ELECTRICAL SAFETY INSPECTION REPORT
|
|
- Augustine Harper
- 6 years ago
- Views:
Transcription
1 ELECTRICAL SAFETY INSPECTION REPORT A & B OUTERWEAR LTD. Plot # 29-30, CEPZ, Chittagong, Bangladesh. Factory List: 1. Inspected by: Al-Amin Report Generated by: Al-Amin Inspected on March 7 th 2015
2 SUMMARY The factory is established in owned three building and four shed. Building-1 is three storied; Building-2 is two storied and building three is one storied. Building-1 was constructed in 2010 and production started in same year. Building-2 was constructed in 2011 and production started in same year. Building-3 was constructed in The factory had approximately 1114 workers. The Factory was surveyed for electrical safety by Woosun Energy and Construction Co., Ltd. (WEC). The purpose of the survey was to identify significant electrical safety issues and to provide recommendations for remediation based on applicable standards specified by the Accord. The scope of this initial electrical safety inspection was limited to the review and identification of major electrical safety issues. The inspection did not include identification of minor deficiencies, which would be further dealt with as part of follow-up inspections. Table below summarizes the major electrical safety issues identified during the inspection. Recommendations have been provided to address each issue. The implementation schedule shall be developed by the factory to remediate each of the findings. The specific timing of improvements, including any requested extensions due to design/installation constraints, shall be submitted to the Accord for an approval. Page 2 of 12
3 FINDINGS AND RECOMMENDATIONS FINDING NO: E- 1 Thermographic scanning of the entire electrical system has not been performed. Thermographic scanning of the entire electrical system must be performed twice in a year. FINDING NO: E-2 Electrical Single Line Diagram (SLD) is unavailable. Have a qualified engineer to create an as-built electrical SLD, mentioning all the required information, and get it reviewed by Accord. REMEDIATION TIMEFRAME: 12 WEEKS FINDING NO: E- 3 Insulation resistance test of electrical equipment is not performed. Insulation resistant test of all the cables must be performed once every 2 year cycle and recorded (this must require a complete power shut off). Page 3 of 12
4 FINDING NO: E- 4 Electric safety program is not initiated. Electrical safety training and awareness program for the electrical personnel and workers must be initiated and recorded. FINDING NO: E- 5 Factory does not have maintenance record. Maintenance Manager or Safety Officer must keep accurate records and ensure that they reflect actual factory day to day operations. FINDING NO: E- 6 Transformer Oil Test report is unavailable. Check the transformer oil condition by performing oil test, this must be done twice a year and recorded. FINDING NO: E- 7 Earth Pit resistance record is unavailable. Record earth pit resistances for all the earth pits, and do it once a year. Page 4 of 12
5 FINDING NO: E-8 Instruction for CPR (Cardiopulmonary Resuscitation) or Electrical shock restoration is not present. Hang this first aid and CPR instructions near all electrical equipment (LT panel, MDB, FDB, DB, SDB) on a visible location. FINDING NO: E- 9 CATEGORY: CABLE & CABLE SUPPORTS Wire is used in place of DO fuse and HT cables dropping from 11kV OH line not supported firmly to the pole. Replace the wire with standard DO fuse and the HT cable dropping from 11kV pole must be firmly fixed to the pole with supports and clamps. HT cable protected by DO fuse, dropping from pole. FINDING NO: E- 10 CATEGORY: TRANSFORMER ROOM No separation between LT panels and HT units (transformer, HT switchgear). Make a brick built separation between LT and HT units; ensure that after making separator you have adequate ventilation (cross ventilation) and working clearance around each electrical equipment. PRIORITY: P3 REMEDIATION TIMEFRAME: 16 WEEKS 315 kva transformer in substation. Page 5 of 12
6 FINDING NO: E- 11 CATEGORY: TRANSFORMER ROOM HT cable laid over the LT cables. Cables of different voltage levels must be separated in different trays. HT and LT cable. FINDING NO: E- 12 CATEGORY: TRANSFORMER ROOM No space around transformer for performing maintenance work. Ensure a minimum 1.07m working space around the transformer. REMEDIATION TIMEFRAME: 16 WEEKS 500 kva transformer in substation. FINDING NO: E- 13 CATEGORY: TRANSFORMER ROOM Oil leakage has been observed from transformer. Stop oil leakage from transformer and keep top of transformer clean. 500 KVA transformer Page 6 of 12
7 FINDING NO: E- 14 CATEGORY: TRANSFORMER ROOM Silica gel inside the breather is replaced by pebbles. Remove the pebbles from breather and replace it by silica gel after thorough cleaning of breather. The oil cup attached to breather must be filled by clean transformer oil. Transformer breather FINDING NO: E- 15 CATEGORY: EARTHING SYSTEM Impedance of main earthing of factory electrical system is very high (255.7 ohms) Check properly may be loose connection is one of the cause. Main earthing busbar. FINDING NO: E- 16 No base plate and compression gland, excessive dust, lint and debris deposit underneath the panel (typical issue). Dust, lint and debris must be thoroughly cleaned to avoid fire hazard. Provide covers (of noncombustible material) if any additional gap remains after installing cable glands. LT panel. Page 7 of 12
8 FINDING NO: E- 17 Cable connected MCCB without Lug. (Typical issue) Cable must be connected to MCCB by cable lug. MCCB inside the LT panel. FINDING NO: E- 18 Cable connected to busbar without lug (typical). Cables must be connected to busbar with proper size of cable lug. Bus bar inside the LT panel FINDING NO: E- 19 CATEGORY: EARTHING SYSTEM Earthing system of LT panel is not properly done. (Typical) Every panel must be used earthing busbar. Inappropriate earthing Page 8 of 12
9 FINDING NO: E- 20 CATEGORY:CABLE & CABLE SUPPORTS Cable passes through wall are not protected and not supported. Cable must be supported by cable tray and remaining gap is must be sealed. Distribution cables FINDING NO: E- 21 Phase barrier/separator not installed (typical issue). Put a purposely made phase separator (rubber type) between two phases; also terminate cables by proper sized cable lugs and cover cable lugs by heat shrink. Cables terminating at MCCB in panel on production floor. FINDING NO: E- 22 CATEGORY: CABLE & CABLE SUPPORTS Cables are covered by lint and dust. Thoroughly clean the combustible materials. Suggested to include in routine cleanliness/maintenance work. Distribution cables Page 9 of 12
10 FINDING NO: E- 23 CATEGORY: WIRINGS Cable duct/channels have excessive lint/dust (typical issue). Clean all the cable channels/ducts and cover them with checkered/perforated plates. Cable raceways in production floor. FINDING NO: E- 24 Hot spots detected at termination point of MCCB due to loose connection. (72 degree) Arrange periodic inspection & thermal scan to identify the overloading, loose connection, unbalanced load which may cause the excessive heat-rise and take action immediately REMEDIATION TIMEFRAME: 4 WEEKS Hot spot inside distribution board. FINDING NO: E- 25 Multiple cable termination at a terminal of MCCB (typical issue). Multiple cables connecting at a MCCB terminal must be disconnected. Existing multiple circuits may be distributed through bus bars. REMEDIATION TIMEFRAME: 2 WEEKS Cable terminating at MCCB in panel. Page 10 of 12
11 FINDING NO: E- 26 Cables inside distribution board is disorganized. Organize all the power cables securely and neatly inside distribution board to prevent from electrical hazards. Panel on ground floor. FINDING NO: E- 27 Power cables are bent excessively (typical issue). Avoid power cable bending in electrical system; in unavoidable case bend cables without any stress but not less than 135 degrees. Cable terminating at MCCB inside distribution board. FINDING NO: E- 28 Multiple cables connected in the busbar through a single lug (typical issue). Every cable must be connected to the busbar through its own single lug (one lug per cable). REMEDIATION TIMEFRAME: 4 WEEKS Wires terminating at busbar inside panel. Page 11 of 12
12 FINDING NO: E- 29 MCCB without enclosure and mounted on wooden plank. Remove the wooden plank. Provide standard MCCB protective enclosures. REMEDIATION TIMEFRAME: 4 WEEKS Cables terminating at MCCB. Page 12 of 12
ELECTRICAL SAFETY INSPECTION REPORT. MTM Garments Ltd.
ELECTRICAL SAFETY INSPECTION REPORT MTM Garments Ltd. 15934/16004, Chanpara, Medical Road, Uttarkhan, Dhaka, Bangladesh. Factory List MTM Garments Ltd. Inspected by: Hemlal Dahal Report Generated by: Hemlal
More informationELECTRICAL SAFETY INSPECTION REPORT
ELECTRICAL SAFETY INSPECTION REPORT A PLUS INDUSTRIES LIMITED. Plot-28, Milk Vita Rd., Section-07, Mirpur, Dhaka Factory List: 1. A Plus Industries Ltd. Inspected by: Yoon Report Generated by: Nezar Inspected
More informationELECTRICAL SAFETY FOLLOW UP INSPECTION REPORT (8th) Factory Name Address Factory ID
Factory Name Address Factory ID Shirir Chala, Bagherbazar 11705 Electrical Safety dates Initial Date 09/07/2014 30/10/2016 Date of 5 th Follow Up Report Received Date 24/08/2014 02/01/2017 Date of 6 th
More informationELECTRICAL SAFETY INSPECTION REPORT.
ELECTRICAL SAFETY INSPECTION REPORT., Plot no: 72 & 82, DEPZ, Ganakbari, Savar, Dhaka, Bangladesh. Factory List: 1.Experience Clothing Company Ltd. Inspected on March 31, 2014 SUMMARY Experience Clothing
More informationLaying of cables and lines in electrical installations and data networks
Technical bulletin Laying of cables and lines in electrical installations and data networks Date: 08/2006 This technical bulletin provides you with information on specific technical subjects. It is based
More informationFigure 1: Device components
Order No. : 2860 10 Order No. : 2830 10 Operation- and Assembly Instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically skilled persons. Failure to observe
More informationINSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 FIRE PREVENTION FOR CABLES, CABLE TRAYS AND CONDUITS
CERN INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 Edms 335813 TIS IS 48 Edited by: TIS/GS Publication Date: June 2001 Original: English FIRE PREVENTION FOR CABLES, CABLE
More informationTRF STEP-DOWN TRANSFORMER USER MANUAL
TRF STEP-DOWN TRANSFORMER USER MANUA www.ventilation-system.com 2013 ! WARNING The present operation manual consisting of the technical details, operating instructions and technical specification applies
More informationIdentification - electrical services
Identification - electrical services Aesthetic All live phase cable sheathing to be brown coloured and neutral phase cable sheathing to be blue coloured, all labelled L1, L2, L3 & N respectively in accordance
More informationOperating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130
Operating Manual (Edition 04/2004) sinamics Line Reactors SINAMICS G130 Contents 1. Safety Information 2 2. General 5 3. Mechanical Installation 6 4. Electrical Installation 8 5. Technical Specifications
More informationBY ADRIAN MESSER, UE Systems, Inc.
ELECTRICAL EQUIPMENT RELIABILITY WITH ULTRASOUND AND INFRARED BY ADRIAN MESSER, UE Systems, Inc. Ultrasound and infrared technologies are a perfect match when conducting inspections of electrical equipment.
More informationACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO
SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationMinimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE)
PART 1: GENERAL 1.01 Telecommunications Engineer Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) B. Registered Communications Distribution Designer
More informationSECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.
SECTION 33 71 49.23 MEDIUM VOLTAGE CABLE INSTALLATION PART 1 GENERAL 1.1 SCOPE A. Work included in this Section: Medium Voltage Cable (4 kv and 12 kv) Installation and Termination. Removal and return of
More informationIncorrect Temperature Measurements: The Importance of Transmissivity and IR Viewing Windows
Incorrect Temperature Measurements: The Importance of Transmissivity and IR Viewing Windows Abstract IR viewing windows save lives. Most Thermographers today are thankful to perform their scans without
More informationGESTAMP CHATTANOOGA, LLC CHATTANOOGA, TENNESSEE
GESTAMP CHATTANOOGA, LLC CHATTANOOGA, TENNESSEE April, 2013 Infrared Inspection Report Gestamp Chattanooga, LLC Company Contact Emil Richards Project: 06020413 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227
More information220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX
220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX JAMNAGAR 220KV CABLE NETWORK: 2 2. DESIGN 2A. NETWORK: 220 KV NETWORK DESIGN IS DESIGNED WITH 100% REDUNDANCY FROM 220 KV BUS TO LOAD. THIS IS ACHIEVED
More informationOperating Instructions Dimmer for V Incandescent Lamps
Operating Instructions Incandescent Lamps 1. Safety instructions Attention: Electrical equipment must be installed and fitted only by qualified electricians and in observance of the current accident prevention
More informationPreventing Fieldbus Physical Layer Problems
Preventing Fieldbus Physical Layer Problems 1 Introduction Foundation Fieldbus is highly reliable when correctly installed and maintained. The key is in knowing what must be done to start with and to maintain
More informationTRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES
1.0 SCOPE TABLE OF CONTENTS 2.0 CABLES SPLICES 2.1 Definitions 2.2 Scope of Specifications and Drawings 2.3 General Requirements 2.4 Routing Cables 2.5 Connectors 2.6 Conductor Connections 2.7 Heat Shrinkable
More informationTeSys contactors. Model d. Type of contactor LC1- LC1- LC1- LC1- LC1-D115 & D09 D18 D25 D38 D40 D50 D95 LC1-D150 DT20 & DT25 DT32 & DT40
Characteristics Type of contactor LC- LC- LC- LC- LC-D & D09 D8 D2 D38 D40 D0 D9 LC-D0 DT20 & DT2 DT32 & DT40 Environment Rated insulation voltage (Ui) Conforming to IEC 947-4-, overvoltage category III,
More informationMILLITARY SPECIFICATION SHEET
INCH-POUND MILLITARY SPECIFICATION SHEET 10 November 2000 SUPERSEDING MIL-R-6106/14B 10 March 1989 RELAY, ELECTRIC, PERMANENT DRIVE, 50 AMP, SPDT (DB) DOUBLE MAKE DOUBLE BREAK AUXILIARY CONTACTS (5 AMP),
More informationKRF EMC Filters Installation, Operation and Maintenance Manual
KRF EMC Filters Installation, Operation and Maintenance Manual KRF EMC Filters limit high frequency noise, as well as: Reduce interference Protect sensitive equipment Eliminate drive cross-talk Meet FCC
More informationSpecification. NGTS Issue 1 October 1993
The Electrical Standards for SHE Transmission s area are non-maintained versions of National Grid Technical Specifications that are applicable to the SHE Transmission System only. These specific versions
More informationIndyGo Facility Upgrades Project 35671EE
SECTION 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Identification for raceways. 2. Identification of power and control cables. 3. Identification for
More information7 Day Digital Programmer 3 Channel Surface Mount
7 Day Digital Programmer 3 Channel Surface Mount Model: TRT038N Installation & Operating Instructions 1. General Information These instructions should be read carefully and retained for further reference
More informationHARMONIZATION OF SYNOPTIC BLOCK DIAGRAMS ON THE CONTROL PANELS OF MV SWITCHGEAR AND CONTROLGEAR
HARMONIZATION OF SYNOPTIC BLOCK DIAGRAMS ON THE CONTROL PANELS OF MV SWITCHGEAR AND CONTROLGEAR Yvan L. Tits ELECTRABEL 8, Boulevard du Régent, B-1000 Brussels (Belgium) Tel: +32 2 518 62 66 - Fax: +32
More informationFiberglass - Technical Data
- Technical Data Cable Tray Thermal Contraction and Expansion X : Denotes hold-down clamp (anchor) at support. _ : Denotes expansion guide clamp at support. It is important that thermal contraction and
More informationLC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC
Product datasheet Characteristics LC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC Price* : 86.25 GBP Main Range Product name Product or component type Device short name Contactor application Utilisation category
More information(1) These Regulations may be called PEMRA Standards for Cable Television Regulations 2003.
PEMRA Cable Television (Operations) Regulations, 2002. Pakistan Electronic Media Regulatory Authority (PEMRA) The Pakistan Electronic Media Regulatory Authority (PEMRA) is pleased to make the Standards
More informationI r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
DATASHEET - NZMC1-A160 Circuit-breaker, 3p, 160A Part no. NZMC1-A160 Catalog No. 283296 Similar to illustration Delivery program Product range Circuit-breaker Protective function System and cable protection
More informationLC1D12P7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A V AC coil
Characteristics TeSys D contactor - 3P(3 NO) - AC-3 -
More informationLC1D09FE7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A V AC coil
Product datasheet Characteristics LC1D09FE7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationSample Test Project. District / Zonal Skill Competitions. Skill- Electrical Installation. Category: Construction and Building Technology
Sample Test Project District / Zonal Skill Competitions Skill- Electrical Installation Category: Construction and Building Technology Version 1 Dec 2017 Skill- Electrical Installation 1 Table of Contents
More informationLIGHTING: ENCLOSED AND GASKETED AREA FLUORESCENT. Applications. Illustrated Feature. Certifications and Compliances
Applications Enclosed and gasketed fixtures for use where vapors, moisture, dirt or corrosive atmospheres are encountered. For use in hazardous locations defined by the NEC as Class I, Division 2. Groups
More informationINSTRUCTION & OPERATION MANUAL. MODEL MMW-05 (5kW) MUROMACHI MICROWAVE FIXATION SYSTEM
INSTRUCTION & OPERATION MANUAL MODEL MMW-05 (5kW) MUROMACHI MICROWAVE FIXATION SYSTEM MUROMACHI KIKAI CO., LTD. TOKYO PRECAUTIONS The Microwave Fixation System is developed to rapidly halt brain chemical
More informationMASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz
Mobile Communications MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz CAUTION THESE SERVICING INSTRUCTIONS ARE FOR USE BY QUALI- FIED PERSONNEL ONLY. TO
More informationInstallation Manual IPT Installation of skillet systems with 125 A track current. MV a-E.
www.wampfler.com Page 1 of 27 Index Page 1 Basics...4 2 Basic understanding of an IPT -system...5 3 General rules regarding metal parts in close proximity...6 3.1 Envelope free of ferromagnetic material...6
More informationLC1D80F7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 80 A V AC 50/60 Hz coil
Product datasheet Characteristics LC1D80F7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationLC1D12B7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A - 24 V AC coil
Characteristics TeSys D contactor - 3P(3 NO) - AC-3 -
More informationSQM40/41 Actuators for air and gas dampers
SQM40/41 Actuators for air and gas dampers Description SQM40/41 actuators are used for the positioning of flow control valves, butterfly valves, dampers or any application requiring rotary motion. The
More informationLC1D50AF7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 50 A V AC 50/60 Hz coil
Product data sheet Characteristics LC1D50AF7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationIllustrated Feature. Options
Applications Enclosed and gasketed fixtures for use where vapors, moisture, dirt or corrosive atmospheres are encountered. For use in hazardous locations defined by the NEC as Class I, Division 2. Groups
More informationTechnical Specifications
INSTALLATION SHEET AND OPERATORS MANUAL General Description: The is a mixer/preamplifier that includes 6 channels that each include a microphone input at screw terminals and an aux input at an RCA jack.
More informationPCR AUTOMATIC HEAT TREATMENT CONSOLE
Maritime Stress PO Box 2898, 30 Estates Road Dartmouth, NS, B2W 4Y2, Canada Toll Free: 1-877-468-1781 Phone: (902) 468-7873 Fax: (902) 468-2304 Website: E-mail: info@maritimestress.com OPERATION MANUAL
More informationCP1 OAD. Owner s Manual. Stereo Control Preamplifier. Ultrafidelity
OAD Ultrafidelity CP1 Stereo Control Preamplifier Owner s Manual Contents Section Page No. Introduction........................................................................ 1 Warnings.................................................................................
More informationOperating instructions
108183 2017-05-17 Page 1 0359 Operating instructions TPPL-EX series Hazardous environments luminaires Please read the instructions carefully before starting any works! Content: 1. Safety instructions 2.
More informationSINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS
SINAMICS G130 Operating Instructions 03/2013 SINAMICS s dv/dt filter plus Voltage Peak Limiter Safety information 1 General 2 SINAMICS SINAMICS G130 Operating Instructions Mechanical installation 3 Electrical
More informationStudent Services & Classroom Addition
SECTION 260513 - MEDIUM-VOLTAGE CABLES PART 1 - GENERAL 1.1 SUMMARY A. Section includes cables and related cable splices, terminations, and accessories for mediumvoltage (2001 to 35,000 V) electrical distribution
More informationIntroduction Front Panel Functions Rear Panel Functions Precautions Placement & Ventilation... 5
Contents Introduction... 2 Front Panel Functions... 3 Rear Panel Functions... 3 Precautions... 5 Placement & Ventilation... 5 Installation & Operation... 5 Care & Maintenance... 7 Troubleshooting... 8
More informationTRANSCENSION 6-CHANNEL DMX DIMMER PACK (order code: BOTE40) USER MANUAL
www.prolight.co.uk TRANSCENSION 6-CHANNEL PACK (order code: BOTE40) USER MANUAL SAFETY WARNING FOR YOUR OWN SAFETY, PLEASE READ THIS USER MANUAL CAREFULLY BEFORE YOUR INITIAL START-UP! CAUTION! Keep this
More informationFORENSIC CASEBOOK. By Bob Huddleston, Eastman Chemical Co. One of the most common. reasons for marriage failure
The Case of the Energized Cable Cutting Incident How miscommunication leads to an electrical helper slicing through live 13.8kV cable and miraculously walking away to tell about it By Bob Huddleston, Eastman
More informationPendant Light Fitting IEC Series 6470/2
> Available light sources high-pressure sodium lamps (HSE) metal halide lamps (HIE) halogen lamps (QT) > Versatile mounting methods > Enclosure made of saltwater-resistant aluminium www.stahl.de 11435E
More informationLC1D65AF7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC 50/60 Hz coil
Characteristics TeSys D contactor - 3P(3 NO) - AC-3 -
More informationIMPORTANT SAFETY INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS When using this electronic device, basic precautions should always be taken, including the following: 1. Read all instructions before using the product. 2. Do not use this
More informationLC1D32P7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A V AC 50/60 Hz coil
Characteristics TeSys D contactor - 3P(3 NO) - AC-3 -
More informationLC1D09F7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A V AC coil
Product data sheet Characteristics LC1D09F7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationModel LTM-1400 User Manual LTM Multiformat 1x4 Assignment Router / DA. (Component, Y/C, Composite, Balanced Audio, RS422) 2001 Laird Telemedia.
Model LTM-1400 User Manual LTM-1400 2001 Laird Telemedia. CE GENERAL DESCRIPTION The LTM-1400 is a Multi-format Assignment Router/Distribution Amplifier System for the most complex Multimedia signal management.
More informationI r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
DATASHEET - NZMH2-A100 Circuit-breaker, 3p, 100A Part no. NZMH2-A100 Catalog No. 259099 Similar to illustration Delivery program Product range Circuit-breaker Protective function System and cable protection
More informationwww.greenelectricalsupply.com MaxLite 6 & 8 Commercial Downlight Retrofit General Safety Information To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts,
More informationOperating Manual. Mark Levinson Nº28 Preamplifier. Madrigal Audio Laboratories, Inc. 15
Operating Manual Mark Levinson Nº28 Preamplifier Madrigal Audio Laboratories, Inc. 15 WARNING: TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE THIS APPLIANCE TO RAIN OR MOISTURE. CAUTION RISK
More information7 Day Digital Programmer
7 Day Digital Programmer Cat. No. TRT034 Operating & Installation Instructions What is a programmer?...an explanation for householders Programmers allow you to set On and Off time periods. Some models
More informationDGC-1000A CLAMP-ON GROUND RESISTANCE TESTER
DGC-1000A CLAMP-ON GROUND RESISTANCE TESTER USERS MANUAL HOLD OFF FUNC REC For detailed specifications and ordering info go to www.testequipmentdepot.com EN 61010-2-032 CAT III 300V, CAT II 600V Pollution
More informationToronto Hydro - Electric System
Toronto Hydro - Electric System FIT Commissioning Requirements and Reports Comments and inquiries can be e-mailed to: FIT@torontohydro.com Customers without e-mail access can submit through regular mail
More informationPBC series. RoHS. Ready. IEC-Type Contactors & Accessories 9-80 Amp AC-3, Amp AC-1 AC Coils. P&B PBC Series IEC Type Contactors & Accessories
PBC series IEC-Type Contactors & Accessories 9-80 Amp AC-3, 25-125 Amp AC-1 AC Coils File E38802 (PBC) RoHS Ready Users should thoroughly review the technical data before selecting a product part number.
More informationT L Audio. User Manual C1 VALVE COMPRESSOR. Tony Larking Professional Sales Limited, Letchworth, England.
T L Audio User Manual C1 VALVE COMPRESSOR Tony Larking Professional Sales Limited, Letchworth, England. Tel: 01462 490600. International +44 1462 490600. Fax: 01462 490700. International +44 1462 490700.
More informationUsing Ultrasound and Infrared Technologies for Metal-Clad Switchgear Inspections
Using Ultrasound and Infrared Technologies for Metal-Clad Switchgear Inspections Adrian Messer, Manager of US Operations UE Systems, Inc. Ph: 864-224-4517 Cell: 914-282-3504 Web: www.uesystems.com Email:
More informationOPERATION AND MAINTENANCE MANUAL
OPERATION AND MAINTENANCE MANUAL SERIAL NUMBER CUSTOMER: SALES REP.: CONTENTS Mixer Installation / Assembly / Dimension Drawings Safety... 1 Customer Service Contact... 1 Initial Inspection... 2 Installation...2
More informationVITALink Taped Splice Straight Through Crimp
A Marmon Wire & Cable Berkshire Hathaway Company VITALink Taped Splice Straight Through Crimp 2 Hour Fire-Rated Splice VITALink MC Cables, UL FHIT 120 Installation Instructions Description The VITALink
More informationInstallation Manual SaVi Note Underwater LED Light
Installation Manual SaVi Note Underwater LED Light Model Numbers SAVI-NOTE7, SAVI-NOTE0 Table of Contents Safety Precautions...2 SaVi Note Install Instructions...3- M Instructions...- Warnings READ AND
More informationThis SOP is applicable to all WMATA personnel working on the Rail System, contractors performing the work and WMATA contractor escorts.
RFP: FQ13024/WJG CONTRACT NO. FQ13024 APPENDIX C STANDARD OPERATING PROCEDURES (SOP) SOP #33 REMOVAL AND RESTORATION OF THIRD RAIL POWER FOR WORK BY CONTRACTOR S FORCES MAINLINE, REVENUE SYSTEM PURPOSE
More informationDescription Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100
DATASHEET - NZMN3-4-AE400 Circuit-breaker, 4p, 400A Part no. NZMN3-4-AE400 Catalog No. 265891 Similar to illustration EL-Nummer (Norway) 0004358857 Delivery program Product range Circuit-breaker Protective
More informationACCESSORIES MANUAL PART NUMBER: PRODUCT REVISION: 1 TNP100. Tilt N Plug Interconnect Box USER'S GUIDE
MANUAL PART NUMBER: 400-0091-001 PRODUCT REVISION: 1 TNP100 Tilt N Plug Interconnect Box USER'S GUIDE INTRODUCTION Your purchase of the TNP100 Tilt N Plug Interconnect Box is greatly appreciated. We are
More informationModular Power System acc. VG MoFess Module for Military Ground Vehicles
This new modular Power System for Military Ground Vehicles based on a standard box incorporating up to three different power modules. The power inlet module (230 V AC) includes line filter, lightning protection
More informationSJOF-BS604B. Fiber Optic Splice Closure User Manual Rev.1
Fiber Optic Splice Closure 1. Introduction 1.1 General SAMJIN s SJOF-BS604B protects fiber optic splicing point in various installation conditions such as aerial, manholes, ducts, wall and direct buried
More informationDry Type Transformers. Section 10. BuyLog Catalog 10-1
For more information on these products, order publications listed in Section 27. Find What You Need Faster - Page headings and table format make product selection easier. Easy Cross Reference - Frame size
More informationOperating Manual. Mark Levinson Nº25 Dual Monaural Phono Preamplifier. Madrigal Audio Laboratories, Inc. 1
Operating Manual Mark Levinson Nº25 Dual Monaural Phono Preamplifier Madrigal Audio Laboratories, Inc. 1 WARNING: TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE THIS APPLIANCE TO RAIN OR MOISTURE.
More informationI R T Electronics Pty Ltd A.B.N. 35 000 832 575 26 Hotham Parade, ARTARMON N.S.W. 2064 AUSTRALIA National: Phone: (02) 9439 3744 Fax: (02) 9439 7439 International: +61 2 9439 3744 +61 2 9439 7439 Email:
More informationProtective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A
DATASHEET - NZMN3-VE630 Circuit-breaker, 3p, 630A Part no. NZMN3-VE630 Catalog No. 259133 EL-Nummer (Norway) 0004358791 Similar to illustration Delivery program Product range Circuit-breaker Protective
More informationInstallation Manual Original Instructions - IW4001
Installation Manual Original Instructions - IW4001 Installation Manual 1 General Operator and Supervisor Information Signal Word Definition Signal Word Panel Table of Contents Operator and Supervisor Information
More informationI r A Protection against direct contact Finger and back-of-hand proof to VDE 0106 part 100
Circuit-breaker,3p,400A Partno. LZMC3-A400-I Articleno. 111955 Similar to illustration Deliveryprogramme Product range Circuit-breaker Protective function System and cable protection Standard/Approval
More informationPOLICY & APPLICATION GUIDE FOR 11kV POLYMERIC CABLES
1. SCOPE This document provides information and guidance on the application of polymeric cables on the SPEN 11kV network. Throughout this document, references to 11kV shall by inference also relate to
More informationMini LED Pin Spot Light Model: PLS00571
Mini LED Pin Spot Light Model: PLS00571 1 Please read these instructions carefully before use and retain for future reference. IMPORTANT SAFETY INFORMATION When using electrical appliances basic safety
More informationCellular Signal Booster
Drive G-M Cellular Signal Booster THE ALUMINUM CASING OF YOUR SIGNAL BOOSTER!! WILL ADJUST TO THE TEMPERATURE OF ITS ENVIRONMENT, BUT IS DESIGNED TO PROTECT THE SIGNAL BOOSTER TECHNOLOGY. FOR EXAMPLE,
More informationSINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS
SINAMICS G130 / G150 Line harmonics filter Operating Instructions 05/2010 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 / G150 Operating Instructions Mechanical installation 3 Electrical
More information3 Cleaning. 4 Technical data
EXC+ EXC- Sig- SIG+ SEN- SEN+ 2.4 Attaching cable to the analog board Attaching cable of the weighing cell to the system solution Connect the cable to the appropriate terminal strip of the Ex1 system solution
More informationPower and Control T YPE BY RAVI GANATR November/December IAEI NEWS
Power and Control 26 1999 November/December IAEI NEWS T YPE BY RAVI GANATR This article discusses how the requirements in both the installation code and the product standard are utilized to manufacture
More informationPublic Works Division Lighting District Fiber Optic Specifications April 2009
Public Works Division Lighting District Fiber Optic Specifications April 2009 7000 Florida Street Punta Gorda, Florida 33950 Tele: 941.575.3600 Fax : 941.637.9265 www.charlottecountyfl.com/publicworks
More informationINSTALLATION INSTRUCTIONS RGB / RGBW 24V LED TAPE
LLI-LCC4.4W LLI-LCCW4.4W LLI-LCCW5.8W **DANGER: Prior to installation, disconnect power at the source.** Make sure you have all components listed below: LED tape 24VDC Power Supply Connectors (if creating
More informationDLP200M 2 Relay Module for Heating and Cooling Plants
Product Sheet TH6.24 Thermostat Type DLP200M DLP200M 2 Relay Module for Heating and Cooling Plants The DLP 200 M is a relay module for activation of loads (namely thermal actuators or circulators) in wireless
More informationLC1D50AFE7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 50 A V AC 50/60 Hz coil
Product data sheet Characteristics LC1D50AFE7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationDescription Set value in neutral conductor is synchronous with set value Ir of main pole. CSA 100. conductor. I r A 50-63
Circuit-breaker,4p,63A Partno. NZMH1-4-A63 Articleno. 284426 Similar to illustration Deliveryprogram Product range Circuit-breaker Protective function System and cable protection Standard/Approval IEC
More informationMagnecraft Power Relays
Description DPST-NO, 30 A; DPDT, 30 A (NO) / 3 A (NC) Description The series power relays offer a small package size and features Class F insulation for a maximum coil temperature of 55 C (3 F). These
More informationENCAPSULATED TRANSFORMERS FOR HARSH LOCATIONS
SECTION ENCAPSULATED TRANSFORMERS FOR HARSH LOCATIONS 600 Volt Class, Encapsulated Single Phase and Three Phase Description and Applications... 8 Copper NEMA R Features... 8 Copper Single Phase Selection
More informationGP-500 SERIES - Low Voltage
M O T O R & G E N E R A T O R P R O T E C T I O N AUTOMATIC INSULATION RESISTANCE TESTERS Meg-Alert is an automatic, in-line insulation resistance tester and monitor with test capabilities from 500 to
More informationUser Manual. 360W LED Moving Zoom KEEP THIS MANUAL FOR FUTURE NEEDS. 36pcs10W 4 in 1 RGBW LEDs
User Manual 360W LED Moving Zoom 36pcs10W 4 in 1 RGBW LEDs KEEP THIS MANUAL FOR FUTURE NEEDS 1. Dispacking Thank you for choosing our moving head. For your own safety, please read this manual before installing
More informationTERMINATIONS AND JOINTS FOR XLPE-INSULATED kv MEDIUM VOLTAGE CABLES
Accessories TERMINATIONS AND JOINTS FOR XLPE-INSULATED 12 36 kv MEDIUM VOLTAGE CABLES Cable Systems, Cables and Accessories Test values for terminations 1) Testing to DIN VDE 0278-629-1 (Testing methods
More informationDLP600M 6+1 Relay Module for Heating and Cooling Plants
Product Sheet TH6.25 Thermostat Type DLP600M DLP600M 6+1 Relay Module for Heating and Cooling Plants The DLP 600 M is a relay module for activation of loads (namely thermal actuators or circulators) in
More informationTHE EFFECT OF LOOSE CONNECTORS ON SHIELDING EFFECTIVENESS
THE EFFECT OF LOOSE CONNECTORS ON SHIELDING EFFECTIVENESS Asheridge Communications (A Teleste PLC Company) has undertaken a study to further understand the issues of RFI (Radio Frequency Interference)
More informationLED Thunder S-150 Code 1097
LED Thunder S-150 Code 1097 User Manual 1 1 SAFETY INSTRUCTIONS This device has left the factory in perfect condition. In order to maintain this condition and to ensure a safe operation, it is absolutely
More information