Next Generation PoE Standards and Codes Update. Frank Straka Panduit Corporation
|
|
- Junior Cannon
- 6 years ago
- Views:
Transcription
1 Next Generation PoE Standards and Codes Update Frank Straka Panduit Corporation
2 Introduction Power over Ethernet is a HOT topic! New power levels dramatically increasing PoE device types New standards for equipment and cabling New code developed by NFPA for 2017 NEC New UL listing for PoE cables What do you need to know and what should you do?
3 Topics for Discussion Review the new PoE standard Discuss impact of PoE on cabling performance Discuss impact of NFPA codes on cabling Recommendation for putting it all together
4 What is PoE? Data and power over a single twisted pair cable Category 5e, 6, or 6A Terminology: Power Sourcing Equipment (PSE): A device that delivers (sources) power over a twistedpair copper cabling channel to a powered device. For example, a switch. Powered Device: (PD): A device that receives power from a PSE over the twisted-pair copper cabling channel. For example, an IP phone. Endspan: PSE type located at the end of the twisted-pair channel. For example, a switch. Midspan: PSE type located between a non-poe switch and a PD. Also called a PoE injector
5 How does PoE work? TODAY: IEEE802.3af, IEEE802.3at Type 1 & 2 Trade names of PoE, PoE+ Max speed of 1000BASE-T Power on 2 out of 4 pairs Up to 600mA / pair (300mA / wire) PSE: Max of 30W PD: Max of 25.5W PSE PD
6 Where is PoE Going? TOMORROW: IEEE802.3bt, Types 1, 2, 3, and 4 Trade names of PoE++, 4PPoE Max speed of 10GBASE-T Power on 4 out of 4 pairs Up to 960mA / pair (480mA / wire) PSE: Max of 99.9 W PD: Max of 71 W PSE PD
7 PoE Standards Summary Type Standards Maximum Current Number of Energized Pairs Power at Source Power at Device Maximum Data Rate Standard Ratified PoE IEEE 802.3af (802.3at Type 1) 350 ma W 13 W 1000BASE-T 2003 PoE+ IEEE 802.3at Type ma 2 30 W 25.5 W 1000BASE-T 2009 PoE++ (4PPoE) Proposed IEEE 802.3bt Type 3 Proposed IEEE 802.3bt Type ma 960 ma 4 60 W 99 W 51 W 71 W 10GBASE-T Expected 1Q2018 No IEEE standard Cisco UPOE HDBaseT ( 600 ma 1000 ma 4 60 W 100 W 51 W 100 W Varies Exists today no official ratification
8 Why is the new PoE standard exciting? TODAY TOMORROW
9 Summary of New PoE Standards Uses 4 out of 4 pairs Up to 71W to end devices Up to 10GBASE-T data rates Called PoE++ or 4PPoE
10 Topics for Discussion Review the new PoE standards Discuss impact of PoE on cabling performance Discuss impact of NFPA codes on cabling Recommendations for putting it all together
11 Cabling PoE Frequently Asked Questions What are the cabling requirements for PoE? For the new 4PPoE standard, 4-pair Category 5e or higher. Will the device get the power it needs regardless of cable length? YES. As long as the channel is standards compliant Cat 5e to Cat 6A at 100 meters or less, it will get the power it needs. Is there a difference between Categories? YES. PoE++ will run on Cat 5e and higher cabling. However, Category 6A provides the best thermals and power efficiency.
12 Standards Governing Cabling PoE IEEE P802.3bt Task Force Overall standard governing equipment and cabling TIA TSB-184-A Technical Service Bulletin on Guidelines for Supporting Power Delivery Over Balanced Twisted-Pair Cabling ISO/IEC TR and CENELEC TR International cabling guidelines for PoE++ ANSI/TIA-568-C.2 Familiar standard covering cabling performance IEC Standard for connectivity with engaging / disengaging PoE
13 TSB-184-A Overview Revision of old document to support higher power and current levels Tested multiple cable bundle sizes Measured temperature rise in center of bundle Limit temperature rise to less than 15 o C above ambient Temperature rise can: Cause signal degradation (e.g., attenuation) Cause long-term damage if temperature exceeds cable rating
14 Actual Results from TSB-184-A Testing 100-cable bundles Cat 6 and 6A, 28, 26, and 23 AWG performance with PoE Implications: All gauges work, have different bundle size limits All gauges will have different temp rises for different bundles sizes Cat 6A has best performance
15 Max Bundle Sizes for 15 o C Temp Rise 26 AWG Category 5e Category 6 Category 6A Category 8 Air Conduit Air Conduit Air Conduit Air Conduit Air Conduit 600mA mA mA From TIA TSB-184-A, Draft 6.1, Table A.5. Subject to change as document goes through ballot process (and subject to NEC 2017 compliance) Follow these guidelines to stay under 15 o C temperature rise Consult cable vendor for actual thermal rise in bundles Values shown here are conservative
16 ANSI/TIA-568-C.2 Overview Balanced Twisted-Pair Telecommunications Cabling and Components Standards Most people are familiar with this standard It is what you test channels and links to Provides guidance on effect of heat on cable insertion loss
17 Effect of Heat on Channel Length Temperature ( o C, ( o F)) Maximum* horizontal length, unscreened (m) Maximum* horizontal length, screened (m) 20 (68) (77) (86) (95) (104) (113) (122) (131) (140) * Assumes 10 meters of patch at 20 degrees C From ANSI/TIA-568-C.2, Table G.2 Additional insertion loss at higher temperature de-rates maximum channel lengths Conservative values Use vendor headroom warranties to estimate performance Consult cable vendor for specific performance
18 Temperature Rise Per Bundle Size Bundle Size MODEL, Cat 5e, 600 ma MODEL, Cat 6A, 600 ma MEAS., Cat 6A, 600 ma MODEL, Cat 5e, 1000 ma MODEL, Cat 6A, 1000 ma MEAS., Cat 6A, 1000 ma o C 0.8 o C 0.2 o C 3.7 o C 2.2 o C 1.4 o C o C 1.9 o C 0.5 o C 8.2 o C 5.2 o C 3.4 o C o C 3.2 o C 0.8 o C 13.3 o C 8.8 o C 5.7 o C o C 3.8 o C 1.0 o C 15.8 o C 10.7 o C 6.8 o C o C 5.3 o C 1.1 o C 21.3 o C 14.7 o C 8.9 o C o C 5.7 o C 1.2 o C 22.9 o C 15.9 o C 9.2 o C Cat 6A has the least temperature rise Both measured and modeled What does that mean for you?
19 What is the Impact to You? Heat of cable governed by: Ambient temperature Type of PoE used Category cable type (and its implementation) Bundle size Insertion Loss affected by Heat Therefore, can a relationship be established between bundle size and channel length? For a given ambient temperature, and assuming 4PPoE type 4?
20 Putting it all Together 5m loss! Use the channel table to compute effect of temperature rise to channel length Model shows 7 o C improvement with Cat 6A over Cat 5e Cat 5e exceeds 15 o C limit 7 o C translates to a loss of ~3 meters Measured shows 13.7 o C improvement with Cat 6A over Cat 5e 13.7 o C translates to a loss of ~5 meters Recommendation: INSTALL CAT 6A!
21 Ways to Mitigate Heat Rise 91 cable bundle 3 bundles of 37, no separation 3 bundles of 37, 1 separation 14.7 o C heat rise 11.8 o C heat rise 8.2 o C heat rise 25% higher 30% lower Per draft 6.1 of TSB-184-A, assuming Cat 6A cables, 1000 ma on all 4 pairs
22 Cat 6A is more efficient Cat 5e = more heat = more power lost Cat 6A is more efficient Larger wires, less heat, more power transferred How efficient? Cable Type Power Lost Category 5e 24.4 W Category 6A 20.1W Category 6A is 4.3 W more efficient per link!
23 Summary of PoE Performance Standards Install Cat 6A Cat 6A has larger bundle sizes Cat 6A can go longer reaches with PoE Cat 6A is more efficient
24 Topics for Discussion Review the new PoE standards Discuss impact of PoE on cabling performance Discuss impact of NFPA codes on cabling Recommendations for putting it all together
25 Impact of 2017 NEC Code Generally does not apply for power supplied over a communications cable when power levels are 60 watts or less Applicable for PoE++, Type 4 Not applicable for PoE++, Type 3 60 W covers vast majority of installations Recognizes a new UL listing for Limited Power (LP) cables LP listed cables are NOT required to run PoE If you do not have LP listing, you have to watch bundle sizes per ampacity table Uncertainty on how inspection will work Likely will vary by state and local interpretations Speculation: Inspections may occur by application type
26 When will the 2017 NEC Apply to Me? Depends on state Some states do not have statewide adoption Some states 1 or 2 versions behind Code is always open to interpretation at a local/state level!
27 How to Apply the 2017 Code Type Standards Maximum Current Number of Energized Pairs Power at Source Power at Device PoE IEEE 802.3af (802.3at Type 1) 350 ma W 13 W PoE+ IEEE 802.3at Type ma 2 30 W 25.5 W PoE++ (4PPoE) Proposed IEEE 802.3bt Type ma 4 60 W 51 W PoE++ (4PPoE) Proposed IEEE 802.3bt Type ma 4 90 W 71.3 W NEC 2017 not a concern NEC 2017 imposes new requirements
28 If the NEC 2017 Requirements Apply You are running IEEE802.3bt Type 4 PoE++ Either: Use a LP listed cable rated to at least 0.5A OR Refer to ampacity table for bundle size. Bundle size depends on: Cable Temperature Rating Wire Gauge Ambient temperature
29 LP Cables LP means Limited Power Example Marking: TYPE CMP-LP(0.5A) (UL) 23 AWG 90 o C New LP marking after CMP LP(0.5A) covers PoE++ Type 4 up to 100W 0.5A refers to amperes per wire Higher LP ratings such as 0.7A are up to 140W
30 Ampacity Table AWG Number of 4-Pair Cables in a Bundle Temp Rating Temp Rating Temp Rating Temp Rating Temp Rating Temp Rating Temp Rating 60 o C 75 o C 90 o C 60 o C 75 o C 90 o C 60 o C 75 o C 90 o C 60 o C 75 o C 90 o C 60 o C 75 o C 90 o C 60 o C 75 o C 90 o C 60 o C 75 o C 90 o C NA NA NA Note 1: For bundle sizes over 192 cables, or for conductor sizes smaller than 26 AWG, ampacities shall be permitted to be determined by qualified personnel under engineering supervision. Note 2: Where only half of the conductors in each cable are carrying current, the values in the table shall be permitted to be increased by a factor of 1.4. For common 23AWG cables: Maximum bundle size for a 60 o C rated cable running 802.3bt Type 4 is 91 cables Maximum bundle size for a 75 o C or 90 o C cable running 802.3bt Type 4 is 192 cables
31 Summary of 2017 NEC Code Only applies for > 60W (Type 4) New UL listing for LP cables LP rating of at least 0.5A needed Without LP refer to ampacity table
32 Topics for Discussion Review the new PoE standards Discuss impact of PoE on cabling performance Discuss impact of NFPA codes on cabling Recommendations for putting it all together
33 How big to bundle? Now there are 2 documents discussing bundle sizes Performance (TSB-184-A) NEC ampacity table for non-lp cables How do you put them together?
34 What you need to know What is the ambient temperature? What is the length of the channel? Is the cable LP rated? If not, what is the cable temperature rating and wire gauge? What this determines: Maximum bundle size
35 Example: 92 meter channel needed, Setting: Want to run PoE++, type 4 Cable has 60 o C rating Ambient is 30 o C Cable is 23AWG Cable is Cat 6A Cable is NOT LP rated no LP cables NEC 2017 ampacity table limits to 91 cables Per ANSI/TIA-568-C.2 IL table: Channel derating of 8 meters occurs with a cable temperature of 45 o C 45 o C derating implies a 15 o C bundle temperature rise over ambient (30 o C + 15 o C) Per TSB-184-A, Cat 6A bundle model says cable can be >91 cables for 15 o C temp rise Per actual test data, Cat 6A bundle can be > 100 cables for 15 o C temp rise BUNDLE SIZE LIMIT: 91 cables per NEC 2017 ampacity table
36 Example: 92 meter channel needed, Setting: Want to run PoE++, type 4 Cable has 60 o C rating Ambient is 30 o C Cable is 23AWG Cable is Cat 6A Cable IS LP listed for 0.5A with LP cables LP cables allow you to not refer to ampacity table Per ANSI/TIA-568-C.2 IL table: Channel derating of 8 meters occurs with a cable temperature of 45 o C 45 o C derating implies a 15 o C bundle temperature rise over ambient (30 o C + 15 o C) Per TSB-184-A, Cat 6A bundle model says cable can be >91 cables for 15 o C temp rise Per actual test data, Cat 6A bundle can be > 100 cables for 15 o C temp rise BUNDLE SIZE LIMIT: Follow TSB-184-A or vendor guidance on bundle size limit
37 Example: 92 meter channel needed, Setting: Want to run PoE++, type 4 Cable has 75 o C rating Ambient is 30 o C Cable is 24AWG Cable is Cat 5e Cable IS LP listed with Cat 5e LP cables LP cables allow you to not refer to ampacity table Per ANSI/TIA-568-C.2 IL table: Channel derating of 8 meters occurs with a cable temperature of 45 o C 45 o C derating implies a 15 o C bundle temperature rise over ambient (30 o C + 15 o C) Per TSB-184-A, Cat 5e model says cable can be <61 cables for 15 o C temp rise BUNDLE SIZE LIMIT: Follow TSB-184-A for 61 cables Cat 5e has much worse performance. INSTALL CAT 6A!
38 Summary LP shifts bundle size to TSB-184-A Without LP, TSB-184-A & ampacity table Understand ambient, bundle temp Install Cat 6A for best performance
39 Questions?
Advanced PoE - The Impact of Higher Power PoE++ on Twisted-Pair Structured Cabling
Advanced PoE - The Impact of Higher Power PoE++ on Twisted-Pair Structured Cabling Next Generation PoE Connect significantly more devices due to higher power Affects cabling due to the additional heat
More informationHow to Implement PoE in Your Harsh Industrial Environment
Produced by: Engineering 360 Media Solutions July 2018 How to Implement PoE in Your Harsh Industrial Environment Sponsored by: Quabbin Wire & Cable Co., Inc. There is little doubt that the internet of
More informationSelecting Cables for Power over Ethernet
Hitachi Cable America Inc. Selecting Cables for Power over Ethernet Factors to Consider when Selecting the Appropriate Cable 8/12/217 Ratio of Power Dissipated vs 1 Power over Ethernet Standards and applications
More informationUse Case Summary. Faisal Ahmad, Akros Silicon IEEE 802.3bt, September 2014
Use Case Summary Faisal Ahmad, Akros Silicon IEEE 802.3bt, September 2014 1 Objectives To compile a list of use cases that the task force will consider to meet its objectives For purposes of discussion,
More informationChallenges for testing 10GBASE-T
Challenges for testing 10GBASE-T Adrian Young Customer Support Manager adrian.young@flukenetworks.com Check list Category 6A component compliant connector Category 6A compliant cable Perfect terminations
More informationCATEGORY 6A CABLING SOLUTIONS
10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Need of 10 Gigabit Service Application as
More informationCATEGORY 6A CABLING SOLUTIONS
10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Premium Line Category 6A Cabling Solutions
More informationIEEE-SA SCC-18 Report by Representatives to NFPA NEC CMP-6 January 6-8, 2010 on Actions Taken on Proposals by CMP-6 for NEC 2011 ROC Prepared by
IEEE-SA SCC-18 Report by Representatives to NFPA NEC CMP-6 January 6-8, 2010 on Actions Taken on Proposals by CMP-6 for NEC 2011 ROC Prepared by Bruce McClung, McSquared Electrical Consulting LLC l.b.mcclung@ieee.org
More informationPre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017
Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM-2017-2 Date: 05/26/2017 Additional specification information for data communication to cameras and between Library
More informationRobert Burén. Product Manager. Nexans Cabling Solutions. 10G Solutions
Robert Burén Product Manager 10G Solutions Nexans Cabling Solutions 1 10 Gigabit Ethernet.Performance 30 GByte can be transmitted within 24 seconds Example: MRI-scan size is 30GB as average A memory device
More information10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System
10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System Next-Generation Category 6A UTP Cabling System Drivers for 10 GbE Aggregation of Gigabit Links Server Consolidation and
More informationLCS2 Cat. 6 RJ 45 Patch panels and units
87045 LIMOGES Cedex Telephone: 33 0 5 55 06 87 87 - Fax: 33 0 5 55 06 88 88 LCS2 Cat. 6 RJ 45 CONTENTS Page 1. General characteristics....1 2. Presentation...2 3. Installation...2 4. Technical characteristics...2
More informationThe need for Encircled Flux, real or imaginary?
Version 1.7 The need for Encircled Flux, real or imaginary? Harley Lang, RCDD Fluke Networks 14 March, 2013 Presentation agenda What s the issue Mandrels are they needed? Review of standards Coupled Power
More informationPoE: Adding Power to (IoT)
Sponsored by: PoE: Adding Power to (IoT) Sponsored by: December 20th, 2018 1 Today s Speakers Sponsored by: Steve Bell Senior Analyst - IoT Heavy Reading Mohammad Shahid Khan Chief Manager (PLM & AE),
More informationIEEE 802.3af Power via MDI Standard Compliant Mid-Span Insertion Solution. Presented by PowerDsine: David Pincu -
IEEE 802.3af Power via MDI Standard Compliant Mid-Span Insertion Solution Presented by PowerDsine: David Pincu - davidp@powerdsine.com Objectives! Investigate the Channel /Link options! Identify the requirements
More informationTB876BSX-3WH Class E A / Cat.6A STP Keystone Jack (Auto press-fit)
TB876BSX-3WH / Cat.6A STP Keystone Jack (Auto press-fit) Copper braid can be fully contacted and covered for 23-26 AWG solid wire. Press-fit process. 100% RoHS compliant, without soldering. Unique design
More informationtechnicalreport MegaLine Connect100 Class E A links over 100 metres in length Data communication technology 09/2018 Classic structure 2-connector link
technicalreport Data communication technology 09/2018 Classic structure 2-connector link Ethernet transmission with twisted pair cables Limiting factors for links > 100 m Example structure of a 2-connector
More informationCATEGORY 5e CABLING SOLUTIONS
With the high speed data transmission requirement in LAN, 1998 IEEE ratified standard 802.3z defined protocol 1000BASE-T over Category 5e and higher level Ethernet cabling system. After that, with the
More informationHDBaseT vs. IP. Bob Ferguson, RCDD, CTS I Belden Regional Sales Engineer Broadcast and Audio Video Group
HDBaseT vs. IP Bob Ferguson, RCDD, CTS I Belden Regional Sales Engineer Broadcast and Audio Video Group System Support All Three Video and Audio HDBaseT 5Play Video USB 2.0 Control Signals 100BaseT Ethernet
More information10 Mb/s Single Twisted Pair Ethernet Preliminary Cable Properties Steffen Graber Pepperl+Fuchs
10 Mb/s Single Twisted Pair Ethernet Preliminary Cable Properties Steffen Graber Pepperl+Fuchs IEEE802.3 10 Mb/s Single Twisted Pair Ethernet Study Group 9/8/2016 1 Overview Cable Properties Cable Measurements
More informationTender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab*
Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab* General Scope of Work: Supply and installation of Computer Laboratory setup in MIU Location of Installation:
More informationMIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project
1.1.0 GENERAL The purpose of this specification is to establish a requirement for the installation of a voice, video and data cable network. The cable (copper), wire, hardware, equipment racks, jumpers,
More informationPower Injector 1520 Series
Power Injector 1520 Series Technical Specifications Input voltage 100 to 240 VAC Output voltage 56.0 VDC Voltage range tolerance 54 VDC to 57 VDC Maximum current 1.43 A No load current 15 ma 56VDC@0.71A
More informationGIGALAN AUGMENTED CABLE CAT6A F/UTP 23AWGX4P LSZH
GIGALAN AUGMENTED CABLE CAT6A F/UTP 23AWGX4P LSZH Product Type LAN Cable Product Family Construction GigaLan Augmented RoHS Compliant Category 6A F/UTP LSZH General Characteristics Features Installation
More informationSECTION COMMUNICATIONS HORIZONTAL CABLING
(NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 - GENERAL 1.1 SECTION
More informationContinuous Currents. When inspectors see a photovoltaic (PV) power system. through Curious Cables. by John Wiles
PV Wiring: Continuous Currents through Curious Cables by John Wiles When inspectors see a photovoltaic (PV) power system for the first time, they will usually be faced with a type of wiring method not
More informationNCB-C6SGRYR M Category 6 STP Solid Cord. Specification. Doc. Version: /09/30
NCB-C6SGRYR-305 305M Category 6 STP Solid Cord Specification Doc. 2010/09/30 Version History Date Version Description 2010/04/13 1.0 Initial (Dennis Yu) Add Conductor OD Insulation Material/OD/Average
More informationGIGALAN CAT.6 U/UTP 23AWGx4P - LSZH (EXP)
GIGALAN CAT.6 U/UTP 23AWGx4P - LSZH (EXP) Product Type LAN Cable Product Family Construction GigaLan RoHS-2 Compliant Category 6 U/UTP (unshielded) LSZH General Characteristics Features Installation Environment
More informationCategory 5e F/UTP Euroclass D ca Cables
Category 5e F/UTP Euroclass D ca Cables Datasheet: GD103437v2 APPLICATION The Brand-Rex GPF D ca cables are compliant with the European Construction Products Regulation, achieving Euroclass level D ca
More informationFUTURE PROOF YOUR CONNECTIONS
FUTURE PROOF YOUR CONNECTIONS DataMax Commercial Data Cable The Strongest Link. When you choose Quabbin Wire and Cable you are not only selecting a premier cable, you are also investing in productivity
More informationPre-terminated cabling system Modular cassette technology with 6x RJ45 C6 A ports
RJ45 - Cat. 6A Pre-terminated cabling system Modular cassette technology with 6x RJ45 C6 A ports Compatible with FO trunks Modern data centre trunk solution in modular cassette technology Pre-terminated
More informationLCS 2 RJ 45 Cat. 6A HD panels and units
87045 LIMOGES Cedex Telephone: (+33) 05 55 06 87 87 - Fax: +33 (0)5 55 06 88 88 Page 0 335 85/86 1. General characteristics....1 2. Presentation...1 3. Positioning...1 4. Technical characteristics...1
More informationWhat really changes with Category 6
1 What really changes with Category 6 Category 6, the standard recently completed by TIA/EIA, represents an important accomplishment for the telecommunications industry. Find out which are the actual differences
More informationTB806AUX Class E A / Cat.6A UTP Keystone Jack (Auto press-fit)
TB806AUX / Cat.6A UTP Keystone Jack (Auto press-fit) Cable holder with Strain Relief (SR) function: secure the cable with cable tie, and not wiggle to affect the termination and transmission. Cap: easy
More informationEverything you always wanted to know about HDBaseT*
Everything you always wanted to know about HDBaseT* * But were afraid to ask Bill Lauby Sr. Product Manager Leviton Network Solutions Speaker Bio Bill Lauby, Sr. Product Manager Leviton Network Solutions
More informationPower and Control T YPE BY RAVI GANATR November/December IAEI NEWS
Power and Control 26 1999 November/December IAEI NEWS T YPE BY RAVI GANATR This article discusses how the requirements in both the installation code and the product standard are utilized to manufacture
More informationFlygt Submersible Motor Cables
Flygt Submersible Motor Cables This brochure contains an overview of the Flygt motor cable assortment. The cables are especially designed for submersible use and made of carefully selected materials. The
More informationCOMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationThe University of Texas at Austin September 30, 2011
SECTION 27 08 20 COPPER TESTING PART 1 - GENERAL 1.1 SUMMARY A. Test measurements shall be taken for all balanced-twisted pair cabling, including horizontal and backbone copper cables and wall-to-rack
More informationHARTING Ethernet cabling cables and connectors, 4 wire
Industrial Cat. 5e Standard cable, 4-wire Type A for permanent installation or to build-up PROFINET system cables PVC X 8 wire X Cat. 5e X Cat. 6 Cat. 6 A Cat. 7 Cable structure Core structure Wire insulation
More informationAMP CO Plus System Overview & Design Application Guide
AMP CO Plus System Overview & Design Application Guide Modern Infrastructures Solutions for the Future A publication of Tyco Electronics Introduction Structured premise cabling systems have become state
More informationGenSPEED Category 5e Cables 3
Datacom GenSPEED Category 5e Cables 3 GenSPEED Category 5e cables are available in a wide variety of performance levels and constructions. With many options to pick from, you can select the GenSPEED Category
More informationSECTION COMMUNICATIONS HORIZONTAL CABLING
SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors including patch panels. 3. Cabling identification
More informationCopper Solution Contents Cabinets Fiber Optic Solution
Contents Copper Solution Category 6A + Cabling Solutions Cat.6A + 1000MHz S/FTP Installation Cable A1 Cat.6A + S/FTP Patch Cord A2 Cat.6A + 90 Fully Shielded Die-casting Keystone Jack A3 Modular German
More informationProduct information 19" 1U HD Patch Panel 48xRJ45/s, Cat. 6A, gray, fully populated
Product information 19" 1U HD Patch Panel 48xRJ45/s, Cat. 6A, gray, fully populated R512417 966740615 1 Pcs. 090.6102 Metal patch panel with integrated cable tie shelf. 19" 1U HD patch panel 4 12-port/s
More informationHighBand 25. TrueNet Category 6 Solutions
HighBand 25 TrueNet Category 6 Solutions The highest performing cross-connect system in the world. A unique high-density solution with superior cable management. ADC KRONE s HighBand 25 cross connect solution
More informationSECTION 7 -- CROSS-CONNECT SYSTEMS
DETAIL ENGINEERING REQUIREMENTS AT&T March, 2016 Section 7, ATT-TP-76400 Revised NA SECTION 7 -- CROSS-CONNECT SYSTEMS CONTENTS PAGE 1. GENERAL... 7-2 1.1. Introduction... 7-2 1.2. Cable Holes... 7-2 1.3.
More informationCambria County Association for the Blind and Handicapped 175 Industrial Park Road Ebensburg, PA Prepared for: Prepared by:
Cable Management in Solar PV Arrays: A Review of Requirements in the National Electrical Code and how CAB Cable Rings and Saddles Meet These Requirements Prepared for: Cambria County Association for the
More informationGenSPEED 10 MTP Category 6A Cable An Unshielded 6A Cable with Superior Protection Against Alien Crosstalk
GenSPEED A Cables GenSPEED 10 MTP A Cable An Unshielded 6A Cable with Superior Protection Against Alien Crosstalk 10 MTP unshielded-twisted pair (UTP) design provides industry-leading protection from external
More informationInterface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE
Interface Practices Subcommittee AMERICAN NATIONAL STANDARD Specification for Braided 75 Ω, Mini-Series Quad Shield Coaxial Cable for CMTS and SDI cables NOTICE The Society of Cable Telecommunications
More informationAbout Nexans 3. About Berk-Tek 4. LANmark-1000 Cat 6 UTP 5. LANmark-1000 Category 6 Plenum 6. LANmark-1000 Category 6 Riser 11
Table of contents About Nexans 3 About Berk-Tek 4 LANmark-1000 Cat 6 UTP 5 LANmark-1000 Category 6 Plenum 6 LANmark-1000 Category 6 Riser 11 LANmark-1000 Category 6 Patch 16 21 7/10/07 - http://www.berktek.com
More informationCATEGORY 6 CABLING SOLUTIONS
With over 20 years experience and know-how on communicating products design & developing, Premium Line has built maturity systems both in high tech develop and research center & complete structural quality
More informationPart Number: 7940A Cat 6 DataTuff, (4 pr) 23 AW G Solid BC, PO/PVC, EtherNet/IP, CMR, CMX-Outdoor
Part Number: Cat 6 DataTuff, (4 pr) 23 AW G Solid BC, PO/PVC, EtherNet/IP, CMR, CMX-Outdoor Product Description Four Cat 6 23 AW G solid bare copper conductors, bonded pair polyolefin Insulation, DATATUFF
More informationCoastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents
PART 1 - GENERAL 1.1 SUMMARY SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors. 3. Cabling system identification products. 1.2
More informationHDBaseT in AV Systems: 7 Basics for Successful Deployment. Dan Underbrink, RCDD Principal Applications Engineer Leviton Network Solutions
HDBaseT in AV Systems: 7 Basics for Successful Deployment Dan Underbrink, RCDD Principal Applications Engineer Leviton Network Solutions Ensuring a Successful HDBaseT Deployment 1. Understand HDBaseT signal
More informationHD-One DX/DX500 HDMI Extender
HD-One DX/DX500 HDMI Extender User Manual Version 2.0 tvone 2791 Circleport Drive, Erlanger, KY 41018, USA. Americas: 859-282-7303 EMEA: +44 (0) 1843 873322 Email: tech.usa@tvone.com www.tvone.com CSG-DX-500
More informationSafety Codes Council Conference Banff C Panel Discussion
Safety Codes Council Conference Banff 2014 90 C Panel Discussion Tim Driscoll OBIEC Consulting Ltd. George Morlidge Fluor Canada Ltd. Scott Basinger Eaton Canada René Leduc Marex Canada Limited Perspectives
More informationCategory 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards.
27 08 00 Certification and Commissioning of Communication Systems (Revision date: 7/3/12) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are
More informationOASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices
OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices Berk-Tek recommends installing a well-designed structured cabling channel per the TIA standards. This includes up to 100
More informationDetailed Specifications & Technical Data
For more Information please call 1-800-Belden1 General Description: CAT6A (625MHz), 4-Pair, U/UTP-Unshielded, Plenum-CMP, Premise Horizontal Cable, 23 AWG Solid Bare Copper Conductors, FEP Insulation,
More informationObsolete Product(s) - Obsolete Product(s)
Power over ethernet 10 W module Preliminary data Features Input voltage range: 38.5 V to 60 V 10 W output Based on ST devices integrating standard PoE interface and current mode PVM controller IEEE 802.3af
More informationSTRUCTURED CABLE SYSTEM (SCS)
PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated
More informationBelden IBDN System 10GX Enabling Technologies
Belden IBDN System 10GX Enabling Technologies by Paul Kish Director, Systems and Standards Revision 1 November 2008 Belden Belden IBDN System 10GX Enabling Technologies 1/17 Introduction The IEEE 802.3an
More informationCalifornia Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.
PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated
More informationData Communication Products
Data Communication Products Premises Copper Table of Contents Premises Category cables Category 6A 650MHz UTP Cable... 2 Category 6A 650MHz FTP Cable... 4 Category 6+ 550MHz UTP Cable... 6 Category 6+
More informationUser Manual Entry Line Industrial Fast Ethernet Switch 4x 10/100Base-TX, 1x 100Base-X Fiber Port 4x PoE+ up to 30W
User Manual Entry Line Industrial Fast Ethernet Switch 4x 10/100Base-TX, 1x 100Base-X Fiber Port 4x PoE+ up to 30W Entry Line Fast Ethernet Switch Fast Ethernet Switch with PoE+ for Industrial Use Page
More informationWIRE AND CABLE FIRE TESTS
TEST CSA C22.2 No 2556-13 Section 9.4 (FV-2/VW-1) (Small Scale Vertical) # OF VALUES REPORTED FOOTAGE REQUIRED 3 3 pieces: 24 each 5 7 days PERFORMANCE TIME CSA-FT1 (Small Scale Vertical) 3 5 pieces: 24
More informationDimensions. Electrical Specifications. Environmental Specifications. General Specifications. Mechanical Specifications.
CPC331T-01 GS8E-XT1-BK GigaSPEED XL GS8E T1 Crossover Stranded Cordage Modular Patch Cord, Black Jacket Dimensions Cord Length, maximum 30 m 100 ft Cord Length, minimum 1 m 1 ft Electrical Specifications
More informationPREMIUM 5e F/UTP PRODUCTS
Siemon s end-to-end cabling system is guaranteed to provide transmission performance margins in excess of industry standards for category 5e parameters, while featuring excellent EMI resistance. has been
More informationHIGH-PERFORMANCE COPPER AND FIBER SYSTEM SOLUTIONS. DELIVERING CUSTOMER-DRIVEN Performance, Quality & Service
HIGH-PERFORMANCE COPPER AND FIBER SYSTEM SOLUTIONS DELIVERING CUSTOMER-DRIVEN Performance, Quality & Service Partners since 2004, Panduit and General Cable have offered a comprehensive line of physical
More informationAbout Nexans 3. About Berk-Tek 4. Hyper Plus 5e Cat 5e UTP 5. HyperPlus 5e Plenum 6. Hyper Plus 5e Riser 10. HyperPlus 5e Patch 14
Table of contents About Nexans 3 About Berk-Tek 4 Hyper Plus 5e Cat 5e UTP 5 HyperPlus 5e Plenum 6 Hyper Plus 5e Riser 10 HyperPlus 5e Patch 14 HyperPlus 5e OSP 18 22 7/10/07 - http://www.berktek.com Page
More informationMohawk Master Catalog
Mohawk Master Catalog Cabling Excellence for Open Architecture Mohawk s Green Initiative Even in the early stages of product development, ecological aspects from energy and resource consumption to the
More informationENGINEERING COMMITTEE
ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 32 2016 Ampacity of Coaxial Telecommunications Cables NOTICE The Society of Cable Telecommunications Engineers
More informationBenefits of a Small Diameter Category 6A Copper Cabling System
Benefits of a Sall Diaeter Category 6A Copper Cabling Syste The Panduit TX6A-SD Gig UTP Copper Cabling Syste with MaTriX Technology is a cost effective, sall diaeter Category 6A UTP cabling syste that
More informationEffective earthing of screened cables
NOVEMBER 2006 Effective earthing of screened cables All metallic containment items, other extraneous metalwork and the screens of telecommunications cables in an information technology environment must
More informationPoE Over Coax Extender Kit
Comply with IEEE.802.3af User Manual Data Sheet PoE Over Coax Extender Kit PoEoC-15K PoEoC-15-HOST PoEoC-15-D Host Unit - PSE Side Device Unit PD Side By using RF technology, this kit can extend the transmission
More informationCisco Aironet 1520 Series Outdoor Mesh Access Point Power Injector Installation Instructions
Cisco Aironet 1520 Series Outdoor Mesh Access Point Power Injector Installation Instructions This document describes the Cisco Aironet 1520 Series Outdoor Mesh Access Point Power Injector (hereafter referred
More informationHigh Temperature Operation of Extruded Distribution Cable Systems. White Paper
High Temperature Operation of Extruded Distribution Cable Systems White Paper October 2018 NOTICE The information contained herein is, to our knowledge, accurate and reliable at the date of publication.
More informationUSER GUIDE. AXIS T8640 Ethernet Over Coax Adaptor PoE+ ENGLISH
USER GUIDE AXIS T8640 Ethernet Over Coax Adaptor PoE+ ENGLISH Electromagnetic Compatibility (EMC) This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in
More informationC6 A modul and C6 A modul K. The new connection system for a wide variety of applications of course with Cat.6 A
C6 A modul and C6 A modul K The new connection system for a wide variety of applications of course with Cat.6 A Intelligent system solution for structured cabling Nowadays the need for high data transfer
More informationANSI/TIA-PN D-R1. Broadband Coaxial Cabling and Components Standard Draft 2, March 8, 2017 TABLE OF CONTENTS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 Broadband Coaxial Cabling and Components Standard Draft 2, March 8, 2017 TABLE
More informationANSI/TIA-PN D. Broadband Coaxial Cabling and Components Standard Draft 1, October 11, 2016 TABLE OF CONTENTS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 Broadband Coaxial Cabling and Components Standard Draft 1, October 11, 2016
More informationCAT5E NETWORK PATCH LEADS
CAT5E NETWORK PATCH LEADS Cat5e UTP Patch Leads - 50 MHz The Category 5 enhanced UTP patch leads conform to the TIA/EIA-568-B specification. Cables are pre-made to the T568A pinout specification with tangle
More informationVocia VI-6. Operation Manual
Vocia VI-6 Operation Manual Biamp Systems 9300 S.W. Gemini Drive, Beaverton, Oregon 97008 U.S.A. (503) 641-7287 www.biamp.com table of contents vocia INPUT 6 (vi-6) features..............................................................
More informationUC Copper / Fibre summary on USPs. Zoran Borcic, Axel Koplev
UC Copper / Fibre summary on USPs Zoran Borcic, Axel Koplev Draka UC Cable Key Elements UC Copper Range Shielded solutions Focus on Cat. 6 A / 7/ 7 A Prepare for Cat.8 / 40G Patent based design Cat. 6
More informationNanoStation NanoStation. NanoStation. Compact, Hi-Power, 2x2 MIMO AirMax TDMA Station. *Respaldo y Garantía. Datasheet
Compact, Hi-Power, 2x2 MIMO AirMax TDMA Station Models: NSM2, NSM3, NSM365, NSM5, LOCOM2, LOCOM5, LOCOM9 Cost Effective, Hi-Performance Compact and Versatile Design Powerful integrated Antenna *Respaldo
More informationHigh Speed Data Connector (HSSDC) For 100 MBit/Sec Token Ring. John L. Hill AMP Incorporated July, 1998
High Speed Data Connector (HSSDC) For 100 MBit/Sec Token Ring John L. Hill AMP Incorporated July, 1998 High Performance Cable Assembly Characteristics Controlled/Matched Impedance Connectors and Cables
More informationVolition TM RJ45 K5e Jacks
Volition TM RJ45 K5e Jacks Part of our 3M Volition Network Solutions, the new K5e range is our ultimate Category 5e hardware component (ISO/IEC 11801, EN 50173 and ANSI/TIA/EIA-568). The K5e jack is a
More informationBenefits of a Small Diameter Category 6A Copper Cabling System
Benefits of a Sall Diaeter Category 6A Copper Cabling Syste The Panduit TX6A-SD Gig UTP Copper Cabling Syste with MaTriX Technology is a cost effective, sall diaeter Category 6A UTP cabling syste that
More informationMagic Patch Patch Leads & Accessories
Magic Patch Patch Leads & Accessories T: 01376 346600 F: 01376 346620 www.connectixcablingsystems.com Issue 1.1 Magic Patch Cabling Systems TM Magic Patch Connectix Cabling Sytems TM range of patch leads,
More informationDescription: Pair Color Code Chart: Pair Color Chart 1 Brown White Brown 2 Orange White Orange 3 Green White Green 4 Blue White Blue.
Description: OZLINX CAT5e cable has a guaranteed performance; exceeds the Category 5e performance requirements and provides positive PSACR up to 155MHz for bandwidth requirement in the future. Product
More information3M Sensored Termination (15 kv) QX-T15I-vi1-E
3M Sensored Termination () QX-T15I-vi1-E Data Sheet May 2016 Kit Contents: Each kit contains sufficient quantities of the following materials to make three single-phase terminations. 31" (REF) One piece
More informationLAN Cabling Systems Copper
LAN Cabling Systems Copper Table of content About Nexans 3 Copper 4 Essential Cat 5e Cable 5 LANmark-6 Cable 7 LANmark-6A Cable 9 LANmark-7 Cable 11 LANmark-7A Cable 13 Legal Notice 14 8/20/11 - http://www.nexans-fi.com
More informationPremise Installation Guide
Premise Installation Guide Table Of Contents Overview of Cabling Standards...1-2 Horizontal Cabling System Structure...3-5 Work Area... 6 Horizontal Distances of Copper Links (Open Office)... 7 Twisted
More informationUSER MANUAL. PSE-2 10Gb POE Injector MODEL: P/N: Rev 1.
USER MANUAL MODEL: PSE-2 10Gb POE Injector P/N: 2900-300452 Rev 1 www.kramerav.com This page is intentionally left blank Contents 1 Introduction 1 2 Getting Started 2 2.1 Achieving the Best Performance
More informationllen-bradley 194R-HM4-NFPA3
Technical Data Rotary Disconnect Switch Specifications Bulletin Number 194R Topic Page Product Line Overview 2 General Specifications Fuse Description 12 Approximate Dimensions 14 Additional Resources
More informationSY-HDBT-SLIM-100S Extender Set
Installation Guide SY-HDBT-SLIM-100S Extender Set with HDMI, Ethernet, IR, RS232 and Power over 100m of cat6 Cable HDBaseT HDMI Extenders SY Electronics Ltd, Unit 7, Worrall Street, Salford, Greater Manchester,
More informationREQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus
REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus PART 1: GENERAL REQUIREMENTS A. Contractor Work 1. Provide and install (except as noted in this document), cable,
More informationCHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT
CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT Purchasing and Warehouse Services Department October 1, 2007 Addendum No. 1 INVITATION FOR BID No. 08-09 Temporary Faculty Offices, Chabot College All Prospective
More informationRadioRA 2 Enhancement and Interface, 120V main repeater with MHz to MHz or MHz to MHz
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-794 Fax: 936-560-4685 RRAINREPWH RR2 ain Repeater Lutron Catalog Number anufacturer Description Weight per unit Product Category RRAINREPWH Lutron
More information