1 DESIGNGUIDELINES Testing General 1.1. For acceptance, 100% of the media must be tested and pass all testing requirements. When errors or defective components are found, the source of each error shall be determined, corrected, and the components re-tested at contractor's expense, following the testing procedures described in this document. Cable runs that fail due to distance are not acceptable and will be rerun at the contractor s expense The Infrastructure Contractor shall provide all labor, materials, tools, field-test instruments and equipment required for the complete testing, identification and administration of the work. In addition to the tests detailed in this document, the contractor shall notify GCS of any additional tests that are deemed necessary to guarantee a fully functional system. The contractor shall carry out and record any additional measurement results at no additional charge Guilford County Schools Technology Services or their designated representative will select a random sample of 10% of the installed links. GCS Technology Services representative shall test randomly selected links and the results are to be stored in accordance with this document. The results obtained shall be compared to the results provided by the Infrastructure Contractor. If more than 2% of the sample results differ in terms of the pass/fail determination, the Infrastructure Contractor under supervision of the GCS Technology Services representative shall repeat 100% testing of all links. The expense incurred to re-test will be borne solely by the Infrastructure Contractor. 2. Test Documentation 2.1. Test documentation shall be provided to Guilford County Schools Technology Services on CD-ROM and printed. The CD shall be clearly marked on the cover and on the CD itself with the words Test Results, the project name, and the date of completion (month and year). Testing must be performed within a 30 day window prior to acceptance Test documentation shall be in a Microsoft Excel format worksheet The test equipment by name, manufacturer, model number and last calibration date shall also be provided at the end of the document Testing documentation shall include a printed description of the test method used and the specific settings of the equipment during the test When repairs and re-tests are performed, the problem found and corrective action taken shall be noted, and both the failed and passed test data shall be co-located in the documentation. 3. Testing Procedures 3.1. Fiber Testing shall be carried out in accordance with this document. This includes testing the attenuation and polarity of the installed cable plant with an optical loss test set (OLTS) and the installed condition of the cabling system and its components with an optical time domain reflectometer (OTDR). The condition Page 1 of 5

2 DESIGNGUIDELINES of the fiber endfaces shall also be verified. Testing shall be performed on each cabling link (connector to connector) All tests shall be documented and submitted to Guilford County Schools Technology Services staff including OLTS dual wavelength attenuation measurements for multimode links and OTDR traces and event tables for multimode links All testing procedures and field-test instruments shall comply with applicable requirements of: ANSI Z136.2, ANS For Safe Use Of Optical Fiber Communication Systems Utilizing Laser Diode And LED Sources ANSI/EIA/TIA B, Light Launch Conditions For Long-Length Graded-Index Optical Fiber Spectral Attenuation Measurements ANSI/TIA/EIA A, Measurement of Fiber Point Discontinuities Using an OTDR ANSI/TIA/EIA A, Measurement of Fiber or Cable Length Using an OTDR ANSI/TIA/EIA A, Measurement of Fiber or Cable Attenuation Using an OTDR ANSI/TIA/EIA A, Optical Power Loss Measurements of Installed Multimode Fiber Cable Plant ANSI/TIA/EIA-568-B.1, Commercial Building Telecommunications Cabling Standard, Part 1, General Requirements ANSI/TIA/EIA-568-B.3, Optical Fiber Cabling Components Standard TIA/EIA TSB-140, Additional Guidelines for Field-Testing Length, Loss and Polarity of Optical Fiber Cabling Systems Manufacturer specifications and recommendations Trained technicians who have successfully attended an appropriate training program, which includes testing with an OLTS and an OTDR and have obtained a certificate as proof thereof shall execute the tests. These certificates may have been issued by any of the following organizations or an equivalent organization: Manufacturer of the fiber optic cable and/or the fiber optic connectors Manufacturer of the test equipment used for the field certification Training organizations (e.g., BICSI, ACP [Association of Cabling Professionals ], Cabling Business Institute) Optical loss testing The link attenuation shall be calculated by the following formulas as specified in ANSI/TIA/EIA-568-B Link Attenuation (db) = Cable_Attn (db) + Connector_Attn (db) + Splice_Attn (db) Cable_Attn (db) = Attenuation_Coefficient (db/km) * Length (Km) Connector_Attn (db) = number_of_connector_pairs * connector_loss (db) Maximum allowable connector_loss = 0.75 db Splice_Attn (db) = number_of_splices * splice_loss (db) Maximum allowable splice_loss = 0.3 db Page 2 of 5

3 DESIGNGUIDELINES The values for the Attenuation_Coefficient (db/km) are listed: Wavelength 850nm = 3.5 db/km Wavelength 1000nm = 1.5 db/km OTDR testing Reflective events (connections) shall not exceed 0.75 db Non-reflective events (splices) shall not exceed 0.3 db Magnified endface inspection Fiber connections shall be visually inspected for endface quality Documentation The date and time the test results were saved in the memory of the tester The fiber identification (matches physical label) The length for each optical fiber Test results to include OLTS attenuation link and channel measurements at the appropriate wavelength(s) and the margin (difference between the measured attenuation and the test limit value) Test results to include OTDR link and channel traces and event tables at the appropriate wavelength(s) The length for each optical fiber as calculated by the OTDR The overall Pass/Fail evaluation of the link-under-test for visual inspection The overall Pass/Fail evaluation of the link-under-test for OLTS and OTDR measurements Voice and Paging The backbone copper cabling will be tested end-to-end for compliance with Category 5e performance specifications as stated in the TIA/EIA 568-A. The test equipment used will be in compliance with industry standard Level II test equipment, and the TIA/EIA PN-3287 (TSB-67) test procedures. Tests will include: Wire map, Cable length, Attenuation, Near end crosstalk, ACR, Power Sum NEXT, Power SUM ELFEXT, Propagation Delay and Delay Skew Horizontal Category Every cabling link in the installation shall be tested in accordance with the field test specifications defined in the most recent EIA/TIA 568-B Transmission Performance Specifications for 4-pair, Category 6 Cabling. This document will be referred to as the Cat 6 Standard The installed twisted-pair horizontal links shall be tested from the TC to the outlet against the Permanent Link performance limits specification as defined in the CAT 6 Standard The test equipment (tester) shall comply with the accuracy requirements for the level III field testers as defined in the CAT 6 Standard. The tester including the appropriate interface adapter must meet the manufacturer specified accuracy requirements. The tester shall be within the calibration period recommended by the manufacturer. The tester interface adaptors must be of high quality and the cable shall not show any twisting or kinking. Page 3 of 5

4 DESIGNGUIDELINES Tests will include the following: Wire Map, Cable Length, Attenuation, NEXT, Power Sum NEXT, ACR, Power Sum ACR, ELFEXT, Power Sum ELFEXT, Return Loss, Propagation Delay, and Delay Skew Horizontal Category 5e Every cabling link in the installation shall be tested in accordance with the field test specifications defined in the most recent EIA/TIA 568-B Transmission Performance Specifications for 4-pair, Category5e Cabling. This document will be referred to as the Cat 5e Standard The installed twisted-pair horizontal links shall be tested from the TC to the outlet against the Permanent Link performance limits specification as defined in the CAT 5e Standard Perform testing of Category 5e cables with a level IIe tester meeting EIA/TIA -PN-3287 (TSB for 5e) Tests will include the following: Wire Map, Cable Length, Attenuation, NEXT, Power Sum NEXT, Power Sum ELFEXT, Propagation Delay, and Delay Skew Coaxial All testing will comply with National Cable Television Association Standards (NCTA) and/or Society of Cable Telecommunications Engineers Standards (SCTE) Coax cabling shall be tested for continuity and loss. Test results between each tap and TCO will be tested at 700mhz. Test results must provide the length of each run and the amount of loss with an acceptable loss not greater than 6.96 db loss per 100 feet plus 1 db for connectors. 4. As Built Drawings 4.1. Completed laminated as built drawings shall be posted in the TER and TCs and a paper copy of each shall be given to GCS Technology Services within three (3) weeks of substantial completion As built drawings will include scaled architectural floor plans depicting final device and equipment locations, labeling, and route of backbone, trunk and distribution cables. All CATV tap locations shall be shown. Electronic copy of architectural floor plans will be provided by Contractor/Engineer in format compatible with most recent release of AutoCAD upon request Copies of Project Construction Documents or details there from are NOT acceptable as-built drawings. 5. Inspections 5.1. Pathways All pathways shall be inspected by GCS Technology Services staff prior to the installation of cabling. Inspections may be performed on a space-by-space basis if requested by the Electrical Contractor. Pathways which do not meet specifications will not be approved. Approval of pathways is required prior to cable installation Cabling All cable plant installations shall be inspected by GCS Technology Services staff prior to termination. Inspections may be performed on a space-by-space basis if requested by the Infrastructure Contractor. Cabling that does not meet specifications will not be approved. All cabling issues must be resolved prior to Page 4 of 5

5 DESIGNGUIDELINES termination. (Termination prior to inspection shall not excuse the contractor from any liability in meeting specifications.) 5.3. Terminations All terminations shall be inspected by GCS Technology Services staff prior to acceptance. Inspections may be performed on a space-by-space basis if requested by the Infrastructure Contractor. Terminations that do not meet specifications will not be approved. All termination issues must be resolved prior to acceptance by GCS. 6. Warranty 6.1. All technology work referenced within this specification will be warranted that all materials and equipment furnished under the contract are in good working order, free from defects, and in conformance with system specifications All installations must conform to the manufacturer s official published specifications The warranty shall begin at the systems acceptance date and remain in effect for a period of twenty-five (25) years from that date The Infrastructure Contractor agrees to repair, adjust, and/or replace (as determined by GCS Technology Services to be in its best interest) any defective equipment, materials, or other parts of the system at the Infrastructure Contractor s sole cost Guilford County Schools will incur no costs for service or replacement of parts during the warranty period. All third party warranties shall be passed through from the Infrastructure Contractor to Guilford County Schools The Infrastructure Contractor will warrant and supply evidence that the installation of materials and hardware will be made in strict compliance with all applicable provisions of the National Electric Code, the rules and regulations of the Federal Communications Commission, and state and/or local codes or ordinances that may apply The Infrastructure Contractor will warrant that the system will function as specified in the approved manufacturer s Technical Description Guide Test reports and warranty registration forms are all critical documents for warranty purposes and will be required by GCS Technology Services before completion and acceptance can be granted. At substantial completion provide the following: A copy of the completed manufacturer registration form Copies of all warranty certificates i.e., Panduit, Corning, etc. END OF Page 5 of 5

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards.

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards. 27 08 00 Certification and Commissioning of Communication Systems (Revision date: 7/3/12) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are

More information

The University of Texas at Austin September 30, 2011

The University of Texas at Austin September 30, 2011 SECTION 27 08 20 COPPER TESTING PART 1 - GENERAL 1.1 SUMMARY A. Test measurements shall be taken for all balanced-twisted pair cabling, including horizontal and backbone copper cables and wall-to-rack

More information

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION PART 1 - GENERAL 1.1 SUMMARY SCOPE SECTION 25170 TESTING, IDENTIFICATION AND ADMINISTRATION 1. This section includes the minimum requirements for the testing, certification administration and identification

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 - GENERAL 1.1 SECTION

More information

Telecommunication Infrastructure Project September 20, 2002

Telecommunication Infrastructure Project September 20, 2002 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Category rated UTP systems shall be provided and tested in accordance with the performance level established in Specification

More information

SECTION TESTING OF COPPER CABLES

SECTION TESTING OF COPPER CABLES SECTION 27 08 13 TESTING OF COPPER CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction,

More information

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017 Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM-2017-2 Date: 05/26/2017 Additional specification information for data communication to cameras and between Library

More information

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall obtain authorization from

More information

SSA Fibre-Optic Extender 160 Fibre Installation Guidelines Version 1.2

SSA Fibre-Optic Extender 160 Fibre Installation Guidelines Version 1.2 SSA Fibre-Optic Extender 160 Version 1.2 0.1 Introduction This document provides information on the specification and installation of optical fibre networks to support SSA optical extender products. SSA

More information

RCIT Cable Certification Testing Revised 10/2017

RCIT Cable Certification Testing Revised 10/2017 RCIT Testing Revised 10/2017 General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall

More information

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1. PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

SPECIAL SPECIFICATION 6559 Telecommunication Cable

SPECIAL SPECIFICATION 6559 Telecommunication Cable 2004 Specifications CSJ 0015-09-147, etc. SPECIAL SPECIFICATION 6559 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing, training,

More information

SPECIAL SPECIFICATION 8540 Telecommunication Cable

SPECIAL SPECIFICATION 8540 Telecommunication Cable 2004 Specifications CSJ 0914-00-307 & CSJ 0914-25-003 SPECIAL SPECIFICATION 8540 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing,

More information

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents PART 1 - GENERAL 1.1 SUMMARY SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors. 3. Cabling system identification products. 1.2

More information

What really changes with Category 6

What really changes with Category 6 1 What really changes with Category 6 Category 6, the standard recently completed by TIA/EIA, represents an important accomplishment for the telecommunications industry. Find out which are the actual differences

More information

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School BILOXI PUBLIC SCHOOL DISTRICT Biloxi Junior High School Request for Proposals E-Rate 2014-2015 - Internal Connections Submit Proposals To: Purchasing Department Attn: Traci Barnett 160 St. Peter Street

More information

STRUCTURED CABLE SYSTEM (SCS)

STRUCTURED CABLE SYSTEM (SCS) PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus PART 1: GENERAL REQUIREMENTS A. Contractor Work 1. Provide and install (except as noted in this document), cable,

More information

Request for Proposal (RFP)

Request for Proposal (RFP) Request for Proposal (RFP) Data Network for OCMS 017 Inquiries and requests regarding this RFP should be directed to: Michael Hale Technology Director Oconee County Schools PO Box 16 5-A School Street

More information

Mar11 Rev E

Mar11 Rev E Product Specification 108-1832 11Mar11 Rev E MT-RJ Patch Panel and Outlet Jacks (Standard, XG, SECURE and SECURE XG) 1. SCOPE 1.1. Content This specification, which meets the Optical Fiber Cabling Components

More information

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE Prepared in cooperation and approval from BICSI Building Industry Consulting Services International and

More information

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008 Information & Communications Technology Group Standards June 2008 Appendix F UTP cabling Version 1.1 Appendix F UTP cabling 1. Introduction This Section details the required standards for Unshielded Twisted

More information

IEEE 802.3af Power via MDI Standard Compliant Mid-Span Insertion Solution. Presented by PowerDsine: David Pincu -

IEEE 802.3af Power via MDI Standard Compliant Mid-Span Insertion Solution. Presented by PowerDsine: David Pincu - IEEE 802.3af Power via MDI Standard Compliant Mid-Span Insertion Solution Presented by PowerDsine: David Pincu - davidp@powerdsine.com Objectives! Investigate the Channel /Link options! Identify the requirements

More information

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE)

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) PART 1: GENERAL 1.01 Telecommunications Engineer Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) B. Registered Communications Distribution Designer

More information

Public Works Division Lighting District Fiber Optic Specifications April 2009

Public Works Division Lighting District Fiber Optic Specifications April 2009 Public Works Division Lighting District Fiber Optic Specifications April 2009 7000 Florida Street Punta Gorda, Florida 33950 Tele: 941.575.3600 Fax : 941.637.9265 www.charlottecountyfl.com/publicworks

More information

Delaware County Community College Project # Marple Campus Renovation - Phase % Construction Documents November 23, 2011

Delaware County Community College Project # Marple Campus Renovation - Phase % Construction Documents November 23, 2011 SECTION 271323 - COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 - GENERAL 1.1 DESCRIPTION A. This section provides the specifications for the work related to the optical fiber system in the project.

More information

Fiber Optic Testing. The FOA Reference for Fiber Optics Fiber Optic Testing. Rev. 1/31/17 Page 1 of 12

Fiber Optic Testing. The FOA Reference for Fiber Optics Fiber Optic Testing.   Rev. 1/31/17 Page 1 of 12 Fiber Optic Testing Testing is used to evaluate the performance of fiber optic components, cable plants and systems. As the components like fiber, connectors, splices, LED or laser sources, detectors and

More information

Viavi T-BERD 5800 CPRI Testing Guide with ALU BBU Emulation

Viavi T-BERD 5800 CPRI Testing Guide with ALU BBU Emulation Viavi T-BERD 5800 CPRI Testing Guide with ALU BBU Emulation Scope Version 4 January 2018 Firmware 26.0.0.6c1973b or Later REQUIRED! This document describes Common Public Radio Interface (CPRI) testing

More information

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Copper Cabling Troubleshooting Handbook

Copper Cabling Troubleshooting Handbook NETWORKSUPERVISION Copper Cabling Troubleshooting Handbook NETWORKSUPERVISION Table of Contents Introduction 2 Troubleshooting Basics 3 Link Models 4 The automated DTX Series diagnostics 5 Causes of Cabling

More information

Kennebec Valley Community College CABLE PLANT SPECIFIC A T IONS

Kennebec Valley Community College CABLE PLANT SPECIFIC A T IONS Kennebec Valley Community College CABLE PLANT SPECIFIC A T IONS Table of Contents SECTION A: DESIGN... 3 A.1 OVERVIEW... 3 A.2 INSIDE CABLE PLANT (ICP)... 3 A.2.1 WIRING HORIZONTAL... 3 A. 2.2 WIRING VERTICAL...

More information

SPECIAL SPECIFICATION 6735 Video Optical Transceiver

SPECIAL SPECIFICATION 6735 Video Optical Transceiver 2004 Specifications CSJ 0924-06-244 SPECIAL SPECIFICATION 6735 Video Optical Transceiver 1. Description. This Item governs the furnishing and installation of Video optical transceiver (VOTR) in field location(s)

More information

SECTION FIBER OPTIC STATION CABLES

SECTION FIBER OPTIC STATION CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications shall include all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

The Road to Single Mode: Direction for choosing, installing and testing single mode fiber

The Road to Single Mode: Direction for choosing, installing and testing single mode fiber The Road to Single Mode: Direction for choosing, installing and testing single mode fiber Adrian Young Leviton Network Solutions Jim Davis Fluke Networks Adrian Young, Sr. Applications Engineer Leviton

More information

UNM IT/Telecommunications Guide Specification Labeling 11/07/

UNM IT/Telecommunications Guide Specification Labeling 11/07/ Labeling 1 PART 1: GENERAL 1.01 SCOPE OF WORK A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing

More information

A guide to Woolworths Limited additional requirements. for the testing of twisted pair and fibre installation.

A guide to Woolworths Limited additional requirements. for the testing of twisted pair and fibre installation. 22 nd August 2013 A guide to Woolworths Limited additional requirements for the testing of twisted pair and fibre installation. Background This document has been prepared by VTI Services and approved by

More information

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk Paul Vanderlaan Product Development Engineer Belden Presented at BICSI January 20, 1999 Introduction New Parameters involving

More information

ENGINEERING COMMITTEE Interface Practices Subcommittee SCTE STANDARD SCTE

ENGINEERING COMMITTEE Interface Practices Subcommittee SCTE STANDARD SCTE ENGINEERING MITTEE Interface Practices Subcommittee SCTE STANDARD SCTE 240 2017 SCTE Test Procedures for Testing CWDM Systems in Cable Telecommunications Access Networks NOTICE The Society of Cable Telecommunications

More information

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE AND COMPONENTS. July 19, 2013

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE AND COMPONENTS. July 19, 2013 804.01 Description 804.02 General 804.03 Materials 804.04 Warranties 804.05 Fiber Optic Cable 804.06 Fan-Out Kit 804.07 Drop Cable 804.08 Fiber Optic Patch Cord 804.09 Fiber Termination Panel 804.10 Fusion

More information

LITWARRANTY Rev. 5 W a r r a n t y P r o g r a m S t r u c t u r e d C a b l i n g S y s t e m s

LITWARRANTY Rev. 5 W a r r a n t y P r o g r a m S t r u c t u r e d C a b l i n g S y s t e m s LITWARRANTY Rev. 5 W a r r a n t y P r o g r a m S t r u c t u r e d C a b l i n g S y s t e m s STRUCTUREd CAbLINg SYSTEm WARRANTY PRogRAm As transmission speeds continue to increase, HellermannTyton

More information

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables NEMA Standards Publication WC 63.1-2005 Performance Standard for Twisted Pair Premise Voice and Data Communications Cables Published by: National Electrical Manufacturers Association 1300 North 17th Street,

More information

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables NEMA Standards Publication Performance Standard for Twisted Pair Premise Voice and Data Communications Cables Published by: National Electrical Manufacturers Association 1300 North 17th Street, Suite 1752

More information

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project 1.1.0 GENERAL The purpose of this specification is to establish a requirement for the installation of a voice, video and data cable network. The cable (copper), wire, hardware, equipment racks, jumpers,

More information

Telecommunciations Infrastructure Project September 20, A. Broadband radio frequency active and passive components

Telecommunciations Infrastructure Project September 20, A. Broadband radio frequency active and passive components PART 1 - GENERAL 1.1 SECTION INCLUDES A. Broadband radio frequency active and passive components B. Broadband optical active and passive components C. Coaxial cable and connectors D. Support and termination

More information

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0553 Identification for Communications Systems

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0553 Identification for Communications Systems 1 General 1.1 Scope of work 1.1.1 The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the completion of

More information

Job Aid Server and CSS Separation Avaya S8700 Media Server

Job Aid Server and CSS Separation Avaya S8700 Media Server Overview of server separation Job Aid and CSS Separation Avaya S8700 Media This job aid provides information regarding the separation of S8700 Media s and the Separation of duplicated Center Stage Switch

More information

Field Testing and Troubleshooting of PON LAN Networks per IEC Jim Davis Regional Marketing Engineer Fluke Networks

Field Testing and Troubleshooting of PON LAN Networks per IEC Jim Davis Regional Marketing Engineer Fluke Networks Field Testing and Troubleshooting of PON LAN Networks per IEC 61280-4 Jim Davis Regional Marketing Engineer Fluke Networks Agenda Inspection and Cleaning APC vs UPC PON basics Wavelengths Architecture

More information

SPECIAL SPECIFICATION 1118 Dual OC-3 ATM MPEG-2 Encoder

SPECIAL SPECIFICATION 1118 Dual OC-3 ATM MPEG-2 Encoder 1993 Specifications CSJ 0521-04-190 SPECIAL SPECIFICATION 1118 Dual OC-3 ATM MPEG-2 Encoder 1. Description. Furnish, install, and make fully operational an Asynchronous Transfer Mode (ATM) Video Encoder

More information

Part 1: How to Avoid Confusion When Testing Insertion Loss According to TIA/EIA-568 B.1 and B.3

Part 1: How to Avoid Confusion When Testing Insertion Loss According to TIA/EIA-568 B.1 and B.3 Fiber Optic Services And Products EYE ON FIBER Volume 1, Issue 2 August 2002 Part 1: How to Avoid Confusion When Testing Insertion Loss According to TIA/EIA-568 B.1 and B.3 I have been reviewing a Draft

More information

Volition TM RJ45 K5e Jacks

Volition TM RJ45 K5e Jacks Volition TM RJ45 K5e Jacks Part of our 3M Volition Network Solutions, the new K5e range is our ultimate Category 5e hardware component (ISO/IEC 11801, EN 50173 and ANSI/TIA/EIA-568). The K5e jack is a

More information

SPECIAL SPECIFICATION 6191 Fiber Optic Cable

SPECIAL SPECIFICATION 6191 Fiber Optic Cable 2004 Specifications CSJ 0014-02-014, etc SPECIAL SPECIFICATION 6191 Fiber Optic Cable 1. Description. Furnish, install, splice, field terminate, and test the fiber optic cables. 2. Materials. A. General

More information

SPECIAL SPECIFICATION :1 Video (De) Mux with Data Channel

SPECIAL SPECIFICATION :1 Video (De) Mux with Data Channel 1993 Specifications CSJ 0924-06-223 SPECIAL SPECIFICATION 1160 8:1 Video (De) Mux with Data Channel 1. Description. This Item shall govern for furnishing and installing an 8 channel digital multiplexed

More information

Request for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS

Request for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS VOFP Cabling RFP 1 Request for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS For The Village of Franklin Park 2014 VOFP Cabling RFP 2 TABLE OF CONTENTS I. PROJECT DESCRIPTION

More information

Special Specification 6242 Special Fiber Optic Cable

Special Specification 6242 Special Fiber Optic Cable Special Specification 6242 Special Fiber Optic Cable 1. DESCRIPTION 2. MATERIALS The contractor to install, splice, field terminate, test and document all fiber systems. A. General Requirements. Provide

More information

Uniprise Solution Brochure. North America/CALA.

Uniprise Solution Brochure. North America/CALA. Uniprise Solution Brochure North America/CALA Exceptional Value. Headroom to Standards. Simplicity by Design. Uniprise delivers quality, easy-to-use solutions that work from day one to support customer

More information

Sidelighter TM Optical distance to fault measurement module

Sidelighter TM Optical distance to fault measurement module Sidelighter TM Optical distance to fault measurement module Available only at: Sidelighter TM Introducing the latest in optical fiber measurements and versatility Artisan Laboratories Corporation s hand

More information

Michigan State University Construction Standards EXTERIOR FIBER OPTIC CABLE SYSTEM PAGE

Michigan State University Construction Standards EXTERIOR FIBER OPTIC CABLE SYSTEM PAGE PAGE 271800-1 SECTION 271800 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Instalaciones de fibra optica en entornos de centro de datos y campus para suportar 40, 100G y mas

Instalaciones de fibra optica en entornos de centro de datos y campus para suportar 40, 100G y mas Instalaciones de fibra optica en entornos de centro de datos y campus para suportar 40, 100G y mas Jim Davis Regional Marketing Engineer Fluke Networks Agenda Inspection and Cleaning Loss Budgets TIA (Cabling)

More information

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED.

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED. Beaverton School District Capital Program Purchasing 16550 SW Merlo Road, Beaverton, OR 97006 Phone: 503-591-4539 SOLICITATION ADDENDUM NO. 1 ITB 15-0012 THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION

More information

A. As defined in Section Telecommunications General Requirements

A. As defined in Section Telecommunications General Requirements PART 1 - GENERAL 1.1 SECTION INCLUDES A. Related Sections B. Applicable Publications C. Conditions D. Scope E. Compliance, Tests, and Inspections F. Delivery and Storage of Materials G. Coordination of

More information

STANDARD FOR MULTI-DWELLING UNIT (MDU) OPTICAL FIBER CABLE. Publication S First Edition - June 2012

STANDARD FOR MULTI-DWELLING UNIT (MDU) OPTICAL FIBER CABLE. Publication S First Edition - June 2012 STANDARD FOR MULTI-DWELLING UNIT (MDU) OPTICAL FIBER CABLE Publication S-115-730 First Edition - June 2012 Published By Insulated Cable Engineers Association, Inc. Post Office Box 1568 Carrollton, Ga 30112,

More information

About Nexans 3. About Berk-Tek 4. LANmark-1000 Cat 6 UTP 5. LANmark-1000 Category 6 Plenum 6. LANmark-1000 Category 6 Riser 11

About Nexans 3. About Berk-Tek 4. LANmark-1000 Cat 6 UTP 5. LANmark-1000 Category 6 Plenum 6. LANmark-1000 Category 6 Riser 11 Table of contents About Nexans 3 About Berk-Tek 4 LANmark-1000 Cat 6 UTP 5 LANmark-1000 Category 6 Plenum 6 LANmark-1000 Category 6 Riser 11 LANmark-1000 Category 6 Patch 16 21 7/10/07 - http://www.berktek.com

More information

TC3301. User's Manual

TC3301. User's Manual 1000Base-T Ethernet Fiber Optic Converter User's Manual 1. Features p 1000Mbps for twisted pair, and 1000Mbps for fiber p Local Dry Contact Alarm Relay p Multimode (850nm) and Single Mode (1310nm/1550nm)

More information

About Nexans 3. About Berk-Tek 4. Hyper Plus 5e Cat 5e UTP 5. HyperPlus 5e Plenum 6. Hyper Plus 5e Riser 10. HyperPlus 5e Patch 14

About Nexans 3. About Berk-Tek 4. Hyper Plus 5e Cat 5e UTP 5. HyperPlus 5e Plenum 6. Hyper Plus 5e Riser 10. HyperPlus 5e Patch 14 Table of contents About Nexans 3 About Berk-Tek 4 Hyper Plus 5e Cat 5e UTP 5 HyperPlus 5e Plenum 6 Hyper Plus 5e Riser 10 HyperPlus 5e Patch 14 HyperPlus 5e OSP 18 22 7/10/07 - http://www.berktek.com Page

More information

Connect with the industry s best CAT6 and CAT5e channel solutions!

Connect with the industry s best CAT6 and CAT5e channel solutions! Connect with the industry s best CAT6 and CAT5e channel solutions! Our CAT6 and CAT5e channel solutions far exceed the TIA/EIA specifications performance standards! To ensure consistent and continuing

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Challenges for testing 10GBASE-T

Challenges for testing 10GBASE-T Challenges for testing 10GBASE-T Adrian Young Customer Support Manager adrian.young@flukenetworks.com Check list Category 6A component compliant connector Category 6A compliant cable Perfect terminations

More information

Datasheet: CertiFiber Pro Optical Loss Test Set

Datasheet: CertiFiber Pro Optical Loss Test Set Datasheet: CertiFiber Pro Optical Loss Test Set The CertiFiber Pro is the Tier 1 (basic) fiber certification solution and part of the Versiv Cabling Certification product family. The Versiv line also includes

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors including patch panels. 3. Cabling identification

More information

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE AND COMPONENTS. January 20, 2017

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE AND COMPONENTS. January 20, 2017 804.01 Description 804.02 General 804.03 Materials 804.04 Warranties 804.05 Fiber Optic Cable 804.06 Fan-Out Kit 804.07 Drop Cable 804.08 Fiber Optic Patch Cord 804.09 Fiber Termination Panel 804.10 Fusion

More information

500 Business Center Drive Pittsburgh, PA USA CAGE 1BGJ7. June 2015 Part Numbers FIBER DRIVER

500 Business Center Drive Pittsburgh, PA USA CAGE 1BGJ7. June 2015 Part Numbers FIBER DRIVER Market Central www.secureswitch.com 500 Business Center Drive Pittsburgh, PA 15205 USA 412.494.2800 CAGE 1BGJ7 June 2015 Part Numbers Fiber Driver ST Female (Lead Free) 61-00091 Fiber Driver - ST - Female

More information

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project 1.1.0 GENERAL MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project The purpose of this specification is to establish a requirement for the installation of

More information

SPECIAL SPECIFICATION 1987 Single Mode Fiber Optic Video Transmission Equipment

SPECIAL SPECIFICATION 1987 Single Mode Fiber Optic Video Transmission Equipment 1993 Specifications CSJ 0027-12-086, etc. SPECIAL SPECIFICATION 1987 Single Mode Fiber Optic Video Transmission Equipment 1. Description. This Item shall govern for the furnishing and installation of color

More information

How to accelerate your cabling system approvals

How to accelerate your cabling system approvals How to accelerate your cabling system approvals Adrian Young Fluke Networks November, 2013 Singapore Objectives for this session Resolve field failures on the spot Look at real world examples of fault

More information

CC-Link IE Controller Network Compatible. CC-Link IE Controller Network Recommended Network Wiring Parts Test Specifications

CC-Link IE Controller Network Compatible. CC-Link IE Controller Network Recommended Network Wiring Parts Test Specifications Model Title CC-Link IE Controller Network Compatible CC-Link IE Controller Network Recommended Network Wiring Parts Specifications Management number: BAP-C0401-028-A CC-Link Partner Association (1/31)

More information

U SER S G UIDE. TS2002A Fiber Optic Test Kit

U SER S G UIDE. TS2002A Fiber Optic Test Kit U SER S G UIDE TS2002A Fiber Optic Test Kit TS2002A Test System Black Box TS2002A test system performs optical power loss measurement for both multimode and single-mode LAN/WAN fiber optic installations.

More information

Project No. # Page 1

Project No. # Page 1 PART 1 - GENERAL This section of the has references, products, procedures, processes, and work descriptions/summaries that are common to many Washington State University Pullman (WSUP) campus telecommunications

More information

3M 8900 Single-mode SC Crimplok Connector

3M 8900 Single-mode SC Crimplok Connector 3M 8900 Single-mode SC Crimplok Connector Technical Report June 1999 80-6110-1441-8 1 1.0 Product Description & Requirements The 3M SC Single-mode Crimplok Connector is designed to provide the customer

More information

HONEYWELL VIDEO SYSTEMS HIGH-RESOLUTION COLOR DOME CAMERA

HONEYWELL VIDEO SYSTEMS HIGH-RESOLUTION COLOR DOME CAMERA Section 00000 SECURITY ACCESS AND SURVEILLANCE HONEYWELL VIDEO SYSTEMS HIGH-RESOLUTION COLOR DOME CAMERA PART 1 GENERAL 1.01 SUMMARY The intent of this document is to specify the minimum criteria for the

More information

Data Network Wiring Standard. Part 1: General Section Includes Publications and Standards

Data Network Wiring Standard. Part 1: General Section Includes Publications and Standards Part 1: General 1.01 Section Includes A. Fiber Optic Cable B. Fiber Optic Distribution Cabinets C. Interbuilding Fiber Optic Cabling/Patch Cords D. Fiber Optic Connectors E. Interbuilding Distribution

More information

WJHW, Inc. 6 April 2016 Texas Tech University Issue for CD Set Sports Performance Complex Lubbock, Texas

WJHW, Inc. 6 April 2016 Texas Tech University Issue for CD Set Sports Performance Complex Lubbock, Texas SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide materials, labor, and methods for telecommunications grounding and bonding system in accordance with

More information

1995 Metric CSJ SPECIAL SPECIFICATION ITEM 6031 SINGLE MODE FIBER OPTIC VIDEO TRANSMISSION EQUIPMENT

1995 Metric CSJ SPECIAL SPECIFICATION ITEM 6031 SINGLE MODE FIBER OPTIC VIDEO TRANSMISSION EQUIPMENT 1995 Metric CSJ 0508-01-258 SPECIAL SPECIFICATION ITEM 6031 SINGLE MODE FIBER OPTIC VIDEO TRANSMISSION EQUIPMENT 1.0 Description This Item shall govern for the furnishing and installation of color Single

More information

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017 SECTION 27 15 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Selection of a cable depends on functions such as The material Singlemode or multimode Step or graded index Wave length of the transmitter

Selection of a cable depends on functions such as The material Singlemode or multimode Step or graded index Wave length of the transmitter Fibre Optic Communications The greatest advantage of fibre cable is that it is completely insensitive to electrical and magnetic disturbances. It is therefore ideal for harsh industrial environments. It

More information

IT/Telecommunications Technical and Wiring Standards. Phillips Exeter Academy

IT/Telecommunications Technical and Wiring Standards. Phillips Exeter Academy IT/Telecommunications Technical and Wiring Standards FOR Phillips Exeter Academy Exeter, NH No deviations will be permitted from these specifications without the express written consent of Phillips Exeter

More information

ENGINEERING COMMITTEE

ENGINEERING COMMITTEE ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 04 2014 Test Method for F Connector Return Loss NOTICE The Society of Cable Telecommunications Engineers (SCTE)

More information

PATCH CORDS, PLUGS & CABLES

PATCH CORDS, PLUGS & CABLES PATCH CORDS, PLUGS & CABLES 3.1 SECTION CONTENTS Modular Cords...3.2 Cable Assemblies...3.3 Plugs & Connectors...3.4 Bundled Cable...3.5 Category 5e & 6 UTP Cable...3.6 Coax Cable...3.7 Fiber Optic Cable...3.8

More information

MTS/T-BERD Platforms WDMPMD Module

MTS/T-BERD Platforms WDMPMD Module ACTERNA TEST & MEASUREMENT SOLUTIONS MTS/T-BERD Platforms WDMPMD Module Key Features A unique solution combining OSA, PMD, and SA test functions in one plug-in module The most compact PMD/WDM/SA test solution

More information

Project No. # Page 1

Project No. # Page 1 PART 1 - GENERAL This section of the has references, products, procedures, processes, and work descriptions/summaries that are common to many Washington State University Pullman (WSUP) campus telecommunications

More information

SECTION 686 VIDEO DECODER DESCRIPTION

SECTION 686 VIDEO DECODER DESCRIPTION 686 SECTION 686 VIDEO DECODER DESCRIPTION 686.01.01 GENERAL A. This specification describes the functional, performance, environmental, submittal, documentation, and warranty requirements, as well as the

More information

TC Mbps - 622Mbps FIBER OPTIC MODE CONVERTER/REPEATER (Rev A0.1) User's Manual

TC Mbps - 622Mbps FIBER OPTIC MODE CONVERTER/REPEATER (Rev A0.1) User's Manual TC3004 50Mbps - 622Mbps FIBER OPTIC MODE CONVERTER/REPEATER (Rev A0.1) MODEL: S/N: DATE: Notice! Although every effort has been made to insure that this manual is current and accurate as of date of publication,

More information

HDTV SIGNAL AMPLIFIERS. 34 series USER GUIDE GUÍA PARA EL USUARIO MODE D EMPLOI CM-3410 CM-3412 CM-3414 CM-3418

HDTV SIGNAL AMPLIFIERS. 34 series USER GUIDE GUÍA PARA EL USUARIO MODE D EMPLOI CM-3410 CM-3412 CM-3414 CM-3418 HDTV SIGNAL AMPLIFIERS 34 series USER GUIDE GUÍA PARA EL USUARIO MODE D EMPLOI CM-3410 CM-3412 CM-3414 CM-3418 Table of Contents Product Overview... 3 Package Contents and Accessories... 3 Instructions...4

More information

Aerial Cable Installation Best Practices

Aerial Cable Installation Best Practices Aerial Cable Installation Best Practices Panduit Corp. 2007 BEST PRACTICES Table of Contents 1.0 General... 3 2.0 Introduction... 3 3.0 Precautions... 4 4.0 Pre-survey... 5 5.0 Materials and Equipment...

More information

Technical Specifications Florida Gulf Coast University

Technical Specifications Florida Gulf Coast University Technical Specifications Florida Gulf Coast University 9/19/2018 Page 1 of 21 Approved Vendors (alphabetical order) Aztek (CIP) Certified Installer Plus Mr. Scott Coyne 4730 Enterprise Avenue Suite #308

More information

T-BERD /MTS-6000, -6000A and Platforms OFI Multifunction Loss Test Module

T-BERD /MTS-6000, -6000A and Platforms OFI Multifunction Loss Test Module COMMUNICATIONS TEST & MEASUREMENT SOLUTIONS T-BERD /MTS-6000, -6000A and -8000 Platforms OFI Multifunction Loss Test Module Key Features One-button automated testing, including continuity check, bidirectional

More information

TC3005(LED/ELED/LASER) User's Manual

TC3005(LED/ELED/LASER) User's Manual 1. Description The gives users the ability to convert signals to format for data transmission (and vice-versa). These conversions can benefit users by extending transmission distances and/or enabling dissimilar

More information

We will look first at the cable, and then the transceivers (which act as both transmitter and receiver on each end of the fiber cable).

We will look first at the cable, and then the transceivers (which act as both transmitter and receiver on each end of the fiber cable). Nuclear Sensors & Process Instrumentation Fiber Cable Basics Fiber-optic communication is a method of transmitting information from one place to another by sending light through an optical fiber. The light

More information

VersiVision. FVTMHA0xA / FVRMHA0xA 16-CHANNEL DIGITALLY ENCODED VIDEO 1-CHANNEL BI-DIRECTIONAL DATA MULTIPLEXER USER S MANUAL.

VersiVision. FVTMHA0xA / FVRMHA0xA 16-CHANNEL DIGITALLY ENCODED VIDEO 1-CHANNEL BI-DIRECTIONAL DATA MULTIPLEXER USER S MANUAL. VersiVision FVTMHA0xA / FVRMHA0xA 16-CHANNEL DIGITALLY ENCODED VIDEO 1-CHANNEL BI-DIRECTIONAL DATA MULTIPLEXER USER S MANUAL Revision B April 2013 VERSITRON, Inc. 83 Albe Drive / Suite C Newark, DE 19702

More information

SECTION 683 VIDEO OPTICAL TRANSCEIVER WITH BI-DIRECTIONAL DATA CHANNEL DESCRIPTION

SECTION 683 VIDEO OPTICAL TRANSCEIVER WITH BI-DIRECTIONAL DATA CHANNEL DESCRIPTION 683 SECTION 683 VIDEO OPTICAL TRANSCEIVER WITH BI-DIRECTIONAL DATA CHANNEL DESCRIPTION 683.01.01 GENERAL A. The Contractor shall furnish the designated quantity of Video Optical Transceiver (VOTR) pairs

More information

CATEGORY 6A CABLING SOLUTIONS

CATEGORY 6A CABLING SOLUTIONS 10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Premium Line Category 6A Cabling Solutions

More information