Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk

Size: px
Start display at page:

Download "Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk"

Transcription

1 Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk Paul Vanderlaan Product Development Engineer Belden Presented at BICSI January 20, 1999 Introduction New Parameters involving category 5 cabling have recently been introduced and are currently under development in the standards committee. Several parameters will be specified and regulated in an attempt to assure the end user that the installed system will perform as designed. Three documents are currently in draft status. They are presently identified as the TSB-95 for Category 5, TIA/EIA 568A Addendum-5, and the recently released TIA/EIA 568A Addendum-3. This presentation covers the new parameters Power Sum Near-End Crosstalk (PS-NEXT), Equal Level Far-End Crosstalk (ELFEXT), and Powersum Equal Level Far- End crosstalk (PS-ELFEXT). Additionally, Alien crosstalk will be discussed and the effect various bundling techniques have upon the parameter. Various methods of bundling cables via binders, cinch ties, and conduit will evaluated. Finally, recommendations will be provided to minimize possible cable damage while maximizing LAN performance, if bundled cables are employed in the installation. Near-End Crosstalk : Past and Present Near-end crosstalk (NEXT) is simply defined as the unwanted signal coupling from a near-end transmitter into a pair measured at the same end. In the case of Figure 1, the signal is transmitted on orange pair. The coupled power, as indicated by the orange wave, is measured at the same end on the blue pair. Near End Crosstalk (NEXT) Figure 1

2 Category 5 cables were originally specified in the ANSI/TIA/EIA-568-A document. This document was originally intended to assure that 2 pair networks (one transmitting pair, one receiving pair) would perform to their intended levels. However, with the creation of new encoding schemes utilizing all four pairs for data transmission, there is now a need to characterize and limit the crosstalk from more than one pair. This additional parameter is known as Powersum Near-End Crosstalk (PS-NEXT). It is defined in proposed TIA/EIA 568A Addendum-5 as the computation of the unwanted signal coupling from multiple transmitters at the near-end into a pair measured at the near-end. In the case of Figure 2, the signals are transmitted on orange, green and brown pairs. The coupled power, as indicated by the three orange waves, is measured at the same end on the blue pair. Power Sum Near End Crosstalk (PS-NEXT) Figure 2 This is important in such systems such as Gigabit Ethernet or 100BaseT4 systems, which utilize all four pairs for the transmission of data. Figure 3 is an example of a NEXT trace of a 100-meter sample of cable as measured on an analyzer. The three combinations of orange/blue, green/blue and brown/blue are represented by the green, blue, and black traces respectively. The calculated PS-NEXT performance is indicated by the red trace. Note that the red trace is always higher due to the summation of the three traces from below.

3 Power Sum Near End Crosstalk (PS-NEXT) Far-End Crosstalk Figure 3 Far-end crosstalk (FEXT) is defined as a measure of the unwanted signal coupling from a transmitter at the near-end into a neighboring pair measured at the far-end. Figure 4 is the illustrated example. The signal is transmitted on the orange pair and the red arrow indicates the FEXT coupling. The FEXT level, indicated by the orange waveform, is reduced by attenuation as it travels down the blue pair. In old networks, each end of the cable had one transmitter and one receiver. Any information that coupled onto the adjacent pair was not important, for that pair, at the opposite end, was a dedicated transmitter not listening for transmitted data. However, newer systems utilizing bi-directional transmission schemes, have four transmitters and receivers at each end. Each pair end is sending and receiving data. It becomes necessary to limit the coupled noise from adjacent pairs to ensure data integrity.

4 Far End Crosstalk (FEXT) Figure 4 Figure 5 is an example of a FEXT trace of a 100-meter sample of cable as measured on an analyzer. The red arrow #1 indicates a smooth straight line of coupled FEXT. Since the attenuation at low frequencies is low, the line is almost straight. However, as the frequency increases, the signal level becomes affected by the attenuation of the pair. This is indicated by the gradual roll-off of the trace at the red arrow #2. It is apparent that the FEXT measurement is dependent on attenuation. This, in turn, makes the measurement length dependent as well. This can create field testing problems. Longer lengths of cable appear to exhibit better FEXT than short lengths. Therefore, a length independent measurement is needed to assure the performance of the channel. Far-End Crosstalk Trace Figure 5

5 Equal Level Far-End Crosstalk Equal Level Far-End Crosstalk (ELFEXT) is defined as the measure of the unwanted signal coupling from a transmitter at the near-end into a neighboring pair measured at the far-end relative to the received signal level measured on that same pair. In simple terms, it puts the attenuation back into the FEXT signal. Figure 6 is the illustrated example. The signal is transmitted on the orange pair and the red arrow indicates the FEXT coupling. The FEXT level, indicated by the orange waveform, is reduced by attenuation as it travels down the blue pair. When the attenuation is removed from the measurement the resultant is a higher signal level as indicated by the yello w waveform. This is the calculated ELFEXT. Equal Level Far End Crosstalk (ELFEXT) Figure 6 Figure 7 exhibits the components of ELFEXT. Arrow #1 indicates the FEXT coupling from the orange pair to the blue pair. Arrow # 2 indicated the attenuation characteristic of the blue pair. The equation is simple: ELFEXT= FEXT - Attenuation. The blue trace, indicated by arrow #3, is the resultant calculated ELFEXT. With the attenuation removed, the ELFEXT trace is very linear and smooth.

6 FEXT - Attenuation = ELFEXT Figure 7 Power Sum Equal Level Far-End Crosstalk Finally, the last parameter discussed is power sum equal level far-end crosstalk (PS-ELFEXT). It is defined as the computation of the unwanted signal coupling from multiple transmitters at the near-end into a pair measured at the far-end relative to the received signal level measured on that same pair. Similar to PS- NEXT this is merely the summation of the three combinations of ELFEXT into one trace. Figure 8 indicates the three coupled FEXT disturbances onto the blue pair. The orange waveforms are then summed, the attenuation of the pair removed, and the resultant yellow trace is the computed PS-ELFEXT. Power Sum Equal Level Far End Crosstalk (PS- ELFEXT) Figure 8

7 Cable Bundling and Alien Crosstalk Several questions have been raised recently as to the feasibility of bundling cables to speed the cable pulling process. Is bundling cables permitted within the ANSI/TIA/EIA-568-A? Can bundling cable degrade the cables' internal electrical performance? Can bundling cable reduce the potential LAN performance? Should you be concerned? The answer to all these questions is yes. Old Bundled Cable specifications Originally, the bundled cable specifications were vaguely specified in ANSI/TIA/EIA-568-A, Section 13.1 Hybrid Cables. This only addressed overall jacketed cable groups (e.g. 6 jacketed cables with an overall jacket) Assemblies wrapped with a binder or mylar tape were not covered and therefore exempt from the requirements. The document specified cable to cable NEXT as 6+10log(n) db, where n = number of cables within the jacket assembly. This requirement was almost impossible to meet in cable counts higher than 3 cables. As an example, for two jacketed cables, the crosstalk from cable to cable was 9 db tighter than their respective internal NEXT specification. Six cables required a 13.9dB tighter NEXT specification. The high degree of difficulty in meeting these specifications in conjunction with the lack of a sound technological reason for the tight specification led to a more sensible approach. The new requirement is specified in the newly released ANSI/TIA/EIA 568-A-3 Addendum 3. This document creates a new definition to address wrapped or bound bundles of cables. It is aimed specifically at the manufacturers and assembly houses that generate this material. Currently, this document only addresses PS-NEXT from other cables in the assembly. Alien Crosstalk What is alien crosstalk and where is it regulated? There is no mention of alien crosstalk in any of the industry standards. The term alien crosstalk is not a recognized definition within the standards. Simply put, alien crosstalk is crosstalk noise from adjacent data cables as demonstrated in Figure 9. This phenomena falls under the TIA/EIA 568-A-3 Addendum 3, which addresses bundled cables' crosstalk performance. The requirement states that PS-NEXT from adjacent cables must be 3 db better than the cable's internal pair to pair requirements. This is an important parameter for network cards are unable to compensate for noise external to the cable so it is important to minimize the effects of adjacent cables. Alien Power Sum Near End Crosstalk (PSNEXT) Figure 9

8 Alien Near-End Crosstalk Testing In an attempt to generically characterize alien crosstalk performance, several bundling scenarios were examined. All cable samples were 100 meter, "high" performance category 5 cables. All samples were laid out and tested on the floor with bend radii well within the requirements of ANSI/TIA/EIA-568-A. Bundles of six cables were bound using various methods including: cabling and double wrapped with binders, cinched with plastic cinch ties, and pulled loosely into a 1 inch EMC conduit. The six cables in the conduit only represent a 22% fill factor. To more closely represent a typical 40% fill installation, 4 additional cables were pulled into the conduit and tested. Assemblies utilizing a type of mylar wrap were not considered due to the questionable ability to meet plenum smoke requirements. Figure 10 is a picture of the cabled and bound sample. It is an attempt to simulate a neat assembly that might be provided by a manufacture or third party assembly house randomly selecting cables and bundling them in an aesthetically pleasing manner without regard to the impact of cable performance. Figure 10 Figure 11 represents a particular cable's internal performance before cabling. Figure 12 indicates the subunit performance after the assembly process. Notice the 100 MHz performance has deteriorated from over 10 db of NEXT margin to less than 1 db. The NEXT performance, for which the customer has paid a significant amount of money, has been lost. Cable NEXT Performance Before Binding Figure 11

9 Cable NEXT Performance After Binding Figure 12 The alien, or cable to cable crosstalk, is depicted in Figure 13. The first red arrow indicates the specification for NEXT performance as specified in Addendum 3. It is 3 db tighter than the Category 5 specification. Arrows 2A and 2B indicate points of significant failure. The margin as indicated in the lower left hand corner is db. It is interesting to note that the NEXT from cable to cable actually exceeds Category 5 internal requirements. Not only has the process degraded the internal to the point of near failure, now there is crosstalk from the adjacent cable in excess of category 5 limits. Alien Power Sum NEXT Six Cables Double Bound

10 Cinch ties were used to bind the next sample. Figure 14 and 15 are provided to give an idea as to the frequency and tightness of the cinching. The sample was cinched every 48 inches in accordance with the minimum support distance in ANSI/TIA/EIA-569-A. The cinching slightly deformed the cables' jackets. Additionally, the cables were allowed to lie in their natural state. No attempt to spread the individual cables apart was made. Figure 16 indicates 4.6 db of margin to the Addendum-3 specification. Figure 14 Figure 15 Alien Power Sum NEXT Six Cables Cinched Every 48 Inches Figure 16 The conduit samples consisted of six 100m cables pulled into approximately 280ft of 1 inch EMT conduit. This left 24 feet of exposed cable on each end of the sample under test. This was an attempt to simulate an installation with cable on each end representing patch cable going to the desktop and through the wiring closet. The conduit consisted of two 140ft straight runs connected at the far end by two 90 degree bends to

11 form the shape of a 140 ft long letter U. Figure 17 represents the conduit at 22% fill. There is 3.5 db margin to the Addendum --3 specification. Alien Power Sum NEXT Six Cables - 22% Conduit Fill Figure 17 When four more cables were pulled in to raise the fill factor to 40%, the margin dropped to 3.0 db. It is important to note that due to the intensive and lengthy measurements needed in the verification process, only the two worst performing cables in the 22% fill trial were remeasured and plotted. It is believed that this is a valid assumption since the cable to cable performance was approximately equal on an adjacent cable to cable basis. This being the case, it is not expected that the addition of 4 more cables would radically change the alien NEXT performance of any given cable. Figure 18 indicates that the alien NEXT performance dropped.5 db to a 3.0 db margin to the respective specification. Alien Power Sum NEXT Ten Cables - 40% Conduit Fill Figure 18

12 Figure 19 is a summary of the margins for the respective bundling techniques. There are no surprises here in that the loosest bundled sample, the cinched bundle, exhibited the best alien crosstalk performance while the tightest, the cabled and double bound, exhibited the worst. However, it is possible that the deterioration of the individual cable's integrity, during the cabling assembly process, did exacerbate the alien NEXT failure. Alien Power Sum NEXT Margins to Addendum 3 Alien Equal Level Far End Crosstalk Testing Figure 19 Alien equal level far-end crosstalk (ELFEXT) is the same concept as mentioned earlier in the presentation. The only difference is the crosstalk is from cable to cable rather than pair to pair. Figure 20 illustrates this example. It is important to note that there is no current or proposed specification to regulate Alien ELFEXT. This was an attempt to characterize the performance and in no way indicates that any particular construction would pass or fail any future cable specification. The specification used for comparative purposes is the proposed category 5 Channel ELFEXT limit. Alien Power Sum Equal Level Far End Crosstalk (PS-ELFEXT)

13 Figure 20 Figure 21 is the cabled and double bound sample. The margin as indicated is only.2 db to the channel specification. There is almost no margin left for connectors or any other installation effects. Figure 22, 23 and 24 represent the cinched, 22% filled conduit and 40% filled conduit. Alien Power Sum ELFEXT Six Cables Double Bound Figure 21

14 Alien Power Sum ELFEXT Six Cables Cinched Every 48 Inches Figure 22 Alien Power Sum ELFEXT Six Cables - 22% Conduit Fill Figure 23

15 Alien Power Sum ELFEXT Ten Cables - 40% Conduit Fill Figure 24 Figure 25's table summarizes the performance of the various assemblies. As expected the cabled and double bound assembly had the worst alien ELFEXT performance. However, the cinched assembly no longer has the best performance. This may be due to the nature of ELFEXT, which depicts the coupling along the entire length of the cable unlike NEXT, which primarily represents only near end performance. The cinching of the ties may be producing periodic coupling, which is greater that that found in the cables enclosed loosely in conduit. Alien ELFEXT Margins to the Cat 5 Channel PS-ELFEXT Specification Figure 25

16 Conclusion There are new cable requirements, PS-NEXT, ELFEXT, and PS-ELFEXT which are under development or have been defined by Draft documents in TIA subcommittees. ANSI/TIA/EIA-568-A Addendum-3 specifically addresses the crosstalk from cable to cable, otherwise known as alien crosstalk. Cables are designed to meet their respective requirements. Care must be taken when cables are assembled by a third party. Unplanned twisting of the cable core can be detrimental to the internal performance. As an example, the cabled and double bound sample lost 10 db of internal crosstalk margin. Continuous tightly bound assemblies seem to have an inherent disadvantage for Alien crosstalk. The cabled and double bound sample failed Addendum -3 alien PS-NEXT by 4.5 db and only passed the category 5 channel PS-ELFEXT requirements by 0.2 db. Cinched cables appear to meet current requirements of alien PS-NEXT and exhibit good alien PS-ELFEXT, However, tight cinching may degrade the alien PS-ELFEXT at a higher rate than the alien PS-NEXT. Conduit does not appear to excessively degrade cable to cable performance. When compared to the cinched sample, the 22% filled conduit reduced alien PS-NEXT performance by 1.1 db but improved alien PS-ELFEXT performance by 1.9 db. The 40% filled conduit reduced the performance of alien PS-NEXT by 0.5 db but improved alien PS-ELFEXT by 1 db. It is important to realize that current generation hand held testers cannot verify alien crosstalk performance. In order to help assure maximum LAN performance bundled types of cable constructions should be avoided. If bundled assemblies are required, be sure to obtain the material from sources that have the capability to verify their finished assembly's performance to these new requirements.

What really changes with Category 6

What really changes with Category 6 1 What really changes with Category 6 Category 6, the standard recently completed by TIA/EIA, represents an important accomplishment for the telecommunications industry. Find out which are the actual differences

More information

Connect with the industry s best CAT6 and CAT5e channel solutions!

Connect with the industry s best CAT6 and CAT5e channel solutions! Connect with the industry s best CAT6 and CAT5e channel solutions! Our CAT6 and CAT5e channel solutions far exceed the TIA/EIA specifications performance standards! To ensure consistent and continuing

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 - GENERAL 1.1 SECTION

More information

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION PART 1 - GENERAL 1.1 SUMMARY SCOPE SECTION 25170 TESTING, IDENTIFICATION AND ADMINISTRATION 1. This section includes the minimum requirements for the testing, certification administration and identification

More information

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017 Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM-2017-2 Date: 05/26/2017 Additional specification information for data communication to cameras and between Library

More information

Challenges for testing 10GBASE-T

Challenges for testing 10GBASE-T Challenges for testing 10GBASE-T Adrian Young Customer Support Manager adrian.young@flukenetworks.com Check list Category 6A component compliant connector Category 6A compliant cable Perfect terminations

More information

Data Communications Competence Center

Data Communications Competence Center The Effect of Short Link Resonance on the NEXT and PSNEXT Performance of 7m Channels Data Communications Competence Center DCCC082102R1 July 11, 07 Test Summary This report compares the results of NEXT

More information

Belden IBDN System 10GX The next level of cabling performance

Belden IBDN System 10GX The next level of cabling performance Belden IBDN System 10GX The next level of cabling performance by Paul Kish Director Belden IBDN Systems and Standards Introduction There is a new standard under development in the IEEE 2.3an task force

More information

Belden IBDN System 10GX Enabling Technologies

Belden IBDN System 10GX Enabling Technologies Belden IBDN System 10GX Enabling Technologies by Paul Kish Director, Systems and Standards Revision 1 November 2008 Belden Belden IBDN System 10GX Enabling Technologies 1/17 Introduction The IEEE 802.3an

More information

Alien Crosstalk measurement limitations at low frequencies (1 MHz to ~ 10 MHz)

Alien Crosstalk measurement limitations at low frequencies (1 MHz to ~ 10 MHz) Alien Crosstalk measurement limitations at low frequencies (1 MHz to ~ 10 MHz) Prepared for IEEE802.3an 10GBase-T task group Henriecus ( Henri or Riekus ) Koeman Fluke Networks 1 Alien crosstalk Henriecus

More information

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project 1.1.0 GENERAL The purpose of this specification is to establish a requirement for the installation of a voice, video and data cable network. The cable (copper), wire, hardware, equipment racks, jumpers,

More information

IEEE 802.3af Power via MDI Standard Compliant Mid-Span Insertion Solution. Presented by PowerDsine: David Pincu -

IEEE 802.3af Power via MDI Standard Compliant Mid-Span Insertion Solution. Presented by PowerDsine: David Pincu - IEEE 802.3af Power via MDI Standard Compliant Mid-Span Insertion Solution Presented by PowerDsine: David Pincu - davidp@powerdsine.com Objectives! Investigate the Channel /Link options! Identify the requirements

More information

DESIGN!!GUIDELINES!!!!!

DESIGN!!GUIDELINES!!!!! DESIGNGUIDELINES 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 1. Testing General 1.1. For acceptance, 100% of the media

More information

Data Communications Competence Center

Data Communications Competence Center s Data Communications Competence Center DCCC00 June 9, 00 Test Summary Active testing was performed on Berk-Tek s -pair, Category e cables. The testing demonstrates the ability of this cable to reliably

More information

Do you know if your Cat. 6 patch cord has been tested according to standards?

Do you know if your Cat. 6 patch cord has been tested according to standards? White Paper 02. Juli 2002 Andreas Clauser Hauptsitz Binzstrasse 31 CH-8622 Wetzikon Tel +41 1 933 8375 Fax +41 1 930 49 41 Internet www.rdm.com Do you know if your Cat. 6 patch cord has been tested according

More information

About Nexans 3. About Berk-Tek 4. LANmark-1000 Cat 6 UTP 5. LANmark-1000 Category 6 Plenum 6. LANmark-1000 Category 6 Riser 11

About Nexans 3. About Berk-Tek 4. LANmark-1000 Cat 6 UTP 5. LANmark-1000 Category 6 Plenum 6. LANmark-1000 Category 6 Riser 11 Table of contents About Nexans 3 About Berk-Tek 4 LANmark-1000 Cat 6 UTP 5 LANmark-1000 Category 6 Plenum 6 LANmark-1000 Category 6 Riser 11 LANmark-1000 Category 6 Patch 16 21 7/10/07 - http://www.berktek.com

More information

CATEGORY 6A CABLING SOLUTIONS

CATEGORY 6A CABLING SOLUTIONS 10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Premium Line Category 6A Cabling Solutions

More information

Robert Burén. Product Manager. Nexans Cabling Solutions. 10G Solutions

Robert Burén. Product Manager. Nexans Cabling Solutions. 10G Solutions Robert Burén Product Manager 10G Solutions Nexans Cabling Solutions 1 10 Gigabit Ethernet.Performance 30 GByte can be transmitted within 24 seconds Example: MRI-scan size is 30GB as average A memory device

More information

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall obtain authorization from

More information

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents PART 1 - GENERAL 1.1 SUMMARY SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors. 3. Cabling system identification products. 1.2

More information

Section Communications Optical Fiber Backbone Cabling

Section Communications Optical Fiber Backbone Cabling Part 1 1.1 Related Documents 1.1.1 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections apply to this Section. 1.2 Related

More information

HDBaseT Installation Guide

HDBaseT Installation Guide Installation Guide This document provides the best practices for installing Ethernet cable with setups. We strongly recommend to use ATEN certified cable (2L-2910) to provide best performance and to guarantee

More information

CATEGORY 6A CABLING SOLUTIONS

CATEGORY 6A CABLING SOLUTIONS 10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Need of 10 Gigabit Service Application as

More information

HDBT Installation Guide

HDBT Installation Guide KRAMER ELECTRONICS LTD. HDBT Installation Guide MODELS: Kramer HDBT Cable Recommendations for Usage and Termination Guidelines For the latest information on our products and a list of Kramer distributors,

More information

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008 Information & Communications Technology Group Standards June 2008 Appendix F UTP cabling Version 1.1 Appendix F UTP cabling 1. Introduction This Section details the required standards for Unshielded Twisted

More information

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards.

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards. 27 08 00 Certification and Commissioning of Communication Systems (Revision date: 7/3/12) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are

More information

White Paper. Cabling for Success with DXLink TM Author: Curry Kinyon Co-Author: Jeff Howes Co-Author: Ann Yanecek

White Paper. Cabling for Success with DXLink TM Author: Curry Kinyon Co-Author: Jeff Howes Co-Author: Ann Yanecek Cabling for Success with DXLink TM Author: Curry Kinyon Co-Author: Jeff Howes Co-Author: Ann Yanecek Page 1 AMX Cabling for Success with DXLink TM V 2.0 10.2012 Table of Contents EXECUTIVE SUMMARY... 3

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors including patch panels. 3. Cabling identification

More information

PREMIUM 5e F/UTP PRODUCTS

PREMIUM 5e F/UTP PRODUCTS Siemon s end-to-end cabling system is guaranteed to provide transmission performance margins in excess of industry standards for category 5e parameters, while featuring excellent EMI resistance. has been

More information

COLORED CATEGORY 5e BULK CABLE, SOLID-CONDUCTOR PATCH CABLE, & CATEGORY 5e BACKBONE CABLE

COLORED CATEGORY 5e BULK CABLE, SOLID-CONDUCTOR PATCH CABLE, & CATEGORY 5e BACKBONE CABLE COLORED CATEGORY 5e BULK CABLE, SOLID-CONDUCTOR PATCH CABLE, & CATEGORY 5e BACKBONE CABLE Key Features Choose Category 5 cable that meets the proposed enhanced standard. Different colors make it easy to

More information

POET-1 P.O.E. TEST PORT MEASUREMENT TOOL INSTRUCTION BOOK

POET-1 P.O.E. TEST PORT MEASUREMENT TOOL INSTRUCTION BOOK POET-1 P.O.E. TEST PORT MEASUREMENT TOOL INSTRUCTION BOOK IB6386-01 9-1-2015 TABLE OF CONTENTS DESCRIPTION 2 HOW TO CABLE THE POET-1 2 HOW TO TAKE A MEASUREMENT 3 EASE OF USE 3 APPLICATIONS 3 CARE AND

More information

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 48-3 2011 Test Procedure for Measuring Shielding Effectiveness of Braided Coaxial Drop Cable Using the GTEM Cell

More information

SYSTIMAX GigaSPEED XL Solution

SYSTIMAX GigaSPEED XL Solution SYSTIMAX GigaSPEED XL Solution The Culmination of a Relentless Pursuit of Excellence SYSTIMAX Structured Connectivity Solutions www.systimax.com A study reported that 79% of employees use a company network.

More information

Brian Holden Kandou Bus, S.A. IEEE GE Study Group September 2, 2013 York, United Kingdom

Brian Holden Kandou Bus, S.A. IEEE GE Study Group September 2, 2013 York, United Kingdom Simulation results for NRZ, ENRZ & PAM-4 on 16-wire full-sized 400GE backplanes Brian Holden Kandou Bus, S.A. brian@kandou.com IEEE 802.3 400GE Study Group September 2, 2013 York, United Kingdom IP Disclosure

More information

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices Berk-Tek recommends installing a well-designed structured cabling channel per the TIA standards. This includes up to 100

More information

Field Testing and Troubleshooting of PON LAN Networks per IEC Jim Davis Regional Marketing Engineer Fluke Networks

Field Testing and Troubleshooting of PON LAN Networks per IEC Jim Davis Regional Marketing Engineer Fluke Networks Field Testing and Troubleshooting of PON LAN Networks per IEC 61280-4 Jim Davis Regional Marketing Engineer Fluke Networks Agenda Inspection and Cleaning APC vs UPC PON basics Wavelengths Architecture

More information

Lab - Build and Test Network Cables

Lab - Build and Test Network Cables Introduction In this lab, you will build and test straight-through and crossover Unshielded Twisted-Pair (UTP) Ethernet network cables. Note: With a straight-through cable, the color of wire used by pin

More information

Description: Pair Color Code Chart: Pair Color Chart 1 Brown White Brown 2 Orange White Orange 3 Green White Green 4 Blue White Blue.

Description: Pair Color Code Chart: Pair Color Chart 1 Brown White Brown 2 Orange White Orange 3 Green White Green 4 Blue White Blue. Description: OZLINX CAT5e cable has a guaranteed performance; exceeds the Category 5e performance requirements and provides positive PSACR up to 155MHz for bandwidth requirement in the future. Product

More information

SMART CLASSix 24/48 UTP Patch Panels -

SMART CLASSix 24/48 UTP Patch Panels - Features Support 24 ports per 1U, 48 ports per 2U. Conform to ANSI/TIA/EIA-568-B.2-1, ISO/IEC 11801 2 nd edition (2002) and CENELEC EN50173 (2002) for Category 6/Class E. Simple labor-saving termination

More information

GIGALAN CAT.6 U/UTP 23AWGx4P - LSZH (EXP)

GIGALAN CAT.6 U/UTP 23AWGx4P - LSZH (EXP) GIGALAN CAT.6 U/UTP 23AWGx4P - LSZH (EXP) Product Type LAN Cable Product Family Construction GigaLan RoHS-2 Compliant Category 6 U/UTP (unshielded) LSZH General Characteristics Features Installation Environment

More information

Draft Baseline Proposal for CDAUI-8 Chipto-Module (C2M) Electrical Interface (NRZ)

Draft Baseline Proposal for CDAUI-8 Chipto-Module (C2M) Electrical Interface (NRZ) Draft Baseline Proposal for CDAUI-8 Chipto-Module (C2M) Electrical Interface (NRZ) Authors: Tom Palkert: MoSys Jeff Trombley, Haoli Qian: Credo Date: Dec. 4 2014 Presented: IEEE 802.3bs electrical interface

More information

OCC Installation Conduit Guidelines Excerpt from Optical Cable Corporation s INSTALLATION GUIDE

OCC Installation Conduit Guidelines Excerpt from Optical Cable Corporation s INSTALLATION GUIDE Installation Conduit Guidelines Excerpt from Optical Cable Corporation s INSTALLATION GUIDE Conduit Installation A conduit cable installation involves placement of one or more optical cables inside a preinstalled

More information

Fiber Optic Testing. The FOA Reference for Fiber Optics Fiber Optic Testing. Rev. 1/31/17 Page 1 of 12

Fiber Optic Testing. The FOA Reference for Fiber Optics Fiber Optic Testing.   Rev. 1/31/17 Page 1 of 12 Fiber Optic Testing Testing is used to evaluate the performance of fiber optic components, cable plants and systems. As the components like fiber, connectors, splices, LED or laser sources, detectors and

More information

LAN Cabling Systems Copper

LAN Cabling Systems Copper LAN Cabling Systems Copper Table of content About Nexans 3 Copper 4 Essential Cat 5e Cable 5 LANmark-6 Cable 7 LANmark-6A Cable 9 LANmark-7 Cable 11 LANmark-7A Cable 13 Legal Notice 14 8/20/11 - http://www.nexans-fi.com

More information

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1. PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

Clarity Advanced Solutions6A

Clarity Advanced Solutions6A Clarity Advanced Solutions6A Clarity 6A connectivity more effectively supports the internal and alien performance requirements of 10 Gigabit Ethernet. Clarity 6A components use Ortronics innovative technique

More information

COVER

COVER COVER 800-526-0242 www.comprehensiveco.com sales@comprehensiveco.com Pro AV/IT Cat6 Network Cables Pro AV/IT Heavy Duty Cat6 Network Cables Comprehensive s Pro AV/IT Cat6 Heavy Duty Snagless Patch Cables

More information

Copper Cabling Troubleshooting Handbook

Copper Cabling Troubleshooting Handbook NETWORKSUPERVISION Copper Cabling Troubleshooting Handbook NETWORKSUPERVISION Table of Contents Introduction 2 Troubleshooting Basics 3 Link Models 4 The automated DTX Series diagnostics 5 Causes of Cabling

More information

How to Implement PoE in Your Harsh Industrial Environment

How to Implement PoE in Your Harsh Industrial Environment Produced by: Engineering 360 Media Solutions July 2018 How to Implement PoE in Your Harsh Industrial Environment Sponsored by: Quabbin Wire & Cable Co., Inc. There is little doubt that the internet of

More information

technicalreport MegaLine Connect100 Class E A links over 100 metres in length Data communication technology 09/2018 Classic structure 2-connector link

technicalreport MegaLine Connect100 Class E A links over 100 metres in length Data communication technology 09/2018 Classic structure 2-connector link technicalreport Data communication technology 09/2018 Classic structure 2-connector link Ethernet transmission with twisted pair cables Limiting factors for links > 100 m Example structure of a 2-connector

More information

10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System

10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System 10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System Next-Generation Category 6A UTP Cabling System Drivers for 10 GbE Aggregation of Gigabit Links Server Consolidation and

More information

SECTION 683 VIDEO OPTICAL TRANSCEIVER WITH BI-DIRECTIONAL DATA CHANNEL DESCRIPTION

SECTION 683 VIDEO OPTICAL TRANSCEIVER WITH BI-DIRECTIONAL DATA CHANNEL DESCRIPTION 683 SECTION 683 VIDEO OPTICAL TRANSCEIVER WITH BI-DIRECTIONAL DATA CHANNEL DESCRIPTION 683.01.01 GENERAL A. The Contractor shall furnish the designated quantity of Video Optical Transceiver (VOTR) pairs

More information

TX COPPER CABLING SYSTEM

TX COPPER CABLING SYSTEM TX COPPER CABLING SYSTEM PERFORMANCE BEYOND PRODUCTS PANDUIT is the global leader in network connectivity, delivering end-to-end system solutions in support of your most demanding network requirements.

More information

Clarity. Advanced solutions for 10 Gig, Category 6 and 5e copper connectivity PRODUCT SOLUTION GUIDE EXPERTISE. TECHNOLOGY. SOLUTIONS.

Clarity. Advanced solutions for 10 Gig, Category 6 and 5e copper connectivity PRODUCT SOLUTION GUIDE EXPERTISE. TECHNOLOGY. SOLUTIONS. Clarity Advanced solutions for 10 Gig, Category 6 and 5e copper connectivity PRODUCT SOLUTION GUIDE EXPERTISE. TECHNOLOGY. SOLUTIONS. Center Tuned Components Higher Signal-to- Noise Ratio Optimal Mated

More information

STRUCTURED CABLE SYSTEM (SCS)

STRUCTURED CABLE SYSTEM (SCS) PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

HDMI Technology. HDMI Over Category 6 HDBaseT Signal Extenders

HDMI Technology. HDMI Over Category 6 HDBaseT Signal Extenders Product Bulletin PB 494 Belden HDMI Connectivity Solutions Belden now offers a complete solution for sending HDMI signals over long distances without a reduction in signal quality. Whether using Category

More information

384A Adapter Installation Instructions

384A Adapter Installation Instructions Instruction Sheet 860237684 Issue 9, October 2012 SYSTIMAX Solutions 384A Adapter Installation Instructions General The 384A adapter (Figure 1) is a broadband video adapter that provides connectivity to

More information

GenSPEED Category 5e Cables 3

GenSPEED Category 5e Cables 3 Datacom GenSPEED Category 5e Cables 3 GenSPEED Category 5e cables are available in a wide variety of performance levels and constructions. With many options to pick from, you can select the GenSPEED Category

More information

Triax TechInfo. Installing and pulling Fibre Optic cables

Triax TechInfo. Installing and pulling Fibre Optic cables Installation methods for both wire cables and Fibre Optical cables are similar. Fibre cable can be pulled with much greater force than copper wire if you pull it correctly. Just remember these rules: 1)

More information

Selection of a cable depends on functions such as The material Singlemode or multimode Step or graded index Wave length of the transmitter

Selection of a cable depends on functions such as The material Singlemode or multimode Step or graded index Wave length of the transmitter Fibre Optic Communications The greatest advantage of fibre cable is that it is completely insensitive to electrical and magnetic disturbances. It is therefore ideal for harsh industrial environments. It

More information

TEST REPORT NO.: CRT-081 RENDERED TO: Hubbell Premise Wiring 14 Lord s Hill Road Stonington, CT

TEST REPORT NO.: CRT-081 RENDERED TO: Hubbell Premise Wiring 14 Lord s Hill Road Stonington, CT 3933 US ROUTE 11, CORTLAND, NEW YORK 1345, U.S.A. Phone Number: 1-8-345-3851 Fax Number: 67-758-3648 PROJECT NO.: 322866-311 DATE: February 19, 29 TEST REPORT NO.: 322866CRT-81 RENDERED TO: Hubbell Premise

More information

Laying of cables and lines in electrical installations and data networks

Laying of cables and lines in electrical installations and data networks Technical bulletin Laying of cables and lines in electrical installations and data networks Date: 08/2006 This technical bulletin provides you with information on specific technical subjects. It is based

More information

Module 11 : Link Design

Module 11 : Link Design Module 11 : Link Design Lecture : Link Design Objectives In this lecture you will learn the following Design criteria Power Budget Calculations Rise Time Budget Calculation The optical link design essentially

More information

CAT 6 Data Wiring System Connectors

CAT 6 Data Wiring System Connectors All non-rohs products have been discontinued, or will be discontinued soon. Please check the products status on the Hirose website RoHS search at www.hirose-connectors.com, or contact your Hirose sales

More information

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus PART 1: GENERAL REQUIREMENTS A. Contractor Work 1. Provide and install (except as noted in this document), cable,

More information

Follow The Leader In Shielded Technology

Follow The Leader In Shielded Technology 1970s Vampire Tap 1990s Shielded Modular Jack 190s 4 Position Data Connector Follow The Leader In Shielded Technology The new AMP-TWIST Jack is our latest shielded product evolution. It can be terminated

More information

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project 1.1.0 GENERAL MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project The purpose of this specification is to establish a requirement for the installation of

More information

Premise Installation Guide

Premise Installation Guide Premise Installation Guide Table Of Contents Overview of Cabling Standards...1-2 Horizontal Cabling System Structure...3-5 Work Area... 6 Horizontal Distances of Copper Links (Open Office)... 7 Twisted

More information

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables NEMA Standards Publication Performance Standard for Twisted Pair Premise Voice and Data Communications Cables Published by: National Electrical Manufacturers Association 1300 North 17th Street, Suite 1752

More information

PATCH CORDS, PLUGS & CABLES

PATCH CORDS, PLUGS & CABLES PATCH CORDS, PLUGS & CABLES 3.1 SECTION CONTENTS Modular Cords...3.2 Cable Assemblies...3.3 Plugs & Connectors...3.4 Bundled Cable...3.5 Category 5e & 6 UTP Cable...3.6 Coax Cable...3.7 Fiber Optic Cable...3.8

More information

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables NEMA Standards Publication WC 63.1-2005 Performance Standard for Twisted Pair Premise Voice and Data Communications Cables Published by: National Electrical Manufacturers Association 1300 North 17th Street,

More information

GIGALAN AUGMENTED CABLE CAT6A F/UTP 23AWGX4P LSZH

GIGALAN AUGMENTED CABLE CAT6A F/UTP 23AWGX4P LSZH GIGALAN AUGMENTED CABLE CAT6A F/UTP 23AWGX4P LSZH Product Type LAN Cable Product Family Construction GigaLan Augmented RoHS Compliant Category 6A F/UTP LSZH General Characteristics Features Installation

More information

CAT 6 Data Wiring System Connectors

CAT 6 Data Wiring System Connectors All non-rohs products have been discontinued, or will be discontinued soon. Please check the products status on the Hirose website RoHS search at www.hirose-connectors.com, or contact your Hirose sales

More information

Mar11 Rev E

Mar11 Rev E Product Specification 108-1832 11Mar11 Rev E MT-RJ Patch Panel and Outlet Jacks (Standard, XG, SECURE and SECURE XG) 1. SCOPE 1.1. Content This specification, which meets the Optical Fiber Cabling Components

More information

Job Aid Server and CSS Separation Avaya S8700 Media Server

Job Aid Server and CSS Separation Avaya S8700 Media Server Overview of server separation Job Aid and CSS Separation Avaya S8700 Media This job aid provides information regarding the separation of S8700 Media s and the Separation of duplicated Center Stage Switch

More information

Introduction to Fibre Optics

Introduction to Fibre Optics Introduction to Fibre Optics White paper White Paper Introduction to Fibre Optics v1.0 EN 1 Introduction In today s networks, it is almost impossible to find a network professional who has never been in

More information

Table 4-1: Rating Levels

Table 4-1: Rating Levels OBJECTIVES 1. Describe various level ratings that apply to telecommunication cables and jacks and identify where each is implemented. 2. Describe the various levels of the cabling category rating systems.

More information

Peak Atlas IT. RJ45 Network Cable Analyser Model UTP05. Designed and manufactured with pride in the UK. User Guide

Peak Atlas IT. RJ45 Network Cable Analyser Model UTP05. Designed and manufactured with pride in the UK. User Guide GB05-7 Peak Atlas IT RJ45 Network Cable Analyser Model UTP05 Designed and manufactured with pride in the UK User Guide Peak Electronic Design Limited 2001/2013 In the interests of development, information

More information

STRUCTURED CABLING SYSTEMS (SCS)

STRUCTURED CABLING SYSTEMS (SCS) STRUCTURED CABLING SYSTEMS (SCS) ModSecur - Structured Cabling Systems (SCS) A Structured Cabling System (SCS) is the backbone of any building, campus or site communication infrastructure. The sharp growth

More information

Is Now Part of To learn more about ON Semiconductor, please visit our website at

Is Now Part of To learn more about ON Semiconductor, please visit our website at Is Now Part of To learn more about ON Semiconductor, please visit our website at ON Semiconductor and the ON Semiconductor logo are trademarks of Semiconductor Components Industries, LLC dba ON Semiconductor

More information

In-Line or 75 Ohm In-Line

In-Line or 75 Ohm In-Line or 5 Ohm 1dB Adjustable Gain 800/1900 Smart Technology Contents: Quick Install Overview.... 2 Installation Diagram.... Understanding the Lights... 9 Warnings and Recommendations....11 Appearance of device

More information

RTPGE Prototype Channel & Alien Test Results

RTPGE Prototype Channel & Alien Test Results RTPGE Prototype Channel & Alien Test Results Richard Mei Bryan Moffitt Jeff Oberski Todd Herman Curtis Donahue Dave Estes 1 Recommended worst case - common scenario 1A Three channels each with 2 inline

More information

The characteristics of a video signal and methods to overcome distance limitations

The characteristics of a video signal and methods to overcome distance limitations The characteristics of a video signal and methods to overcome distance limitations Rich Hanna, CTS Regional Application Specialist, Southeast Extron Electronics Monday, January 24, 2005 9:00 AM 4:00 PM

More information

SECTION 7 -- CROSS-CONNECT SYSTEMS

SECTION 7 -- CROSS-CONNECT SYSTEMS DETAIL ENGINEERING REQUIREMENTS AT&T March, 2016 Section 7, ATT-TP-76400 Revised NA SECTION 7 -- CROSS-CONNECT SYSTEMS CONTENTS PAGE 1. GENERAL... 7-2 1.1. Introduction... 7-2 1.2. Cable Holes... 7-2 1.3.

More information

About Nexans 3. About Berk-Tek 4. Hyper Plus 5e Cat 5e UTP 5. HyperPlus 5e Plenum 6. Hyper Plus 5e Riser 10. HyperPlus 5e Patch 14

About Nexans 3. About Berk-Tek 4. Hyper Plus 5e Cat 5e UTP 5. HyperPlus 5e Plenum 6. Hyper Plus 5e Riser 10. HyperPlus 5e Patch 14 Table of contents About Nexans 3 About Berk-Tek 4 Hyper Plus 5e Cat 5e UTP 5 HyperPlus 5e Plenum 6 Hyper Plus 5e Riser 10 HyperPlus 5e Patch 14 HyperPlus 5e OSP 18 22 7/10/07 - http://www.berktek.com Page

More information

5e. Max bandwidth is 400MHz Cat 6 max bandwidth of 500MHz Cat 6E max bandwidth of 550MHz ( E stands for enhanced ) Cat 6A max bandwidth of 625MHz

5e. Max bandwidth is 400MHz Cat 6 max bandwidth of 500MHz Cat 6E max bandwidth of 550MHz ( E stands for enhanced ) Cat 6A max bandwidth of 625MHz Before we talk about Hubbell s range of Copper connectivity products we first need to understand the difference between the various categories of copper products! Quite simply put the category of a copper

More information

SPECIAL SPECIFICATION 6911 Fiber Optic Video Data Transmission Equipment

SPECIAL SPECIFICATION 6911 Fiber Optic Video Data Transmission Equipment 2004 Specifications CSJ 3256-02-079 & 3256-03-082 SPECIAL SPECIFICATION 6911 Fiber Optic Video Data Transmission Equipment 1. Description. Furnish and install Fiber Optic Video Data Transmission Equipment

More information

White Paper. Cabling for Success with DXLink TM Author: Curry Kinyon Co-Author: Jeff Howes Co-Author: Ann Yanecek

White Paper. Cabling for Success with DXLink TM Author: Curry Kinyon Co-Author: Jeff Howes Co-Author: Ann Yanecek C ABLING FOR SUCCESS WITH DXLINK White Paper Cabling for Success with DXLink TM Author: Curry Kinyon Co-Author: Jeff Howes Co-Author: Ann Yanecek Page 1 AMX White Paper Cabling for Success with DXLink

More information

Term 1 Grade 11 -Task Sheet 2. Group: N/A (Not Applicable) Finishing Time: Make a CAT5 cable. Picture 1. Picture 2

Term 1 Grade 11 -Task Sheet 2. Group: N/A (Not Applicable) Finishing Time: Make a CAT5 cable. Picture 1. Picture 2 Term 1 Grade 11 -Task Sheet Name: SIS No Group: N/A (Not Applicable) Signed Date: Grade Start Time: Finishing Time: Make a CAT5 cable Picture 1 Picture Task Sheet Unit OBJECTIVE Understand the steps to

More information

USER MANUAL. PT-571HDCP DVI Line Transmitter. PT-572HDCP+ DVI Line Receiver MODELS: P/N: Rev 8

USER MANUAL. PT-571HDCP DVI Line Transmitter. PT-572HDCP+ DVI Line Receiver MODELS: P/N: Rev 8 KRAMER ELECTRONICS LTD. USER MANUAL MODELS: PT-571HDCP DVI Line Transmitter PT-572HDCP+ DVI Line Receiver P/N: 2900-000689 Rev 8 Contents 1 Introduction 1 2 Getting Started 2 2.1 Achieving the Best Performance

More information

EVLA Fiber Selection Critical Design Review

EVLA Fiber Selection Critical Design Review EVLA Fiber Selection Critical Design Review December 5, 2001 SJD/TAB 1 Fiber Selection CDR Decision about what fiber to install Select cable Jan 2002 Order cable Jan 2002 Receive cable May 2002 Start installation

More information

LCS2 Cat. 6 RJ 45 Patch panels and units

LCS2 Cat. 6 RJ 45 Patch panels and units 87045 LIMOGES Cedex Telephone: 33 0 5 55 06 87 87 - Fax: 33 0 5 55 06 88 88 LCS2 Cat. 6 RJ 45 CONTENTS Page 1. General characteristics....1 2. Presentation...2 3. Installation...2 4. Technical characteristics...2

More information

SMART CLASSix 48 UTP Patch Panels (with patching switches) -

SMART CLASSix 48 UTP Patch Panels (with patching switches) - Features Front-mounted Patching Switches connect ports internally, dramatically reducing the need for patch cords Compatible to Unshielded Twisted Pairs (UTP) cabling systems High performance panel that

More information

SPECIAL SPECIFICATION 1291 Fiber Optic Video Data Transmission Equipment

SPECIAL SPECIFICATION 1291 Fiber Optic Video Data Transmission Equipment 1993 Specifications CSJ 0500-01-117 SPECIAL SPECIFICATION 1291 Fiber Optic Video Data Transmission Equipment 1. Description. This Item shall govern for the furnishing and installation of Fiber Optic Video

More information

ADDENDUM #3. SPECIAL NOTE: Addendum #3 information shall supersede the information contained in the Contract Documents

ADDENDUM #3. SPECIAL NOTE: Addendum #3 information shall supersede the information contained in the Contract Documents WESLEYAN U N I V E R S I T Y Facilities 170 Long Lane Middletown, Connecticut 06457 (860) 685-3476 FAX (860) 685-3101 ADDENDUM #3 Date: March 4, 2013 Project: To: CFA A Rehearsal Hall AHU Replacement Annual

More information

RJ45FC6-BLU. Base Data. Category 6 modular keystone jack - Blue - 1/bag. Article Number: Part No. RJ45FC6-BLU. Type RJ45FC6. Color.

RJ45FC6-BLU. Base Data. Category 6 modular keystone jack - Blue - 1/bag. Article Number: Part No. RJ45FC6-BLU. Type RJ45FC6. Color. insertions Contact set constructed of phosphor bronze Category 6 modular keystone jack - Blue - 1/bag Article Number: 852-25065 Part Number: Type: RJ45FC6 Base Data Part No. Type Color Features RJ45FC6

More information

Keysight Technologies Method of Implementation (MOI) for BroadR-Reach Link Segment Tests Using E5071C ENA Option TDR

Keysight Technologies Method of Implementation (MOI) for BroadR-Reach Link Segment Tests Using E5071C ENA Option TDR Revision 2.00 August 28, 2014 BroadR-Reach Link Segment Keysight Technologies Method of Implementation (MOI) for BroadR-Reach Link Segment Tests Using E5071C ENA Option TDR 1 Table of Contents 1. Revision

More information

3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT

3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT 3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT For Tape Over Wire (TOW) and Wire-Over-Tape (WOT) Shielded Cable For 250 2000 kcmil cable with 650-mil primary insulation thickness Instructions

More information

VGA, Audio & RS232 Extender SET over Single CAT5 with RGB Delay Control & IR Pass Through

VGA, Audio & RS232 Extender SET over Single CAT5 with RGB Delay Control & IR Pass Through VGA, Audio & RS232 Extender SET over Single CAT5 with RGB Delay Control & IR Pass Through Model #: VGA-C5ARS-SET 2010 Avenview Inc. All rights reserved. The contents of this document are provided in connection

More information