ELECTRICAL SAFETY INSPECTION REPORT.
|
|
- Catherine Lucas
- 5 years ago
- Views:
Transcription
1 ELECTRICAL SAFETY INSPECTION REPORT., Plot no: 72 & 82, DEPZ, Ganakbari, Savar, Dhaka, Bangladesh. Factory List: 1.Experience Clothing Company Ltd. Inspected on March 31, 2014
2 SUMMARY Experience Clothing Company Ltd., factory is established in a two five storeyed (G+4) building and 1 shed. The building reportedly,constructed in The factory began production in The building was approved for industrial purpose and the factory during survey, reported had about 3100 workers working on regular basis. The Factory was surveyed for electrical safety by Woosun Energy and Construction Co., Ltd. (WEC). The purpose of the survey was to identify significant electrical safety issues and to provide recommendations for remediation based on applicable standards specified by the Accord. The scope of this initial electrical safety inspection was limited to the review and identification of major electrical safety issues. The inspection did not include identification of minor deficiencies, which will be further addressed as part of follow-up inspections. Table below summarizes the major electrical safety issues identified during the inspection. Recommendations have been provided to address each issue. An implementation schedule shall be developed by the factory to remediate each of the findings. The specific timing of improvements, including any requested extensions due to design / installation constraints, shall be submitted to the Accord for approval. Page 2 of 7
3 FINDINGS AND RECOMMENDATIONS E- 1 Transformer room is congested. Maintain safe working space surrounding the existing power transformer. Barrier is very close the transformer. 6 Months E- 2 Transformer breather not installed. Transformer breather must be installed to prevent moisture ingression. Breather is damaged. E- 3 Cables terminating to transformer bushings are not supported. Cable riser supporting cables must be firmly fixed. Power cable connected to the LV side of transformer. Page 3 of 7
4 E- 4 SWITCH BOARD & PANELS Crowded inside panel (MCCB, MCB, Bus bars and Wires) Panel must not be crowded with devices and apparatus. Each panel must be installed with devices and apparatus to maintain safety clearances inside panel. Wires are crowded inside the common busbar panel. E- 5 SWITCH BOARD & PANELS Multiple cables terminating to MCCB in panel. Multiple cable connecting at a MCCB terminal must be disconnected. Existing multiple circuits may be distributed through bus bars. MCCB inside distribution panel. E- 6 SWITCH BOARD & PANELS Multiple cables connected at a terminal of the bus bar. Multiple cable terminating at a terminal in busbars must be separated. Bus bar inside the distribution board. Page 4 of 7
5 E- 7 SWITCH BOARD & PANELS Insufficient working area in front of panel (Operating area). Adequate working space must be provided in front of every panel for operators (operating platform). Panel installed on raised plinth must have platform constructed for operators. 3 Months MDB installed in the washing area very close to the machine operation area. E- 8 GENERATOR ROOM Cables terminating to generator output terminal box are laid on floor. Cable terminating at Generator output terminal box must be supported on riser and protected. Existing cables laid on floor may be installed in cable trench or on trays. Cables on the floor in generator room. E- 9 CABLE & CABLE SUPPORTS Power cables installed close to steam lines. Existing power cables installed along side the steam line must be covered to protect against external heat from the steam lines. Adequate clearance may be provided from the steam lines. Power cables and steam carrying pipe. 3 Months Page 5 of 7
6 E- 10 CABLE & CABLE SUPPORTS Cables in electrical shafts are not protected. Cables in electrical shaft must be securely clamped to the tray/ladder and must be protected. Power cable goes through one floor to another without protection. E- 11 GENERATOR ROOM Inadequate working space around the generators. Expand the existing generator room to provide safe working space. generator placed very close the wall. 6 Months E- 12 Transformer guarded with wire mesh fencing. Transformer may be separated from panels by constructing barrier walls. Substation transformer guarded with wire mesh fencing. 6 Months Page 6 of 7
7 E- 13 WIRINGS Cables terminating to distribution panels (switchboards) are not protected. Cables, terminating to panel, between floor and base of panel must be protected in rigid conduits with ample strength. Conduit must be securely fixed to the wall with saddle or clamps. Wiring through flexible PVC conduit. E- 14 CABLE & CABLE SUPPORTS Cables from electrical shaft exiting at various floors are not supported. Cables leaving supports (tray/ladder) in electrical shafts must be supported till the cables are terminated at the panel. From the LT panel cables are going to different floor. 3 Months E- 15 CABLE & CABLE SUPPORTS Cables partially supported in tray and raceways (cables are not placed inside tray in few sections). Cables supported in tray must be securely laid in the tray and fixed securely. Cables laid on cables tray below ceiling Page 7 of 7
ELECTRICAL SAFETY INSPECTION REPORT
ELECTRICAL SAFETY INSPECTION REPORT A PLUS INDUSTRIES LIMITED. Plot-28, Milk Vita Rd., Section-07, Mirpur, Dhaka Factory List: 1. A Plus Industries Ltd. Inspected by: Yoon Report Generated by: Nezar Inspected
More informationELECTRICAL SAFETY INSPECTION REPORT
ELECTRICAL SAFETY INSPECTION REPORT A & B OUTERWEAR LTD. Plot # 29-30, CEPZ, Chittagong, Bangladesh. Factory List: 1. Inspected by: Al-Amin Report Generated by: Al-Amin Inspected on March 7 th 2015 SUMMARY
More informationELECTRICAL SAFETY INSPECTION REPORT. MTM Garments Ltd.
ELECTRICAL SAFETY INSPECTION REPORT MTM Garments Ltd. 15934/16004, Chanpara, Medical Road, Uttarkhan, Dhaka, Bangladesh. Factory List MTM Garments Ltd. Inspected by: Hemlal Dahal Report Generated by: Hemlal
More informationELECTRICAL SAFETY FOLLOW UP INSPECTION REPORT (8th) Factory Name Address Factory ID
Factory Name Address Factory ID Shirir Chala, Bagherbazar 11705 Electrical Safety dates Initial Date 09/07/2014 30/10/2016 Date of 5 th Follow Up Report Received Date 24/08/2014 02/01/2017 Date of 6 th
More informationACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO
SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationIdentification - electrical services
Identification - electrical services Aesthetic All live phase cable sheathing to be brown coloured and neutral phase cable sheathing to be blue coloured, all labelled L1, L2, L3 & N respectively in accordance
More informationMinimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE)
PART 1: GENERAL 1.01 Telecommunications Engineer Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) B. Registered Communications Distribution Designer
More informationSAQCC FIRE D&GS TRAINING SUB COMMITTEE COURSE CURRICULUM
SAQCC FIRE D&GS TRAINING SUB COMMITTEE COURSE CURRICULUM COURSE ORIGINATOR Cabling and Conduit K Norgate DATE 23rd August 2013 Amendment 1 5th October 2013 Technical changes - Issued Amendment 2 6th October
More informationSpecification. NGTS Issue 1 October 1993
The Electrical Standards for SHE Transmission s area are non-maintained versions of National Grid Technical Specifications that are applicable to the SHE Transmission System only. These specific versions
More informationGUIDELINES FOR CABLE LAYING (PEM ELECTRICAL)
GUIDELINES FOR CABLE LAYING (PEM ELECTRICAL) DOCUMENT NUMBER: PE-GL-999-507-E002, Rev. 00 ISSUE DATE: 15.05.14 BHARAT HEAVY ELECTRICALS LIMITED POWER SECTOR PROJECT ENGINEERING MANAGEMENT NOIDA PREFACEE
More informationIECEx International Conference 2017 Shanghai, China. Electrical Installations Design, Selection, Erection and Inspection Part 2 of 2
IECEx International Conference 2017 Shanghai, China Electrical Installations Design, Selection, Erection and Inspection Part 2 of 2 10. Cable entry systems and blanking elements 10.2 Selection of cable
More information220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX
220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX JAMNAGAR 220KV CABLE NETWORK: 2 2. DESIGN 2A. NETWORK: 220 KV NETWORK DESIGN IS DESIGNED WITH 100% REDUNDANCY FROM 220 KV BUS TO LOAD. THIS IS ACHIEVED
More informationSITE All work shall be performed at Center Park Substation (1895 Kernan Blvd, Jacksonville, Fl ). DATE: 04/03/2018
DATE: 04/03/2018 TO: The Contractor FROM: System Protection & Control Projects 20413 SUBJECT: Technical Specifications for Center Park APSTF Project PROJECT OVERVIEW This is a general specification that
More informationIndyGo Facility Upgrades Project 35671EE
SECTION 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Identification for raceways. 2. Identification of power and control cables. 3. Identification for
More informationSECTION Q -- EQUIPMENT REMOVAL AND CABLE MINING
SECTION Q -- EQUIPMENT REMOVAL AND CABLE MINING CONTENTS PAGE 1. GENERAL...Q-2 1.1. Introduction...Q-2 1.2. General Requirements...Q-2 1.3. Alarm Circuits...Q-3 1.4. Disconnecting Live Circuits From Service...Q-3
More informationCambria County Association for the Blind and Handicapped 175 Industrial Park Road Ebensburg, PA Prepared for: Prepared by:
Cable Management in Solar PV Arrays: A Review of Requirements in the National Electrical Code and how CAB Cable Rings and Saddles Meet These Requirements Prepared for: Cambria County Association for the
More informationBILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School
BILOXI PUBLIC SCHOOL DISTRICT Biloxi Junior High School Request for Proposals E-Rate 2014-2015 - Internal Connections Submit Proposals To: Purchasing Department Attn: Traci Barnett 160 St. Peter Street
More informationSECTION 5900 TRAFFIC SIGNALS CITY OF LEE S SUMMIT, MISSOURI DESIGN CRITERIA
SECTION 5900 TRAFFIC SIGNALS CITY OF LEE S SUMMIT, MISSOURI DESIGN CRITERIA TABLE OF CONTENTS Section Title Page 5901 GENERAL... 2 5902 DESIGN CRITERIA... 2 5902.1 Codes and Standards... 2 5902.2 Signal
More informationRequest for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling
Request for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling Due Date: Allowable Contract Date from Posted 470 The Clarkdale- Jerome School District is requesting
More informationUser Manual. 360W LED Moving Zoom KEEP THIS MANUAL FOR FUTURE NEEDS. 36pcs10W 4 in 1 RGBW LEDs
User Manual 360W LED Moving Zoom 36pcs10W 4 in 1 RGBW LEDs KEEP THIS MANUAL FOR FUTURE NEEDS 1. Dispacking Thank you for choosing our moving head. For your own safety, please read this manual before installing
More informationInstallation Manual IPT Installation of skillet systems with 125 A track current. MV a-E.
www.wampfler.com Page 1 of 27 Index Page 1 Basics...4 2 Basic understanding of an IPT -system...5 3 General rules regarding metal parts in close proximity...6 3.1 Envelope free of ferromagnetic material...6
More informationPublic Works Division Lighting District Fiber Optic Specifications April 2009
Public Works Division Lighting District Fiber Optic Specifications April 2009 7000 Florida Street Punta Gorda, Florida 33950 Tele: 941.575.3600 Fax : 941.637.9265 www.charlottecountyfl.com/publicworks
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationLaying of cables and lines in electrical installations and data networks
Technical bulletin Laying of cables and lines in electrical installations and data networks Date: 08/2006 This technical bulletin provides you with information on specific technical subjects. It is based
More informationCover Sheet. Scanning Report of Flexible Riser Pipe Section EVI /7/2005. Inspection Report
Cover Sheet Document Number EVI-2005-0002 Document Date 7/7/2005 Document Title Customer -other- AEA Technologies Type Inspection Report Prepared by: Date: Reviewed by: Date: Approved by: Date: Evisive,
More informationSINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS
SINAMICS G130 Operating Instructions 03/2013 SINAMICS s dv/dt filter plus Voltage Peak Limiter Safety information 1 General 2 SINAMICS SINAMICS G130 Operating Instructions Mechanical installation 3 Electrical
More informationPower and Control T YPE BY RAVI GANATR November/December IAEI NEWS
Power and Control 26 1999 November/December IAEI NEWS T YPE BY RAVI GANATR This article discusses how the requirements in both the installation code and the product standard are utilized to manufacture
More informationOPERATION AND MAINTENANCE MANUAL
OPERATION AND MAINTENANCE MANUAL SERIAL NUMBER CUSTOMER: SALES REP.: CONTENTS Mixer Installation / Assembly / Dimension Drawings Safety... 1 Customer Service Contact... 1 Initial Inspection... 2 Installation...2
More informationSafety Codes Council Conference Banff C Panel Discussion
Safety Codes Council Conference Banff 2014 90 C Panel Discussion Tim Driscoll OBIEC Consulting Ltd. George Morlidge Fluor Canada Ltd. Scott Basinger Eaton Canada René Leduc Marex Canada Limited Perspectives
More information(1) These Regulations may be called PEMRA Standards for Cable Television Regulations 2003.
PEMRA Cable Television (Operations) Regulations, 2002. Pakistan Electronic Media Regulatory Authority (PEMRA) The Pakistan Electronic Media Regulatory Authority (PEMRA) is pleased to make the Standards
More informationRequest for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points
Request for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points Due Date: Allowable Contract Date from Posted 470 The Palo Verde Elementary School District is requesting
More informationCable installation guidelines
The Quality Connection Cable installation guidelines Business Unit Industrial Projects 2 Cable installation guidelines www.leoni-industrial-projects.com GENERAL Installation methods Many different methods
More informationATT-TP Common Systems Cable and Wire Installation and Removal Requirements Cable Racks and Raceways
Common Systems Cable and Wire Installation and Removal Requirements Cable Racks and Raceways This practice provides the benchmark cable installation and removal requirements for AT&T Technical Equipment
More informationINSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 FIRE PREVENTION FOR CABLES, CABLE TRAYS AND CONDUITS
CERN INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 Edms 335813 TIS IS 48 Edited by: TIS/GS Publication Date: June 2001 Original: English FIRE PREVENTION FOR CABLES, CABLE
More informationKwangil Electronic Introduction
www.kicable.com Introduction Dear Valuable customs of Kwang IL Wire & Cable Co, Inc. First of all, I d like to appreciate all the supports and cooperations given to us, and we sincerely hope all of you
More informationLighting Busway: Case Study Busway Vs Cable
Lighting Busway: Case Study Busway Vs Cable Agenda Customer Profile Customer Expectation Existing Lighting system and Problem Schneider solution Calculation Cable Vs Busway Customer Benefit Key Success
More informationAutomatic Test System AT-S + with STAR + Technology Features
AT-S + with STAR + Technology Features AT-S + offers all the known benefits of our STAR technology, now also for AC safety power sources. It is the perfect symbiosis of CEWA GUARD and STAR technology.
More informationSignalling Cable Equivalent Sizes
Signalling Cable Equivalent Sizes Signatures removed from electronic version Submitted by... Jim Harper Nominated Responsible Manager Synopsis This Standard Authorises the use of cables to GS/ES 0872 as
More informationEngineering Instruction
Engineering Instruction Electrical Distribution Unit Approved by: Paul Poynton, A/Professional Head Electrical Engineering, Sydney Trains Authorised by: Jonathon McKinnon, Engineering Technical Publications
More informationICS Digital Menu. Installation Guide Version 1.1
ICS Digital Menu Installation Guide Version 1.1 Installation Overview This document was written to assist technicians and electricians in installing the ICS Digital Menu. A thorough understanding of electrical
More informationMeeting the Challenge of a Difficult Job Speciality Contractor ACE Awards
1 Category 2: Meeting the Challenge of a Contractor: Kenny Electric Project Name: Comcast Denver Facility Upgrade No Commercial Breaks Comcast of Denver is the national hub for television and Internet
More informationTab 10 - The NESC and Underground Applications. Restricted Siemens Industry, Inc All rights reserved.
Tab 10 - The NESC and Underground Applications Restricted Siemens Industry, Inc. 2017 All rights reserved. siemens.com/poweracademy The National Electric Safety Code (NESC) The NESC provides guidelines
More informationRECOGNITION OF PRIOR LEARNING CANDIDATE APPLICATION FORM UEE30811 CERTIFICATE III IN ELECTROTECHNOLOGY - ELECTRICIAN
RECOGNITION OF PRIOR LEARNING CANDIDATE APPLICATION FORM UEE30811 CERTIFICATE III IN ELECTROTECHNOLOGY - ELECTRICIAN APPLICATION FORM MUST BE FULLY D TO PROCEED WITH THE RPL PROCESS. PLEASE ENSURE THE
More informationSQM40/41 Actuators for air and gas dampers
SQM40/41 Actuators for air and gas dampers Description SQM40/41 actuators are used for the positioning of flow control valves, butterfly valves, dampers or any application requiring rotary motion. The
More informationInstruction Manual MODEL RSP SANITARY ELECTRONIC PRESSURE TRANSMITTER
Instruction Manual Anderson Instrument Co. Inc. 156 Auriesville Road Fultonville, NY 12072 1-800-833-0081 Fax 518-922-8997 www.andinst.com Instrument Model Number Instrument Serial Number MODEL RSP SANITARY
More informationSJOF-BS604B. Fiber Optic Splice Closure User Manual Rev.1
Fiber Optic Splice Closure 1. Introduction 1.1 General SAMJIN s SJOF-BS604B protects fiber optic splicing point in various installation conditions such as aerial, manholes, ducts, wall and direct buried
More informationPreventing Fieldbus Physical Layer Problems
Preventing Fieldbus Physical Layer Problems 1 Introduction Foundation Fieldbus is highly reliable when correctly installed and maintained. The key is in knowing what must be done to start with and to maintain
More informationECS INSTALLATION OF SERVICE WAYS AND CABLES (SCHNEIDER ELECTRIC)
THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE ENGINEERING CONSTRUCTION STANDARD ECS 02-0037 INSTALLATION OF SERVICE WAYS AND CABLES (SCHNEIDER ELECTRIC) Network(s):
More information4-PROJECTOR BAR WITH 3 X 9W LEDS AND 1 X 1W FLASH LED USER GUIDE
4-PROJECTOR BAR WITH 3 X 9W LEDS AND 1 X 1W FLASH LED USER GUIDE 10482 - Version 1 / 04-2016 English LIVESET - LIVESET - 4-Projector bar with 3 x 9W LEDs and 1 x 1W Flash LED 1 - Safety information Important
More information2179-CD Series Fiber Optic Splice Closure. Installation Instructions
2179-CD Series Fiber Optic Splice Closure Installation Instructions 1.0 Product Introduction The new 3M TM 2179-CD Series Fiber Optic Splice Closure can be used in buried, underground, aerial, and pedestal
More informationMODELS USIX-024 AND USIX-120 INSTRUCTION SHEET FOR FEDERAL SIGNAL UNISTAT STATUS INDICATOR MODEL USIX
2562089B REV. B 110 Printed in U.S.A. MODELS USIX-024 AND USIX-120 INSTRUCTION SHEET FOR FEDERAL SIGNAL UNISTAT STATUS INDICATOR MODEL USIX Address all communications and shipments to: FEDERAL SIGNAL CORPORATION
More informationElectrical Installation Booklet Shipyard Standards
Marine Institute of Memorial University of Newfoundland Electrical Installation Booklet Shipyard Standards Marine Engineering Systems Design Department Revision 0 List of Revisions Revision Description
More informationHONEYWELL VIDEO SYSTEMS HIGH-RESOLUTION COLOR DOME CAMERA
Section 00000 SECURITY ACCESS AND SURVEILLANCE HONEYWELL VIDEO SYSTEMS HIGH-RESOLUTION COLOR DOME CAMERA PART 1 GENERAL 1.01 SUMMARY The intent of this document is to specify the minimum criteria for the
More informationMy Kohler Generator Installation, Model 20RESD MIKE LIZOTTE MARION, MA.
My Kohler Generator Installation, Model 20RESD MIKE LIZOTTE MARION, MA. Why Kohler Like any major purchase that I make I do a significant amount of research to ensure that I am getting a good value, high
More informationDISCLAIMER. This document is current at the date of downloading. Hunter Water may update this document at any time.
DISCLAIMER This Standard Technical Specification was developed by Hunter Water to be used for construction or maintenance of water and/or sewerage works that are to become the property of Hunter Water.
More informationNC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM
NC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM Content 1. General 5 2. The products of NC-1000 system 6 3. Mounting of the frame 8 4. Earthing of the frame 8 NC-1000 FIBRE OPTIC
More informationMetrotown Station and Exchange Upgrades
Metrotown Station and Exchange Upgrades Welcome to the Metrotown Station and Exchange Upgrade Open House Purpose of the Open House: Inform neighbours, businesses and customers about: the conceptual design
More informationMarch 4 th, Addendum No. 1. Brooklyn College Systems Integrator Broadcast Television Equipment Project No: BY019/
Facilities Planning, Construction, and Management Office of Financial Management Procurement Services 555 West 57 th Street 11 th Floor New York, New York 10019 CUNY.Builds@mail.cuny.edu March 4 th, 2013
More informationSECTION INTERCOMMUNICATIONS AND PROGRAM SYSTEMS
SECTION 27 51 23 SPEC WRITER NOTES: 1. Use this section only for NCA projects. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Contact Department of Veterans
More informationOperating Instructions Dimmer for V Incandescent Lamps
Operating Instructions Incandescent Lamps 1. Safety instructions Attention: Electrical equipment must be installed and fitted only by qualified electricians and in observance of the current accident prevention
More informationPreparing a home for TransACT fibre-to-the-premise (FTTP) services
Preparing a home for TransACT fibre-to-the-premise (FTTP) services A guide for builders, telecommunications cablers and home owners transact.com.au For more information call TransACT s FTTP Sales Manager,
More informationErrata NFPA 70. Proposed 2014 Edition
Reference: 14-1 (Log #392) CC Action Errata NFPA 70 National Electrical Code (Report on Comments) Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes the following
More informationPOLICY & APPLICATION GUIDE FOR 11kV POLYMERIC CABLES
1. SCOPE This document provides information and guidance on the application of polymeric cables on the SPEN 11kV network. Throughout this document, references to 11kV shall by inference also relate to
More informationAGENDA. NEC Code-Making Panel 16. Report on Proposal Meeting. Jan. 9-14, Hilton Head, SC
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 16 Report on Proposal Meeting Jan. 9-14,
More informationWinch Adjustable Feed Level Tubes for the Adult Turkey Feeder Installation & Operator s Instruction Manual MF /99
Winch Adjustable Feed Level Tubes for the Adult Turkey Feeder Installation & Operator s Instruction Manual MF7-8 6/99 June 999 MF7B Chore-Time Warranty Winch Adjustable Feed Level Tubes for ATF Chore-Time
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 26 0553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSample Test Project. District / Zonal Skill Competitions. Skill- Electrical Installation. Category: Construction and Building Technology
Sample Test Project District / Zonal Skill Competitions Skill- Electrical Installation Category: Construction and Building Technology Version 1 Dec 2017 Skill- Electrical Installation 1 Table of Contents
More informationUNM IT/Telecommunications Guide Specification Labeling 11/07/
Labeling 1 PART 1: GENERAL 1.01 SCOPE OF WORK A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing
More information2178-L/S Series Fiber Optic Splice Case with Gasket
2178-L/S Series Fiber Optic Splice Case with Gasket Instructions for: 2178-S Splice Case 2178-LS Splice Case 2178-LL Splice Case 2181-LS Cable Addition Kit May 1997 34-7041-9949-5-A 1 Table of Contents
More informationLighting Information
Lighting Information PLEASE NOTE THAT THE ENTIRE INVENTORY MAY NOT BE AVAILABLE FOR YOUR PRODUCTION. PLEASE CONFIRM INVENTORY WITH THE TECHNICAL DIRECTOR AT LEAST 30 DAYS PRIOR TO YOUR EVENT. Welcome to
More informationAfrican Development Bank Group
African Development Bank Group African Development Bank's Field Office in Abuja, Nigeria LOT 5A: VOL 3 - BILLS OF QUANTITIES: IT WORKS Prepared by Interstate Architects Ltd. In Conjunction with: IAA Associates
More informationCaution. Hanging the Screen:
Installation Instructions for Laminar and Laminar XL Projection Screens Caution 1. Read Instructions through completely before proceeding; keep them for future reference. Follow these instructions carefully.
More informationDragonfly Quad. User Manual V1.4. Order code: EQLED101
Dragonfly Quad User Manual V1.4 Order code: EQLED101 Safety advice WARNING FOR YOUR OWN SAFETY, PLEASE READ THIS USER MANUAL CAREFULLY BEFORE YOUR INITIAL START-UP! Before your initial start-up, please
More informationThis SOP is applicable to all WMATA personnel working on the Rail System, contractors performing the work and WMATA contractor escorts.
RFP: FQ13024/WJG CONTRACT NO. FQ13024 APPENDIX C STANDARD OPERATING PROCEDURES (SOP) SOP #33 REMOVAL AND RESTORATION OF THIRD RAIL POWER FOR WORK BY CONTRACTOR S FORCES MAINLINE, REVENUE SYSTEM PURPOSE
More informationUnlocking of building entrance door shall be possible by pressing the monitor's door-opener button.
DIGITAL COLOR VIDEO INTERCOM SYSTEM The contractor shall supply, install, test and commission a modern Electronic Digital Color Video Entry Phone System of an approved manufacturer and design to facilitate
More informationECS COMBINED CUT-OUT AND CT CHAMBER INSTALLATION
Document Number: ECS 13-0080 Network(s): Summary: ENGINEERING CONSTRUCTION STANDARD ECS 13-0080 COMBINED CUT-OUT AND CT CHAMBER INSTALLATION EPN, LPN, SPN This standard details the procedure for installing
More informationOPTEVA 828 LOBBY ATM FRONT LOAD PLAN VIEW FRONT ELEVATION SIDE ELEVATION
L0 CALL -800--600 OPTEVA 88 LOBBY ATM FRONT LOAD WITH 0mm ( 6") CEN III AND CEN IV SAFE CONSULT WITH DIEBOLD INSTALLATION/SERVICE BRANCH FOR ADDITIONAL DETAILS AND INFORMATION. PLEASE SEE PLANNING AND
More informationBuilding + Mounting Learn Rooftop Basics
Building + Mounting Learn Rooftop Basics A Build-It-Ourselves Guide to Wireless Mesh Networks 1 Introduction This module provides helpful tips for installing wireless equipment on rooftops. It should be
More informationR OPTEVA 868 THROUGH THE WALL ATM. 305mm (12") MAXIMUM WALL THICKNESS IN AREA OF UNIT OUTLINE OF OPTIONAL ILLUMINATED SIGNAGE PANEL
OPTEVA 868 THROUGH THE WALL ATM WITH 40mm ( 6") CEN III AND CEN IV SAFE L0 CALL -800--600 0 (6") REQUIRED FOR WALLS EXCEEDING 0mm (2") CONSULT WITH DIEBOLD INSTALLATION/SERVICE BRANCH FOR ADDITIONAL DETAILS
More informationISS New Audio & Visual installations Design and Physical install guidelines v1.5
ISS New Audio & Visual installations Design and Physical install guidelines v1.5 David Neal 11/05/2018 Contents Background... 3 Installation Standards... 3 Display Screen and Projector positioning... 3
More informationFORENSIC CASEBOOK. By Bob Huddleston, Eastman Chemical Co. One of the most common. reasons for marriage failure
The Case of the Energized Cable Cutting Incident How miscommunication leads to an electrical helper slicing through live 13.8kV cable and miraculously walking away to tell about it By Bob Huddleston, Eastman
More informationSchedule of Rate for Electrical Items Name of work:- Supplying of electrical items for day to day electrical maintenance work.
Page 1 of 15 Schedule of Rate for Electrical Items Name of work:- Supplying of electrical items for day to day electrical maintenance work. 1 1.5 sq mm multistrand single core PVC copper conductor cable.
More informationRequest for Proposal, 15MCO503 VIDEO VISITATION Date Required: Thursday, Jun 4, 2015 Time Required: 3:00 PM Local Time
Request for Proposal, 15MCO503 VIDEO VISITATION Date Required: Thursday, Jun 4, 2015 Time Required: 3:00 PM Local Time The following document contains questions submitted by Prospective Bidders and the
More informationHARMONIZATION OF SYNOPTIC BLOCK DIAGRAMS ON THE CONTROL PANELS OF MV SWITCHGEAR AND CONTROLGEAR
HARMONIZATION OF SYNOPTIC BLOCK DIAGRAMS ON THE CONTROL PANELS OF MV SWITCHGEAR AND CONTROLGEAR Yvan L. Tits ELECTRABEL 8, Boulevard du Régent, B-1000 Brussels (Belgium) Tel: +32 2 518 62 66 - Fax: +32
More informationVibratory Deck Sieves 15 in. (380 mm)
Instruction Sheet P/N 1604433-01 Vibratory Deck Sieves 15 in. (380 mm) Introduction This instruction sheet covers the vibratory deck sieves listed in the following tables. 15-Inch Deck Sieves with 2.5
More informationR OPTEVA 868 THROUGH THE WALL ATM. 305mm (12") MAXIMUM WALL THICKNESS IN AREA OF UNIT OUTLINE OF OPTIONAL ILLUMINATED SIGNAGE PANEL
OPTEVA 868 THROUGH THE WALL ATM WITH mm ( 2") CEN-L SAFE L00 CALL -800-999-600 22 (9 6") REQUIRED FOR WALLS EXCEEDING 0mm (2") CONSULT WITH DIEBOLD INSTALLATION/SERVICE BRANCH FOR ADDITIONAL DETAILS AND
More informationEXISTING/DEMOLITION MECHANICAL PLAN DRAWING KEYED NOTES: 1065 S. MAIN ST. BLDG D STE. A LAS CRUCES, NM 88005 (575) 647-1554 FAX (575) 647-1563 rbm@rbm.cc PROJECT NO.: 12121L CAD DWG FILE: DRAWN BY: CHECKED
More informationSection Communications Optical Fiber Backbone Cabling
Part 1 1.1 Related Documents 1.1.1 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections apply to this Section. 1.2 Related
More informationTechnical Specifications
INSTALLATION SHEET AND OPERATORS MANUAL General Description: The is a mixer/preamplifier that includes 6 channels that each include a microphone input at screw terminals and an aux input at an RCA jack.
More informationCLF Manuals CLF Colour Par CLF Colour 12 Par CLF Colour Par 12 Version 1.0 November 2012 Version 1.0 1
CLF Manuals CLF Colour Par 12 CLF Colour Par 12 Version 1.0 November 2012 1 1.BEFORE YOU BEGIN What is included Ø 1 x Fixture Ø 1 x Power cable with plug Ø 1 x User Manua Unpacking Instructions Immediately
More informationDMX LED light effect with 4 lenses
DMX LED light effect with 4 lenses User manual 1 Safety precautions WARNING: This unit may cause serious injury to the eyes when used incorrectly. It is therefore strongly advised to read this user manual
More informationB2590/65SNZ. Crank-Up. Installation & Operation Instruction Manual NZ Iss 1
B2590/65SNZ Crank-Up Installation & Operation Instruction Manual 9111410NZ Iss 1 Useful Information Date of Purchase Retailer Installer Serial Number Contents Warranty P3 Safety Precautions P4 Introduction
More informationINSTALLATION INSTRUCTIONS FOR. MODEL 2230LED
INSTALLATION INSTRUCTIONS FOR MODEL 2230LED www.sportablescoreboards.com 1 Table of Contents MODEL 2230LED... 3 8 X 4 INDOOR SCOREBOARD... 3 THE SCOREBOARD SYSTEM SHOULD INCLUDE THE FOLLOWING PARTS:...
More informationDraft for Public Comment
Draft for Public Comment Form 36 Version 6.1 DPC: 03/302646 DC Head Office 389 Chiswick High Road London W4 4AL Telephone: +44(0)20 8996 9000 Fax: +44(0)20 8996 7001 Date: 27 March 2003 Origin: National
More informationUSER MANUAL Table of Contents
USER MANUA Table of Contents Safety Information. 3 Specifications.. 4 Main Power Connection.. 5 DMX-512 Connection...... 5 DMX Profile... 7 Main Control Menu... 8 Rigging the Fixture.10 Cleaning & Maintenance...10
More information4 Wiring Brochure Wiring and installation of specific control
- Wiring Brochure tekmarnet 4 User Switch 480 W 480 09/09 1 Information Brochure Choose controls to match application 2 Application Brochure Design your mechanical applications 3 Rough In Wiring Rough-in
More informationCity of Winter Springs, FL
City of Winter Springs, FL Request for Quote RFQ/006/17/LS Commission Chambers Audio Visual System Upgrades The City of Winter Springs will be upgrading its Commission Chambers (Chambers) audio visual
More informationTABLE OF CONTENTS FOREWORD... 3 INTRODUCTION SCOPE NORMATIVE REFERENCES... 4
TITLE SPECIFICATION FOR DANGER AND DATE: NOVEMBER 2006 PAGE: 1 OF 13 TABLE OF CONTENTS Page FOREWORD... 3 INTRODUCTION... 4 1 SCOPE... 4 2 NORMATIVE S... 4 3 WARNING TAPE... 4 3.1 Material... 4 3.2 Size...
More informationVGAD-12 ORDERCODE
VGAD-12 ORDERCODE 101220 Congratulations! You have bought a great, innovative product from DMT. The DMT Media Spinner brings excitement to any venue. Whether you want simple plug-&-play action or a sophisticated
More informationCOMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More information