 to 18, 26.5 and 50 GHz Technical Overview High Performance Power Limiters Broad frequency range up to 50 GHz maximizes the operating range of your instrument High power
More informationLED Driver Linear / area dimming. Driver LCAI 38/75W TW lp Tunable White
Driver LCAI 38/75W TW lp Tunable White Product description 2-channel LED Driver with LI DT8 Output power: 38 W or 75 W Power input on standby < 0.3 W Nominal life-time up to 50,000 h 5-year guarantee Properties
More informationLC1D12P7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A V AC coil
Characteristics TeSys D contactor - 3P(3 NO) - AC-3 -
More informationDatasheet. LED Transformers. LED Transformer 120W 24V V. LED Transformers
LED Transformers Datasheet LED Transformers LED Transformer 120W 24V 220-240V Product description Philips full-electronic constant voltage LED Transformers are designed to operate 24VDC LED solutions used
More informationOperating Manual RISH OPTIMA VAF
Operating Manual RISH OPTIMA VAF 2-60-006-00-00511_Rev. A - 5/2014 Section DIGITAL MULTIFUNCTION INSTRUMENT Programmable Multi-function Digital Panel Meter Installation & Operating Instructions Contents
More informationLC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC
Product datasheet Characteristics LC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC Price* : 86.25 GBP Main Range Product name Product or component type Device short name Contactor application Utilisation category
More informationModel /29S RF Splitter
Instruction Manual Model 1584-29/29S RF Splitter March 2013, Rev. 0 LNB VOLTAGE A B MODEL 1584 COMBINER CROSS TECHNOLOGIES INC. GND+DC ON Data, drawings, and other material contained herein are proprietary
More informationOT 100/ /700 P5
OT 100/120 277/700 P5 OPTOTRONIC Outdoor Constant current LED drivers Areas of application _ Street and urban lighting _ Industry _ Suitable for luminaires of protection class I Product benefits _ High
More informationLED control gear Compact fixed output
Driver LC 40W 900mA fixc SR SNC ESSENCE series Product description Independent fixed output LED Driver Constant current LED Driver Output current 900 ma Max. output power 39 W Nominal life-time up to 50,000
More informationALM-6813/6812 INSTALLATION AND PROGRAMMING MANUAL
ALM-6813/6812 INSTALLATION AND PROGRAMMING MANUAL Installation and programming Manual v2.2 1 MARSS Solar Defender SYSTEM This guidebook provides the essential instructions to install and configure the
More informationLED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series
Driver LC 200W 1050mA UNV ADV IND ADVANCED series Product description Independent constant current LED Driver For dry, damp and wet locations Max. output power 200 W Up to 93.7 % efficiency For luminaires
More informationSelf Excited Automatic Voltage Regulator For Generator Compatible with Marathon SE350* Operation Manual
Self Excited Automatic Voltage Regulator For Generator Compatible with Marathon SE350* Operation Manual s * Use for reference purpose only and not a genuine Marathon product. 1. INTRODUCTION Sensing Input
More informationHenkel Installation Handbook LINEGUARD 2001
Henkel Installation Handbook LINEGUARD 2001 HENKEL ITALIA S.r.l. Microprocessor instruments Henkel Installation Handbook Lineguard 2001 Page 2 Summary 1. The Microprocessor Instruments... 4 1.1. Norms
More informationArc Detecting and Protection System
Data Sheet Arc Detecting and Protection System Protection of Switchboards Personnel safety, the cost of employees. Loss of supply and operation of the switchboard, the cost of a production down time. Damage
More informationTable of Contents. Introduction Pin Description Absolute Maximum Rating Electrical Specifications... 4
Table of Contents Introduction... 1 Pin Description... 2 Absolute Maximum Rating... 3 Electrical Specifications... 4 Mechanical Specifications... 5 Thermal Specifications... 6 Over Temperature Protection...
More informationMultifunction Digital Timer
Multifunction Digital Timer 72 x72 mm Timer with Easy-to-use Functions Nine output modes accommodate a wide variety of applications. All parameters set by scroll-through menus accessed from the front panel.
More informationWeekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N
Weekly Timer 1/4 DIN Size Timer Features Prompted Programming and Large LCD Display 24 hours x 7 days programming using just 5 switches 16 program steps and cycle operation Two independent 15 A control
More informationSeries CT7N Bimetallic Overload Relays
Series CT7N imetallic Overload Relays Choose CT7N overloads in DC applications and when monitoring Variable Frequency Drives Sprecher + Schuh has always paid particular attention to the subject of motor
More informationINSTRUCTIONS FOR USE Pro-Ject Receiver Box S
INSTRUCTIONS FOR USE Pro-Ject Receiver Box S Dear music lover, thank you for purchasing a PRO-JECT AUDIO receiver. In order to achieve maximum performance and reliability you should study these instructions
More informationAgilent 86120B, 86120C, 86122A Multi-Wavelength Meters Technical Specifications
Agilent 86120B, 86120C, 86122A Multi-Wavelength Meters Technical Specifications March 2006 Agilent multi-wavelength meters are Michelson interferometer-based instruments that measure wavelength and optical
More informationCircuit-Breakers for Motor Protection Series 8523/8
> Accessories Auxiliary contacts 1 NC + 1 NO or 2 NC + 2 NO Undervoltage trip Shunt release > Switch operation with knop > Secure switching > Clear switch setting indicator > Different current setting
More informationPBC series. RoHS. Ready. IEC-Type Contactors & Accessories 9-80 Amp AC-3, Amp AC-1 AC Coils. P&B PBC Series IEC Type Contactors & Accessories
PBC series IEC-Type Contactors & Accessories 9-80 Amp AC-3, 25-125 Amp AC-1 AC Coils File E38802 (PBC) RoHS Ready Users should thoroughly review the technical data before selecting a product part number.
More informationAgilent 87075C Multiport Test Set Product Overview
Agilent 87075C Multiport Test Set Product Overview A complete 75 ohm system for cable TV device manufacturers Now, focus on testing, not reconnecting! For use with the Agilent 8711 C-Series of network
More informationModular pulse operated latching relay 16 A
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 Modular pulse operated latc / 05 / 07 / 08 / 10 / 11 / 12 / 14 / 16 / 20 and 927 00 / 49 CONTENTS PAGES 1. Description,
More informationLED Driver Compact dimming
Driver CA 15W 180-350mA flexc PH-C SR ADV ADVACED series Product description Dimmable constant current ED Driver (SEV) Independent ED Driver with cable clamps Selectable output current between 180, 250
More informationTC3005(LED/ELED/LASER) User's Manual
1. Description The gives users the ability to convert signals to format for data transmission (and vice-versa). These conversions can benefit users by extending transmission distances and/or enabling dissimilar
More informationORDERING Page 6 STANDARDS, DIMENSIONS and ACCESSORIES Request bulletin SDA
BE1-59NC CAPACITOR NEUTRAL OVERVOLTAGE RELAY The BE1-59NC Capacitor Neutral Overvoltage Relay provides sensitive protection for capacitor banks. ADVANTAGES Helps avoid cascading capacitor failures. Sensing
More informationllen-bradley 194R-HM4-NFPA3
Technical Data Rotary Disconnect Switch Specifications Bulletin Number 194R Topic Page Product Line Overview 2 General Specifications Fuse Description 12 Approximate Dimensions 14 Additional Resources
More informationDA8-T DA8-T MANUAL
J C F A U D I O MANUAL 1.0 contact@jcfaudio.com www.jcfaudio.com Safety Information Do not repair, modify, service this device except in the manner in which it is described in this manual. Doing so can
More informationP P S - M W S C A N 1 H
µ-controller-systems / HARD- & SOFTWARE-DESIGN POWER-SUPPLIES FROM MILLIWATTS TO KILOWATTS Device: PPS-MWS-3000-4500-CAN1H 06 / 2017 Page 1 / 6 S w i t c h i n g M o d e P o w e r S u p p l y f o r M a
More informationLC1D12B7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A - 24 V AC coil
Characteristics TeSys D contactor - 3P(3 NO) - AC-3 -
More informationTelemetry Receiver Installation Guide
BBV Telemetry Receiver Installation Guide Models covered Rx400P Building Block Video Ltd., Unit 1, Avocet Way, Diplocks Industrial Estate, Hailsham, East Sussex, UK. Tel: +44 (0)1323 842727 Fax: +44 (0)1323
More informationUSER MANUAL. Compact dimensions 6 DIN modules, with 4 LED s display with 7 segments, for an excellent reading of the measurements
DUCATI SISTEMI S. P. A. DUCA47 USER MANUAL Introduction The instrument DUCA47 is a digital multimeter that allows the measurement of the principal electrical parameters in threephase 230/400Vac networks
More informationDescription. Specifications and Ordering Information 1900/27 Vibration Monitor
R Specifications and Ordering Information 1900/27 Vibration Monitor Description The 1900/27 is a single-channel, stand-alone, locally mounted vibration monitor. It can be used as a stand-alone machinery
More informationDATA SHEET. Synchronisers, FAS-113DG ANSI code 25
DATA SHEET Synchronisers, ANSI code 25 Synchronisation of generator to busbar Circuit breaker time compensation LED indication of status LED for activated control LED for synchronising signal 35 mm DIN
More informationArc-fault Protection System
Short Form Catalogue Arc-fault Protection System Protection of Switchboards Improve personnel safety. Minimize production down time. Reduce damage to material and the cost of repair or replacement. Arcing
More informationConcert Series ORDERCODE D3470 ORDERCODE D3471 ORDERCODE D3472 D3470 D3471 D3472
Concert Series ORDERCODE D3470 ORDERCODE D3471 ORDERCODE D3472 D3470 D3471 D3472 Congratulations! You have bought a great, innovative product from DAP Audio. The DAP Audio Concert Series brings excitement
More informationINSTALLATION AND OPERATION M
INSTALLATION AND OPERATION M RUBYSTAR INSTALLATION AND OPERATION MANUAL Safety Instructions : Only authorised installers should install and or replace Rubystar inverters. Ensure that all electrical installations
More informationFeatures XT SC 012 B B A
Motor Control and Protection. XT IEC Manual and Combination Motor Controllers Selection XT IEC Manual and Combination Motor Controllers Manual and Combination Motor Controllers Design XT = XT IEC power
More informationWeekly Time Switch. Rated time Time setting range Time division 24 hrs x 7 days 00:00 to 23:59 1min
Weekly Time Switch Easy Programming with Large LCD Display and Interactive Functions Programming for 24 hrs x 7 days using just five switches. Sixteen program steps available. Power supply freely selectable
More informationTC Mbps - 622Mbps FIBER OPTIC MODE CONVERTER/REPEATER (Rev A0.1) User's Manual
TC3004 50Mbps - 622Mbps FIBER OPTIC MODE CONVERTER/REPEATER (Rev A0.1) MODEL: S/N: DATE: Notice! Although every effort has been made to insure that this manual is current and accurate as of date of publication,
More informationINSTALLATION & USER GUIDE
INSTALLATION & USER GUIDE Digidim 458 8-Channel Dimmer STEP 1 Assemble Dimmer Unit STEP 2 Mount Dimmer Chassis STEP 3 Electrical Installation STEP 4 Attach Module and Make Connections STEP 5 Replace Cover
More informationType: NZMN1 A100 Article No.: Sales text Circuit breaker3p systems/cable prot. Ordering information Number of poles
Type: NZMN1 A100 Article No.: 259085 Sales text Circuit breaker3p systems/cable prot. Ordering information Number of poles Description Rated current = rated uninterrupted current Setting range 3 pole I
More informationIdentification - electrical services
Identification - electrical services Aesthetic All live phase cable sheathing to be brown coloured and neutral phase cable sheathing to be blue coloured, all labelled L1, L2, L3 & N respectively in accordance
More information3.5. Control Relays and Timers. Contents. 9575H Series 3000 Type AA, AC and DC. General Purpose Relays Type AA
.5 9575H Series 000 Relay Contents 9575H Series 000 Type AA, AC and DC Product Selection....................... Accessories............................ Technical Data and Specifications........... Dimensions............................
More informationLandis+Gyr domestic single phase meter for residential
Landis+Gyr domestic single phase meter for residential AMR/AMM applications 31.07.2008 / 1 Mini-Flex Meter ZCF100 31.07.2008 / 2 Device Concept Proven Technology The Device Concept bases on the proven
More informationMagnecraft General Purpose Relays 750R Series DPDT and 3DPT, 10 A
and 3DPT, 10 A UL Listed when used with proper Magnecraft s The 750R series octal base, plug-in relays offer clear or full-feature covers with multiple mounting options and accessories. 750R 750R Full-Feature
More informationMG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV
MG-XV operating instruction Measuring of norm signals, 4-8-digit Panel instrument type MG-BV Construction instrument type MG-AV Contents 1. Brief description... 3 2. Safety instructions... 3 2.1. Proper
More informationMULTIS L72. Operating instructions
GB MULTIS L72 Operating instructions 2 SOCOMEC - Ref. : 876 091B ENGLISH GB Contents PRELIMINARY OPERATIONS 4 GENERAL INFORMATION 5 PRESENTATION 4 INSTALLATION 5 Mechanical environment Climatic environment
More information