SECTION COMMUNICATIONS HORIZONTAL CABLING

Size: px
Start display at page:

Download "SECTION COMMUNICATIONS HORIZONTAL CABLING"

Transcription

1 SECTION COMMUNICATIONS HORIZONTAL CABLING PART 1 GENERAL 1.1 RELATED DOCUMENTS AND SECTIONS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. B. Related Sections: 1.2 SUMMARY 1. Division 27 Section Common Work Results for Communications for project scope of work, contractor qualifications, definitions, substitutions, warranty, etc. 2. Division 27 Sections Communications Equipment Room Fittings and "Communications Backbone Cabling" for voice and data cabling associated with system panels and devices. 3. Division 28 Section "Conductors and Cables for Electronic Safety and Security" for voice and data cabling associated with system panels and devices. A. Section Includes: 1. Pathways. 2. UTP Cable. 3. Cable Connecting Hardware and Patch Panels. 4. Communications Outlet/Connectors. 5. Cabling System Identification Products. 6. Cable Management System. 7. Testing. 1.3 SUBMITTALS A. See requirements under Division 27 Section Common Work Results for Communications. 1.4 PERFORMANCE REQUIREMENTS A. General Performance: Horizontal cabling system shall comply with transmission standards in TIA/EIA-568-C.1 and IEEE Std 802.3ae, when tested according to test procedures of this standard. This Contractor shall notify this Engineer, prior to cable installation, should the path distance the Contractor has chosen to install the cable exceeds the maximum distance allowed by BICSI. Matrix Proj. No Communications Horizontal Cabling

2 1.5 QUALITY ASSURANCE A. Surface-Burning Characteristics: As determined by testing identical products according to ASTM E 84 by a qualified testing agency. Identify products with appropriate markings of applicable testing agency. 1. Flame-Spread Index: 25 or less. 2. Smoke-Developed Index: 50 or less. B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. C. Communications Pathways and Spaces: Comply with TIA/EIA-569-B. D. Grounding: Comply with ANSI-J-STD-607-A. 1.6 DELIVERY, STORAGE, AND HANDLING A. Test cables upon receipt at Project site. Test each pair of UTP cable for open and short circuits. 1.7 PROJECT CONDITIONS A. Environmental Limitations: Do not have delivered or install cables and connecting materials until wet work in spaces is complete and dry, and temporary HVAC system is operating and maintaining ambient temperature and humidity conditions at occupancy levels during the remainder of the construction period. 1.8 COORDINATION A. Coordinate layout and installation of communications pathways and cabling with Owner's communications and LAN equipment and service suppliers. B. Coordinate communications outlet/connector locations with location of power receptacles at each work area. C. Coordinate work with other trades. 1.9 CLOSE-OUT DOCUMENTS A. Refer to Division 27 Section Common Work Results for Communication for close-out document requirements, including, but not limited to the following: 1. Operation and Maintenance manuals; 2. List of Contractors and Parts and Equipment Suppliers complete with contact person, proper company name, address, and telephone numbers; 3. All Contractor and Manufacturer warranties; 4. Training Video and training sign-in sheet. Matrix Proj. No Communications Horizontal Cabling

3 PART 2 PRODUCTS 2.1 PATHWAYS A. General Requirements: Comply with TIA/EIA-569-B. B. Cable Support: NRTL labeled for support of Category 6 cabling, designed to prevent degradation of cable performance and pinch points that could damage cable. 1. Support brackets with cable tie slots for fastening cable ties to brackets. 2. Lacing bars, spools, J-hooks, and D-rings. 3. Straps and other devices. 4. Cable ties shall be Velcro. C. Conduit and Boxes: Comply with requirements in Division 26 Section "Raceway and Boxes for Electrical Systems." Flexible metal conduit shall not be used. Outlet boxes shall be no smaller than 2-1/4"(W) x 3-3/4"(L) x 3-1/4"(D). D. For firestopping, provide fittings that have been UL tested for through-penetration firestops. Fittings shall be passive and designed for use on both sides of a wall/floor. Provide in galvanized finish and in sizes required through firewalls. Acceptable Manufacturer: Wiremold FlameStopper. 2.2 UTP CABLE A. Description: 100-ohm, 4-pair UTP, formed into 25-pair, binder groups with a FEP insulation and a FR, low smoke PVC Jacket. 1. Comply with ICEA S for mechanical properties. 2. Comply with TIA/EIA-568-C.1 for performance specifications. 3. Comply with TIA/EIA-568-C.2, Category Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444 and NFPA 70 for the following type: a. Communications, Plenum Rated: Type CMP, complying with NFPA For communication outlets with two RJ-45s, provide one cable for data (gray) and one cable for voice (blue). For communication outlets with three RJ-45s, provide two cables for data (gray and yellow) and one cable for voice (blue). 6. Upon entering the MDF, the cables shall be formed into a 10' slack coil and secured in "D" rings on the plywood wall. 7. Acceptable Manufacturers: a. Berk-Tek: LANmark-1000 Category 6, # (Gray), # (Blue), and # (Yellow). Matrix Proj. No Communications Horizontal Cabling

4 b. General Cable:.GenSPEED 6000 Category 6, # (Gray), # (Blue), and # (Yellow). 8. It was determined that the cable lengths would comply with Standards on paper. However, due to Contractor discretion in actual routing (shall be run perpendicular and parallel to building lines) and coordination with other trades, Contractor shall verify that the furthest outlet s cable length does not exceed the length, as stipulated in the Standards. If the cable length exceeds the distance, this Contractor shall work with the Engineer to establish an IDF in order to comply with Standards, at no additional cost to the Owner including backboard, four-strand 50 um laser optimized fiber optic cable between closets, fiber and copper patch panels, cross connects, and testing. If this situation occurs, Contractor shall submit shop drawings for this scope. 2.3 UTP PATCH PANELS AND CORDS A. General Requirements for Cable Connecting Hardware: Comply with TIA/EIA-568-C.2, IDC type, with modules designed for punch-down caps or tools. Cables shall be terminated with connecting hardware of same category or higher for a performance warrantied system. B. Connecting Blocks: 110-style IDC for Category 6. Provide blocks for the number of cables terminated on the block, plus 25 percent spare. Integral with connector bodies, including plugs and jacks where indicated. 1. Number of Terminals per Field: One for each conductor in assigned cables. C. Patch Panels (T568A): Modular panels housing multiple-numbered jack units with IDCtype connectors at each jack for permanent termination of pair groups of installed cables. 1. Number of Jacks per Field: One for each four-pair UTP cable indicated. 2. Provide Category 6 UTP patch panels (rack mount) per TIA 568-C.2 as verified by ETL. Panels shall have 110 IDC type to eight position eight conductor connectors with no exposed PC boards. Jacks shall be manufactured with printed circuit board (PCB) and have T568A pin/pair assignment (unless otherwise noted on the drawings). Patch panels shall be provided with individual port and patch panel labeling identification areas and shall be labeled consistent with the data jack system labeling outlined in this specification. 3. Provide quantity to accommodate number of outlets indicated on drawings. 4. Provide rear cable management (including stress relief bars) and horizontal cable management guide either as an integral part of the patch panel or as a separate piece and station support bars. Each 48 port patch panel is to have a dedicated horizontal cable guide located adjacent to the patch panel in the rack or as indicated on drawings. 5. The building and room number in which the patch panel resides shall be prominently displayed. 6. Patch panels and each port of each patch panel shall be labeled per the Owner s specifications. Matrix Proj. No Communications Horizontal Cabling

5 7. Allow 50% of the rack space for Owner provided switches, servers, transceivers, shelves, and UPS. 8. Acceptable Manufacturers: a. Leviton: extreme 6+ #69586-U48. b. Ortronics: Clarity6 #OR-PHD66U48. D. Provide dedicated patch panels in which to terminate the GRAY CAT 6 data cables mount GRAY patch panel(s) below any fiber optic cable cabinet (located at the top of the rack allow space if none exists). Provide dedicated patch panels in which to terminate the YELLOW CAT 6 data cables mount below the GRAY patch panel(s). Provide dedicated patch panels in which to terminate the BLUE CAT 6 data cables mount below the YELLOW patch panel(s). However, when only two, CAT 6 cables are being installed, BLUE cables and jacks shall replace the YELLOW cables and jacks - the YELLOW cables and jacks shall be eliminated. 1. In the 3 port design, cables shall terminate in RJ-45 jacks mounted on three-port face plates. The GRAY and YELLOW cables shall connect to the top and middle port for data and the BLUE cable on the bottom port for voice. For the two-port applications, GRAY shall be on top and BLUE in the middle with a blank cap at the bottom. 2. RJ-45 jacks shall match the cables in color. E. Patch/Line Cords: Factory-made, four-pair cables in lengths listed below; terminated with eight position modular plug at each end. Shall incorporate cross-over lead concept and built-in exclusion features. Provide one patch cord for each end of each link (i.e., two per link), as shown on the drawings, plus 30% spares. Confirm final color with Engineer/Owner prior to ordering. 1. Provide cords in the following lengths (confirm length and Owner preferred colors prior to ordering): a. Line Cords: 50% - 10 feet and 50% - 15 feet. b. Patch Cords: 50% - 3 feet and 50% - 7 feet. c. Provide 30% spare cords (Qty/Lengths: ½ at 3 feet and ½ at 7 feet). 2. Acceptable Manufacturers a. Leviton extreme 6+ SlimLine Patch Cord Series. b. Legrand Ortronics: Clarity6 Modular Patch Cord Series. 3. Contractor shall sequentially label (with flexible cable labels or order sequentially pre-printed from the factory) each patch cord with the same number on both ends (1, 1; 2, 2; 3, 3; etc.). Contractor shall place a tag on the frame to indicate the last number used on the patch cords. Matrix Proj. No Communications Horizontal Cabling

6 2.4 COMMUNICATIONS OUTLET/CONNECTORS (T568A) A. RJ45 jacks shall match the cables in color and be made of high impact, flame retardant UL-rated 94V-0 thermoplastic. The jacks shall be designed with integral locking mechanism which, upon insertion into the face plate port, shall provide maximum pullout strength at the interface. B. RJ45 jacks shall be recessed mount, 100-ohm, balanced, twisted-pair connector; four-pair, eight-position modular, flat. Comply with TIA-568-C.0, TIA-568-C.1, TIA-568-C.2, and TIA-606-B specifications. The jacks shall individually snap-in to faceplate. Legend shall be machine printed (no less than 12 point type), in the field, using adhesive-tape label or snap-in, clear-label covers and machine-printed paper inserts. Termination of all jacks shall be 110-type insulation displacement connectors (IDC), T568A pin/pair assignment and shall utilize printed circuit board technology. C. Acceptable Manufacturers: 1. Leviton: extreme 6+ (#61110-RW6) with QuickPort Multimedia Outlet System Faceplate SMW or #41290=DMW White with flat mounting connector inserts # QW and blanks, as necessary. 2. Ortronics: Clarity 6 (white) with Series II Faceplate #OR or #OR Fog White with flat mounting module #OR and blanks, as necessary. 2.5 IDENTIFICATION PRODUCTS A. Labeling shall comply with Owner s specifications. B. Horizontal cables shall be labeled at each end of the cable. Additional labeling may be required at the intermediate locations such as conduits ends. C. Labeling shall start at the closest room to the Telecommunications Room and continue, in a logical manner clockwise, until each location is designated. D. Work station outlets in each room shall be numbered sequentially in a clockwise fashion beginning with the first outlet to the left of the primary entrance door. The RJ-45 jacks on the outlet faceplates shall be aligned vertically. The jacks shall be designated A, B, and C from top to bottom, which shall correspond to the Patch Panels designated GRAY, YELLOW and (BLUE as used) in the Telecommunications Room. BLUE Patch Panel shall not be required in two cable and two port applications. E. The work station outlets shall be numbered in clockwise order 1, 2, 3 etc. As an example, Room 100 is equipped with three work station outlets. The top of the first outlet faceplate shall reflect "RM 100" and the three jacks shall be labeled A1, B1 and C1. The second outlet shall be "RM 100," labeled A2, B2 and C2. The third, "RM 100", A3, B3 and C3. F. Patch Panels in the Telecommunications Room shall be labeled A, B, and (C as used) to correspond to the three ports on the outlet faceplates. To follow through with the Room 100 example, the first three ports on Patch Panel A shall be labeled Room 100, 1, 2, and 3. Patch Panel B shall be labeled Room 100, 1, 2, and 3. And, Patch Panel C (as used) shall be labeled Room 100, 1, 2, and 3. If the next room number is 102 and it has five outlet boxes, the next five ports on each Patch Panel A, B, and (C as used) shall be labeled "RM 102," 1, 2, 3, 4, and 5. The Patch Panel ports shall be numbered as they appear in a particular room, not by the physical port number. Matrix Proj. No Communications Horizontal Cabling

7 1. In the two cable/three port face plate applications, the top port shall remain A with the cable and jack GRAY for data. The middle port shall be B with the cable and jack BLUE for voice. The bottom port shall be left blank for future use. The corresponding Patch Panels in the TR shall be designated A with GRAY cables and jacks and B with BLUE cables and jacks. G. Comply with TIA/EIA-606-B and UL 969 for labeling materials, including label stocks, laminating adhesives, and inks used by label printers. H. Comply with requirements in Division 26 Section "Identification for Electrical Systems." I. Each box shall have a recessed designation strip with clear plastic cover for jack identification. Lettering shall be typed not handwritten. The associated termination shall be permanently labeled. 2.6 VOICE CABLE A. From the existing service provider s demarc, extend a 25 pair house cable from a 66 block mounted on the plywood wall to a 24 port, rack mounted patch panel. One pair shall be terminated on each port 1 through 23 and two pair on port 24. This configuration shall be used for FAX lines or any other requirement for analog service. 2.7 GROUNDING A. Comply with requirements in Division 26 Section "Grounding and Bonding for Electrical Systems" for grounding conductors and connectors. B. Comply with ANSI-J-STD-607-A. PART 3 EXECUTION 3.1 WIRING METHODS A. Wiring Method: Install cables in raceways and category compliant j-hooks. 1. Comply with requirements for raceways and boxes specified in Division 26 Section "Raceway and Boxes for Electrical Systems." B. Wiring within Enclosures: Bundle, lace, and train cables to terminal points with no excess and without exceeding manufacturer's limitations on bending radii. Provide and use lacing bars and distribution spools. 3.2 INSTALLATION OF PATHWAYS A. Comply with requirements for demarcation point, pathways, cabinets, and racks specified in Division 27 Section "Communications Equipment Room Fittings." Drawings indicate general arrangement of pathways and fittings. B. Comply with TIA/EIA-569-B for pull-box sizing and length of conduit and number of bends between pull points. C. Comply with requirements in Division 26 Section "Raceway and Boxes for Electrical Systems" for installation of conduits and wireways. Matrix Proj. No Communications Horizontal Cabling

8 3.3 INSTALLATION OF CABLES A. Comply with NECA 1. B. General Requirements for Cabling: 1. Comply with TIA/EIA-568-C Comply with BICSI ITSIM, Ch. 6, Cable Termination Practices. 3. Install 110-style IDC termination hardware unless otherwise indicated. 4. Terminate conductors; no cable shall contain un-terminated elements. Make terminations only at indicated outlets, terminals, cross-connects, and patch panels. 5. Cables may not be spliced. Secure and support cables at intervals not exceeding 48 inches and not more than 6 inches from cabinets, boxes, fittings, outlets, racks, frames, and terminals. 6. Install lacing bars to restrain cables, to prevent straining connections, and to prevent bending cables to smaller radii than minimums recommended by manufacturer. 7. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI ITSIM, "Cabling Termination Practices" Chapter. Install lacing bars and distribution spools. 8. Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation and replace it with new cable. 9. Cold-Weather Installation: Bring cable to room temperature before de-reeling. Heat lamps shall not be used for heating. 10. In the communications equipment room, install a 10-foot long service loop on each end of cable. 11. Pulling Cable: Comply with BICSI ITSIM, Ch. 4, "Pulling Cable." Monitor cable pull tensions. C. UTP Cable Installation: 1. Comply with TIA/EIA-568-C.2. 2 Do not untwist UTP cables more than 1/2 inch from the point of termination to maintain cable geometry. D. Open-Cable Installation: 1. Install cabling with horizontal and vertical cable guides in communications spaces with terminating hardware and interconnection equipment. 2. Suspend UTP cable (not in a wireway or pathway) a minimum of 8 inches above ceilings by cable supports not more than 48 inches apart. Matrix Proj. No Communications Horizontal Cabling

9 3. Cable shall not be run through structural members or in contact with pipes, ducts, or other potentially damaging items. E. Group connecting hardware for cables into separate logical fields. F. Separation from EMI Sources: 3.4 FIRESTOPPING 1. Comply with BICSI TDMM and TIA/EIA-569-A for separating unshielded copper voice and data communication cable from potential EMI sources, including electrical power lines and equipment. 2. Separation between open communications cables or cables in nonmetallic raceways and unshielded power conductors and electrical equipment shall be as follows: a. Electrical Equipment Rating Less Than 2 kva: A minimum of 5 inches. b. Electrical Equipment Rating between 2 and 5 kva: A minimum of 12 inches. c. Electrical Equipment Rating More Than 5 kva: A minimum of 24 inches. 3. Separation between communications cables in grounded metallic raceways and unshielded power lines or electrical equipment shall be as follows: a. Electrical Equipment Rating Less Than 2 kva: A minimum of 2-1/2 inches. b. Electrical Equipment Rating between 2 and 5 kva: A minimum of 6 inches. c. Electrical Equipment Rating More Than 5 kva: A minimum of 12 inches. 4. Separation between communications cables in grounded metallic raceways and power lines and electrical equipment located in grounded metallic conduits or enclosures shall be as follows: a. Electrical Equipment Rating Less Than 2 kva: No requirement. b. Electrical Equipment Rating between 2 and 5 kva: A minimum of 3 inches. c. Electrical Equipment Rating More Than 5 kva: A minimum of 6 inches. 5. Separation between Communications Cables and Electrical Motors and Transformers, 5 kva or HP and Larger: A minimum of 48 inches. 6. Separation between Communications Cables and Fluorescent Fixtures: A minimum of 12 inches. A. Comply with TIA/EIA-569-A, Annex A, "Firestopping." B. Comply with Section and BICSI TDMM, "Firestopping Systems" Article. Matrix Proj. No Communications Horizontal Cabling

10 3.5 GROUNDING A. Install grounding according to BICSI TDMM, "Grounding, Bonding, and Electrical Protection" Chapter. B. Comply with ANSI-J-STD-607-A. C. Locate grounding bus bar to minimize the length of bonding conductors. Fasten to wall allowing at least 2-inch clearance behind the grounding bus bar. Connect grounding bus bar with a minimum No. 4 AWG grounding electrode conductor from grounding bus bar to suitable electrical building ground. D. Bond metallic equipment to the grounding bus bar, using not smaller than No. 6 AWG equipment grounding conductor. 3.6 IDENTIFICATION A. Labeling shall comply with Owner s specifications. Identify system components, wiring, and cabling complying with TIA/EIA-606-B. Comply with requirements for identification specified in Division 26 Section "Identification for Electrical Systems." 1. Administration Class: Color-code cross-connect fields. Apply colors to voice and data service backboards, connections, covers, and labels. B. Provide factory-finished and labeled backboards. C. Paint and label colors for equipment identification shall comply with TIA/EIA-606-B for Class 3 level of administration, including optional identification requirements of this standard. D. Cable Schedule: Post in prominent location in each equipment room and wiring closet. List incoming and outgoing cables and their designations, origins, and destinations. Protect with rigid frame and clear plastic cover. Furnish an electronic copy of final comprehensive schedules for Project. Provide paper copies as determined by Owner. E. Cabling Administration Drawings: Show building floor plans with cabling administrationpoint labeling. Identify labeling convention and show labels for communications closets, backbone pathways and cables, entrance pathways, terminal hardware and positions, horizontal cables, work areas and workstation terminal positions, grounding buses and pathways, and equipment grounding conductors. Follow convention of TIA/EIA-606-B. Furnish electronic record of all drawings, in software and format selected by Owner. Provide paper copies as determined by Owner. F. Cable and Wire Identification: 1. Label each cable within 4 inches of each termination and tap, where it is accessible in a cabinet or junction or outlet box, and elsewhere as indicated. 2. Identification within Connector Fields in Equipment Rooms and Wiring Closets: Label each connector and each discrete unit of cable-terminating and connecting hardware. Matrix Proj. No Communications Horizontal Cabling

11 G. Labels shall be preprinted or computer-printed type with printing area and font color that contrasts with cable jacket color but still complies with requirements in TIA/EIA-606-B. Cable labels shall utilize flexible vinyl or polyester that flex as cables are bent. 3.7 HORIZONTAL CABLE SYSTEM PERFORMANCE VERIFICATION A. Field Quality Control (UTP) 1. Perform tests and inspections. 2. Tests and Inspections: a. Visually inspect UTP jacket materials for NRTL certification markings. Inspect cabling terminations in communications equipment rooms for compliance with color-coding for pin assignments, and inspect cabling connections for compliance with TIA/EIA-568-C.1. b. Visually confirm Category 6, marking of outlets, cover plates, outlet/connectors, and patch panels. c. Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components. d. Test UTP backbone copper cabling for DC loop resistance, shorts, opens, intermittent faults, and polarity between conductors. Test operation of shorting bars in connection blocks. Test cables after termination but not cross-connection. 1) Test instruments shall meet or exceed applicable requirements in TIA/EIA-568-C.2. Perform tests with a tester that complies with performance requirements in "Test Instruments (Normative)" Annex, complying with measurement accuracy specified in "Measurement Accuracy (Informative)" Annex. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration. e. UTP Performance Tests: 1) Test for each outlet. Perform the following tests according to TIA/EIA- 568-C.0, TIA/EIA-568-C.1, and TIA/EIA-568-C.2: a) Wire map. b) Length (physical vs. electrical, and length requirements). c) Insertion loss. d) Near-end crosstalk (NEXT) loss. e) Power sum near-end crosstalk (PSNEXT) loss. f) Equal-level far-end crosstalk (ELFEXT). g) Power sum equal-level far-end crosstalk (PSELFEXT). Matrix Proj. No Communications Horizontal Cabling

12 h) Return loss. i) Propagation delay. j) Delay skew. f. Final Verification Tests: Perform verification tests for UTP systems after the complete communications cabling and workstation outlet/connectors are installed. 1) Voice Tests: These tests assume that dial tone service has been installed. Connect to the network interface device at the demarcation point. Go off-hook and listen and receive a dial tone. If a test number is available, make and receive a local, long distance, and digital subscription line telephone call. 2) Data Tests: These tests assume the Information Technology Staff has a network installed and is available to assist with testing. Connect to the network interface device at the demarcation point. Log onto the network to ensure proper connection to the network. 3. End-to-end cabling shall be considered defective if it does not pass tests and inspections. 4. Prepare test and inspection reports. B. Documentation 1. Contractor shall provide documentation to include test results and as-built drawings. Drawings shall be developed in CAD (i.e., AutoCAD 2009 or higher). a. Each MDF and IDF shall contain a copy of that building's as-built drawing affixed to an adjacent wall or located in an interior pouch for quick reference. Revised rack and equipment cabinet elevations shall be provided including serial numbers of all installed equipment. b. Provide three sets of black line, as-built drawing sets. c. Provide CD-ROM reflecting all the work with actual device and equipment locations. Drawings to be submitted in.dwg or.dxf format. 2. Document data for each measurement. Data for submittals shall be printed in a summary report that is formatted similar to Table 10.1 in BICSI TDMM, or transferred from the instrument to the computer, saved as text files, and printed and submitted. a. Provide the testing results database on CD-ROM for the completed job. The CD-ROM shall include the software tools required to view, inspect, and print any selection of test reports. b. Additionally, provide one hard copy of UTP cabling results. These results shall be submitted to the Engineer prior to the Contractor calling for substantial completion inspection. Matrix Proj. No Communications Horizontal Cabling

13 c. Provide each communications room with its own notebook containing the corresponding test reports for the copper cabling. Each notebook shall have a clear front pocket and be labeled with that communications room s designation. 3. Provide a bill of materials of all installed equipment and wiring, rack, and backboard equipment layouts showing placement of support equipment, and model and serial numbers of all installed equipment. C. Acceptance 1. Acceptance of the Data Communications System, by the Owner, shall be based on: D. Project Completion 3.8 TRAINING a. Copy of all test results: All workstation data cables must meet the criteria established above. The Contractor is responsible for additional UTP cable to be installed if any show defective during testing. b. Copy of as-built drawings (AutoCAD 2010 or higher disk copy and three black line copies) shall contain the following. 1) Changes and/or deviations from the construction (bid) prints. 2) Cable Schedule: The schedule shall reflect all incoming and outgoing cables and their designations, origins and destinations. Also, the schedule shall show the Patch Panel port assignments to a particular voice/data outlet by number and room location. All communication outlet addresses and locations. 3) Cabling Administration: Building floor plans (1/16 inch minimum) highlighting, in bold print, the voice/data outlet number, location, and room number. Horizontal cable routing. 1. Upon completion of the work of this Section, thoroughly clean all exposed portions of the installation, removing all traces of soil, labels, grease, oil, or other foreign material, and using only the type cleaner recommended by the manufacturer of the item being cleaned. Cover all exposed cabling and termination devices. A. Provide a minimum of two site personnel with training on the network cabling system for up to two hours on site. Training shall cover the location labeling scheme, documentation structure and contents, documentation orientation, and system reconfiguration (i.e., reassignment of Communication Outlet function via patching). Training shall take place at time of Substantial Completion before building is occupied by Owner. 3.9 WARRANTY A. Per Division 27 Section Common Work Results for Communications. *** END OF SECTION *** Matrix Proj. No Communications Horizontal Cabling

14 THIS PAGE INTENTIONALLY LEFT BLANK Matrix Proj. No Communications Horizontal Cabling

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors including patch panels. 3. Cabling identification

More information

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents PART 1 - GENERAL 1.1 SUMMARY SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors. 3. Cabling system identification products. 1.2

More information

ADDENDUM NO. 2 This addendum consists of 8 pages. Kenai Peninsula Borough Purchasing & Contracting

ADDENDUM NO. 2 This addendum consists of 8 pages. Kenai Peninsula Borough Purchasing & Contracting KENAI PENINSULA BOROUGH Purchasing and Contracting 144 North Binkley Street Soldotna, Alaska 99669-7520 Toll-free within the Borough: 1-800-478-4441, Ext. 2260 PHONE: (907) 714-2260 FAX: (907) 714-2373

More information

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED.

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED. Beaverton School District Capital Program Purchasing 16550 SW Merlo Road, Beaverton, OR 97006 Phone: 503-591-4539 SOLICITATION ADDENDUM NO. 1 ITB 15-0012 THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 - GENERAL 1.1 SECTION

More information

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017 SECTION 27 15 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus PART 1: GENERAL REQUIREMENTS A. Contractor Work 1. Provide and install (except as noted in this document), cable,

More information

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017 Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM-2017-2 Date: 05/26/2017 Additional specification information for data communication to cameras and between Library

More information

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION PART 1 - GENERAL 1.1 SUMMARY SCOPE SECTION 25170 TESTING, IDENTIFICATION AND ADMINISTRATION 1. This section includes the minimum requirements for the testing, certification administration and identification

More information

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1. PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

A. All communications equipment rooms shall be installed in a neat and workmanlike manner.

A. All communications equipment rooms shall be installed in a neat and workmanlike manner. SECTION 27 11 00 - COMMUNICATIONS EQUIPMENT ROOM FITTINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE Prepared in cooperation and approval from BICSI Building Industry Consulting Services International and

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT Purchasing and Warehouse Services Department October 1, 2007 Addendum No. 1 INVITATION FOR BID No. 08-09 Temporary Faculty Offices, Chabot College All Prospective

More information

STRUCTURED CABLE SYSTEM (SCS)

STRUCTURED CABLE SYSTEM (SCS) PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

Section Communications Optical Fiber Backbone Cabling

Section Communications Optical Fiber Backbone Cabling Part 1 1.1 Related Documents 1.1.1 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections apply to this Section. 1.2 Related

More information

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School BILOXI PUBLIC SCHOOL DISTRICT Biloxi Junior High School Request for Proposals E-Rate 2014-2015 - Internal Connections Submit Proposals To: Purchasing Department Attn: Traci Barnett 160 St. Peter Street

More information

PREMIUM 5e F/UTP PRODUCTS

PREMIUM 5e F/UTP PRODUCTS Siemon s end-to-end cabling system is guaranteed to provide transmission performance margins in excess of industry standards for category 5e parameters, while featuring excellent EMI resistance. has been

More information

IndyGo Facility Upgrades Project 35671EE

IndyGo Facility Upgrades Project 35671EE SECTION 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Identification for raceways. 2. Identification of power and control cables. 3. Identification for

More information

SECTION FIBER OPTIC STATION CABLES

SECTION FIBER OPTIC STATION CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications shall include all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices Berk-Tek recommends installing a well-designed structured cabling channel per the TIA standards. This includes up to 100

More information

SECTION TESTING OF COPPER CABLES

SECTION TESTING OF COPPER CABLES SECTION 27 08 13 TESTING OF COPPER CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction,

More information

The University of Texas at Austin September 30, 2011

The University of Texas at Austin September 30, 2011 SECTION 27 08 20 COPPER TESTING PART 1 - GENERAL 1.1 SUMMARY A. Test measurements shall be taken for all balanced-twisted pair cabling, including horizontal and backbone copper cables and wall-to-rack

More information

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE)

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) PART 1: GENERAL 1.01 Telecommunications Engineer Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) B. Registered Communications Distribution Designer

More information

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection. SECTION 271300 - COMMUNICATIONS BACKBONE CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project 1.1.0 GENERAL The purpose of this specification is to establish a requirement for the installation of a voice, video and data cable network. The cable (copper), wire, hardware, equipment racks, jumpers,

More information

Structured Cabling Introduction & Installation Guide

Structured Cabling Introduction & Installation Guide Structured Cabling Introduction & Installation Guide Structured Cabling Overview General Structure - Cat5e/Cat6 Cabling The structure illustrated has the following key points: Face plates present outlet

More information

SECTION INTERCOMMUNICATIONS AND PROGRAM SYSTEMS

SECTION INTERCOMMUNICATIONS AND PROGRAM SYSTEMS SECTION 27 51 23 SPEC WRITER NOTES: 1. Use this section only for NCA projects. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Contact Department of Veterans

More information

UNM IT/Telecommunications Guide Specification Labeling 11/07/

UNM IT/Telecommunications Guide Specification Labeling 11/07/ Labeling 1 PART 1: GENERAL 1.01 SCOPE OF WORK A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing

More information

SECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.

SECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes. SECTION 33 71 49.23 MEDIUM VOLTAGE CABLE INSTALLATION PART 1 GENERAL 1.1 SCOPE A. Work included in this Section: Medium Voltage Cable (4 kv and 12 kv) Installation and Termination. Removal and return of

More information

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab*

Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab* Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab* General Scope of Work: Supply and installation of Computer Laboratory setup in MIU Location of Installation:

More information

Clarity. Advanced solutions for 10 Gig, Category 6 and 5e copper connectivity PRODUCT SOLUTION GUIDE EXPERTISE. TECHNOLOGY. SOLUTIONS.

Clarity. Advanced solutions for 10 Gig, Category 6 and 5e copper connectivity PRODUCT SOLUTION GUIDE EXPERTISE. TECHNOLOGY. SOLUTIONS. Clarity Advanced solutions for 10 Gig, Category 6 and 5e copper connectivity PRODUCT SOLUTION GUIDE EXPERTISE. TECHNOLOGY. SOLUTIONS. Center Tuned Components Higher Signal-to- Noise Ratio Optimal Mated

More information

B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines.

B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines. PART 1 - GENERAL 1.1 SUMMARY A. This section includes: 1. Support Structures 2. Cable trays and ladder rack 3. Racks (including wire managers) 4. Cables (copper and optical fiber) 5. Jacks and faceplates

More information

Liberty Mutual Structured Cabling Specification Bid and Build Structured Cabling Technical Specification for:

Liberty Mutual Structured Cabling Specification Bid and Build Structured Cabling Technical Specification for: Bid and Build Structured Cabling Technical Specification for: Horizontal & Backbone Requirements Page 1 of 30 PUBLICATION RECORD Document Version Publication Date Primary Author Description Revision 1.0

More information

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Technical Specifications Florida Gulf Coast University

Technical Specifications Florida Gulf Coast University Technical Specifications Florida Gulf Coast University 9/19/2018 Page 1 of 21 Approved Vendors (alphabetical order) Aztek (CIP) Certified Installer Plus Mr. Scott Coyne 4730 Enterprise Avenue Suite #308

More information

DESIGN!!GUIDELINES!!!!!

DESIGN!!GUIDELINES!!!!! DESIGNGUIDELINES 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 1. Testing General 1.1. For acceptance, 100% of the media

More information

Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING

Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING Revision 05/01/2017 Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING PART 1 GENERAL 1.1 SECTION INCLUDES A. Voice, Data, and Fiber Cable Product materials B. Voice, Data, and Fiber Cable Execution

More information

Request for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS

Request for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS VOFP Cabling RFP 1 Request for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS For The Village of Franklin Park 2014 VOFP Cabling RFP 2 TABLE OF CONTENTS I. PROJECT DESCRIPTION

More information

SECTION 7 -- CROSS-CONNECT SYSTEMS

SECTION 7 -- CROSS-CONNECT SYSTEMS DETAIL ENGINEERING REQUIREMENTS AT&T March, 2016 Section 7, ATT-TP-76400 Revised NA SECTION 7 -- CROSS-CONNECT SYSTEMS CONTENTS PAGE 1. GENERAL... 7-2 1.1. Introduction... 7-2 1.2. Cable Holes... 7-2 1.3.

More information

Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5

Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5 Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5 1.0 INTRODUCTION Customer to define background and introduction to the project based on

More information

STRUCTURED CABLING SYSTEMS (SCS)

STRUCTURED CABLING SYSTEMS (SCS) STRUCTURED CABLING SYSTEMS (SCS) ModSecur - Structured Cabling Systems (SCS) A Structured Cabling System (SCS) is the backbone of any building, campus or site communication infrastructure. The sharp growth

More information

HighBand 25. TrueNet Category 6 Solutions

HighBand 25. TrueNet Category 6 Solutions HighBand 25 TrueNet Category 6 Solutions The highest performing cross-connect system in the world. A unique high-density solution with superior cable management. ADC KRONE s HighBand 25 cross connect solution

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD, applicable TC -, and CEHNC Design Guide 0-- (Standard is single UTOs and Double UTOs) B. Roads-Service, Lanes Adequate access is provided to the and AAR D. Testing Results-provided

More information

The Uniduct Nonmetallic Latching Raceway

The Uniduct Nonmetallic Latching Raceway Uniduct One-Piece Latching Raceway The Uniduct Nonmetallic Latching Raceway System is a one-piece single channel design, ideally suited to route and protect fiber optic, UTP, and and other low-voltage

More information

Public Works Division Lighting District Fiber Optic Specifications April 2009

Public Works Division Lighting District Fiber Optic Specifications April 2009 Public Works Division Lighting District Fiber Optic Specifications April 2009 7000 Florida Street Punta Gorda, Florida 33950 Tele: 941.575.3600 Fax : 941.637.9265 www.charlottecountyfl.com/publicworks

More information

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards.

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards. 27 08 00 Certification and Commissioning of Communication Systems (Revision date: 7/3/12) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are

More information

Project No. # Page 1

Project No. # Page 1 PART 1 - GENERAL This section of the has references, products, procedures, processes, and work descriptions/summaries that are common to many Washington State University Pullman (WSUP) campus telecommunications

More information

SECTION CONTROL, COMMUNICATION AND SIGNAL WIRING

SECTION CONTROL, COMMUNICATION AND SIGNAL WIRING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 27 10 00 CONTROL, COMMUNICATION AND SIGNAL WIRING SPEC WRITER NOTES: 1. Edit this specification section between // //, to fit project, or delete if not applicable.

More information

GenSPEED Category 5e Cables 3

GenSPEED Category 5e Cables 3 Datacom GenSPEED Category 5e Cables 3 GenSPEED Category 5e cables are available in a wide variety of performance levels and constructions. With many options to pick from, you can select the GenSPEED Category

More information

Description: Pair Color Code Chart: Pair Color Chart 1 Brown White Brown 2 Orange White Orange 3 Green White Green 4 Blue White Blue.

Description: Pair Color Code Chart: Pair Color Chart 1 Brown White Brown 2 Orange White Orange 3 Green White Green 4 Blue White Blue. Description: OZLINX CAT5e cable has a guaranteed performance; exceeds the Category 5e performance requirements and provides positive PSACR up to 155MHz for bandwidth requirement in the future. Product

More information

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008 Information & Communications Technology Group Standards June 2008 Appendix F UTP cabling Version 1.1 Appendix F UTP cabling 1. Introduction This Section details the required standards for Unshielded Twisted

More information

WJHW, Inc. 6 April 2016 Texas Tech University Issue for CD Set Sports Performance Complex Lubbock, Texas

WJHW, Inc. 6 April 2016 Texas Tech University Issue for CD Set Sports Performance Complex Lubbock, Texas SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide materials, labor, and methods for telecommunications grounding and bonding system in accordance with

More information

DATA/TELECOMMUNICATIONS REQUEST FOR PRICING

DATA/TELECOMMUNICATIONS REQUEST FOR PRICING Category 6A 10Gig DATA/TELECOMMUNICATIONS REQUEST FOR PRICING TABLE OF CONTENTS 1. GENERAL 3 1.1. Work Included... 3 1.2. Scope of Work... 3 1.3. Regulatory References... 4 1.4. Quality Assurance... 4

More information

CATEGORY 6 CABLING SOLUTIONS

CATEGORY 6 CABLING SOLUTIONS With over 20 years experience and know-how on communicating products design & developing, Premium Line has built maturity systems both in high tech develop and research center & complete structural quality

More information

10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System

10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System 10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System Next-Generation Category 6A UTP Cabling System Drivers for 10 GbE Aggregation of Gigabit Links Server Consolidation and

More information

ISSUED BY: Christine Barber PROJECT NAME: Meadville Branch - Wealth Management Office BDP PROJECT NUMBER: CLIENT S NUMBER:

ISSUED BY: Christine Barber PROJECT NAME: Meadville Branch - Wealth Management Office BDP PROJECT NUMBER: CLIENT S NUMBER: ADDENDUM 02 DATE: 13 June 2017 CLIENT NAME: PNC Bank ISSUED BY: Christine Barber PROJECT NAME: Meadville Branch - Wealth Management Office ISSUED TO: Ryan Campbell, CBC Ryan Doyle, Perry Const. Mike Cole,

More information

Multi-Media Installation Guide

Multi-Media Installation Guide Multi-Media Installation Guide Coaxial Page 2 Data Plug Page 7 Data Jack Page 10 Telephone Page 13 Splicing Page 15 Cable Types Cable Types Two basic types of cable are used in multimedia installations.

More information

Belden IBDN System 10GX 10GX Modules and 10GX Patch Panels

Belden IBDN System 10GX 10GX Modules and 10GX Patch Panels C O M M E R C I A L N E T W O R K I N G C O P P E R 5.6 Belden IBDN System GX GX Modules and GX Patch Panels AX2272 GX Module, Black GX Module The GX Module is a revolutionary punch down UTP connector

More information

3M Supported Applications Map 100,000 (2005) Single-mode. Fiber. Multimode. Fiber. Copper

3M Supported Applications Map 100,000 (2005) Single-mode. Fiber. Multimode. Fiber. Copper 3M Volition Network Solutions introduces Category 5e (Cat. 5e) copper cabling system to complement its leading fiber optic structured cabling system. Customers can now enjoy a single source of supply and

More information

SPECIAL SPECIFICATION 8540 Telecommunication Cable

SPECIAL SPECIFICATION 8540 Telecommunication Cable 2004 Specifications CSJ 0914-00-307 & CSJ 0914-25-003 SPECIAL SPECIFICATION 8540 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing,

More information

Telecommunication Infrastructure Project September 20, 2002

Telecommunication Infrastructure Project September 20, 2002 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Category rated UTP systems shall be provided and tested in accordance with the performance level established in Specification

More information

Belden IBDN System 10GX The next level of cabling performance

Belden IBDN System 10GX The next level of cabling performance Belden IBDN System 10GX The next level of cabling performance by Paul Kish Director Belden IBDN Systems and Standards Introduction There is a new standard under development in the IEEE 2.3an task force

More information

Power and Control T YPE BY RAVI GANATR November/December IAEI NEWS

Power and Control T YPE BY RAVI GANATR November/December IAEI NEWS Power and Control 26 1999 November/December IAEI NEWS T YPE BY RAVI GANATR This article discusses how the requirements in both the installation code and the product standard are utilized to manufacture

More information

Family Health Centers, Inc. Request for Proposal. for. Family Health Centers East Broadway Data and Communications Cabling Project

Family Health Centers, Inc. Request for Proposal. for. Family Health Centers East Broadway Data and Communications Cabling Project Family Health Centers, Inc. Request for Proposal for Family Health Centers East Broadway Data and Communications Cabling Project Date Issued: 06/07/2014 Date Due: 06/16/2014 Page 1 of 22 Table of Contents

More information

Jenkins County K-12 School Code SECTION DATA/VOICE CONDUIT SYSTEM

Jenkins County K-12 School Code SECTION DATA/VOICE CONDUIT SYSTEM PART 1 - GENERAL SECTION 27 1000 DATA/VOICE CONDUIT SYSTEM 1.01 SYSTEM DESCRIPTION A. A complete low voltage conduit and outlet system for the data/voice cabling system shall be provided by the contractor.

More information

SPECIAL SPECIFICATION 6559 Telecommunication Cable

SPECIAL SPECIFICATION 6559 Telecommunication Cable 2004 Specifications CSJ 0015-09-147, etc. SPECIAL SPECIFICATION 6559 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing, training,

More information

Frequency ASRL(db) Attenuation Max. NEXT Power Sum (MHz) Minimum db/100m db/1000ft Minimum db/100m Minimum db/100m

Frequency ASRL(db) Attenuation Max. NEXT Power Sum (MHz) Minimum db/100m db/1000ft Minimum db/100m Minimum db/100m Cat.5e 4 Pair UTP Cable Application: Voice ISDN 10Base T(IEEE 802.3) Fast Ethernet(IEEE802.3u) 100Vg-AnyLAN(IEEE 802.12) Token Ring(IEEE 802.5) TP-PMD(ANSI X3T9.5) 100Base-T Ethernet(IEEE 802.5) 155/622

More information

SECTION COMMUNICATIONS STRUCTURED CABLING

SECTION COMMUNICATIONS STRUCTURED CABLING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 27 15 00 COMMUNICATIONS STRUCTURED CABLING SPEC WRITER NOTES: 1. Edit this specification section between // //, to fit project, or delete if not applicable. 2.

More information

SPECIAL SPECIFICATION 2344 TMC Support Equipment

SPECIAL SPECIFICATION 2344 TMC Support Equipment 2004 Specifications CSJ 0912-00-488 SPECIAL SPECIFICATION 2344 TMC Support Equipment 1. Description. Furnish Traffic Management Center (TMC) support equipment in the City of Missouri City TMC location

More information

Primex Wireless, Inc. July, Wells Street Lake Geneva, WI

Primex Wireless, Inc. July, Wells Street Lake Geneva, WI Division 0 0 0 0 Primex Wireless, Inc. July, 00 Wells Street Lake Geneva, WI 00--0 www.primexwireless.com Product Guide Specification Specifier Note: This product specification is written according to

More information

HONEYWELL VIDEO SYSTEMS HIGH-RESOLUTION COLOR DOME CAMERA

HONEYWELL VIDEO SYSTEMS HIGH-RESOLUTION COLOR DOME CAMERA Section 00000 SECURITY ACCESS AND SURVEILLANCE HONEYWELL VIDEO SYSTEMS HIGH-RESOLUTION COLOR DOME CAMERA PART 1 GENERAL 1.01 SUMMARY The intent of this document is to specify the minimum criteria for the

More information

GenSPEED 10 MTP Category 6A Cable An Unshielded 6A Cable with Superior Protection Against Alien Crosstalk

GenSPEED 10 MTP Category 6A Cable An Unshielded 6A Cable with Superior Protection Against Alien Crosstalk GenSPEED A Cables GenSPEED 10 MTP A Cable An Unshielded 6A Cable with Superior Protection Against Alien Crosstalk 10 MTP unshielded-twisted pair (UTP) design provides industry-leading protection from external

More information

Effective earthing of screened cables

Effective earthing of screened cables NOVEMBER 2006 Effective earthing of screened cables All metallic containment items, other extraneous metalwork and the screens of telecommunications cables in an information technology environment must

More information

Product information 19" 1U HD Patch Panel 48xRJ45/s, Cat. 6A, gray, fully populated

Product information 19 1U HD Patch Panel 48xRJ45/s, Cat. 6A, gray, fully populated Product information 19" 1U HD Patch Panel 48xRJ45/s, Cat. 6A, gray, fully populated R512417 966740615 1 Pcs. 090.6102 Metal patch panel with integrated cable tie shelf. 19" 1U HD patch panel 4 12-port/s

More information

Belden IBDN System 10GX Enabling Technologies

Belden IBDN System 10GX Enabling Technologies Belden IBDN System 10GX Enabling Technologies by Paul Kish Director, Systems and Standards Revision 1 November 2008 Belden Belden IBDN System 10GX Enabling Technologies 1/17 Introduction The IEEE 802.3an

More information

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0553 Identification for Communications Systems

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0553 Identification for Communications Systems 1 General 1.1 Scope of work 1.1.1 The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the completion of

More information

CABLING STANDARDS FOR

CABLING STANDARDS FOR RFB for Wiring in the Outagamie County Courtrooms Attachment B September 1, 2016 CABLING STANDARDS FOR GENERAL The purpose of this document is to provide guidelines for all structured cable installations

More information

DINTEK LAN Cabling Systems

DINTEK LAN Cabling Systems 4 Pair UTP Cable Application: Voice Fast Ethernet(IEEE802.3) VgAnyLAN(IEEE 802.12) Token Ring(IEEE 802.5) TPPMD(ANSI X3T9.5) BaseT Ethernet(IEEE 802.3u) 155/622 Mbps 1.2/ 2.4 Gbps ATM 0BaseT Ethernet 550

More information

Follow The Leader In Shielded Technology

Follow The Leader In Shielded Technology 1970s Vampire Tap 1990s Shielded Modular Jack 190s 4 Position Data Connector Follow The Leader In Shielded Technology The new AMP-TWIST Jack is our latest shielded product evolution. It can be terminated

More information

CATEGORY 6A CABLING SOLUTIONS

CATEGORY 6A CABLING SOLUTIONS 10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Premium Line Category 6A Cabling Solutions

More information

CATEGORY 5e CABLING SOLUTIONS

CATEGORY 5e CABLING SOLUTIONS With the high speed data transmission requirement in LAN, 1998 IEEE ratified standard 802.3z defined protocol 1000BASE-T over Category 5e and higher level Ethernet cabling system. After that, with the

More information

Information Technology Services DESIGN AND INSTALLATION STANDARDS

Information Technology Services DESIGN AND INSTALLATION STANDARDS Requirements and Guidelines for: New Construction, Renovations, Upgrades, and Retrofits. Revised: June 5, 2015 VIU ITS Network Services 2 TABLE OF CONTENTS 0 GENERAL... 5 1 FIBER OPTIC CABLING... 5 1.1

More information

About Nexans 3. About Berk-Tek 4. Hyper Plus 5e Cat 5e UTP 5. HyperPlus 5e Plenum 6. Hyper Plus 5e Riser 10. HyperPlus 5e Patch 14

About Nexans 3. About Berk-Tek 4. Hyper Plus 5e Cat 5e UTP 5. HyperPlus 5e Plenum 6. Hyper Plus 5e Riser 10. HyperPlus 5e Patch 14 Table of contents About Nexans 3 About Berk-Tek 4 Hyper Plus 5e Cat 5e UTP 5 HyperPlus 5e Plenum 6 Hyper Plus 5e Riser 10 HyperPlus 5e Patch 14 HyperPlus 5e OSP 18 22 7/10/07 - http://www.berktek.com Page

More information

About Nexans 3. About Berk-Tek 4. LANmark-1000 Cat 6 UTP 5. LANmark-1000 Category 6 Plenum 6. LANmark-1000 Category 6 Riser 11

About Nexans 3. About Berk-Tek 4. LANmark-1000 Cat 6 UTP 5. LANmark-1000 Category 6 Plenum 6. LANmark-1000 Category 6 Riser 11 Table of contents About Nexans 3 About Berk-Tek 4 LANmark-1000 Cat 6 UTP 5 LANmark-1000 Category 6 Plenum 6 LANmark-1000 Category 6 Riser 11 LANmark-1000 Category 6 Patch 16 21 7/10/07 - http://www.berktek.com

More information

CATEGORY 6A CABLING SOLUTIONS

CATEGORY 6A CABLING SOLUTIONS 10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Need of 10 Gigabit Service Application as

More information

A. The requirements of Section govern the work specified in this section.

A. The requirements of Section govern the work specified in this section. SECTION 27 05 10 - COMMUNITY ANTENNA TELEVISION CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The requirements of Section 27 01 00 govern the work specified in this section. B. Refer to the following

More information

6000 Series Patch Panel Terminating Instructions

6000 Series Patch Panel Terminating Instructions 6000 Series Patch Panel Terminating Instructions INTRODUCTION The 6000 Series patch panels include a unique feature not found on any other patch panel. This feature allows you to angle each of the four

More information

Clarity Advanced Solutions6A

Clarity Advanced Solutions6A Clarity Advanced Solutions6A Clarity 6A connectivity more effectively supports the internal and alien performance requirements of 10 Gigabit Ethernet. Clarity 6A components use Ortronics innovative technique

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Request for Proposal (RFP)

Request for Proposal (RFP) Request for Proposal (RFP) Data Network for OCMS 017 Inquiries and requests regarding this RFP should be directed to: Michael Hale Technology Director Oconee County Schools PO Box 16 5-A School Street

More information

Compact Module. Category 6 FTP Cabling System

Compact Module. Category 6 FTP Cabling System Compact Module Shielded design for improved EMI performance Suitable for Gigabit Ethernet applications and beyond Ultra-slimline design Colour coded for quick and accurate termination Interchangeable with

More information

LCS 2 RJ 45 Cat. 6A HD panels and units

LCS 2 RJ 45 Cat. 6A HD panels and units 87045 LIMOGES Cedex Telephone: (+33) 05 55 06 87 87 - Fax: +33 (0)5 55 06 88 88 Page 0 335 85/86 1. General characteristics....1 2. Presentation...1 3. Positioning...1 4. Technical characteristics...1

More information

Audio/Visual for Lower Level and Board Room A2.0 Projector:

Audio/Visual for Lower Level and Board Room A2.0 Projector: Audio/Visual for Lower Level and Board Room A2.0 Projector: A2.1 Projector must meet or exceed the following specifications: A2.1.1 3LCD imaging engine capable of native WXGA (1024x768) resolution. A2.1.2

More information

Cat.6 4 Pair UTP Cable

Cat.6 4 Pair UTP Cable 4 Pair UTP Cable Application: Voice Fast Ethernet(IEEE802.3u) VgAnyLAN(IEEE 802.12) Token Ring(IEEE 802.5) TPPMD(ANSI X3T9.5) BaseT Ethernet(IEEE 802.5) 155/622 Mbps 1.2/ 2.4 Gbps ATM 0BaseT Ethernet 550

More information

Model Extend HDMI audio and video connections up to 300 feet. Add up to 8 additional receivers with a dedicated network switch

Model Extend HDMI audio and video connections up to 300 feet. Add up to 8 additional receivers with a dedicated network switch HDMI Extender over Single CAT 6 Cable with IR Control Model 103002 Extend HDMI audio and video connections up to 300 feet Utilize existing Cat 6 wiring for an easy installation Add up to 8 additional receivers

More information

SPECIAL SPECIFICATION 6686 BSIF CCTV Central Equipment

SPECIAL SPECIFICATION 6686 BSIF CCTV Central Equipment 2004 Specifications CSJ 0922-00-025, 0921-02-173 & 0921-06-208 SPECIAL SPECIFICATION 6686 BSIF CCTV Central Equipment 1. Description. Furnish and install closed circuit television (CCTV) central equipment

More information

5400 Series Nonmetallic Raceway

5400 Series Nonmetallic Raceway 5400 Series Nonmetallic Raceway Nonmetallic Raceway with Twin Snap Cover System Available Factory Prewired PREWIRED SURGE COMMUNICATIONS FIBER OPTIC CAT5 Wiremold 5400 Series Raceway provides wire and

More information

Volition TM RJ45 K5e Jacks

Volition TM RJ45 K5e Jacks Volition TM RJ45 K5e Jacks Part of our 3M Volition Network Solutions, the new K5e range is our ultimate Category 5e hardware component (ISO/IEC 11801, EN 50173 and ANSI/TIA/EIA-568). The K5e jack is a

More information