1 REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus PART 1: GENERAL REQUIREMENTS A. Contractor Work 1. Provide and install (except as noted in this document), cable, connectors, wall plates, terminators, pull boxes, patch panels, racks/brackets, etc. and all other items necessary for a complete working data/communications system. All work by the Contractor will be in accordance and compliance with the practices set forth in TIA/EIA-568-A Commercial Building Telecommunications Cabling Standard, Oct Ensure timely cleanup of all facilities and buildings related to this project, during construction and at completion. 3. Provide for the certification of s 15 year manufacturer warranty on all equipment installed. NOTE: Final number of drops is subject to change from the attached drawings; MTC Project Manager will give one week notice of any changes prior to beginning of work. B. Drawings Maintain a clean set of Blueline Contract Documents on site at all times and note any deviations in installation on a day-to-day basis. The markup set will serve as As-Built Drawings and will be turned over to MTC at final inspection. C. Documentation Provide documentation including but not limited to a detailed punch down list for all horizontal and backbone cabling. D. Contractor Qualifications and Response The following must be provided by each potential contractor with the bid package. Any portion not included will be cause for possible elimination from the bid process. 1. Contractor must show proof of having at least one (1) BICSI Registered Communications Distribution Designer (RCDD) on staff. Current certification number must also be provided.

2 2. Contractor must show proof of a certified installer on staff. Copy of certification must be provided. Contractor must be able to certify the completed project and provide for the 15 year manufacturer warranty of equipment and Category 6 compliance.

3 PART 2: MATERIALS AND EQUIPMENT All equipment will be provided by the contractor except as noted. Please see below for a list of acceptable parts. All parts not on the list must be approved by the MTC Project Manager. Each communication workstation location, except as noted otherwise, will utilize the following equipment. 1. Faceplates Faceplates must have label strips and clear label strip plastic covers top and bottom. All empty spaces on the faceplate will be filled with a blank as specified in this document. Acceptable products: Products Manufacturer Part Number Color Single Gang (Two Port) IFP12OW Office White Single Gang (Six Port) IFP16OW Office White 2. Modular Category 6 Jacks Application Manufacturer Part Number Color Classroom Runs HXJ6GN Green MDF/IDF Runs HXJ6BK Black NOTE: All jacks will be terminated using a single position 110 punch down tool. Stuffer caps will be affixed after termination has been effected, in order to provide strain relief to each conductor at the point of termination. 3. Face plate blanks Product Manufacturer Part Number Color Blanks (10-pack) SFB10 Office White 4. Fiber Connectors Product Manufacturer Part Number Color FSP Adapter Panel LC FSPLCDS12Y Yellow Duplex - SM

4 FSP Adapter Panel LC Duplex OM4 MM FSP Adapter Panel LC Duplex OM4 MM for Classroom Cabinet FSP Adapter Panel Blank FSPLCDS12AQ Aqua FSPLCDS3AQ Aqua FSPB 5. Floor Box Plates Product Manufacturer Part Number Color Integration Module HWM2KGY10 (10 Pack) Gray0 6. Optical Fiber Cabinets (LIU) Product Manufacturer Part Number Color Rack Mount FCR525SPR Enclosure 3 RU Rack Mount FCR350SP36R Enclosure 2 RU Hinged Rack Mount Panel FPR3SP 7. Patch Panels Patch Panels for the Data Distribution Cables will be Category 6, T568A, preloaded, with 110 connection blocks on the rear and 8 position modular jacks on the front. Panels will be mounted on Relay Racks or Wall Mount Brackets as specified herein. Manufacturer Part Number P6E48U 8. Relay Racks Where indicated a 7 rack will be provided and installed for mounting patch panels, concentrators, and other equipment. Each 7 rack will be securely bolted to the floor and wall mount racks will be bolted to the plywood backboard provided. Additional cable management devices, shelves, and other accessories will be provided where specified by the MTC Project Manager.

5 Manufacturer Acceptable Wall/Rack mount kit Part Number CS1976 HLWRK 9. Classroom Cabinets 12U rack unit 21 W (19 rack width) x 24 H x 24 D locking, swinging cabinet with smoke plexiglass door, mounted to the backboard. Manufacturer Rack Technologies Part Number RMW-RT12-WC Horizontal Cable All Horizontal cable designated as Category 6 (Cat6) on the Drawings will be plenum-rated Category 6 Unshielded Twisted Pair (UTP), 24 AWG with solid copper conductors. The Horizontal cable will run from the station jack to the appropriate cross-connect in the telecommunications closet. The length of each Horizontal cable run will not exceed 275 feet. Runs that exceed this must be brought to the attention of the MTC Project Manager for resolution prior to the cable being pulled. Only plenum rated Category 6 cable will be used in the installation. Cable color is BLUE. All Horizontal cable on this project will be from the same manufacturer. Note: A data sheet is required (see Part 2 - Materials, A. & B.) which verifies that all cables submitted meet the cable specification criteria set forth here. Do not submit cable for consideration that does not meet these standards. Acceptable Manufacturers: General, Essex, Mohawk

6 PART 3: INSTALLATION 1. FIBER OPTIC CABLE All fiber terminations will be LC. Entrance fiber: Provide (48) strands of Multimode OM4 fiber optic cable and (48) strands of Single mode fiber optic cable from Richland Hall room 101 and the MDF, located in room 016. Riser fiber: Provide (24) strands of Multimode OM4 fiber optic cable and (24) strands of Single mode fiber optic cable from the MDF (room 016) to the IDF for each floor. Classroom cabinets: Provide (6) strands of Multimode OM4 fiber optic cable from each classroom cabinet (as indicated on the drawings) to the MDF/IDF for that floor, and (6) strands of multimode OM4 from room 136 to the IDF. Fiber optic cable runs through the cable tray must use plenum rated cable. 2. STATION JACK INSTALLATION FLUSH MOUNT Station jacks will be installed on the wall in an electrical outlet box or in an MP-2 type caddy as specified on the drawings. Use existing boxes installed by the general contractor. 3. HORIZONTAL CABLE All cable runs installed will be continuous without splices, bridges or any other connecting device between origination and termination points, except for runs through buried conduit to outdoor locations. Bridge points for burial cable must be identified and approved through MTC Project Manager prior to installation. All terminations in patch panels and punch down blocks will be done in a sequential manner based on room and will comply with all EIA/TIA 568-A specifications. A detailed punch list will be provide for all terminations.

7 The contractor will provide a 4-pair Category 6 cable from the appropriate MDF or IDF closet to each Category 6 modular jack as indicated on the drawings. Each cable will be labeled with the unique destination room number 4 to 12 from the end of the termination point in the telecommunications closet. Cables will be terminated in a CAT 6, 568A patch panel as specified in this document. 4. CABLE INSTALLATION REQUIREMENTS All cable installation and termination must comply with the provisions in TIA/EIA 568-A. The Contractor will submit a sample of assembled cable, connectors, raceway and accompanying specification sheets prior to installation for approval of quality, workmanship and materials. For all Category 6 cabling, maintain cable twist-rate at all termination points. The amount of cable untwist will be no more than 1/2. Do not strip back the cable jacket any more than is necessary to terminate the individual conductors. All 110 connections will be installed using a single 110 punch down tool and all terminations will be trimmed flush with connector blocks. Leave enough cable (approximately 1 foot at the workstation & 3 feet at the backboard or rack, unless specified elsewhere in this document) to allow easy termination of the cable. Install or use existing vertical cable management panels for all floor-mounted racks. Do not install horizontal cable management trays in the racks. All vertical drops of cable in rooms will be inside the walls except where specifically noted on drawings. Any exceptions to this must be submitted in writing to the MTC Project Manager five working days prior to scheduled date and will be subject to MTC approval. Horizontal cable that runs outside the walls will be installed in Mediatrax. Cable runs in hallways and corridors will be bundled neatly together; use cable trays where available. Tie wraps and J-hooks may be used to keep cables together. All plastic type molding, conduit, cable trays and raceways must be anchored to the wall with the appropriate type of wall screw and bracket every five (5) feet. All changes in cable direction will be at 90 degrees. All penetrations will be sleeved and fire stopped in accordance with National Fire Protection Agency (NFPA) and Standard Building codes. Fire stop material must be UL listed. Cables will not be tie wrapped to electrical or gas lines.

8 D-rings will be provided and mounted to route the horizontal cables at the backboard locations. Enough cable slack will be provided to neatly route the horizontal cable through D rings to the appropriate 110 type block. No circuit will be run in the same conduit or raceway with power conductor. Installation of the cable will be in accordance with the marked floor plan. All deviations to the cable route will be submitted in writing to the MTC Project Manager five working days prior to scheduled date and will be subject to approval by MTC. For classrooms in which a backboard is mounted, all drops designated as classroom drops will terminate in a CAT6 patch panel installed in this cabinet (Contractor to provide, specified above). Note that a number of drops in each room are designated for home runs to the MDF/IDF. For each drop marked on the floor plan, multiple cable counts will be noted with a number. Typical counts per location are as follows: o Standard wall drops: (2) CAT6 cables/jacks, black jack color o Classroom wall drops: typically (2-4) CAT6 cables/jacks, green jack color o Floor boxes: typically (4) CAT6 cables/jacks, black jack color. Please take note of counts to floor boxes on the main library open areas on second and third floors cable counts vary and some boxes will be completely unused. o 44 high emergency/courtesy telephones: (1) CAT6 cable/jack, black jack color o IP cameras: (2) CAT6 cables/jacks per outdoor camera, (1) cable/jack per indoor camera, black jack color o Classroom wireless access points: (3) CAT6 cable/jacks, black jack color o Hallway wireless access points: (1) CAT6 cable/jack, black jack color o Outdoor emergency callboxes: (2) CAT6 cables/jacks, plus (1) shielded 24 AWG stranded single pair cable for 24V electrical power. Burial grade cable must be used. Cable routing will follow the dictates of the design while avoiding locations of high RFI/EMI radiation or adverse environmental conditions. 5. CABLE TESTING a. Contractor will provide all necessary testing equipment to test all cables. Testing will be performed immediately following the completion of all pulls and terminations.

9 i. Each Category 6 cable terminating in a station jack will be tested from the telecommunications closet with a 4-pair wire tester. The tester will verify continuity, faults, reversals, swaps and pairing. ii. Each Category 6 cable link will also be tested for near-end and far-end crosstalk and attenuation up to and including 300 Mhz and will be verified for acceptable length and proper wire map, in accordance with TSB-67. iii. Each fiber strand including connectors will be tested from end-to-end to measure the total loss or attenuation. Losses on terminated fibers will meet or exceed all EIA/TIA 568 specifications. iv. A hard copy of the test results for each cable run will be provided to MTC. Acceptable test results will be agreed upon by MTC Project Manager and Contractor prior to testing. It is the Contractor s responsibility to replace, repair, re-terminate, or modify any cable run which tests outside the agreed-upon ranges, in such a manner as to be acceptable to MTC. b. Before the system is accepted by MTC, the Contractor will be required to walkthrough the installation with the MTC Project Manager and Network Team members and verify proper installation and conformance to specifications, drawings, and other agreed upon, written details. All cable-related documentation and As-Built Drawings will also be required for review purposes at this time.

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017 Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM-2017-2 Date: 05/26/2017 Additional specification information for data communication to cameras and between Library

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors including patch panels. 3. Cabling identification

More information

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE Prepared in cooperation and approval from BICSI Building Industry Consulting Services International and

More information

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School BILOXI PUBLIC SCHOOL DISTRICT Biloxi Junior High School Request for Proposals E-Rate 2014-2015 - Internal Connections Submit Proposals To: Purchasing Department Attn: Traci Barnett 160 St. Peter Street

More information

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1. PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

CABLING STANDARDS FOR

CABLING STANDARDS FOR RFB for Wiring in the Outagamie County Courtrooms Attachment B September 1, 2016 CABLING STANDARDS FOR GENERAL The purpose of this document is to provide guidelines for all structured cable installations

More information

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents PART 1 - GENERAL 1.1 SUMMARY SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors. 3. Cabling system identification products. 1.2

More information

A. All communications equipment rooms shall be installed in a neat and workmanlike manner.

A. All communications equipment rooms shall be installed in a neat and workmanlike manner. SECTION 27 11 00 - COMMUNICATIONS EQUIPMENT ROOM FITTINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

STRUCTURED CABLE SYSTEM (SCS)

STRUCTURED CABLE SYSTEM (SCS) PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE)

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) PART 1: GENERAL 1.01 Telecommunications Engineer Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) B. Registered Communications Distribution Designer

More information

SECTION FIBER OPTIC STATION CABLES

SECTION FIBER OPTIC STATION CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications shall include all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION PART 1 - GENERAL 1.1 SUMMARY SCOPE SECTION 25170 TESTING, IDENTIFICATION AND ADMINISTRATION 1. This section includes the minimum requirements for the testing, certification administration and identification

More information

Request for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling

Request for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling Request for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling Due Date: Allowable Contract Date from Posted 470 The Clarkdale- Jerome School District is requesting

More information

Follow The Leader In Shielded Technology

Follow The Leader In Shielded Technology 1970s Vampire Tap 1990s Shielded Modular Jack 190s 4 Position Data Connector Follow The Leader In Shielded Technology The new AMP-TWIST Jack is our latest shielded product evolution. It can be terminated

More information

APPENDIX A Verify All Part Numbers (Partial List of Approved Products)

APPENDIX A Verify All Part Numbers (Partial List of Approved Products) SECTION 16651 APPENDIX A Verify All Part Numbers (Partial List of Approved Products) SYSTIMAX SCS: OVER-VOLTAGE PROTECTION 1. Over-voltage Protection Device, 100-Pair with Enclosure, Product 489ACAI-100,

More information

Liberty Mutual Structured Cabling Specification Bid and Build Structured Cabling Technical Specification for:

Liberty Mutual Structured Cabling Specification Bid and Build Structured Cabling Technical Specification for: Bid and Build Structured Cabling Technical Specification for: Horizontal & Backbone Requirements Page 1 of 30 PUBLICATION RECORD Document Version Publication Date Primary Author Description Revision 1.0

More information

B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines.

B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines. PART 1 - GENERAL 1.1 SUMMARY A. This section includes: 1. Support Structures 2. Cable trays and ladder rack 3. Racks (including wire managers) 4. Cables (copper and optical fiber) 5. Jacks and faceplates

More information

Section Communications Optical Fiber Backbone Cabling

Section Communications Optical Fiber Backbone Cabling Part 1 1.1 Related Documents 1.1.1 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections apply to this Section. 1.2 Related

More information

Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5

Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5 Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5 1.0 INTRODUCTION Customer to define background and introduction to the project based on

More information

Technical Specifications Florida Gulf Coast University

Technical Specifications Florida Gulf Coast University Technical Specifications Florida Gulf Coast University 9/19/2018 Page 1 of 21 Approved Vendors (alphabetical order) Aztek (CIP) Certified Installer Plus Mr. Scott Coyne 4730 Enterprise Avenue Suite #308

More information

Preferred ordering guide for NETCONNECT

Preferred ordering guide for NETCONNECT Preferred ordering guide for NETCONNECT MEA Region Contents Copper solutions Category 6A products 3 Category 6A and Category 7 shielded copper cables 3 Category 6A modular shielded panels 3 Category 6A

More information

Brown University. Communications Standard Parts List

Brown University. Communications Standard Parts List CIS - NTG Brown University Communications Standard Parts List All data installations must receive the 25-year Mission Critical Warrantee from Hubbell Premise Wiring. All fiber installations must receive

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 - GENERAL 1.1 SECTION

More information

Request for Proposal (RFP)

Request for Proposal (RFP) Request for Proposal (RFP) Data Network for OCMS 017 Inquiries and requests regarding this RFP should be directed to: Michael Hale Technology Director Oconee County Schools PO Box 16 5-A School Street

More information

Information Technology Services DESIGN AND INSTALLATION STANDARDS

Information Technology Services DESIGN AND INSTALLATION STANDARDS Requirements and Guidelines for: New Construction, Renovations, Upgrades, and Retrofits. Revised: June 5, 2015 VIU ITS Network Services 2 TABLE OF CONTENTS 0 GENERAL... 5 1 FIBER OPTIC CABLING... 5 1.1

More information

Telecommunication Infrastructure Project September 20, 2002

Telecommunication Infrastructure Project September 20, 2002 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Category rated UTP systems shall be provided and tested in accordance with the performance level established in Specification

More information

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED.

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED. Beaverton School District Capital Program Purchasing 16550 SW Merlo Road, Beaverton, OR 97006 Phone: 503-591-4539 SOLICITATION ADDENDUM NO. 1 ITB 15-0012 THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION

More information

Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING

Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING Revision 05/01/2017 Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING PART 1 GENERAL 1.1 SECTION INCLUDES A. Voice, Data, and Fiber Cable Product materials B. Voice, Data, and Fiber Cable Execution

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 27 15 00 COMMUNICATIONS HORIZONTAL CABLING PART 1 GENERAL 1.1 RELATED DOCUMENTS AND SECTIONS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SPECIAL SPECIFICATION 8540 Telecommunication Cable

SPECIAL SPECIFICATION 8540 Telecommunication Cable 2004 Specifications CSJ 0914-00-307 & CSJ 0914-25-003 SPECIAL SPECIFICATION 8540 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing,

More information

Request for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points

Request for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points Request for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points Due Date: Allowable Contract Date from Posted 470 The Palo Verde Elementary School District is requesting

More information

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017 SECTION 27 15 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Connected Solutions. April $ Post, 19 Rack ELERK1FR BK

Connected Solutions. April $ Post, 19 Rack ELERK1FR BK Connected Solutions April 2018 $30.97 Punch & Go Tool ONQAC3400 $139.97 per 305M Category 6 Riser, UTP, 23 AWG, Blue 305 Meter/1000 FT Pull Box CAB24/4PS6FT4BLUHYP $137.97 2 Post, 19 Rack ELERK1FR1194400BK

More information

SPECIAL SPECIFICATION 6559 Telecommunication Cable

SPECIAL SPECIFICATION 6559 Telecommunication Cable 2004 Specifications CSJ 0015-09-147, etc. SPECIAL SPECIFICATION 6559 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing, training,

More information

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project 1.1.0 GENERAL The purpose of this specification is to establish a requirement for the installation of a voice, video and data cable network. The cable (copper), wire, hardware, equipment racks, jumpers,

More information

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT Purchasing and Warehouse Services Department October 1, 2007 Addendum No. 1 INVITATION FOR BID No. 08-09 Temporary Faculty Offices, Chabot College All Prospective

More information

Request for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS

Request for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS VOFP Cabling RFP 1 Request for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS For The Village of Franklin Park 2014 VOFP Cabling RFP 2 TABLE OF CONTENTS I. PROJECT DESCRIPTION

More information

SECTION 7 -- CROSS-CONNECT SYSTEMS

SECTION 7 -- CROSS-CONNECT SYSTEMS DETAIL ENGINEERING REQUIREMENTS AT&T March, 2016 Section 7, ATT-TP-76400 Revised NA SECTION 7 -- CROSS-CONNECT SYSTEMS CONTENTS PAGE 1. GENERAL... 7-2 1.1. Introduction... 7-2 1.2. Cable Holes... 7-2 1.3.

More information

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices Berk-Tek recommends installing a well-designed structured cabling channel per the TIA standards. This includes up to 100

More information

C. Link offers a standard 1-year warranty on all parts and labor. Manufacturer's warranty is available for larger projects.

C. Link offers a standard 1-year warranty on all parts and labor. Manufacturer's warranty is available for larger projects. DIR-SDD-1898 Cabling Services and Related Products C. Link offers a standard 1-year warranty on all parts and labor. Manufacturer's warranty is available for larger projects. Please address all returns

More information

DESIGN!!GUIDELINES!!!!!

DESIGN!!GUIDELINES!!!!! DESIGNGUIDELINES 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 1. Testing General 1.1. For acceptance, 100% of the media

More information

DATA/TELECOMMUNICATIONS REQUEST FOR PRICING

DATA/TELECOMMUNICATIONS REQUEST FOR PRICING Category 6A 10Gig DATA/TELECOMMUNICATIONS REQUEST FOR PRICING TABLE OF CONTENTS 1. GENERAL 3 1.1. Work Included... 3 1.2. Scope of Work... 3 1.3. Regulatory References... 4 1.4. Quality Assurance... 4

More information

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008 Information & Communications Technology Group Standards June 2008 Appendix F UTP cabling Version 1.1 Appendix F UTP cabling 1. Introduction This Section details the required standards for Unshielded Twisted

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION TELECOMMUNICATIONS SYSTEM INFRASTRUCTURE

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION TELECOMMUNICATIONS SYSTEM INFRASTRUCTURE PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. The intent of this standard is to describe the requirements of the telecommunications system infrastructure. Part of this system is the responsibility

More information

DS1 Cross-Aisle Panel

DS1 Cross-Aisle Panel DS1 Cross-Aisle Panel Model 005-0005-0100 Installation Guide 1.1 Overview 1.1.1 Inspection Compare the contents of the DS1 Cross-Aisle Panel shipping container with the packing list. Call Telect if anything

More information

Mfgr. Berk Tek ea , Berk Tek ea , Berk Tek ea. Berk Tek ea ,350.

Mfgr. Berk Tek ea , Berk Tek ea , Berk Tek ea. Berk Tek ea ,350. 8. Pricing Schedule The undersigned has rd and understands all conditions and terms of RFP 336-, is authorized to submit this proposal on behalf of the company, and hereby offers to perform the services

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Family Health Centers, Inc. Request for Proposal. for. Family Health Centers East Broadway Data and Communications Cabling Project

Family Health Centers, Inc. Request for Proposal. for. Family Health Centers East Broadway Data and Communications Cabling Project Family Health Centers, Inc. Request for Proposal for Family Health Centers East Broadway Data and Communications Cabling Project Date Issued: 06/07/2014 Date Due: 06/16/2014 Page 1 of 22 Table of Contents

More information

ADDENDUM NO. 2 This addendum consists of 8 pages. Kenai Peninsula Borough Purchasing & Contracting

ADDENDUM NO. 2 This addendum consists of 8 pages. Kenai Peninsula Borough Purchasing & Contracting KENAI PENINSULA BOROUGH Purchasing and Contracting 144 North Binkley Street Soldotna, Alaska 99669-7520 Toll-free within the Borough: 1-800-478-4441, Ext. 2260 PHONE: (907) 714-2260 FAX: (907) 714-2373

More information

THE OHIO STATE UNIVERSITY COMMUNICATIONS WIRING STANDARD

THE OHIO STATE UNIVERSITY COMMUNICATIONS WIRING STANDARD THE OHIO STATE UNIVERSITY COMMUNICATIONS WIRING STANDARD The objective of the standard wiring plan for the University is to provide an acceptable outlet for any communication device that requires connection

More information

Project No. # Page 1

Project No. # Page 1 PART 1 - GENERAL This section of the has references, products, procedures, processes, and work descriptions/summaries that are common to many Washington State University Pullman (WSUP) campus telecommunications

More information

HighBand 25. TrueNet Category 6 Solutions

HighBand 25. TrueNet Category 6 Solutions HighBand 25 TrueNet Category 6 Solutions The highest performing cross-connect system in the world. A unique high-density solution with superior cable management. ADC KRONE s HighBand 25 cross connect solution

More information

Cable Installation Tips

Cable Installation Tips Cable Installation Tips Campus Network Design & Operations Workshop These materials are licensed under the Creative Commons Attribution-NonCommercial 4.0 International license (http://creativecommons.org/licenses/by-nc/4.0/)

More information

Cable Installation Tips

Cable Installation Tips Cable Installation Tips Campus Network Design & Operations Workshop These materials are licensed under the Creative Commons Attribution-NonCommercial 4.0 International license (http://creativecommons.org/licenses/by-nc/4.0/)

More information

1.0 GENERAL. 1.2 SUMMARY.1 Section Includes:

1.0 GENERAL. 1.2 SUMMARY.1 Section Includes: 1.0 GENERAL 1.1 DOCUMENTS.1 This section of the Specification forms part of the Contract Documents and is to be read, interpreted, and coordinated with all other parts. 1.2 SUMMARY.1 Section Includes:

More information

Telecommunciations Infrastructure Project September 20, A. Broadband radio frequency active and passive components

Telecommunciations Infrastructure Project September 20, A. Broadband radio frequency active and passive components PART 1 - GENERAL 1.1 SECTION INCLUDES A. Broadband radio frequency active and passive components B. Broadband optical active and passive components C. Coaxial cable and connectors D. Support and termination

More information

A. PERFORMANCE REQUIREMENTS

A. PERFORMANCE REQUIREMENTS A. PERFORMANCE REQUIREMENTS 1. Description: a) General: Provide for a complete (furnish and install) EIA/TIA 568-B.2-1 Category 6 Premise Distribution System (PDS) with all accessories and a minimum 25-year

More information

SECTION TESTING OF COPPER CABLES

SECTION TESTING OF COPPER CABLES SECTION 27 08 13 TESTING OF COPPER CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction,

More information

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project 1.1.0 GENERAL MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project The purpose of this specification is to establish a requirement for the installation of

More information

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

blackbox.com/connect The smart choice when price matters most. Need help? Talk to a Black Box cable expert 24/7 at

blackbox.com/connect The smart choice when price matters most. Need help? Talk to a Black Box cable expert 24/7 at blackbox.com/connect The smart choice when price matters most. Need help? Talk to a Black Box cable expert 24/7 at 877-877-2269 The Black Box quality you've come to expect. In stock. Ships today. The smart

More information

Belden IBDN System 10GX 10GX Modules and 10GX Patch Panels

Belden IBDN System 10GX 10GX Modules and 10GX Patch Panels C O M M E R C I A L N E T W O R K I N G C O P P E R 5.6 Belden IBDN System GX GX Modules and GX Patch Panels AX2272 GX Module, Black GX Module The GX Module is a revolutionary punch down UTP connector

More information

IP-LINX. Installation Guide

IP-LINX. Installation Guide Installation Guide Installation Guide, 146653-4 Copyright 2017, Telect, Inc. All Rights Reserved Telect and Connecting the Future are registered trademarks of Telect, Inc. 22425 East Appleway Ave. # 11

More information

Best Friends General Trading FZE

Best Friends General Trading FZE Welcome to Best Friends General Trading FZE Tel. +97 1 50-5426 202, Fax. +971 6 7407428, info@bestfgt.com, besttrd@eim.ae Infrastructure Product Guide Best fgt is UAE based company, operational for last

More information

Structured Cabling Introduction & Installation Guide

Structured Cabling Introduction & Installation Guide Structured Cabling Introduction & Installation Guide Structured Cabling Overview General Structure - Cat5e/Cat6 Cabling The structure illustrated has the following key points: Face plates present outlet

More information

24-Fiber LANLINXS (Model # ) 48-Fiber LANLINXS (Model # ) User Manual

24-Fiber LANLINXS (Model # ) 48-Fiber LANLINXS (Model # ) User Manual 24-Fiber LANLINXS (Model # 055-8632-5000) 48-Fiber LANLINXS (Model # 055-8832-5000) User Manual 24-Fiber LANLINXS (Model # 055-8632-5000) 48-Fiber LANLINXS (Model # 055-8832-5000) User Manual, Part Number

More information

Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab*

Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab* Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab* General Scope of Work: Supply and installation of Computer Laboratory setup in MIU Location of Installation:

More information

6000 Series Patch Panel Terminating Instructions

6000 Series Patch Panel Terminating Instructions 6000 Series Patch Panel Terminating Instructions INTRODUCTION The 6000 Series patch panels include a unique feature not found on any other patch panel. This feature allows you to angle each of the four

More information

WJHW, Inc. 6 April 2016 Texas Tech University Issue for CD Set Sports Performance Complex Lubbock, Texas

WJHW, Inc. 6 April 2016 Texas Tech University Issue for CD Set Sports Performance Complex Lubbock, Texas SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide materials, labor, and methods for telecommunications grounding and bonding system in accordance with

More information

SECTION TELECOMMUNICATIONS INFRASTRUCTURE

SECTION TELECOMMUNICATIONS INFRASTRUCTURE PART 1 - GENERAL 1.1 SUMMARY A. The telecommunications (telecom) infrastructure provides the basic infrastructure for the transport of voice and data signals throughout the facility. This is often regarded

More information

Description: Pair Color Code Chart: Pair Color Chart 1 Brown White Brown 2 Orange White Orange 3 Green White Green 4 Blue White Blue.

Description: Pair Color Code Chart: Pair Color Chart 1 Brown White Brown 2 Orange White Orange 3 Green White Green 4 Blue White Blue. Description: OZLINX CAT5e cable has a guaranteed performance; exceeds the Category 5e performance requirements and provides positive PSACR up to 155MHz for bandwidth requirement in the future. Product

More information

Optical Distribution Box 300 Installation Guide. Version : R0.0

Optical Distribution Box 300 Installation Guide. Version : R0.0 Optical Distribution Box 300 Installation Guide Document No. : OD16-546-L-01 Version : R0.0 Date: 21-Mar-2018 IMPORTANT INSTRUCTIONS When using fiber optic equipment, basic precautions should always be

More information

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0553 Identification for Communications Systems

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0553 Identification for Communications Systems 1 General 1.1 Scope of work 1.1.1 The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the completion of

More information

C6 A modul and C6 A modul K. The new connection system for a wide variety of applications of course with Cat.6 A

C6 A modul and C6 A modul K. The new connection system for a wide variety of applications of course with Cat.6 A C6 A modul and C6 A modul K The new connection system for a wide variety of applications of course with Cat.6 A Intelligent system solution for structured cabling Nowadays the need for high data transfer

More information

Public Works Division Lighting District Fiber Optic Specifications April 2009

Public Works Division Lighting District Fiber Optic Specifications April 2009 Public Works Division Lighting District Fiber Optic Specifications April 2009 7000 Florida Street Punta Gorda, Florida 33950 Tele: 941.575.3600 Fax : 941.637.9265 www.charlottecountyfl.com/publicworks

More information

IT/Telecommunications Technical and Wiring Standards. Phillips Exeter Academy

IT/Telecommunications Technical and Wiring Standards. Phillips Exeter Academy IT/Telecommunications Technical and Wiring Standards FOR Phillips Exeter Academy Exeter, NH No deviations will be permitted from these specifications without the express written consent of Phillips Exeter

More information

A. The requirements of Section govern the work specified in this section.

A. The requirements of Section govern the work specified in this section. SECTION 27 05 10 - COMMUNITY ANTENNA TELEVISION CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The requirements of Section 27 01 00 govern the work specified in this section. B. Refer to the following

More information

btnet new products Modular and preloaded patch panels btnet

btnet new products Modular and preloaded patch panels btnet btnet new products Modular and preloaded patch panels 128 btnet content 130 General characteristics Catalogue 132 UTP and FTP cable 134 Patch panel and cord 135 Pop-up and floor box 136 Fiber optic BTNET

More information

IP-LINX Fiber :: X-XXXX

IP-LINX Fiber :: X-XXXX Fiber :: 055-797X-XXXX User Manual Telect, Inc. All rights reserved. 146653-A0 Table of Contents Chapter 1: Introduction...3 1.1 Tools Required...3 1.2 Additional Parts...3 1.3 Assemblies...3 Chapter 2:

More information

SECTION COMMUNICATIONS STRUCTURED CABLING

SECTION COMMUNICATIONS STRUCTURED CABLING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 27 15 00 COMMUNICATIONS STRUCTURED CABLING SPEC WRITER NOTES: 1. Edit this specification section between // //, to fit project, or delete if not applicable. 2.

More information

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards.

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards. 27 08 00 Certification and Commissioning of Communication Systems (Revision date: 7/3/12) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are

More information

CATEGORY 6A CABLING SOLUTIONS

CATEGORY 6A CABLING SOLUTIONS 10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Premium Line Category 6A Cabling Solutions

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD, applicable TC -, and CEHNC Design Guide 0-- (Standard is single UTOs and Double UTOs) B. Roads-Service, Lanes Adequate access is provided to the and AAR D. Testing Results-provided

More information

RCIT Cable Certification Testing Revised 10/2017

RCIT Cable Certification Testing Revised 10/2017 RCIT Testing Revised 10/2017 General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall

More information

3M Supported Applications Map 100,000 (2005) Single-mode. Fiber. Multimode. Fiber. Copper

3M Supported Applications Map 100,000 (2005) Single-mode. Fiber. Multimode. Fiber. Copper 3M Volition Network Solutions introduces Category 5e (Cat. 5e) copper cabling system to complement its leading fiber optic structured cabling system. Customers can now enjoy a single source of supply and

More information

Delaware County Community College Project # Marple Campus Renovation - Phase % Construction Documents November 23, 2011

Delaware County Community College Project # Marple Campus Renovation - Phase % Construction Documents November 23, 2011 SECTION 271323 - COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 - GENERAL 1.1 DESCRIPTION A. This section provides the specifications for the work related to the optical fiber system in the project.

More information

CATEGORY 6A CABLING SOLUTIONS

CATEGORY 6A CABLING SOLUTIONS 10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Need of 10 Gigabit Service Application as

More information

3M Distribution Box (DDB)

3M Distribution Box (DDB) 3M Distribution Box (DDB) Merged Copper and Fiber Pole/Post Mount Enclosure Installation Instructions November 2015 78-0015-2736-1-A 2 November 2015 78-0015-2736-1-A Contents 1.0 General 2.0 Enclosure

More information

CATEGORY 6 CABLING SOLUTIONS

CATEGORY 6 CABLING SOLUTIONS With over 20 years experience and know-how on communicating products design & developing, Premium Line has built maturity systems both in high tech develop and research center & complete structural quality

More information

UNM IT/Telecommunications Guide Specification Labeling 11/07/

UNM IT/Telecommunications Guide Specification Labeling 11/07/ Labeling 1 PART 1: GENERAL 1.01 SCOPE OF WORK A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing

More information

PREMIUM 5e F/UTP PRODUCTS

PREMIUM 5e F/UTP PRODUCTS Siemon s end-to-end cabling system is guaranteed to provide transmission performance margins in excess of industry standards for category 5e parameters, while featuring excellent EMI resistance. has been

More information

VGA Extender over Cat 6 with Audio Support. Model Extend both video and audio up to 300 meters

VGA Extender over Cat 6 with Audio Support. Model Extend both video and audio up to 300 meters VGA Extender over Cat 6 with Audio Support Model 103004 Extend both video and audio up to 300 meters Utilize a Cat 6 cable instead of a bulky VGA cable Supports a local monitor and local audio Easy installation

More information

Lyndhurst Secondary Technology Package Addendum # Bid Date: Wednesday, August 30, 1:00PM. Items issued in this addendum:

Lyndhurst Secondary Technology Package Addendum # Bid Date: Wednesday, August 30, 1:00PM. Items issued in this addendum: Lyndhurst Secondary Technology Package Addendum #7 8.29.2017 Bid Date: Wednesday, August 30, 2017 @ 1:00PM Items issued in this addendum: A. Contractor questions and responses B. Clarifications A. Contractor

More information

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection. SECTION 271300 - COMMUNICATIONS BACKBONE CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

SPECIAL SPECIFICATION 2344 TMC Support Equipment

SPECIAL SPECIFICATION 2344 TMC Support Equipment 2004 Specifications CSJ 0912-00-488 SPECIAL SPECIFICATION 2344 TMC Support Equipment 1. Description. Furnish Traffic Management Center (TMC) support equipment in the City of Missouri City TMC location

More information

Compact Module. Category 6 FTP Cabling System

Compact Module. Category 6 FTP Cabling System Compact Module Shielded design for improved EMI performance Suitable for Gigabit Ethernet applications and beyond Ultra-slimline design Colour coded for quick and accurate termination Interchangeable with

More information

STRUCTURED CABLING SYSTEMS (SCS)

STRUCTURED CABLING SYSTEMS (SCS) STRUCTURED CABLING SYSTEMS (SCS) ModSecur - Structured Cabling Systems (SCS) A Structured Cabling System (SCS) is the backbone of any building, campus or site communication infrastructure. The sharp growth

More information

Model Extend HDMI audio and video connections up to 300 feet. Add up to 8 additional receivers with a dedicated network switch

Model Extend HDMI audio and video connections up to 300 feet. Add up to 8 additional receivers with a dedicated network switch HDMI Extender over Single CAT 6 Cable with IR Control Model 103002 Extend HDMI audio and video connections up to 300 feet Utilize existing Cat 6 wiring for an easy installation Add up to 8 additional receivers

More information

STANDARDS SECTION (16651) COMMUNICATIONS DISTRIBUTION SYSTEM (Rev. Jun 2011)

STANDARDS SECTION (16651) COMMUNICATIONS DISTRIBUTION SYSTEM (Rev. Jun 2011) PART 1 GENERAL 1.00 DESCRIPTION STANDARDS SECTION 271000 (16651) COMMUNICATIONS DISTRIBUTION SYSTEM (Rev. Jun 2011) A. Furnish and install a complete Communications (Telephone/Data) Distribution System

More information

SECTION CONTROL, COMMUNICATION AND SIGNAL WIRING

SECTION CONTROL, COMMUNICATION AND SIGNAL WIRING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 27 10 00 CONTROL, COMMUNICATION AND SIGNAL WIRING SPEC WRITER NOTES: 1. Edit this specification section between // //, to fit project, or delete if not applicable.

More information