LGX Compatible (LSX) Connector Module) User Manual)

Size: px
Start display at page:

Download "LGX Compatible (LSX) Connector Module) User Manual)"

Transcription

1 LGX Compatible (LSX) Connector Module) User Manual) A LSX Connector Module (72-Position Module Shown) Content Page 1 DESCRIPTION DIMENSIONS AND SPECIFICATIONS INSTALLATION Installing the Connector Module Installing a Connector Pack Breaking Out a Cable Installing a Cable Clamp CABLE ROUTING Routing Stranded Cable Routing Ribbon Cable Routing Quad Cable (Two Active Fibers, Two Spare Fibers)...12 (continued) Rev A Page 1

2 Content Page 5 PATCH CORD ROUTING Patch Cord Routing Within the LSX Module Routing Patch Cords on the LGX Rack Mounting 144-Position Modules Adjacent to 72- or 96-Position Modules Installing Modified Cable Retainers for 144-Position Modules OPERATION Removing a Cover for Easier Access Connecting Patch Cords CUSTOMER INFORMATION AND ASSISTANCE INTRODUCTION This user manual describes the ADC LGX Compatible (LSX) Connector Module, and provides instructions for installation and operation. The LSX connector module is designed to be mounted on either a 19 inch (48.26 cm) or 23 inch (58.42) Lucent LGX compatible rack. Revision History ISSUE DATE REASON FOR CHANGE Issue 1 04/2000 Original Issue 2 02/2001 Incorporate description of quad cables and patch cord routing Trademark Information ADC is a registered trademark of ADC Telecommunications, Inc. LGX is a registered trademark of Lucent Technologies. Admonishments Important safety admonishments are used throughout this manual to warn of possible hazards to persons or equipment. Admonishments in the form of Dangers, Warnings, and Cautions must be followed at all times. These warnings are flagged by use of the triangular alert icon (seen below), and are listed in descending order of severity of injury or damage and likelihood of occurrence. Danger: Danger is used to indicate the presence of a hazard that will cause severe personal injury, death, or substantial property damage if the hazard is not avoided. Warning: Warning is used to indicate the presence of a hazard that can cause severe personal injury, death, or substantial property damage if the hazard is not avoided. Caution: Caution is used to indicate the presence of a hazard that will or can cause minor personal injury or property damage if the hazard is not avoided. Page 2

3 1 DESCRIPTION The LSX connector module is an LGX compatible, rack-mounted termination panel that provides a physical interface between fiber optic cables (terminated on the rear side of the bulkhead) and patch cords (terminated on the front). In a typical application, cables from transmission facilities are patched to fiber optic terminal equipment. The LSX connector module may be used in either an interconnect or cross-connect configuration, in either single mode or multimode applications, and with either stranded or ribbon cable. The cables may be either Intrafacility Fiber (IFC) or Outside Plant (OSP). The LSX connector module is available with 72, 96, or 144 fiber positions. Figure 1 shows the main external features of the 72-position module. Other modules are the same except for number of connectors and panel height. The main features are (from top left counterclockwise): LGX COMPATIBLE CHASSIS BULKHEAD CONNECTOR PACK PATCH CORD GUIDE MOUNTING BET REMOVABLE FRONT COVER PATCH CORD DESIGNATION CARD RADIUS LIMITER B Figure 1. Main External Features of LSX LGX Compatible LSX Module is of solid metal construction and painted putty white. The 72- and 96-position LSX connector modules have a rack height of 7 inches (17.8 cm) and a maximum of nine of these modules may be installed in the LGX frame. The 144-position connector module has a rack height of 9 inches (22.9 cm) and a maximum of seven of these modules may be installed in the LGX frame. Bulkhead holds the pass-through adapter/connectors that provide the physical interface between cables and patch cords. Figure 2 is a rear view of the connector module showing the rear side of the bulkhead. Page 3

4 14084-A Figure 2. LSX Connector Module (Rear View) Connector Pack 6-pack (72-position LSX), 8-pack (96-position LSX), or 12-pack (144-position LSX); mounts in the connector bulkhead providing one column of adapter/connectors. Individual connector packs are easily installed or replaced. All standard connector types are available including FC, SC, FC, ST, LX.5, etc. Patch Cord Guides provide cable management in routing patch cords from connectors to each side. Removable Front Cover provides unimpeded access to connectors for installation of patch cords. Patch Cord Designation Card is used to record patch cord usage. Radius Limiter maintains proper bend radius protection for the fibers. Mounting Brackets may be oriented in either of two positions to accommodate either 19-inch or 23-inch rack mount. The LSX connector module may be ordered empty, loaded with connector packs only, or loaded with both connector packs and pre-terminated, factory-installed cable. While not recommended, field-installed connectors can be accommodated, also. Page 4

5 2 DIMENSIONS AND SPECIFICATIONS Figure 3 shows LSX dimensions. Table 1 lists specifications IN. (37.7 CM) 11.0 IN. (27.9 CM) 7.53 IN. (19.1 CM) 5.00 IN. (12.7 CM) IN. REF (42.8 CM) REF (56.3 CM) 23 IN. MOUNT (58.4 CM) 1.0 IN. (2.5 CM) IN. REF (46.1 CM) 19 IN. MOUNT (48.3 CM) 2.0 IN. (5.1 CM) IN. (2.5 CM) IN. (17.8 CM) HEIGHT ON 72 OR 96 POSITION MODULES OR 9.0 IN. (22.9 CM) HEIGHT ON 144 POSITION MODULES C Figure 3. LSX Connector Module Dimensions Page 5

6 Table 1. LSX Connector Module Specifications PARAMETER Height Width Depth Rack Mount Weight (unloaded) Terminations Fiber Bend Radius SPECIFICATION 72- and 96-position chassis: 7 inches (17.8 cm) 144-position chassis: 9 inches (22.86 cm) inches (42.8 cm) inches (27.9 cm) Mounting bracket can be positioned to accommodate either 19-inch or 23-inch rack 72-position LSX: 9 pounds (4.1 kg) 96-position LSX: 10 pounds (4.5 kg) 144-position LSX: 13 pounds (5.9 kg) 72, 96, or 144 (depending on module type) 1.5 in. (3.8 cm) minimum 3 INSTALLATION The LSX connector module may be shipped empty or loaded with connector packs. If loaded with connector packs, it may also be loaded with a factory-terminated cable stub. If the module was not shipped with a factory-terminated cable stub, a cable clamp (provided with the unit) must be installed. The cable may or may not be already broken out and preterminated. If it is not, cable preparation is required as part of installation. Depending on how the module being installed was equipped, select from the procedures below. Procedures are provided for installing the connector module, installing adapter packs, breaking out a cable, installing a cable clamp, and routing a cable within the module. Only the first procedure is required if the module was pre-terminated in the factory. 3.1 Installing the Connector Module The LSX connector module is designed to be installed from the front side of the rack. To install the connector module: 1. Determine the mounting location and rack width. For a 19-inch rack, remove the two mounting brackets and re-install them using the 19-inch orientation (refer to Figure 3). For 23-inch rack, install the chassis with the mounting brackets positioned as shipped. 2. Secure the mounting brackets to the rack front flange using six #12-24 mounting screws, as shown in Figure 4. Note: If LGX jumper retainers are being used, remove them and reinstall them with the chassis as shown in Figure 4. The jumper retainers are not an ADC product. 3.2 Installing a Connector Pack To install a connector pack, press the connector pack firmly into the desired slot, pressing the plunger-expanders into the mounting holes. See Figure 5. Page 6

7 FRONT FLANGE LGX JUMPER RETAINER (NOT PROVIDED BY ADC) MOUNTING BET LGX JUMPER RETAINER (NOT PROVIDED BY ADC) 12-24X SCREW (6) D Figure 4. Installing the Connector Module (23-Inch Rack Shown) PLUNGER- EXPANDER MOUNTING HOLE CONNECTOR PACK A Figure 5. Installing a Connector Pack (6-Pack Shown) Page 7

8 3.3 Breaking Out a Cable If preparing a cable for installation, break out and prepare the cable corresponding to Figure 6 for stranded cable or Figure 7 for ribbon cable. BREAKOUT LENGTH ( /-6.0 INCH) ( /-15.2 CM) IFC CABLE FANOUT LENGTH ( /-6.0 INCH) ( /-15.2 CM) 1.0 INCH (2.54 CM) REF CLAMP CONNECTORS SUBUNIT DESIGNATION LABEL HEATSHRINK 6.0 INCH (15.2 CM) REF C Figure 6. Recommended Breakout Dimensions for Stranded Cable IFC CABLE INSTALL PROTECTIVE TUBES ON RIBBON TIE WRAP FANOUT CHIP CONNECTORS INDIVIDUAL FIBERS END OF PROTECTIVE TUBE BREAKOUT LENGTH ( /-6.0 INCH) ( /-15.2 CM) D FANOUT LENGTH ( /-6.0 INCH) ( /-15.2 CM) Figure 7. Recommended Breakout Dimensions for Ribbon Cable Page 8

9 3.4 Installing a Cable Clamp Figure 8 shows the cable clamp components. STANDOFF MOUNTING HOLE (4) YOKE (2) STANDOFF (2) RUBBER GROMMET CABLE CLAMP BET MOUNTING HOLE (2) (USE TWO UPPER HOLES FOR OVERHEAD CABLE ENTRY, TWO LOWER HOLES FOR UNDER FLOOR CABLE ENTRY) CABLE CLAMP COVER STANDOFF 12-24X SCREW (2) SCREW (2) CABLE CLAMP BET C (OVERHEAD CABLE POSITION) CLAMP MOUNT PLATE Figure 8. Cable Clamp Components (Overhead Cable) Install the cable clamp components as follows: Note: Figure 8 shows the cable clamp bracket positioned for cable routing from above the module with the bracket fastened using the two upper mounting holes in the cable mount plate. For cable routing from below the module, turn the cable clamp bracket upside down compared to how it is shown in the figure and use the two lower mounting holes in the cable mount plate. 1. Install the cable clamp bracket on the clamp mount plate using two #12-24 screws. Be sure to position the cable clamp bracket corresponding to the note above. 2. Place the two standoffs in the standoff mounting holes in the cable clamp bracket. (Note that there are four standoff mounting holes. Either the two holes on the left or the two holes on the right can be used together, not the two holes in the middle.) 3. Two rubber yokes and either three or four grommets (depending on the kit) are provided with the cable clamp kit for securing the cable to the module. Determine the correct grommet to use by first placing all of the grommets around the cable as shown in figure 9. Page 9

10 GROMMET CABLE GAP IN. (0-8 MM) 1440-A Figure 9. Grommet Selection 4. Measure the gap in each grommet and then select the grommet with a gap that is from approximately zero to inches (7.6 mm) wide. 5. Stack the cable clamp components as shown in Figure 8, with the cable secured within the rubber grommet. For correct location of cable breakout, see Figure 6 (for stranded cable) or Figure 7 (for ribbon cable). 6. Secure the cable clamp components to the standoffs using standoff screws, as shown. 7. If desired, install a cable shield using any of the three shields shipped with the connector module. Figure 10 shows the shield used for overhead cable. (The package also contains an alternate shield used for under-floor cable and a box-shaped shield used with either overhead or under-floor cable.) CABLE CLAMP 4-40X SCREW (4) CABLE SHIELD B Figure 10. Cable Shield Components (Shield shown is used with overhead cable.) Page 10

11 4 CABLE ROUTING 4.1 Routing Stranded Cable After preparing and clamping the cable as described above, route the cable into the rear of the LSX connector module as follows (see Figure 11): 1. Position the cable breakout an inch (2.54 cm) after the cable clamp. 2. Route the subunits to the front center retainer, as shown, with the subunits broken out into individual fibers at that location. 3. Route the fibers around the retainers and then fan them out to the adapter ports, as shown. FROM OVERHEAD FRONT 1.0 IN. (2.54 CM) REF CABLE CLAMP CABLE BREAKOUT HEAT SHRINK SUBUNITS LEFT CABLE CLAMP REAR FRONT CENTER RETAINER BREAKOUT SUBUNIT HERE REAR CENTER RETAINER INDIVIDUAL SUBUNIT RIGHT CABLE CLAMP E Figure 11. Stranded Cable Routing Top View 4.2 Routing Ribbon Cable After preparing and clamping the cable as described above, route the cable into the rear of the LSX connector module as follows (see Figure 12): 1. Position the cable breakout immediately after the cable clamp, as shown. Page 11

12 2. Route the ribbons (within protective tubes) to the rear center retainer and secure the fanout chips at that location. 3. Route the fibers from the fanout chips around the retainers, then fan them out to the adapter ports, as shown. FROM OVERHEAD CABLE CLAMP FRONT CABLE BREAKOUT TIE WRAP PROTECTIVE TUBES LEFT CABLE CLAMP FAN-OUT CHIP REAR CENTER RETAINER REAR INDIVIDUAL PROTECTIVE TUBE RIGHT CABLE CLAMP F Figure 12. Ribbon Cable Routing Top View 4.3 Routing Quad Cable (Two Active Fibers, Two Spare Fibers) After preparing and clamping the cable as described in Section 3, route one-half of the quad cables into the left side and the other half into the right side of the module (see Figure 13). Quad cables entering the module from the left (when viewed from the rear) are terminated on the right half of the module. Quad cables entering the module from the right (when viewed from the rear) are terminated on the left half of the module. 1. Terminate each working pair of fibers to the appropriate adapter locations. 2. Route the fibers through the cable retainers in the module to the rear center retainer 3. Route spare fibers around the retainers and allow them to lie in the bottom of the module. Page 12

13 4. Repeat Steps 1 through 3 for each quad cable in the module. 5. Secure and label spare fiber cables as necessary with tie wraps or lace as required by local practices. 6. Remove excess quad cable slack from the module. Work excess quad cable back to the storage area and secure following local practices. TOP VIEW ACTIVE FIBER SPARE FIBER FRONT CENTER RETAINER BREAKOUT SUBUNIT HERE REAR CENTER RETAINER INDIVIDUAL SUBUNIT C Figure 13. Quad Cable Routing Remove Single Fiber or Fiber Pair Termination Sometimes it may be necessary to remove a fiber or pair of fibers when equipment upgrades occur or a fiber becomes damaged. 1. Identify and label the fiber(s) to be removed. 2. Remove the connector from the adapter and place a dust cap on the connector end. Locate the fiber cable in the module and gently remove it from the cable retainers as necessary. 3. Determine the new fiber(s) to be terminated and remove from the spare cable bundle. 4. Route new fiber(s) through the cable retainers. Remove dust cap from the connector and clean end face of cable. Install connector(s) into the appropriate adapter/connector. 5. Route the removed cable to the spare cable bundle and secure with tie wraps or lace as required by local practices. Page 13

14 4.3.2 Cable Removal Procedure 1. Locate the quad cable to be removed from the cable bundle in the overhead racking. Follow the cable to the breakout point in the module and verify working and spare fiber pairs. 2. Using a light source, verify the spare fibers at the equipment locations specified. Disconnect the working fibers from the equipment and install dust caps. 3. Disconnect the working fiber pair from the adapters and install dust caps on the connector ends. 4. Remove the working and spare fibers from the cable retainers in the module. See Figure Cut the strain relief holding the cables in the vertical cable guide but do not remove the strain relief. 6. Attach the end of a new strain relief to one end of each cut strain relief and use the cut strain relief to pull in the new relief around the cable bundle. 7. Repeat steps 5 and 6 for each strain relief supporting the cable bundle. 8. Remove the quad cable from the cable bundle. 9. Tighten the new strain relief(s) around the cable bundle Cable Install Procedure 1. Label the ends of the new cable in accordance with local practice. 2. Cut the strain relief holding the cable bundle to the rack but do not remove the strain relief. 3. Attach the end of a new strain relief to one end of each cut strain relief and use the cut strain relief to pull in the new relief around the cable bundle. 4. Repeat steps 2 and 3 for each strain relief supporting the cable bundle. 5. Insert the quad cable into the cable bundle. Connect the working fibers to the equipment. 6. Route the quad cable through the radius limiters and retainers on the module and separate the working and spare fiber pairs. See Figure Remove the dust caps from the working fiber pair, clean the end face of the connector, and attach these fibers to the module connectors. 8. Remove the cable slack from the working and spare fiber pairs on the module and route the excess into the overhead cable bundle. 9. Tighten the new strain relief(s) around the cable bundle. Page 14

15 5 PATCH CORD ROUTING Cross-connect jumpers on the LSX modules and LGX frame must be carefully dressed to ensure they are properly protected. 5.1 Patch Cord Routing Within the LSX Module Dress the patch cords vertically down the front of the connector pack on each module and then left or right through the guides and radius limiters on the LSX module as shown in Figure 14. CONNECTOR PACK PATCH CORD GUIDE C RADIUS LIMITER Figure 14. LSX Module Patch Cord Guides and Radius Limiters 5.2 Routing Patch Cords on the LGX Rack Patch cord routing should allow for a minimum of 6 in. (152 mm) of slack loop in the vertical trough. This loop aids in the tracing of patch cords and also facilitates removing a patch cord from the bundle. Additional fiber slack should be expected when installing a set of pre-connectorized patch cords. The following section provides the procedures for disposing of excess patch cord length when installing patch cords on a single stand-alone rack, between two adjacent racks, or between two non-adjacent racks in a lineup. Page 15

16 5.2.1 Cross-Connecting Within a Single Rack Cross-connecting within a single rack (Figure 16) may be required when facility and equipment terminations are intermixed. Use the following procedure to route patch cords within the same rack. 1. Loop the patch cord across the upper raceway. 2. Route one end of the patch cord down the left vertical trough to a module termination point. Route the other end of the patch cord down the right vertical trough to a module termination point. Under certain conditions, a patch cord may need to be terminated beyond the half-way point of a module with the other end routed to a termination on the same side of the module or a different module to ensure that the patch cord is properly suspended in the upper raceway. See Figure B Figure 16. Routing Patch Cords within Standalone Racks Page 16

17 3. Adjust the slack loops of each patch cord to an equal length and then dress the excess length behind the module guides and retainers All cross-connection routing within a single rack should be done with 5 meter (16.5 ft) patch cords. Shorter 3 meter (9.9 ft) patch cords can be used when both ends are terminated in the top half of the frame Cross-Connecting Between Adjacent Racks Cross-connecting between adjacent racks (Figure 17) is accomplished using the following procedure B Figure 17.Routing Specified Length Patch Cords Between Adjacent Racks Page 17

18 1. Terminate one end of the patch cord on the originating module and rack and then route the patch cords left or right to the nearest rack vertical trough. 2. At the destination module and rack, terminate the opposite end of the patch cord and then route the patch cords left or right to the nearest rack vertical trough. 3. Route the patch cord over the upper raceway or jumper support bracket to the adjacent rack. 4. Adjust the slack length at both ends of the patch cord to about equal length and dress the excess length behind the rack retainers and module guides. All cross-connection routing between adjacent racks can be done with 6 meter (19.8 ft) patch cords. Shorter 4 meter (13.2 ft) patch cords can be used when both ends are terminated in the top left of the frame Cross-Connecting to Non-Adjacent Racks Patch cords may be routed through upper or lower raceways to non-adjacent LGX racks in a rack lineup. As a general rule, patch cords originating in LSX modules located in the upper half of an originating rack are routed to the upper raceway. Conversely, patch cords originating in modules located in the lower half of an originating rack are routed to the lower raceway Patch Cord Length Selection The user must select the correct patch cord length based on the number of racks to be traversed, and which raceways will be used to route the patch cord. See Table 2. Page 18

19 Table 2. Jumper Selection Table BOTTOM HALF ORIGIN/BOTTOM HALF DESTINATION (LOWER TO LOWER RACEWAY) NUMBER OF S JUMPER LENGTH IN METERS (FEET) 3, 4 5,6 7,8,9 10,11, ,15,16 17,18 19,20,21 N/A 7.6 (25) 9.2 (30) 10.7 (35) 12.2 (40) 13.6 (45) 15.2 (50) 16.6 (55) 18.1 (60) N/A BOTTOM HALF ORIGIN/TOP HALF DESTINATION (LOWER TO UPPER RACEWAY) NUMBER OF S JUMPER LENGTH IN METERS (FEET) 3 4,5 6,7 8,9,10 11,12 13,14 15,16,17 18,19, (20) 7.6 (25) 9.2 (30) 10.7 (35) 12.2 (40) 13.6 (45) 15.2 (50) 16.6 (55) 18.1 (60) TOP HALF ORIGIN/TOP HALF DESTINATION (UPPER TO UPPER RACEWAY) NUMBER OF S JUMPER LENGTH IN METERS (FEET) 3 4,5 6,7,8 9,10 11,12 13,14 15,16,17 18,19 20, (16) 6.1 (20) 7.6 (25) 9.2 (30) 10.7 (35) 12.2 (40) 13.6 (45) 15.2 (50) 16.6 (55) TOP HALF ORIGIN/BOTTOM HALF DESTINATION (UPPER TO LOWER RACEWAY) NUMBER OF S JUMPER LENGTH IN METERS (FEET) 3,4 5,6,7 8,9 10,11 12,13 14,15,16 17,18 19,20,21 N/A 6.1 (20) 7.6 (25) 9.2 (30) 10.7 (35) 12.2 (40) 13.6 (45) 15.2 (50) 16.6 (55) N/A N/A: Not applicable Page 19

20 Routing Patch Cords in the Lower Raceway Cross-connecting starting in the lower raceway can be accomplished using the following procedure (see Figure 18 and Figure 19). 1. Terminate one end of each patch cord on the originating module and rack and then route the patch cord left or right to the nearest rack vertical trough. 2. Route the patch cord terminated in step 1 down the left or right vertical trough to the lower raceway. 3. At the destination module and rack, terminate the opposite end of each patch cord and then route the patch cord left or right to the nearest rack vertical trough. 4. Route the patch cord terminated in step 3 up the left or right vertical trough and over the upper raceway as shown in Figures 18 and Insert the patch cords in the lower raceway between the origin and destination racks. Adjust the slack loops in the vertical troughs to prevent buildup within the raceway. ORIGINATING TERMINATION LOCATIONS DESTINATION TERMINATION LOCATIONS B Figure 18. Routing Patch Cords in the Lower Raceway (Bottom to Bottom) Page 20

21 DESTINATION TERMINATION LOCATIONS ORIGINATING TERMINATION LOCATIONS B Figure 19. Routing Patch Cords in the Lower Raceway (Bottom to Top) Routing Patch Cords in the Upper Raceway Cross-connecting starting in the upper raceway can be accomplished using the following procedure (see Figure 20 and Figure 21). 1. Terminate one end of each patch cord on the originating module and rack and then route the patch cord left or right to the nearest rack vertical trough. 2. Route the patch cord terminated in step 1 up the left or right vertical trough to the upper raceway. 3. At the destination module and rack, terminate the opposite end of each patch cord and then route the patch cord left or right to the nearest rack vertical trough. 4. Route the patch cord terminated in step 3 up the left or right vertical trough as shown in Figures 20 and Insert the patch cords in the upper raceway between the origin and destination racks. Adjust the slack loops in the vertical troughs to prevent buildup within the raceway. Page 21

22 ORIGINATING TERMINATION LOCATIONS DESTINATION TERMINATION LOCATIONS B Figure 20. Routing Patch Cords in the Upper Raceway (Top to Top) ORIGINATING TERMINATION LOCATIONS DESTINATION TERMINATION LOCATIONS Figure 21. Routing Specified Length Patch Cords in the Upper Raceway (Top to Bottom) B Page 22

23 5.3 Mounting 144-Position Modules Adjacent to 72- or 96-Position Modules Lucent L6X fiber distribution frames with a depth of 12 inches (30.1 cm) are typically used to mount LSX 72-position or 96 position connector modules. When mounting 144-position connector modules, Lucent L6X fiber distribution frames with a depth of 15 inches (38.1 cm) are recommended to accommodate the additional cabling encountered with LX.5 connectors. If a 15 inch deep L6X frame is not available, use a rear duct extension kit (Lucent category #FEX1A-FB or equivalent) to extend the rear doors of the frame back. The new 15 inch deep frame will line up with any existing 12 inch deep frame as shown in Figure 22. In addition, the relative mounting locations for Lucent JR4A-1 and JR4C-1 retainer caps on the front of adjacent racks containing LSX modules of different heights will be skewed horizontally as shown in Figure 23. The degree of retainer misalignment varies with the number of modules used to populate the adjacent rack. 5.4 Installing Modified Cable Retainers for 144-Position Modules The existing cable retainers on the rear of each Lucent rack must be replaced with new, higher-capacity cable retainers when LSX 144-position connector modules are installed. Two new top cable retainers are available (ADC catalog number LSX-ACC001) to provide a left and right cable orientation at the top of each rack upright (see Figure 24). Similarly, the existing rear vertical cable guides mounted on the rack at the left and right of each modules must be replaced with new, higher capacity guides when the rack is configured with LSX 144- position connector modules (rear vertical cable guides included with LSX 144-position connector module). The new rear vertical cable guide is shown in Figure 25. Page 23

24 EXISTING LINE-UP 0F 72 OR 96 POSITION MODULES 12.0 IN. (30.5 CM) 15.0 IN. (38.1 CM) NEW LINE-UP 0F 144 POSITION MODULES TOP VIEW (FRONT) A Figure 22. Front-to-Back Module Misalignment C Figure 23. Relative Misalignment of Retainers Page 24

25 16072-A Figure 24. Top Cable Retainer (Left Orientation Shown) A Figure 25. Rear Vertical Cable Guide Page 25

26 6 OPERATION 6.1 Removing a Cover for Easier Access The front and rear covers of the chassis may be removed to provide easier access for cable routing. To remove a cover, lift it straight out of the hinges. To replace a cover, position the hinge edge of the cover on the hinges and press inward to push the edge into the hinges. 6.2 Connecting Patch Cords Route patch cords outward to both sides, as shown in Figure 26. TOP VIEW B Figure 26. Correct Patch Cord Routing Page 26

27 7 CUSTOMER INFORMATION AND ASSISTANCE For customers wanting information on ADC products or help in using them, ADC offers the services listed below. To obtain any of these services by telephone, first dial the central ADC telephone number, then dial the extension provided below. The central number for calls originating in the U.S.A. or Canada is For calls originating outside the U.S.A. or Canada, dial country code 1 then dial Sales Assistance Extension Systems Integration Extension BCG Technical Assistance Center Extension bcg_tac@adc.com Product Return Department Extension repair&return@adc.com Quotation Proposals Ordering and Delivery General Product Information Complete Solutions (from Concept to Installation) Network Design and Integration Testing System Turn-Up and Testing Network Monitoring (Upstream or Downstream) Power Monitoring and Remote Surveillance Service/Maintenance Agreements Systems Operation Technical Information System/Network Configuration Product Specification and Application Training (Product-Specific) Installation and Operation Assistance Troubleshooting and Repair ADC Return Authorization number and instructions must be obtained before returning products. Product information may also be obtained using the ADC web site at or by writing ADC Telecommunications, Inc., P.O. Box 1101, Minneapolis, MN , U.S.A. Contents herein are current as of the date of publication. ADC reserves the right to change the contents without prior notice. In no event shall ADC be liable for any damages resulting from loss of data, loss of use, or loss of profits and ADC further disclaims any and all liability for indirect, incidental, special, consequential or other similar damages. This disclaimer of liability applies to all products, publications and services during and after the warranty period. This publication may be verified at any time by contacting ADC s Technical Assistance Center at , extension (in U.S.A. or Canada) or (outside U.S.A. and Canada), or by writing to ADC Telecommunications, Inc., Attn: Technical Assistance Center, Mail Station #71, P.O. Box 1101, Minneapolis, MN , U.S.A. All Rights Reserved Printed in U.S.A. Page 27

Traditional RF Splitter/Combiner and Directional Coupler User Manual

Traditional RF Splitter/Combiner and Directional Coupler User Manual Traditional RF Splitter/Combiner and Directional Coupler User Manual Content Page INTRODUCTION... 1 Revision History... 2 Trademark Information... 2 Admonishments... 2 General Safety Precaution... 2 1

More information

Traditional RF Splitter/Combiner and Directional Coupler User Manual

Traditional RF Splitter/Combiner and Directional Coupler User Manual Traditional RF Splitter/Combiner and Directional Coupler User Manual Content Page INTRODUCTION... 1 Revision History... 2 Trademark Information... 2 Admonishments... 2 General Safety Precaution... 2 1

More information

Next Generation Frame (NGF) Fiber Combination Block (FCB) User Manual)

Next Generation Frame (NGF) Fiber Combination Block (FCB) User Manual) Next Generation Frame (NGF) Fiber Combination Block (FCB) User Manual) Fiber Combination Block Content Page INTRODUCTION............................................................................. 2 Revision

More information

LCC (Little Coaxial Connector) Installation Instructions)

LCC (Little Coaxial Connector) Installation Instructions) LCC (Little Coaxial Connector) Installation Instructions) Content Page INTRODUCTION...1 Revision History...1 Trademark Information...1 1 TOOLS...2 1.1 Connection Tool Kit...2 1.2 Tool Illustrations...2

More information

6000 Series Patch Panel Terminating Instructions

6000 Series Patch Panel Terminating Instructions 6000 Series Patch Panel Terminating Instructions INTRODUCTION The 6000 Series patch panels include a unique feature not found on any other patch panel. This feature allows you to angle each of the four

More information

CONNECTING THE FUTURE 19" LINXS LIGHTWAVE INTEGRATED CROSS-CONNECT SYSTEM USER MANUAL

CONNECTING THE FUTURE 19 LINXS LIGHTWAVE INTEGRATED CROSS-CONNECT SYSTEM USER MANUAL CONNECTING THE FUTURE 19" LINXS LIGHTWVE INTEGRTED CROSS-CONNECT SYSTEM USER MNUL 109003 Issue Rev 2 19" Lightwave Integrated Cross-Connect System (LINXS) User Manual Document Number 109003 Issue Rev 2

More information

24-Fiber LANLINXS (Model # ) 48-Fiber LANLINXS (Model # ) User Manual

24-Fiber LANLINXS (Model # ) 48-Fiber LANLINXS (Model # ) User Manual 24-Fiber LANLINXS (Model # 055-8632-5000) 48-Fiber LANLINXS (Model # 055-8832-5000) User Manual 24-Fiber LANLINXS (Model # 055-8632-5000) 48-Fiber LANLINXS (Model # 055-8832-5000) User Manual, Part Number

More information

HD Flex Patch Panel. ASSEMBLY VIEW (FLEX1UPN** shown) FS128B. CONTENTS: (#) indicates FLEX4UPN** quantity

HD Flex Patch Panel. ASSEMBLY VIEW (FLEX1UPN** shown) FS128B. CONTENTS: (#) indicates FLEX4UPN** quantity HD Flex Patch Panel Part Numbers: FLEX1UPN**, FLEX2UPN**, FLEX4UPN** Panduit Corp. 2018 INSTALLATION INSTRUCTIONS Note: HD Flex Patch Panels are compatible with HD Flex Fiber System Components. HD Flex

More information

3M Fiber Optic Wall Mount Enclosure 8430 Series

3M Fiber Optic Wall Mount Enclosure 8430 Series 3M Fiber Optic Wall Mount Enclosure 8430 Series Installation Instructions January 2014 3 78-0013-9429-1-A Table of Contents 1.0 Description...3 2.0 Parts...4 3.0 Assembly...4 4.0 Mounting the Enclosure...6

More information

NGF optical distribution frame

NGF optical distribution frame NGF optical distribution frame Contents Introduction 3 Product overview 3 Things to consider when ordering 4 Frame capacity requirements (important facts on trough space) 4 Frame lineup capacity comparisons

More information

HCS - HES Cabling Systems

HCS - HES Cabling Systems HCS - HES Cabling Systems Installation Manual for HCS High-Capacity Fiber-Optic Rack-Mount Cabinets Be sure to read and completely understand this procedure before applying product. Be sure to select the

More information

DS1 Cross-Aisle Panel

DS1 Cross-Aisle Panel DS1 Cross-Aisle Panel Model 005-0005-0100 Installation Guide 1.1 Overview 1.1.1 Inspection Compare the contents of the DS1 Cross-Aisle Panel shipping container with the packing list. Call Telect if anything

More information

IP-LINX. Installation Guide

IP-LINX. Installation Guide Installation Guide Installation Guide, 146653-4 Copyright 2017, Telect, Inc. All Rights Reserved Telect and Connecting the Future are registered trademarks of Telect, Inc. 22425 East Appleway Ave. # 11

More information

IP-LINX Fiber :: X-XXXX

IP-LINX Fiber :: X-XXXX Fiber :: 055-797X-XXXX User Manual Telect, Inc. All rights reserved. 146653-A0 Table of Contents Chapter 1: Introduction...3 1.1 Tools Required...3 1.2 Additional Parts...3 1.3 Assemblies...3 Chapter 2:

More information

FOSC-600 C and D I N S T A L L A T I O N I N S T R U C T I O N

FOSC-600 C and D I N S T A L L A T I O N I N S T R U C T I O N FOSC-600 C and D I N S T A L L A T I O N I N S T R U C T I O N In-line and butt version Cold applied re-usable fiber optic closure Contents 1 Introduction 1.1 Product description 1.2 Capacity 2 General

More information

DSX-1 Cross-Connect Procedures

DSX-1 Cross-Connect Procedures ADCP-80-348 DSX-1 Cross-Connect Procedures 4-12000-0069 DSX-1 CROSS-CONNECT PROCEDURES ADCP-80-348 Content Page 1. CROSS-CONNECT ROUTING RULE PARAMETERS... 1 2. CROSS-CONNECT CABLE TYPE, LENGTH, AND LEVELS...

More information

OptEnet OC48 Regenerator Module User Manual

OptEnet OC48 Regenerator Module User Manual OptEnet OC48 Regenerator Module User Manual Content Page INTRODUCTION............................................................................. 1 Revision History........................................................................

More information

3M Distribution Box (DDB)

3M Distribution Box (DDB) 3M Distribution Box (DDB) Merged Copper and Fiber Pole/Post Mount Enclosure Installation Instructions November 2015 78-0015-2736-1-A 2 November 2015 78-0015-2736-1-A Contents 1.0 General 2.0 Enclosure

More information

FOSC 450 C6 and D6 Closures

FOSC 450 C6 and D6 Closures FOSC 450 C6 and D6 Closures I N S T A L L A T I O N I N S T R U C T I O N Fiber Optic Splice Closure 1. General Product Information The FOSC 450 C6 and D6 fiber optic splice closures use compressed gel

More information

3M SLiC 530/533/733-2 Port 0.61 Cable Entry Bracket 3M SLiC 530/533/733-2 Port-MSM 0.61 Cable Entry Bracket

3M SLiC 530/533/733-2 Port 0.61 Cable Entry Bracket 3M SLiC 530/533/733-2 Port-MSM 0.61 Cable Entry Bracket 3M SLiC 530/533/733-2 Port 0.61 Cable Entry Bracket 3M SLiC 530/533/733-2 Port-MSM 0.61 Cable Entry Bracket For use with 3M SLiC Free-Breathing Fiber Optic Closures and Terminals Instructions November

More information

Medium Box for Cable Termination

Medium Box for Cable Termination FIST-MB2-T I N S T A L L A T I O N I N S T R U C T I O N Medium Box for Cable Termination Contents 1 Introduction 1.1 Product description. 2 General 2.1 Tools 2.2 Kit contents 3 Installation and pre assembling

More information

FIST-MB2-S. FIST Medium Box for Cable Splicing Only. 4 Cable installation. 1 Introduction. Contents. 2 General. 5. Fiber routing to individual trays

FIST-MB2-S. FIST Medium Box for Cable Splicing Only. 4 Cable installation. 1 Introduction. Contents. 2 General. 5. Fiber routing to individual trays FIST-MB2-S I N S T A L L A T I O N I N S T R U C T I O N FIST Medium Box for Cable Splicing Only Contents 1 Introduction 1.1 Product description 2 General 2.1 Tools 2.2 Kit contents 3 Installation and

More information

K Service Source. Apple High-Res Monochrome Monitor

K Service Source. Apple High-Res Monochrome Monitor K Service Source Apple High-Res Monochrome Monitor K Service Source Specifications Apple High-Resolution Monochrome Monitor Specifications Characteristics - 1 Characteristics Picture Tube 12-in. diagonal

More information

K Service Source. Apple High-Res Monochrome Monitor

K Service Source. Apple High-Res Monochrome Monitor K Service Source Apple High-Res Monochrome Monitor K Service Source Specifications Apple High-Resolution Monochrome Monitor Specifications Characteristics - 1 Characteristics Picture Tube 12-in. diagonal

More information

SECTION O FIBER OPTICS

SECTION O FIBER OPTICS SECTION O FIBER OPTICS CONTENTS PAGE 1. GENERAL...O-2 1.1 Introduction...O-2 1.2 Definitions...O-2 1.3 Requirements...O-2 2. RUNNING, SECURING AND FIRESTOPPING FIBER OPTIC CABLE...O-3 2.1 Running Fiber

More information

OmniReach FTTX Solutions RealFlex DLX Universal Drop Cable Instruction Sheet

OmniReach FTTX Solutions RealFlex DLX Universal Drop Cable Instruction Sheet OmniReach FTTX Solutions RealFlex DLX Universal Drop Cable Instruction Sheet ADCP-90-457 Issue 1 9/2010 Content Page INTRODUCTION.............................................................................

More information

FIST-GCOG2-Dx6. Follow all local safety regulations related to optical fiber plant elements.

FIST-GCOG2-Dx6. Follow all local safety regulations related to optical fiber plant elements. FIST-GCOG2 I N S T A L L A T I O N I N S T R U C T I O N TC-986-IP Rev A, Mar 2017 www.commscope.com FIST-GCOG2-Dx6 Content 1 Introduction 2 General 2.1 Abbreviations 2.2 Kit contents 2.3 Tools 2.4 Accessories

More information

4320 SS-25 Self-Strip Terminating Block

4320 SS-25 Self-Strip Terminating Block 4320 SS-25 Self-Strip Terminating Block Instructions May 2002 78-8130-7677-1 1.0 General The 3M 4320 SS-25 Self-Strip Terminating Block is a factory stubbed, self-stripping connecting block designed for

More information

3M Fiber Optic Splice Closure 2178-XSB/XSB-FR & 2178-XLB/XLB-FR 3M Cable Addition Kit 2181-XB/XB-FR

3M Fiber Optic Splice Closure 2178-XSB/XSB-FR & 2178-XLB/XLB-FR 3M Cable Addition Kit 2181-XB/XB-FR 3M Fiber Optic Splice Closure 2178-XSB/XSB-FR & 2178-XLB/XLB-FR 3M Cable Addition Kit 2181-XB/XB-FR Instructions July 2010 78-8135-0094-5-K 3 1.0 General 1.1 3M Fiber Optic Splice Closure 2178-XSB The

More information

DIGITAL DISTRIBUTING FRAME (DDF) INSTALLATION PROCEDURES FOR PANELS AND MODULES

DIGITAL DISTRIBUTING FRAME (DDF) INSTALLATION PROCEDURES FOR PANELS AND MODULES DIGITAL DISTRIBUTING FRAME (DDF) INSTALLATION PROCEDURES FOR PANELS AND MODULES CommScope 365-301-136-1 Instruction Sheet Issue 10, February 2004 Material ID 847 591 963 General The Digital Distributing

More information

SignalOn Series. L-Band Power Inserter Module INSTALLATION & OPERATION MANUAL. 1.2 GHz. D3.

SignalOn Series. L-Band Power Inserter Module INSTALLATION & OPERATION MANUAL. 1.2 GHz.     D3. SignalOn Series D3.1/CCAP Compliant 1.2 GHz L-Band Power Inserter Module INSTALLATION & OPERATION MANUAL www.atxnetworks.com www.atxnetworks.com Although every effort has been taken to ensure the accuracy

More information

2178 L/S Series Fiber Optic Splice Cases and Accessories

2178 L/S Series Fiber Optic Splice Cases and Accessories 2178 L/S Series Fiber Optic Splice Cases and Accessories The 3M 2178 Fiber Optic Splice Case family has always given you great protection for fiber optic connections. Now, the addition of 3M 2178-L/S Series

More information

Perle Fast Ethernet Fiber to Fiber Media Converter Module. Installation Guide. P/N (Rev D)

Perle Fast Ethernet Fiber to Fiber Media Converter Module. Installation Guide. P/N (Rev D) Perle Fast Ethernet Fiber to Fiber Media Converter Module Installation Guide C-100MM-XXXXX CM-100MM-XXXXX Unmanaged Module Managed Module P/N 5500313-10 (Rev D) Overview This document contains instructions

More information

3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR

3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR 3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR 3M Cable Addition Kit 2181-XL and 2181-XL/FR Instructions September 2017 78-8130-5055-2-M 2 September 2017 78-8130-5055-2-M 1.0 Kit Contents 2.0 General...

More information

NewScope-7A Operating Manual

NewScope-7A Operating Manual 2016 SIMMCONN Labs, LLC All rights reserved NewScope-7A Operating Manual Preliminary May 13, 2017 NewScope-7A Operating Manual 1 Introduction... 3 1.1 Kit compatibility... 3 2 Initial Inspection... 3 3

More information

3 Closure preparation 3.1 Work-stand 3.2. Opening FIST-GCOG2-Dx Preparing drop cable with micro-tubes

3 Closure preparation 3.1 Work-stand 3.2. Opening FIST-GCOG2-Dx Preparing drop cable with micro-tubes FIST-GCOG2-Dx24 I N S T A L L A T I O N I N S T R U C T I O N FTTH closure for micro-tubes and micro-cables Content 1 Introduction 2 Kit content 3 Closure preparation 3.1 Work-stand 3.2. Opening FIST-GCOG2-Dx24

More information

Installation Instructions

Installation Instructions TECP-30-260 Issue 2 July 2016 Installation Instructions OWB-S OWB-S Small Wall-mounted Box CONTENTS 1. Introduction 2. Kit content 3. Installation Instruction 3.1. Box installation 3.2. Conduit installation

More information

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School BILOXI PUBLIC SCHOOL DISTRICT Biloxi Junior High School Request for Proposals E-Rate 2014-2015 - Internal Connections Submit Proposals To: Purchasing Department Attn: Traci Barnett 160 St. Peter Street

More information

NC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM

NC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM NC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM Content 1. General 5 2. The products of NC-1000 system 6 3. Mounting of the frame 8 4. Earthing of the frame 8 NC-1000 FIBRE OPTIC

More information

3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR 3M Cable Addition Kit 2181-XL and 2181-XL/FR

3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR 3M Cable Addition Kit 2181-XL and 2181-XL/FR 3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR 3M Cable Addition Kit 2181-XL and 2181-XL/FR Instructions July 2010 3 1.0 Contents 1.0 General...3 2.0 Kit Contents...3 3.0 Cable Preparation...4 4.0

More information

2179-CD Series Fiber Optic Splice Closure. Installation Instructions

2179-CD Series Fiber Optic Splice Closure. Installation Instructions 2179-CD Series Fiber Optic Splice Closure Installation Instructions 1.0 Product Introduction The new 3M TM 2179-CD Series Fiber Optic Splice Closure can be used in buried, underground, aerial, and pedestal

More information

2178 Fiber Optic Splice Case and 2181 Cable Addition Kit

2178 Fiber Optic Splice Case and 2181 Cable Addition Kit 2178 Fiber Optic Splice Case and 2181 Cable Addition Kit Instructions January 1994 Issue 1, 34-7029-6387-6 1 2 Contents: 1.0 General... 4 2.0 Specifications... 4 3.0 Kit Contents... 5 SECTION 1: 2178 Splice

More information

LTX Optical Distribution Panels. Ordering Guide

LTX Optical Distribution Panels. Ordering Guide Contents LTX Optical Distribution Panels... 1... 1 Section One: LTX Overview... 3 1RU and 2RU Panels... 3 4RU Panels... 3 Patch Panels... 3 Combination Panels Patch and Splice... 4 Section Two: Unloaded

More information

Follow The Leader In Shielded Technology

Follow The Leader In Shielded Technology 1970s Vampire Tap 1990s Shielded Modular Jack 190s 4 Position Data Connector Follow The Leader In Shielded Technology The new AMP-TWIST Jack is our latest shielded product evolution. It can be terminated

More information

RACKS, ENCLOSURES AND CABLE MANAGEMENT

RACKS, ENCLOSURES AND CABLE MANAGEMENT and RS3 RACK SYSTEM (pages 6.2 6.3) RS RACK SYSTEM (pages 6.4 6.5) EXTENDED DEPTH RS RACK SYSTEM (page 6.5) Vertical Side Rail Capacity Cable Manager Covers Accessories 117mm x 152mm (4.6 in. x 6.0 in.)

More information

2178-L/S Series Fiber Optic Splice Case with Gasket

2178-L/S Series Fiber Optic Splice Case with Gasket 2178-L/S Series Fiber Optic Splice Case with Gasket Instructions for: 2178-S Splice Case 2178-LS Splice Case 2178-LL Splice Case 2181-LS Cable Addition Kit May 1997 34-7041-9949-5-A 1 Table of Contents

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS MO036A N-HNS (Building Node Cabinet) N-HNS (BUILDING NODE CABINET) Contents Product description Technical data ODF Splice module Cabling organisation Cable/tube/fibre handling

More information

FOSC-450D. Fiber Optic Splice Closure. 1 Introduction. Content. 5 Cable termination. 6 Fiber routing. 2 General. 7 Installation of the gel block

FOSC-450D. Fiber Optic Splice Closure. 1 Introduction. Content. 5 Cable termination. 6 Fiber routing. 2 General. 7 Installation of the gel block FOSC-450D I N S T A L L A T I O N I N S T R U C T I O N Fiber Optic Splice Closure Content 1 Introduction 2 General 2.1 Kit content 2.2 Tools 2.3 Accessories 2.4 Capacity 3 Preparation of the closure 4

More information

Section Communications Optical Fiber Backbone Cabling

Section Communications Optical Fiber Backbone Cabling Part 1 1.1 Related Documents 1.1.1 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections apply to this Section. 1.2 Related

More information

Gigabit Multi-mode SX to Single Mode LX Converter. User s Manual NGF-728 Series. Warning COPYRIGHT

Gigabit Multi-mode SX to Single Mode LX Converter. User s Manual NGF-728 Series. Warning COPYRIGHT COPYRIGHT Gigabit Multi-mode SX to Single Mode LX Converter User s Manual NGF-728 Series All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTGUARD 350-20-WTC SEALED FIBER OPTIC CLOSURE VIEW ONLINE TABLE OF CONTENTS: GENERAL...2 SPECIFICATIONS...2 PACKAGE CONTENTS...3 PACKAGE CONTENTS: ACCESSORIES...3 RECOMMENDED TOOLS...3 ADD-ON COMPONENTS...4

More information

WaveTrax. Fiber Cable Management System

WaveTrax. Fiber Cable Management System Table of Contents Overview...3 Trough...4 Trough Cover...4 Trough Notching Tool...4 FastLock Coupler...4 Competitive FastLock Coupler...5 Horizontal Elbow...5 Horizontal Elbow Cover...5 Horizontal T...5

More information

Installation. SAPTF33xx-1xx in the Network. Standard Configuration

Installation. SAPTF33xx-1xx in the Network. Standard Configuration SAPTF33xx-1xx in the Network Standard Configuration One Unit A device (SAPTF33xx-100) and one device () are required for the standard configuration. The Unit A device is connected to the while the device

More information

3M Coupling Tray FDTC-10S-COUPLINGTRAY

3M Coupling Tray FDTC-10S-COUPLINGTRAY 3M Coupling Tray FDTC-10S-COUPLINGTRAY for use with 3M Fiber Dome Closures FDC 10S Instructions July 2010 3 1.0 Introduction The 3M Coupling Tray FDTC-10S-COUPLINGTRAY can accommodate up to 10 loose tubes.

More information

The FiberMark1 offers an ideal solution for

The FiberMark1 offers an ideal solution for Large Capacity Fiber Optic Splice Enclosure The Ideal Solution For Large Capacity Voice, Data, and Video Splicing Requirements. The FiberMark1 offers an ideal solution for larger fiber capacity voice,

More information

ADC Passive Optical Network (PON) Test and Turn-Up Procedures

ADC Passive Optical Network (PON) Test and Turn-Up Procedures ADC Passive ptical Network (PN) Test and Turn-Up Procedures ADCP-96-4 Issue 4/009 Content Page INTRDUCTIN............................................................................. LIST F ACRNYMS AND

More information

WCH Slack Storage Housing (WCH-SSH-2 & WCH-SSH-4-12)

WCH Slack Storage Housing (WCH-SSH-2 & WCH-SSH-4-12) Corning Cable Systems SRP-003-448 Issue 3, October 2000 Page 1 of 6 WCH Slack Storage Housing (WCH-SSH-2 & WCH-SSH-4-12) Figure 1 Table of Contents 1. General... 1 2. Description... 1 3. Tools and Materials...

More information

Installation instructions Roxtec RM ES B

Installation instructions Roxtec RM ES B Installation instructions Roxtec RM ES B Environmental side Termination/ interior side Pipe Cable screen/armor Layers Termination/ interior side Cable sheath Layers Environmental side Vertical screen Plastic

More information

BCS 4R DSX-3 Connectivity System. Models , , and User Manual

BCS 4R DSX-3 Connectivity System. Models , , and User Manual BCS 4R DSX-3 Connectivity System Models 010-8332-0410, 010-8332-0401, 010-8324-0410 and 010-8324-0401 User Manual BCS 4R DSX-3 Connectivity System Models 010-8332-0410, 010-8332-0401, 010-8324-0410 and

More information

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE Prepared in cooperation and approval from BICSI Building Industry Consulting Services International and

More information

FIST-GCO2-OTIAN I N S T A L L A T I O N I N S T R U C T I O N

FIST-GCO2-OTIAN I N S T A L L A T I O N I N S T R U C T I O N FIST-GCO2-OTIAN I N S T A L L A T I O N I N S T R U C T I O N 24 Address Point Fibre distribution point (FDP) Installation guide for fibre DP Contents 1 Kit Contents 2 Accessories 3 MOBRA installation

More information

Model GS7000 GainMaker Node Forward Local Injection Module Installation Instructions

Model GS7000 GainMaker Node Forward Local Injection Module Installation Instructions Model GS7000 GainMaker Node Forward Local Injection Module Installation Instructions Introduction The Forward Local Injection (FLI) Module is a field installable accessory for the Model GS7000 GainMaker

More information

ivw-ud322 / ivw-ud322f

ivw-ud322 / ivw-ud322f ivw-ud322 / ivw-ud322f Video Wall Controller Supports 2 x 2, 2 x 1, 3 x 1, 1 x 3, 4 x 1 & 1 x 4 Video Wall Array User Manual Rev. 1.01 i Notice Thank you for choosing inds products! This user manual provides

More information

Litile34 INSTALLATION MANUAL

Litile34 INSTALLATION MANUAL Litile34 INSTALLATION MANUAL Seamless Tiled Panel Wall Solution for Large Area Digital Signage Display (1st Edition 3/25/2009) All information is subject to change without notice. Approved by Checked by

More information

COYOTE CLOSURE FOR UNDERGROUND, AERIAL, AND BURIED SPLICES 6.0" x 22" 8.5" x 22" (15.24 cm x cm cm x cm)

COYOTE CLOSURE FOR UNDERGROUND, AERIAL, AND BURIED SPLICES 6.0 x 22 8.5 x 22 (15.24 cm x cm cm x cm) OCTOBER 2004 COYOTE CLOSURE FOR UNDERGROUND, AERIAL, AND BURIED SPLICES 6.0" x 22" 8.5" x 22" (15.24 cm x 55.88 cm 21.59 cm x 55.88 cm) Be sure to read and completely understand this procedure before applying

More information

Assembling and Mounting the Presentation Display, Speakers, Speaker Screens, and Table Door

Assembling and Mounting the Presentation Display, Speakers, Speaker Screens, and Table Door CHAPTER 8 Assembling and Mounting the Presentation Display, Speakers, Speaker Screens, and Table Door July 13, 2012, This document provides you with the procedures you perform to assemble and mount the

More information

TracVision R6DX Installation Guide

TracVision R6DX Installation Guide TracVision R6DX Installation Guide These instructions explain how to install the TracVision R6DX satellite TV antenna system on an RV or motor coach. Complete instructions on how to use the system are

More information

Installation instructions Roxtec RM PE B

Installation instructions Roxtec RM PE B Installation instructions Roxtec RM PE B Environmental side Termination/ interior side Pipe Cable screen/armor Layers Termination/ interior side Cable sheath Layers Environmental side Plastic film Conductive

More information

2.1 Kit Contents 2.2 Elements needed from the FIST installation kit 2.3 Tools 2.4 Cable preparation table

2.1 Kit Contents 2.2 Elements needed from the FIST installation kit 2.3 Tools 2.4 Cable preparation table FIST-GCO2-F INSTALLATION INSTRUCTION GCO2-FC GCO2-FD Content 1 Introduction 2 General 2.1 Kit Contents 2.2 Elements needed from the FIST installation kit 2.3 Tools 2.4 Cable preparation table 3 Installation

More information

Optical Distribution Box 300 Installation Guide. Version : R0.0

Optical Distribution Box 300 Installation Guide. Version : R0.0 Optical Distribution Box 300 Installation Guide Document No. : OD16-546-L-01 Version : R0.0 Date: 21-Mar-2018 IMPORTANT INSTRUCTIONS When using fiber optic equipment, basic precautions should always be

More information

CABLE MANAGEMENT PRODUCTS Cable Managers & Accessories

CABLE MANAGEMENT PRODUCTS Cable Managers & Accessories CABLE MANAGEMENT PRODUCTS Cable Managers & Accessories Evolution Cable Management Page 5-3 Velocity Cable Management Page 5-8 Velocity Standard Pack Page 5-12 Vertical Cable Management Page 5-13 Global

More information

Industrial Monitor Update Kit

Industrial Monitor Update Kit Industrial Monitor Update Kit (Bulletin Number 6157) Installation Instructions 2 Table of Contents Table of Contents Industrial Monitor Update Kit... 3 Overview... 3 Part 1 - Initial Preparation... 5 Part

More information

Splice Closure Fiber (SCF) Family

Splice Closure Fiber (SCF) Family features and benefits Sealed butt-style closure Aerial, wall, pole, direct buried Ribbon reel-end to reel-end splicing Split end caps Modular fiber management system standards Telcordia GR-771 tested RDUP

More information

1x12 VGA & Audio over CAT5 Splitter

1x12 VGA & Audio over CAT5 Splitter SP-9112 1x12 VGA & Audio over CAT5 Splitter User Manual rev: 160322 Made in Taiwan Safety and Notice The SP-9112 1x12 VGA & Audio over CAT5 Splitter has been tested for conformance to safety regulations

More information

WID-DL74 WID-DL74 BLP WID. Designed for. Installation guide for workitdesk interactive table for. BrightLink Pro

WID-DL74 WID-DL74 BLP WID. Designed for. Installation guide for workitdesk interactive table for. BrightLink Pro WID-DL74 WID-DL74 BLP WID Designed for BrightLink Pro Installation guide for workitdesk interactive table BrightLink Pro for Mounting the table unit 1 Unpack boxes 1 of 4 (Mobile base) and 2 of 4 (Motorized

More information

CNK221/241/261/321/341/361 Cable-Nook Jr. User s Guide

CNK221/241/261/321/341/361 Cable-Nook Jr. User s Guide Cable-Nook Jr. Welcome! We greatly appreciate your purchase of the Cable-Nook Jr. Interconnect Box. We are sure you will find it reliable and simple to use. Superior performance for the right price, backed

More information

INSTALLATION INSTRUCTIONS MO023A

INSTALLATION INSTRUCTIONS MO023A INSTALLATION INSTRUCTIONS MO023A Nexans N3S ODF system NEXANS N3S ODF SYSTEM Content Product description Patching frame Splice frame Doors Splice module Patch module Protective cover and label panel Guides

More information

Instruction Manual.... light years ahead. S739DV & S7739DV Video and Up-the-Coax Control Systems

Instruction Manual.... light years ahead. S739DV & S7739DV Video and Up-the-Coax Control Systems Instruction Manual... light years ahead S739DV & S7739DV Video and Up-the-Coax Control Systems Fiber Options Federal Communications Commission and Industry Canada Radio Frequency Interference Statements

More information

SLiC Fiber Aerial Closure System

SLiC Fiber Aerial Closure System 3 SLiC Fiber Aerial Closure System SLFC 533-SP SLFC 533-TS SLFC 733-SP Instructions May 2005 78-8135-4502-3-B N C H E S R A N G E M IL L IM E T E R S.4 10.6.8 A B C 15 20 I 1.0 Kit Contents Note: Examine

More information

K Service Source. Macintosh Color Display

K Service Source. Macintosh Color Display K Service Source Macintosh Color Display K Service Source Specifications Macintosh Color Display Specifications Characteristics - 1 Characteristics Picture Tube 14-in. diagonal (11.5-in. viewable image)

More information

Cable and Power Management Open-Frame Rack Cable Managers

Cable and Power Management Open-Frame Rack Cable Managers Spec-001 Cable and Power Management Open-Frame Rack Cable Managers CABLETEK Horizontal Cable Manager DCHD shown DCHS4 shown Arrowhead fingers funnel cable into base and hold it securely Vertical and horizontal

More information

GF-KSW-48 Series of Fiber Optic Distribution Box. Instruction Manual

GF-KSW-48 Series of Fiber Optic Distribution Box. Instruction Manual Instruction manual GF/KSW/48 Page Nr 1 GF-KSW-48 Series of Fiber Optic Distribution Box Instruction Manual 1. General Introduction GF-KSW-48 series of fiber optic distribution box is applicable to fiber

More information

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents PART 1 - GENERAL 1.1 SUMMARY SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors. 3. Cabling system identification products. 1.2

More information

Aerial Cable Installation Best Practices

Aerial Cable Installation Best Practices Aerial Cable Installation Best Practices Panduit Corp. 2007 BEST PRACTICES Table of Contents 1.0 General... 3 2.0 Introduction... 3 3.0 Precautions... 4 4.0 Pre-survey... 5 5.0 Materials and Equipment...

More information

Broadband Connectivity System II

Broadband Connectivity System II User Manual Applys to: :: 010-3232-0001 :: 010-3224-0001 :: 010-3201-0407 :: 010-3201-0401 :: 010-3201-0410 :: 710-3201-0002 :: 710-3201-0005 :: 710-3201-1001-U :: 710-3201-1002-U :: 710-3201-2001-U ::

More information

OPTICA TECHNOLOGIES INCORPORATED and the OPTICA TECHNOLOGIES INCORPORATED logo are trademarks of Optica Technologies Incorporated.

OPTICA TECHNOLOGIES INCORPORATED and the OPTICA TECHNOLOGIES INCORPORATED logo are trademarks of Optica Technologies Incorporated. Optica Technologies Incorporated 34600 FXBT Converter Quick Start Guide Product Warranty Safety Warnings 34600/070208 Trademarks OPTICA TECHNOLOGIES INCORPORATED and the OPTICA TECHNOLOGIES INCORPORATED

More information

Replacing the PanelMate epro PS, PanelMate epro PS Classic, PanelMate epro PS EE, and PanelMate epro PS OD 7685x-15xx Series Backlight Assembly

Replacing the PanelMate epro PS, PanelMate epro PS Classic, PanelMate epro PS EE, and PanelMate epro PS OD 7685x-15xx Series Backlight Assembly Introduction Replacing the PanelMate epro PS, PanelMate epro PS Classic, PanelMate epro PS EE, and PanelMate epro PS OD 7685x-15xx Series Assembly Instruction Leaflet IL04802009E Effective September 2008

More information

Spec Sheet. InterReach Fusion Wideband 2.5 GHz WiMAX. In-Building Wireless Networking System. Product Highlights

Spec Sheet. InterReach Fusion Wideband 2.5 GHz WiMAX. In-Building Wireless Networking System. Product Highlights In-Building Wireless Networking System InterReach Fusion is the latest addition to ADC s portfolio of Distributed Antenna Systems. It offers the same superior performance as Unison in an easy-to-install,

More information

APPENDIX A Verify All Part Numbers (Partial List of Approved Products)

APPENDIX A Verify All Part Numbers (Partial List of Approved Products) SECTION 16651 APPENDIX A Verify All Part Numbers (Partial List of Approved Products) SYSTIMAX SCS: OVER-VOLTAGE PROTECTION 1. Over-voltage Protection Device, 100-Pair with Enclosure, Product 489ACAI-100,

More information

Instruction Manual RT-91600D-SL RR-91600D-SL Sixteen Channel Video Multiplexer With Remote Diagnostic Interface

Instruction Manual RT-91600D-SL RR-91600D-SL Sixteen Channel Video Multiplexer With Remote Diagnostic Interface Instruction Manual RT-91600D-SL RR-91600D-SL Sixteen Channel Video Multiplexer With Remote Diagnostic Interface Copyright 2005, American Fibertek, Inc. 0804JD Table of Contents Functional Description...

More information

INSTALLATION GUIDE. LANmark-OF Zone Distribution Box

INSTALLATION GUIDE. LANmark-OF Zone Distribution Box LANmark-OF Zone Distribution Box INSTALLATION GUIDE LANmark-OF Zone Distribution Box Document information Release November 2004 Published by Contact address Nexans Cabling Solutions Alsembergsesteenweg

More information

VGA & Audio over CAT5 Distribution Series

VGA & Audio over CAT5 Distribution Series CATS-VGA-12B/CATS-VGA-16B CATS-VGA-RX1/CATS-VGA-RX1D VGA & Audio over CAT5 Distribution Series User Manual CATS-VGA-12B CATS-VGA-RX1 CATS-VGA-16B CATS-VGA-RX1D Safety and Notice The VGA & Audio over CAT5

More information

Manual No: Revision: D. IQ Box. Software Upgrade Instructions

Manual No: Revision: D. IQ Box. Software Upgrade Instructions Manual No: 577013-834 Revision: D IQ Box Software Upgrade Instructions Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties

More information

Installation instructions Roxtec RM ES systems

Installation instructions Roxtec RM ES systems Safety information Roxtec recommends that all installations are performed without facility operation. Follow national regulations and installation codes. ny action affecting the routed service should be

More information

Cisco ONS Exposed Faceplate Mux/Demux 48-Channel Extended Bandwidth Patch Panel and Splitter Coupler Module

Cisco ONS Exposed Faceplate Mux/Demux 48-Channel Extended Bandwidth Patch Panel and Splitter Coupler Module Cisco ONS 15216 Exposed Faceplate Mux/Demux 48- Extended Bandwidth Patch Panel and Splitter Coupler Module Product Overview The Cisco ONS 15216 Exposed Faceplate Mux/Demux 48- Extended Bandwidth Patch

More information

DVI Rover 700 User Guide

DVI Rover 700 User Guide DVI Rover 700 User Guide Featuring ExtremeDVI Technology DVI Rover 700 This document applies to Part Numbers: 00-00106 through 00-00141 inclusive. FCC Radio Frequency Interference Statement Warning The

More information

DOME OPTIC SPLICE CLOSURE

DOME OPTIC SPLICE CLOSURE FIBER OPTIC SPIICE CLOSURE GJS-JKDH1001-120 BOX DIMENSION: W=140mm H=340mm Weight = 1.80 kgs Outer Internal structure Fuse fiber disc Type sealing ring Plastic hoop base Pole Mount Pole Mount 1 1. product

More information

3. Electronics and MMU2 unit assembly

3. Electronics and MMU2 unit assembly Written By: Jakub Dolezal 2018 manual.prusa3d.com/ Page 1 of 34 Step 1 Tools necessary for this chapter Please prepare tools for this chapter: 2.5mm Allen key for M3 screws 2mm Allen key for nut alignment

More information

HighBand 25. TrueNet Category 6 Solutions

HighBand 25. TrueNet Category 6 Solutions HighBand 25 TrueNet Category 6 Solutions The highest performing cross-connect system in the world. A unique high-density solution with superior cable management. ADC KRONE s HighBand 25 cross connect solution

More information

User Guide. HDMI Fiber Optic Extender. DVI-7350a

User Guide. HDMI Fiber Optic Extender. DVI-7350a User Guide HDMI Fiber Optic Extender DVI-7350a Table of Contents Section Page Product Safety.................................... 1 1.0 Introduction...2 2.0 Specifications...3 3.0 Package Contents...3 4.0

More information