TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 PURPOSE 2.0 SCOPE 3.0 CODES, STANDARDS AND REFERENCES
|
|
- Mark Fields
- 6 years ago
- Views:
Transcription
1
2 TABLE OF CONTENTS 1.0 PURPOSE 2.0 SCOPE 3.0 CODES, STANDARDS AND REFERENCES 4.0 ORDER OF PRECEDENCE 5.0 SYSTEM PARAMETERS 5.1 Frequency 5.2 System Voltage 5.3 Short Circuit Rating 5.4 Insulation Levels 6.0 DEVIATIONS PAGE NO. 2 OF 6
3 1.0 PURPOSE This chapter of the U/G Power Cable Transmission Engineering Standards (TES-P-104) is an introductory chapter to (TES-P-104). It provides general information applicable to underground cables and their applications to the system of Transmission Business Unit (TBU) of Saudi Electricity Company (SEC), Kingdom of Saudi Arabia. Chapters of TES-P-104 and the references therein serve as a guide to the Design Engineer. 2.0 SCOPE The U/G Power Cable Transmission Engineering Standards (TES-P-104): 2.1 Covers the following cable nominal voltage ratings: Service (Low Voltage) Cables: 0.6/1 kv Distribution (Medium Voltage) Cables: 13.8 kv or 34.5 kv Transmission (High Voltage) Cables: 69 kv, 110 kv, 115 kv, 132 kv, 230 kv or 380 kv. 2.2 Reflects the use of the following types of cables and their applications: Cross-Linked Polyethylene Cable (XLPE) Low Pressure Oil-Filled Cable (LPOF). 2.3 Intended to help the Design Engineer in selection of the appropriate type and size of the power cable. 2.4 Contains the type of installation and the installation requirements in details. These are developed to govern the practices and procedures which shall be adopted by the Design Engineer for the design of underground cable systems. 2.5 Covers the drawings and ampacity tables in different installations cases and their requirements in details, which shall enable the engineers to design and install the power cables within the specified parameters. 2.6 Shows the various types and requirements of splicing and terminations of XLPE and LPOF power cables. However, it shall not cover the requirements for LPOF or XLPE cable termination at GIS cable boxes or at oil boxes at power transformers. 2.7 Serves as a guideline in selection of the single core power cable sheath bonding and grounding method of insulated metallic sheath of power cables. 2.8 The technical data provided in this standard (TES-P-104) for 0.6/1 kv, 13.8 kv or 34.5 kv are intended for general information. PAGE NO. 3 OF 6
4 2.9 In case of additional technical requirements, details or information not contained in this standard, the Design Engineer is responsible to have the cable system accurately designed. 3.0 CODES, STANDARDS AND REFERENCES 3.1 Items not specifically covered in this standard (TES-P-104) shall be in accordance with the latest revisions of the referenced Industry Codes and Standards. 3.2 It shall be the responsibility of the Design Engineer preparing the base design or detailed design to be or become knowledgeable of the requirements of the latest Industry Codes and Standards referred in TES-P-104. He shall bring to the attention of TBU of SEC, any latest revisions of these Codes and Standards which may have an impact on the technical requirements of TES-P Whenever different Codes and Standards are used, TBU of SEC approval to the same shall be obtained before proceeding with design. These Codes and Standards shall be equal to or better than those specified in TES-P ORDER OF PRECEDENCE In case of any conflict between various documents and standards or specifications for U/G power cable projects, the order of precedence shall be as follows: 4.1 The Scope of Work and Technical Specifications (SOW/TS) for the project. 4.2 Transmission Materials Standard Specifications (TMSS). 4.3 This standard (TES-P-104). 4.4 Other applicable Transmission Engineering Standards (TES). 4.5 Applicable Industry Codes and Standards. 5.0 SYSTEM PARAMETERS 5.1 Frequency The nominal frequency for SEC system is 60 Hz and the permissible operating frequency range is between 59.9 Hz and 60.1 Hz. The transient frequency variations shall be between 58.5 Hz and 61.5 Hz. 5.2 System Voltage The standard nominal system voltages adopted by SEC are listed in Table The permissible operating voltage range is ± 5% under normal operating conditions and PAGE NO. 4 OF 6
5 ± 10%, for 30 minutes, under emergency operating conditions. These are detailed in Table Table 01-1: System Voltages Nominal System Voltage Voltage Range (Normal Operating Condition, ±5%) Voltage Range (Single Contingency Emergency Operating condition for 30 minutes, ±10%) (kvrms) (kvrms) (kvrms) Short Circuit Rating The 3φ symmetrical interrupting (short circuit) current ratings of the various underground cables shall be as specified in Table Table 01-2: 3φ Symmetrical Interrupting Short Circuit Current Ratings for Various Underground Cables Underground Cable Nominal 3φ Symmetrical Interrupting Voltage Rating Current (kv) (ka rms) /63* /63* /40* * It shall be specified by the design engineer. PAGE NO. 5 OF 6
6 5.0 Insulation Levels The insulation levels for all U/G cables shall not be less than the values specified in Table For installations at an altitude higher than 1000 m, the insulation requirements shall be calculated by multiplying the insulation value indicated in the Table 01-3 below by the altitude correction factor as specified in IEC & IEC Basic lightning impulse insulation levels (BIL) are specified with respect to a standard 1.2/50 μs wave shape and the basic switching impulse insulation level (BSL) is specified for a 250/2500 μs impulse. Nominal System Voltage Table 01-3: Insulation Levels Basic Insulation Level (BIL) Power Frequency Withstand Votage *Dry/Wet Basic Switching Impulse Level (BSL) (Kv rms ) (Kv Peak) (Kv rms ) (Kv rms) / / / / / / *Dry for 1 minute, wet for 10 seconds 6.0 DEVIATIONS 6.1 The Design Engineer who prepares the SOW/TS for the U/G power cable project is responsible to obtain an appropriate waiver from TS&SD for any specific deviation from this Standard (TES-P-104). This waiver shall be taken for over-specification as well as under-specification. 6.2 In case of any deviations from this Standard (TES-P-104) during the Base Design and detailed design of any U/G power cable project, it is the responsibility of the engineer preparing the base design or detailed design to obtain appropriate waiver from TS&SD before finalizing the design. 6.3 Any cases of conflicts or deviations which cannot be resolved shall be referred to TS&SD who will be the final authority for correct interpretation of the standards and associated documents, as applicable. PAGE NO. 6 OF 6
TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES
1.0 SCOPE TABLE OF CONTENTS 2.0 CABLES SPLICES 2.1 Definitions 2.2 Scope of Specifications and Drawings 2.3 General Requirements 2.4 Routing Cables 2.5 Connectors 2.6 Conductor Connections 2.7 Heat Shrinkable
More informationMESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITHOUT METALLIC SCREEN
Engineering Specification Electrical Networks MESP 030000-02 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED Version: 1 Issued: March 2014 Owner: Electrical
More information3M Sensored Termination (15 kv) QX-T15I-vi1-E
3M Sensored Termination () QX-T15I-vi1-E Data Sheet May 2016 Kit Contents: Each kit contains sufficient quantities of the following materials to make three single-phase terminations. 31" (REF) One piece
More informationPRINCIPLES AND APPLICATIONS
GENERATION & NETWORK Digital Automation Measuring and Control Devices AMS7000 PROCOM The optimum operation of an electrical network depends particularly on the reliability and the availability of the protection,
More informationANSI DESIGN TEST REPORT Report No. EU1250-HR-00 Type PVI Intermediate Class Surge Arrester
ANSI DESIGN TEST REPORT Report No. EU1250-HR-00 Type PVI Intermediate Class Surge Arrester This report records the results of the design tests made on Type PVI Intermediate Class surge arresters in accordance
More informationMedium and High Voltage Circuit Breakers Characteristic Time Quantities of the Circuit Breaker with Applications
Workshop 6: Maintenance and monitoring Medium and High Voltage Circuit Breakers Characteristic Time Quantities of the Circuit Breaker with Applications Alexander Herrera OMICRON electronics GmbH 3 December
More informationECONOMICAL 36 kv CABLE SYSTEM FOR THE BELGIAN NETWORK
ECONOMICAL 36 kv CABLE SYSTEM FOR THE BELGIAN NETWORK J. Becker NEXANS BENELUX S.A. F. Musique ELECTRABEL S.A. ABSTRACT In order to tackle the deregulated market with confidence and in a realistic way,
More information640 kv extruded HVDC cable system
640 kv extruded HVDC cable system World s most powerful extruded cable system Pehr Bergelin, Marc Jeroense, Tobias Quist, Hans Rapp NKT Summary In this paper, NKT s new 640 kv extruded DC cable system
More informationAustralian/New Zealand Standard
AS/NZS 4026:2008 AS/NZS 4026:2008 Australian/New Zealand Standard Electric cables For underground residential distribution systems AS/NZS 4026:2008 This Joint Australian/New Zealand Standard was prepared
More informationRZ1-K BS EN XLPE LSZH Flexible Cable
RZ1-K BS EN 50267 XLPE LSZH Flexible Cable Eland Product Group: A9R APPLICATION For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment. A flexible power
More informationSingle output models feature wide-range output adjustability to meet a wide variety of standard and user-specific output voltage requirements.
RoHS Lead-Solder-Exemption Compliant New 3.3 V and 5 V Output Models Universal Input 85-264 VAC Industry-Standard Footprint: 7.0" x 4.3" x 1.97" (177.8 x 109.2 x 50.0 mm) Input Transient & ESD Compliance
More informationLED Driver Linear / area fixed output
Driver LC 10W 350mA fixc lp SNC2 ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 350 ma Max. output power 10.2 W Up to 80 % efficiency For
More information220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX
220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX JAMNAGAR 220KV CABLE NETWORK: 2 2. DESIGN 2A. NETWORK: 220 KV NETWORK DESIGN IS DESIGNED WITH 100% REDUNDANCY FROM 220 KV BUS TO LOAD. THIS IS ACHIEVED
More informationCLP s first 400kV XLPE cable application
CLP s first 400kV XLPE cable application Chris Cheung CLP Power Hong Kong Limited 9 October 2017 Information Classification : PROPRIETARY Information Classification : PROPRIETARY Project Requirement Due
More informationHigh Temperature Operation of Extruded Distribution Cable Systems. White Paper
High Temperature Operation of Extruded Distribution Cable Systems White Paper October 2018 NOTICE The information contained herein is, to our knowledge, accurate and reliable at the date of publication.
More informationINSULATION CONDITION OF DRY-CURED XLPE CABLES MEASURED OVER A PERIOD OF 13 YEARS
2 rd International Conference on Electricity Distribution Lyon, -8 June Paper 47 INSULATION CONDITION OF DRY-CURED XLPE CABLES MEASURED OVER A PERIOD OF YEARS ABSTRACT Jens Zoëga HANSEN Danish Energy Association
More informationHVDC cable accessories
^=r SVENSKA KRAFTNÄT SWEDISH NATIONAL GRID UNIT, BUSINESS AREA OUR REFERENCE TR14-02-5E DATE 2018-09-21 CONSULTATIÖNS NT, NB TECHNICAL GUIDELINE EDITION 1 APPROVED TD HVDC cable accessories This technical
More informationHIGH VOLTAGE CABLE ACCESSORIES - Application, Design, Installation, Testing - Ivan Jovanovic G&W Electric Company
HIGH VOLTAGE CABLE ACCESSORIES - Application, Design, Installation, Testing - Ivan Jovanovic G&W Electric Company 1 Year 1905 First detachable porcelain pothead for 4 kv systems Year 2015 Terminations
More informationRevision of Qualification Procedures for High Voltage and Extra High Voltage AC Extruded Underground Cable Systems
Revision of Qualification Procedures for High Voltage and Extra High Voltage AC Extruded Underground Cable Systems Tutorial vor the ICC Educational Session on November 11 2009 in Scottsdale, AZ by Wim
More informationIEEE DESIGN TEST REPORT Report No. TD E00 Type PVR HD Riser Pole Distribution Class Surge Arrester
IEEE DESIGN TEST REPORT Report No. TD 01 060 E00 Type PVR HD Riser Pole Distribution Class Surge Arrester This report records the results of the design tests made on Type PVR Riser Pole Distribution Class
More informationODW-621. RS-232 Point-to-point applications
Re-timing Data rate up to 250 kbit/s 9-position D-sub connector Redundant power supply inputs Status interface for fault indication Fibre link fault indication (Red) Design for harsh environments 40 to
More information02/11/2015
DIN Rail Mount 17.5 mm MUS/MUSF 80 AC/DC Part number 84872141 Control relays monitoring their own power supply - MUS : Over/undervoltage control Selectable latching (memory) function - MUSF : Over/undervoltage
More informationPRODUCT INFORMATION NYY-J, NYY-O
Fixed installation, direct burial; PVC cable with different application areas, VDE, PVC-Starkstromkabel acc. HD 603 / VDE 0276-603, direct burial and building installation, fixed installation with various
More informationLED Driver Compact fixed output
Driver LC 40W 900mA fixc C SNC ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 900 ma Max. output power 40 W Nominal life-time up to 50,000
More informationLED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series
Driver LC 200W 1050mA UNV ADV IND ADVANCED series Product description Independent constant current LED Driver For dry, damp and wet locations Max. output power 200 W Up to 93.7 % efficiency For luminaires
More informationPHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series
Product description Fixed output built-in LED Driver Constant current LED Driver Output current 900 ma Max. output power 40 W Nominal life-time up to 30,000 h For luminaires of protection class I and protection
More informationLED Driver Compact fixed output
Driver LC 45W 1050mA fixc C SNC ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 1,050 ma output power 45 W Nominal life-time up to 50,000
More informationJul03 Rev C EC
Product Specification Coaxial BNC Solder Receptacle Connector 108-12079 10Jul03 Rev C EC 0990-0940-03 1. SCOPE 1.1. Content This specification covers the performance, tests and quality requirements for
More informationCapacitors and banks 50 Hz 0 400/415 V network voltage
Capacitors and anks 50 Hz 0 Varplus M capacitors 051327 E92427 E92428 E89596 E89598 The range of Varplus M modular capacitors consists of the Varplus M1 and Varplus M4 capacitors, whose different assemly
More informationMedium Voltage 12/20 (24)kV NF C cable system. Xavier Brosse Luanda May 2009
Medium Voltage 12/20 (24)kV NF C 33-226 cable system Xavier Brosse Luanda May 2009 1 Evolution of French standard for MV cables Late 70 s : NF C 33-223 Cable Standard in France result of the move from
More informationTeSys contactors. Model d. Type of contactor LC1- LC1- LC1- LC1- LC1-D115 & D09 D18 D25 D38 D40 D50 D95 LC1-D150 DT20 & DT25 DT32 & DT40
Characteristics Type of contactor LC- LC- LC- LC- LC-D & D09 D8 D2 D38 D40 D0 D9 LC-D0 DT20 & DT2 DT32 & DT40 Environment Rated insulation voltage (Ui) Conforming to IEC 947-4-, overvoltage category III,
More informationTRISHALA ELECTROLYTICS PVT LTD BANGALORE
P TRISHALA ELECTROLYTICS PVT LTD BANGALORE- 560044 AC MOTOR START ALUMINIUM ELECTROLYTIC CAPACITORS (Aluminum Body / Bakelite (Phenolic) Body) Scope Aluminum electrolytic Motor Start Capacitors are used
More informationCatalogue Ignitors and power switches for HID
Catalogue 2012 Ignitors and power switches for HID Overview Product overview Ignitor matrix Standards Page 6 Page 7 Page 8 Product information Ignitors and power switches for HID Page 9 Superimposed-pulse
More informationGV3P80 TeSys GV3P thermal-magn motor circuit breaker 70-80A EverLink
Characteristics TeSys GV3P thermal-magn motor circuit breaker 70-80A EverLink Main Range Product name Device short name Product or component type Device application Trip unit technology Complementary Poles
More information640 kv XLPE HVDC cable system
640 kv XLPE HVDC cable system World s most powerful extruded cable system enables utilization of renewable energy resources nkt.com Demand for higher voltages NKT s new 640 kv XLPE DC cable system is the
More informationLED Driver Compact dimming
Driver CA 15W 180-350mA flexc PH-C SR ADV ADVACED series Product description Dimmable constant current ED Driver (SEV) Independent ED Driver with cable clamps Selectable output current between 180, 250
More informationGV2ME083 TeSys GV2 - Circuit breaker - thermal-magnetic A - spring terminals
Product datasheet Characteristics GV2ME083 TeSys GV2 - Circuit breaker - thermal-magnetic - 2.5...4 A - spring terminals Main Range Product name Device short name Product or component type Device application
More informationDrop Passives: Splitters, Couplers and Power Inserters
ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 153 2016 Drop Passives: Splitters, Couplers and Power Inserters NOTICE The Society of Cable Telecommunications
More informationI/A Series Hardware Fiber Optic LAN Converter
I/A Series Hardware PSS 21H-7F3 B4 The provides bidirectional conversion between coaxial and fiber optic media. The converter is compatible with existing I/A Series system hardware, utilizes industry standard
More informationSURGE PROTECTIVE DEVICES
SURGE PROTECTIVE DEVICES COMPANY INTRODUCTION Bridex Singapore Pte Ltd is founded in 1978 as a manufacturer of instruments transformer for the Asian market. We are the first local electrical switchgear
More informationFibre Optic Modem ODW-611
Fibre Optic Modem ODW-611 PROFIBUS DP to fibre optic link, point-to-point applications The ODW-611 is a fibre optic modem designed for point-to-point fibre optic connections between PROFI- BUS DP networks.
More informationGV2ME. Product data sheet Characteristics. TeSys GV2-Circuit breaker-thermal-magnetic A - screw clamp terminals. Main.
Product data sheet Characteristics GV2ME06 TeSys GV2-Circuit breaker-thermal-magnetic - 1...1.6 A - screw clamp terminals Main Range Product name Device short name Product or component type Device application
More informationGV2ME. Product data sheet Characteristics. TeSys GV2-Circuit breaker-thermal-magnetic A -screw clamp terminals. Main.
Product data sheet Characteristics GV2ME04 TeSys GV2-Circuit breaker-thermal-magnetic- 0.4...0.63 A -screw clamp terminals Main Range Product name Device short name Product or component type Device application
More informationLC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC
Product datasheet Characteristics LC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC Price* : 86.25 GBP Main Range Product name Product or component type Device short name Contactor application Utilisation category
More informationCABLE CLEAT FAQs. Engineering Series. 1. What is a cable cleat?
1. What is a cable cleat? A cable cleat is a cable restraint device (e.g. cable clamp) that is designed and tested to provide securing and retention of cables when installed at intervals along the length
More informationTECHNICAL REPORT IEC/TR
IEC/TR 60909-2 TECHNICAL REPORT Edition 2.0 2008-11 Short-circuit currents in three-phase a.c. systems Part 2: Data of electrical equipment for short-circuit current calculations INTERNATIONAL ELECTROTECHNICAL
More informationB DOUBLE 150 kv LINK, 32 km LONG, IN BELGIUM : DESIGN AND CONSTRUCTION. (Belgium)
, rue d'artois, F-75008 Paris http://www.cigre.org B-05 Session 004 CIGRÉ DOUBLE 50 kv LINK, km LONG, IN BELGIUM : DESIGN AND CONSTRUCTION A. Gille *, V. Beghin G. Geerts, J. Hoeffelman D. Liémans, K.
More informationGV2ME. Main. Device short name. Device application
Product datasheet Characteristics GV2ME32 TeSys GV2-Circuit breaker-thermal-magnetic - 24...32 A - screw clamp terminals Main Range Product name Device short name Product or component type Device application
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD ISO 2186 Second edition 2007-03-01 Fluid flow in closed conduits Connections for pressure signal transmissions between primary and secondary elements Débit des fluides dans les conduites
More informationFibre Optic Modem ODW-622
Fibre Optic Modem ODW-622 RS-232 to fibre optic link, redundant ring or multidrop applications The ODW-622 can be used to create either redundant ring or multidrop solutions for devices with RS-232 interfaces.
More informationR&S ZVA-Zxx Millimeter-Wave Converters Specifications
R&S ZVA-Zxx Millimeter-Wave Converters Specifications Data Sheet Version 19.00 CONTENTS Definitions... 3 General information... 4 Specifications... 5 Test port... 5 Source input (RF IN)... 5 Local oscillator
More informationLC1D09FE7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A V AC coil
Product datasheet Characteristics LC1D09FE7 TeSys D contactor - 3P(3 NO) - AC-3 -
More information3AH3 Vacuum Circuit-Breakers
Catalog HG 11.03 Edition 2018 3AH3 Vacuum Circuit-Breakers Medium-Voltage Equipment siemens.com/3ah3 2 3AH3 Vacuum Circuit-Breakers Siemens HG 11.03 2018 R-HG11-373.tif Contents 3AH3 Vacuum Circuit-Breakers
More informationAMERICAN NATIONAL STANDARD
Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 108 2018 Test Method for Dielectric Withstand of Coaxial Cable NOTICE The Society of Cable Telecommunications Engineers (SCTE) / International
More informationB1-00. SPECIAL REPORT FOR SC B1 (Insulated Cables) Walter Zenger. Special Reporter
CIGRE 2016 B1-00 SPECIAL REPORT FOR SC B1 (Insulated Cables) Walter Zenger Special Reporter 1. General Study Committee (SC) B1 is responsible for all aspects regarding land and submarine insulated cable
More informationLC1D12P7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A V AC coil
Characteristics TeSys D contactor - 3P(3 NO) - AC-3 -
More informationGV2P05. Main. Device short name. Device application
Product datasheet Characteristics GV2P05 Main Range Product name Device short name Product or component type Device application Trip unit technology TeSys TeSys GV2 GV2P Circuit breaker Motor Thermal-magnetic
More informationTERMINATIONS AND JOINTS FOR XLPE-INSULATED kv MEDIUM VOLTAGE CABLES
Accessories TERMINATIONS AND JOINTS FOR XLPE-INSULATED 12 36 kv MEDIUM VOLTAGE CABLES Cable Systems, Cables and Accessories Test values for terminations 1) Testing to DIN VDE 0278-629-1 (Testing methods
More informationHD4/R. MV SF6 circuit-breakers for secondary distribution
HD4/R MV SF6 circuit-breakers for secondary distribution DESCRIPTION CIRCUIT-BREAKER SELECTION AND ORDERING SPECIFIC PRODUCT CHARACTERISTICS OVERALL DIMENSIONS ELECTRIC CIRCUIT DIAGRAM 3 9 25 45 49 1
More informationRack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
More informationEMC Solutions Noise filtering
Power & Signal Quality TRABTECH EMC Solutions Noise filtering Interference-free power supply and signal transmission A permanent supply and safe data link are essential for the operational reliability
More informationSECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.
SECTION 33 71 49.23 MEDIUM VOLTAGE CABLE INSTALLATION PART 1 GENERAL 1.1 SCOPE A. Work included in this Section: Medium Voltage Cable (4 kv and 12 kv) Installation and Termination. Removal and return of
More informationTime-Lag Relays. User s Handbook (General Model)
Time-Lag Relays User s Handbook (General Model) 651.601.387 Rev: V39 Date: 09/2016 Electrotécnica Arteche Smart Grid, S.L. This document, including texts, photos, graphics and any other content, is protected
More informationLED control gear Compact fixed output
Driver LC 40W 900mA fixc SR SNC ESSENCE series Product description Independent fixed output LED Driver Constant current LED Driver Output current 900 ma Max. output power 39 W Nominal life-time up to 50,000
More informationMAP110 AC-DC Series Data Sheet
Description Single-Output Model Selection VOLTAGE RANGE OUTPUT CURRENT OUTPUT CURRENT REGULATION REGULATION %p-p (NOTE 1) ACCURACY MAP110-1005 5V 4.95V to 5.50 16A 2 0.2% 1% 1% 5.09V to 5.11V MAP110-1012
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 61156-6 First edition 2002-03 Multicore and symmetrical pair/quad cables for digital communications Part 6: Symmetrical pair/quad cables with transmission characteristics up
More informationLONWORKS Fibre Optic Router
LONWORKS Fiber Optic Router LRW-112 and LRW-112/PP LONWORKS to fibre optic link, multidrop and redundant ring applications The LRW-112 router offers an easy way to extend the distance between LONWORKS
More informationGenerator protection relay
Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Off-the-shelf generator protection relay for small and medium sized power generators Three-phase time overcurrent and
More informationSPECIAL SPECIFICATION 1987 Single Mode Fiber Optic Video Transmission Equipment
1993 Specifications CSJ 0027-12-086, etc. SPECIAL SPECIFICATION 1987 Single Mode Fiber Optic Video Transmission Equipment 1. Description. This Item shall govern for the furnishing and installation of color
More informationR&S RT-Zxx High-Bandwidth Probes Specifications
R&S RT-Zxx High-Bandwidth Probes Specifications Test & Measurement Data Sheet 14.00 CONTENTS Definitions... 3 Probe/oscilloscope chart... 4 R&S RT-ZZ80 transmission line probe... 5 R&S RT-ZS10/-ZS10E/-ZS20/-ZS30
More informationGV2ME. Main. Device short name. Device application
Product datasheet Characteristics GV2ME10 Main Range Product name Device short name Product or component type Device application Trip unit technology TeSys TeSys GV2 GV2ME Circuit breaker Motor Thermal-magnetic
More informationLC1D25G7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A V AC coil
Product data sheet Characteristics LC1D25G7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationLIVE-LINE WORKING AND. EVALUATION OF RISK ON 400kV TRANSMISSION LINE
LIVE-LINE WORKING AND EVALUATION OF RISK ON 400kV TRANSMISSION LINE A THESIS SUBMITTED TO THE UNIVERSITY OF MANCHESTER FOR THE DEGREE OF DOCTOR OF PHILOSOPHY FACULTY OF SCIENCES AND ENGINEERING 2017 Pietro
More informationLC1D09B7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A - 24 V AC coil
Product data sheet Characteristics LC1D09B7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationLC1D12B7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A - 24 V AC coil
Characteristics TeSys D contactor - 3P(3 NO) - AC-3 -
More informationBharat Heavy Electricals Limited HIGH PRESSURE BOILER PLANT, TIRUCHIRAPPALLI CONTROLS AND INSTRUMENTATION/FB
Bharat Heavy Electricals Limited HIGH PRESSURE BOILER PLANT, TIRUCHIRAPPALLI 620 014. CONTROLS AND INSTRUMENTATION/FB DATA SHEET FOR MULTICORE, ARMOURED, CONTROL CABLE Project: Ennore Sez, 2 x 660 MW,
More informationProtective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A
DATASHEET - NZMN3-VE630 Circuit-breaker, 3p, 630A Part no. NZMN3-VE630 Catalog No. 259133 EL-Nummer (Norway) 0004358791 Similar to illustration Delivery program Product range Circuit-breaker Protective
More informationLED Driver Compact fixed output
Driver LC 10W 250mA fixc R ADV ADV series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 250 ma For luminaires of protection class II For ambient temperatures
More informationHYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.
Linear / area dimming Constant current LED driver DALI Dimmable Product description Dimmable built-in constant current LED Driver Adjustable output current between 1,050 and 1,750mA via DIP switch Max.
More informationCable installation guidelines
The Quality Connection Cable installation guidelines Business Unit Industrial Projects 2 Cable installation guidelines www.leoni-industrial-projects.com GENERAL Installation methods Many different methods
More informationLONWORKS Fibre Optic Converter
LONWORKS Fiber Optic Converter LRW-102 and LRW-102/PP LONWORKS to fibre optic link, multidrop and redundant ring applications The LRW-102 is a fibre optic modem designed for multidrop and redundant ring
More informationTransmission Cables Overhead/Underground Guidance
Transmission Cables Overhead/Underground Guidance There are two ways of transporting electricity around the country. 1. Overhead conductors 2. Underground cables. To identify ScottishPower apparatus in
More informationDiagnostic & Testing Services
Diagnostic & Testing Services Diagnostic & Testing Services Prysmian Cables & System B.V., based in Delft, the Netherlands, provides a full spectrum of pre and post sales services for its customers, including
More informationDS 400 P. Intelligent Electronic Pressure Switch in Hygienic Stainless Steel Ball Housing. on hygienic process connections
Intelligent Electronic Pressure Switch in Hygienic Stainless Steel Ball Housing Description The electronic pressure switch is the successful combination of hygienic process connections with flush welded
More informationR&S ZVA-Zxx Millimeter-Wave Converters Specifications
ZVA-Zxx_dat-sw_en_5214.2033.22_umschlag.indd 1 Data Sheet 13.00 Test & Measurement R&S ZVA-Zxx Millimeter-Wave Converters Specifications 28.01.2013 15:08:06 CONTENTS General information... 3 Definitions...
More informationR&S RT-Zxx High-Voltage and Current Probes Specifications
R&S RT-Zxx High-Voltage and Current Probes Specifications Test & Measurement Data Sheet 14.00 CONTENTS Definitions... 3 Probe/oscilloscope chart... 4 R&S RT-ZH10/-ZH11 high-voltage probes... 5 R&S RT-ZD01
More informationSoft starter, 66 A, V AC, Us= 24 V DC, with control unit, Frame size N. Function Soft starter for three-phase loads, with control unit
DATASHEET - S811+N66N3S Delivery program Soft starter, 66 A, 200-600 V AC, Us= 24 V DC, with control unit, Frame size N Part no. S811+N66N3S Catalog No. 168978 Eaton Catalog No. S811PLUSN66N3S EL-Nummer
More informationGV2ME086 TeSys GV2 - Circuit breaker - thermal-magnetic A - lugs-ring terminals
Product data sheet Characteristics GV2ME086 TeSys GV2 - Circuit breaker - thermal-magnetic - 2.5...4 A - lugs-ring terminals Main Range Product name Device short name Device application Trip unit technology
More informationDetailed Design Report
Detailed Design Report Chapter 4 MAX IV Injector 4.6. Acceleration MAX IV Facility CHAPTER 4.6. ACCELERATION 1(10) 4.6. Acceleration 4.6. Acceleration...2 4.6.1. RF Units... 2 4.6.2. Accelerator Units...
More informationInterface Practices Subcommittee SCTE STANDARD SCTE Composite Distortion Measurements (CSO & CTB)
Interface Practices Subcommittee SCTE STANDARD Composite Distortion Measurements (CSO & CTB) NOTICE The Society of Cable Telecommunications Engineers (SCTE) / International Society of Broadband Experts
More informationPOLICY & APPLICATION GUIDE FOR 11kV POLYMERIC CABLES
1. SCOPE This document provides information and guidance on the application of polymeric cables on the SPEN 11kV network. Throughout this document, references to 11kV shall by inference also relate to
More informationMILLITARY SPECIFICATION SHEET
INCH-POUND MILLITARY SPECIFICATION SHEET 10 November 2000 SUPERSEDING MIL-R-6106/14B 10 March 1989 RELAY, ELECTRIC, PERMANENT DRIVE, 50 AMP, SPDT (DB) DOUBLE MAKE DOUBLE BREAK AUXILIARY CONTACTS (5 AMP),
More informationModular pulse operated latching relay 16 A
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 Modular pulse operated latc / 05 / 07 / 08 / 10 / 11 / 12 / 14 / 16 / 20 and 927 00 / 49 CONTENTS PAGES 1. Description,
More informationIf you want to get an official version of this User Network Interface Specification, please order it by sending your request to:
This specification describes the situation of the Proximus network and services. It will be subject to modifications for corrections or when the network or the services will be modified. The reader is
More information1995 Metric CSJ SPECIAL SPECIFICATION ITEM 6031 SINGLE MODE FIBER OPTIC VIDEO TRANSMISSION EQUIPMENT
1995 Metric CSJ 0508-01-258 SPECIAL SPECIFICATION ITEM 6031 SINGLE MODE FIBER OPTIC VIDEO TRANSMISSION EQUIPMENT 1.0 Description This Item shall govern for the furnishing and installation of color Single
More informationFlygt Submersible Motor Cables
Flygt Submersible Motor Cables This brochure contains an overview of the Flygt motor cable assortment. The cables are especially designed for submersible use and made of carefully selected materials. The
More informationwith handle LIMOGES Cedex 1. DESCRIPTION - USE 3. DIMENSIONS Symbol: Technology: Use:. For controlling a load remotely via a switch 2.
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 25A power contactors silent CONTENTS PAGES 1. Description, use... 1 2. Range... 1 3. Dimensions... 1 4. Positioning - Connection...
More informationPERFORMANCE SPECIFICATION SHEET CONNECTORS, PLUGS, ELECTRICAL, COAXIAL RADIO FREQUENCY, (SERIES BNC (CABLED), PIN CONTACT, CLASS 2)
INCH-POUND MIL-PRF-39012/16H 16 November 2006 SUPERSEDING MIL-PRF-39012/16G 26 September 1994 PERFORMANCE SPECIFICATION SHEET CONNECTORS, PLUGS, ELECTRICAL, COAXIAL RADIO FREQUENCY, (SERIES BNC (CABLED),
More informationAMERICAN NATIONAL STANDARD
Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 129 2017 Drop Passives: Bonding Blocks (Without Surge Protection) NOTICE The Society of Cable Telecommunications Engineers (SCTE) Standards
More informationSPECIAL SPECIFICATION 6911 Fiber Optic Video Data Transmission Equipment
2004 Specifications CSJ 3256-02-079 & 3256-03-082 SPECIAL SPECIFICATION 6911 Fiber Optic Video Data Transmission Equipment 1. Description. Furnish and install Fiber Optic Video Data Transmission Equipment
More information