Rogers Communication Center Cable Documentation and Identification Policy

Size: px
Start display at page:

Download "Rogers Communication Center Cable Documentation and Identification Policy"

Transcription

1 Rogers Communication Center Cable Documentation and Identification Policy Written by: David Tom Revision Date: August 5, 2005 Version Number: 0.2 I. Introduction About This Document: This document provides guidance for the labeling and documentation of Audio/Video/Data cabling used within the Rogers Communication Center. Scope: This policy encompasses all copper and optical cable and wiring that are installed by the Computer System Technology Group, Research Technology Support Group and the Media Systems Technology Group. Cabling owned by Computer and Communication Services is excluded. Definition: Abbreviation: RCC Rogers Communication Centre References: ANSI/UL 969 Marking and Labeling Systems

2 II. Products i. Labels A. Shall meet the legibility, defacement, exposure and adhesion requirements of UL 969. B. Shall be preprinted or computer printed type. Hand written labels are not acceptable. The label font must be legible such as Times New Roman, Arial, or Courier, and a minimum 12-point font size. C. Printing must be protected from the environment. D. Provide vinyl substrate with a white printing area and black print. If cable jacket is white, provide cable label with printing area that is any other color than white, preferably orange or yellow so that the labels are easily distinguishable. E. Shall be flexible vinyl or other substrates to apply easy and flex as cables are bent. F. Shall use aggressive adhesives that stay attached even to the most difficult to adhere to jacketing. III. Execution i. General Guideline All cables must be marked at each end of a conduit, at each end of a passage through a wall or floor, in each hand or manhole, at each corner, and at least every 100 feet of run The label must be attached within 1 ft of where the cable is to be mark. In cases of multi-conductor cables (i.e. bundled cables such as Belden 7710A), both the outer jacket and the individual conductor jackets must be labeled.

3 ii. Label Numbering Cable labels will have the following identification numbering format mark on the label: AAAA BBBB CDDDD AAAA and BBBB are the room designation number where each end of the cable is terminated. If the cable does not terminate in a room, the closest architecture code intersect from the RCC building plan will be used. C is the identification of the type of signal that the cable carries. DDDD is a numerical cable number that is unique for a given AAAA-BBBB-C. Assignment of the room number to AAAA and BBBB will be in sequential ascending order, that is, AAAA will be assigned the lower alphanumeric room number and BBBB will be assigned the higher alphanumeric room number. For example: two co-axial cable designated to transport HD-SDI from Studio A Control Room (RCC232A) to Central Rack/Dub area (RCC230A) would be mark as: 230A-232A-D0001 and 230A-232A-D0002 For cables where each end terminates in the same room (i.e. where AAAA and BBBB are identical), it is permissible for the labels to be shorten to CDDDD C is the identification of the type of signal that the cable carries. DDDD is a numerical cable number that is unique for a given AAAA-BBBB-C. For example: two co-axial cable designated to transport HD-SDI terminate at both end in Studio A Control Room (RCC232A), the label would be mark as: 230A-230A--D0001 and 230A-230A--D0002 or shorten to D0001 and D0002. Multi-conductor cables will have a cable number assigned to each conductor and to the multi-conductor jacket. iii. Additional Guidelines for Video Cables Co-axial cable designated to be able to carry video transmission should not have an end-to-end length of greater than 85 m (278 feet). If a cable length must exceed 85 m, an additional cable label listing the end-to-end length must be place along side each cable numbering label.

4 IV. Documentation i. Wiring List A listing of all cables in Project organized in a systematic fashion matching actual cables. Each cable listing shall contain: a) Cable Number matching that found on the cable labels. b) Drawing Name where cable is reference. c) Cable manufacturer, type, and color. d) Connector Type e) Pin-out detail number. f) Cable Function g) Termination point (including rack location, rack, slot and point) h) Cable length (and a note if it is timed or a critical length) ii. Record Keeping V. Reference i. Signal Type Identification Code D Digital Video E Ethernet (Giga, Fast, 10Gig) V Analog Video R CATV / RF Broadband A Audio F Fibre-channel C Control (i.e. RS232, RS422, GPI) X Reference / House Black G Graphics (VGA/DVI/HDMI) M Triax / Multi conductor camera

5 ii. Rogers Communications Centre Floor Map

6 Figure 1- RCC First Floor

7 Figure 2 - RCC 2nd Floor

UNM IT/Telecommunications Guide Specification Labeling 11/07/

UNM IT/Telecommunications Guide Specification Labeling 11/07/ Labeling 1 PART 1: GENERAL 1.01 SCOPE OF WORK A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing

More information

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION PART 1 - GENERAL 1.1 SUMMARY SCOPE SECTION 25170 TESTING, IDENTIFICATION AND ADMINISTRATION 1. This section includes the minimum requirements for the testing, certification administration and identification

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors including patch panels. 3. Cabling identification

More information

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017 Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM-2017-2 Date: 05/26/2017 Additional specification information for data communication to cameras and between Library

More information

STRUCTURED CABLE SYSTEM (SCS)

STRUCTURED CABLE SYSTEM (SCS) PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

IndyGo Facility Upgrades Project 35671EE

IndyGo Facility Upgrades Project 35671EE SECTION 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Identification for raceways. 2. Identification of power and control cables. 3. Identification for

More information

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents PART 1 - GENERAL 1.1 SUMMARY SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors. 3. Cabling system identification products. 1.2

More information

TELSTRA VELOCITY HOME WIRING GUIDE BRING YOUR NEW HOME TO LIFE

TELSTRA VELOCITY HOME WIRING GUIDE BRING YOUR NEW HOME TO LIFE TELSTRA VELOCITY HOME WIRING GUIDE BRING YOUR NEW HOME TO LIFE SO WHAT IS VELOCITY HOME WIRING? Telstra Velocity home wiring lets you get your entertainment and communications from a single fibre-optic

More information

Triax TechInfo. Installing and pulling Fibre Optic cables

Triax TechInfo. Installing and pulling Fibre Optic cables Installation methods for both wire cables and Fibre Optical cables are similar. Fibre cable can be pulled with much greater force than copper wire if you pull it correctly. Just remember these rules: 1)

More information

Telstra Velocity Home Wiring An essential guide for new home owners

Telstra Velocity Home Wiring An essential guide for new home owners Telstra Velocity Home Wiring An essential guide for new home owners Recommended Telstra Velocity Why is home wiring important to your home? When you use Telstra Velocity you won t need any antennas, modems

More information

SECTION 7 -- CROSS-CONNECT SYSTEMS

SECTION 7 -- CROSS-CONNECT SYSTEMS DETAIL ENGINEERING REQUIREMENTS AT&T March, 2016 Section 7, ATT-TP-76400 Revised NA SECTION 7 -- CROSS-CONNECT SYSTEMS CONTENTS PAGE 1. GENERAL... 7-2 1.1. Introduction... 7-2 1.2. Cable Holes... 7-2 1.3.

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Laying of cables and lines in electrical installations and data networks

Laying of cables and lines in electrical installations and data networks Technical bulletin Laying of cables and lines in electrical installations and data networks Date: 08/2006 This technical bulletin provides you with information on specific technical subjects. It is based

More information

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1. PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

SECTION FIBER OPTIC STATION CABLES

SECTION FIBER OPTIC STATION CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications shall include all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

Cables for robot applications

Cables for robot applications Cables for robot applications 67 Primary cables Robot primary cable Cable design Internal conductor Special conductor Strand class VI (super-fine wire) Highly flexible Core insulation TPM or PUR Core identification

More information

Bravo AV s Structured or Whole-House Wiring Approach

Bravo AV s Structured or Whole-House Wiring Approach Custom Audio & Video Systems: Design and Installation Bravo AV s Structured or Whole-House Wiring Approach THE QUALITY OF THE CABLE YOU USE IS CRITICALLY IMPORT TO THE PERFORMANCE OF YOUR SYSTEM Introduction

More information

3WS(Cape Town/Secretariat)1

3WS(Cape Town/Secretariat)1 For IEC use only 3WS(Cape Town/Secretariat)1 2005-10-04 INTERNATIONAL ELECTROTECHNICAL COMMISSION Technical Committee No. 3: Information structures, documentation and graphical symbols Occurrence-related

More information

NC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM

NC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM NC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM Content 1. General 5 2. The products of NC-1000 system 6 3. Mounting of the frame 8 4. Earthing of the frame 8 NC-1000 FIBRE OPTIC

More information

COVER

COVER COVER 800-526-0242 www.comprehensiveco.com sales@comprehensiveco.com Pro AV/IT Cat6 Network Cables Pro AV/IT Heavy Duty Cat6 Network Cables Comprehensive s Pro AV/IT Cat6 Heavy Duty Snagless Patch Cables

More information

WHAT IS THE BEST COAXIAL CABLE PDF

WHAT IS THE BEST COAXIAL CABLE PDF 01 May, 2018 WHAT IS THE BEST COAXIAL CABLE PDF Document Filetype: PDF 107.64 KB 0 WHAT IS THE BEST COAXIAL CABLE PDF Amazon.com: Black Quad Shield RG-6 Coax Cable for (CATV, Satellite TV, or Broadband

More information

Draft for Public Comment

Draft for Public Comment Draft for Public Comment Form 36 Version 6.1 DPC: 03/302646 DC Head Office 389 Chiswick High Road London W4 4AL Telephone: +44(0)20 8996 9000 Fax: +44(0)20 8996 7001 Date: 27 March 2003 Origin: National

More information

The BRU-SF10 supports single mode optical fiber cable ensuring 2,000m transmission at maximum.

The BRU-SF10 supports single mode optical fiber cable ensuring 2,000m transmission at maximum. As of May 8, 2012 BRU-SF10 1. Single mode fiber cable supported The BRU-SF10 supports single mode optical fiber cable ensuring 2,000m transmission at maximum. 2. Status display on the front panel The following

More information

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0553 Identification for Communications Systems

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0553 Identification for Communications Systems 1 General 1.1 Scope of work 1.1.1 The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the completion of

More information

VGA Extender LR EXT-VGA-141LR. User s Manual

VGA Extender LR EXT-VGA-141LR. User s Manual VGA Extender LR EXT-VGA-141LR User s Manual ASKING FOR ASSISTANCE Technical Support: Telephone (818) 772-9100 (800) 545-6900 Fax (818) 772-9120 Technical Support Hours: 8:00 AM to 5:00 PM Monday thru

More information

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk Paul Vanderlaan Product Development Engineer Belden Presented at BICSI January 20, 1999 Introduction New Parameters involving

More information

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School BILOXI PUBLIC SCHOOL DISTRICT Biloxi Junior High School Request for Proposals E-Rate 2014-2015 - Internal Connections Submit Proposals To: Purchasing Department Attn: Traci Barnett 160 St. Peter Street

More information

SECTION 5900 TRAFFIC SIGNALS CITY OF LEE S SUMMIT, MISSOURI DESIGN CRITERIA

SECTION 5900 TRAFFIC SIGNALS CITY OF LEE S SUMMIT, MISSOURI DESIGN CRITERIA SECTION 5900 TRAFFIC SIGNALS CITY OF LEE S SUMMIT, MISSOURI DESIGN CRITERIA TABLE OF CONTENTS Section Title Page 5901 GENERAL... 2 5902 DESIGN CRITERIA... 2 5902.1 Codes and Standards... 2 5902.2 Signal

More information

Continuous Flex Data Cable

Continuous Flex Data Cable Order from MARYLAND METRICS P.O. Box 61 Owings Mills, MD 111 USA email: sales@mdmetric.com web: http://mdmetric.com Continuous Flex Data Cable 1 phones: ()8- (800)68-0 faxes: ()8-1 (800)8-99 Order from

More information

HDBT Installation Guide

HDBT Installation Guide KRAMER ELECTRONICS LTD. HDBT Installation Guide MODELS: Kramer HDBT Cable Recommendations for Usage and Termination Guidelines For the latest information on our products and a list of Kramer distributors,

More information

AMERICAN NATIONAL STANDARD

AMERICAN NATIONAL STANDARD Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 129 2017 Drop Passives: Bonding Blocks (Without Surge Protection) NOTICE The Society of Cable Telecommunications Engineers (SCTE) Standards

More information

10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System

10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System 10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System Next-Generation Category 6A UTP Cabling System Drivers for 10 GbE Aggregation of Gigabit Links Server Consolidation and

More information

Polymer optical fibre as duplex fibre cable version with PCV or PUR sheath for PROFINET applications type B or C

Polymer optical fibre as duplex fibre cable version with PCV or PUR sheath for PROFINET applications type B or C Polymer optical fibre as duplex fibre cable version with PCV or PUR sheath for PROFINET applications type B or C PROFINET compliant otical cables accordingly Type B and Type C with 2K200/230 PCF twin cable,

More information

Truck router (3Gbps/HD/SD/ASI)

Truck router (3Gbps/HD/SD/ASI) NVISION 8288 Truck router (3Gbps/HD/SD/ASI) The ultra-compact NVISION 8288 truck video routers are the world s smallest large routers with full broadcast quality, resilience and advanced control systems.

More information

GenSPEED Category 5e Cables 3

GenSPEED Category 5e Cables 3 Datacom GenSPEED Category 5e Cables 3 GenSPEED Category 5e cables are available in a wide variety of performance levels and constructions. With many options to pick from, you can select the GenSPEED Category

More information

CHAPTER 14 WIRING SIGNALS AND LIGHTING FIELD GUIDE Wiring Requirements WIRING

CHAPTER 14 WIRING SIGNALS AND LIGHTING FIELD GUIDE Wiring Requirements WIRING WIRING CHAPTER 14 WIRING The installation of all wiring, including electrical cables and conductors, must conform to the National Electrical Code (NEC). The Code represents the minimum required standard.

More information

Tab 10 - The NESC and Underground Applications. Restricted Siemens Industry, Inc All rights reserved.

Tab 10 - The NESC and Underground Applications. Restricted Siemens Industry, Inc All rights reserved. Tab 10 - The NESC and Underground Applications Restricted Siemens Industry, Inc. 2017 All rights reserved. siemens.com/poweracademy The National Electric Safety Code (NESC) The NESC provides guidelines

More information

ULTIMATE SNAP-N-SEAL

ULTIMATE SNAP-N-SEAL ULTIMATE SNAP-N-SEAL F Series Compression Connectors Thomas & Betts introduces the Ultimate Snap-N-Seal Compression Connector, the newest addition to the Snap-N-Seal system. Look for the classic design

More information

VGA Extender LR EXT-VGA-141LR. User s Manual

VGA Extender LR EXT-VGA-141LR. User s Manual VGA Extender LR EXT-VGA-141LR User s Manual Congratulations on your purchase of the VGA Extender LR. Your complete satisfaction is very important to us. Gefen Gefen delivers innovative, progressive computer

More information

Professionally Install Products Right the First Time. TOOL-CRIMP Radial Linear compression tool for BNC, F & RCA connectors

Professionally Install Products Right the First Time. TOOL-CRIMP Radial Linear compression tool for BNC, F & RCA connectors Professionally Install Products Right the First Time Profit with PROFIT Tributaries PROFIT System ProFit System employs radial compression technology which preserves the coaxial cables critical 75 ohm

More information

Traditionally video signals have been transmitted along cables in the form of lower energy electrical impulses. As new technologies emerge we are

Traditionally video signals have been transmitted along cables in the form of lower energy electrical impulses. As new technologies emerge we are 2 Traditionally video signals have been transmitted along cables in the form of lower energy electrical impulses. As new technologies emerge we are seeing the development of new connection methods within

More information

Double Bubble Compression Connectors

Double Bubble Compression Connectors FS59US (Nickel) RG59US (Gold) FS59RCAUS (Nickel) RG59RCAUS (Gold) FS59BNCUS (Nickel) RG59BNCUS (Gold) FS6US (Nickel) RG6US (Gold) FS6RCAUS (Nickel) RG6RCAUS (Gold) FS6BNCUS (Nickel) RG6BNCUS (Gold) RG59

More information

QUEST C6 SOLUTIONS CAT 6 CONNECTIVITY PRODUCTS LAN CONNECTIVITY

QUEST C6 SOLUTIONS CAT 6 CONNECTIVITY PRODUCTS LAN CONNECTIVITY CAT 6 CONNECTIVITY PRODUCTS QUEST C6 SOLUTIONS C6 12-PORT MINI VERTICAL Fig. 3 Fig. 4 C6 16-PORT C6 24-PORT C6 48-PORT CAT 6 PATCH PANELS Quest C6 Patch Panels offer the installers quality and cost effective

More information

onlinecomponents.com

onlinecomponents.com CAT 6 CONNECTIVITY PRODUCTS QUEST C6 SOLUTIONS LAN CONNECTIVITY Fig. 5 Black Fig. 9 Yellow C6 12-PORT MINI VERTICAL Fig. 3 Fig. 4 Fig. 6 Blue 0 Green 3 CAT6 Single Surface Box Fig. 7 Red 1 Ivory C6 16-PORT

More information

TAHOMA opengear frame

TAHOMA opengear frame TAHOMA opengear frame The opengear Frame OG3-FR-CN Apantac opengear implementation uses the OG3-FR-CN frame that comes with cooling and Advanced GigE Network Control This frame has superior flexibility,

More information

5e. Max bandwidth is 400MHz Cat 6 max bandwidth of 500MHz Cat 6E max bandwidth of 550MHz ( E stands for enhanced ) Cat 6A max bandwidth of 625MHz

5e. Max bandwidth is 400MHz Cat 6 max bandwidth of 500MHz Cat 6E max bandwidth of 550MHz ( E stands for enhanced ) Cat 6A max bandwidth of 625MHz Before we talk about Hubbell s range of Copper connectivity products we first need to understand the difference between the various categories of copper products! Quite simply put the category of a copper

More information

2014 Product Catalog

2014 Product Catalog 2014 Product Catalog What are the CleanStage products? CleanStage products are a toolkit for cabling your event s stage with signal and power, providing maximum time savings, operational efficiency, and

More information

Cable Retention Force Testing of Trunk & Distribution Connectors

Cable Retention Force Testing of Trunk & Distribution Connectors ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 102 2016 Cable Retention Force Testing of Trunk & Distribution Connectors NOTICE The Society of Cable Telecommunications

More information

BUS UNITRONIC BUS CAN

BUS UNITRONIC BUS CAN BUS UNITRONIC BUS CAN For CAN bus systems; stationary applications; 120 Ω LAPP KABEL UNITRONIC BUS CAN UNITRONIC BUS CAN is designed to the CAN open and ISO11898 standard. It is well suited for high-speed

More information

White Paper. Fibre Optic Technologies for Satellite Communication and Broadcast Industries. By Tom Lacey Applications Engineering Group PPM Ltd, UK

White Paper. Fibre Optic Technologies for Satellite Communication and Broadcast Industries. By Tom Lacey Applications Engineering Group PPM Ltd, UK White Paper Fibre Optic Technologies for Satellite Communication and Broadcast Industries By Tom Lacey Applications Engineering Group PPM Ltd, UK Abstract The satellite communications and broadcast industries

More information

Interface Practices Subcommittee SCTE STANDARD SCTE Test Method for Drop Cable Center Conductor Bond to Dielectric

Interface Practices Subcommittee SCTE STANDARD SCTE Test Method for Drop Cable Center Conductor Bond to Dielectric Interface Practices Subcommittee SCTE STANDARD SCTE 59 2018 Test Method for Drop Cable Center Conductor Bond to Dielectric NOTICE The Society of Cable Telecommunications Engineers (SCTE) / International

More information

Mini HD-SDI Optical Transceiver Model No : VCF-MF01TXRX

Mini HD-SDI Optical Transceiver Model No : VCF-MF01TXRX User Manual Mini HD-SDI Optical Transceiver Model No : VCF-MF01TXRX NOTE: The casing design is subject to change without notice. Our Mini SD/HD-SDI optical transceiver is a Ultra -mini and economical version

More information

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

1.0 GENERAL. 1.2 SUMMARY.1 Section Includes:

1.0 GENERAL. 1.2 SUMMARY.1 Section Includes: 1.0 GENERAL 1.1 DOCUMENTS.1 This section of the Specification forms part of the Contract Documents and is to be read, interpreted, and coordinated with all other parts. 1.2 SUMMARY.1 Section Includes:

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 - GENERAL 1.1 SECTION

More information

Classified Facility Communications Cabling Infrastructure Design Basics. Pedro De Jesus, PE, RCDD, DCDC Senior Technical Consultant CH2M Hill

Classified Facility Communications Cabling Infrastructure Design Basics. Pedro De Jesus, PE, RCDD, DCDC Senior Technical Consultant CH2M Hill Classified Facility Communications Cabling Infrastructure Design Basics Pedro De Jesus, PE, RCDD, DCDC Senior Technical Consultant CH2M Hill What is a Classified Network? This training covers design requirements

More information

Aerospace Fiber Optics

Aerospace Fiber Optics Aerospace Fiber Optics AFO 101, Session 2 Fiber Optic Assembly Everett Community College. All rights reserved. 1 Session Learning Objectives After completing this session you should be able to: Work safely

More information

Telecommunication Infrastructure Project September 20, 2002

Telecommunication Infrastructure Project September 20, 2002 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Category rated UTP systems shall be provided and tested in accordance with the performance level established in Specification

More information

VGA CAT-5 1:8 Distribution S VGA CAT-5 Distribution R. EXT-VGA-CAT5-148S EXT-VGA-CAT5-148R User Manual

VGA CAT-5 1:8 Distribution S VGA CAT-5 Distribution R. EXT-VGA-CAT5-148S EXT-VGA-CAT5-148R User Manual VGA CAT-5 1:8 Distribution S VGA CAT-5 Distribution R EXT-VGA-CAT5-148S EXT-VGA-CAT5-148R User Manual INTRODUCTION Congratulations on your purchase of the VGA CAT-5 1:8 Distribution S. Your complete satisfaction

More information

SWISS TIMING Service catalogue FIS World Cup Ski Jumping / Ski Flying 2017/2018

SWISS TIMING Service catalogue FIS World Cup Ski Jumping / Ski Flying 2017/2018 1. Equipment Scoring System Ski Jumping UPS backed up 1 computer network (main and backup network) 5 judging terminals Speed measurement (main and backup speed measurement) FIS certified video distance

More information

FLAT AND ROUND CABLE PRODUCT DESCRIPTION DESIGN ADVANTAGES. IDC Systems Cable

FLAT AND ROUND CABLE PRODUCT DESCRIPTION DESIGN ADVANTAGES. IDC Systems Cable Cable PRODUCT DESCRIPTION Thomas & Betts flat cable provides the means to reduce mass and weight in flexible wiring assemblies. Available with PVC, TPE or FEP insulation, the cable is extruded to provide

More information

Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD Specification for Braided 75 Ω, Mini-Series Quad Shield Coaxial Cable for CMTS and SDI cables NOTICE The Society of Cable Telecommunications

More information

FIM-108 MATRIX FIBER INTERFACE INSTRUCTION MANUAL

FIM-108 MATRIX FIBER INTERFACE INSTRUCTION MANUAL FIM-108 MATRIX FIBER INTERFACE INSTRUCTION MANUAL FIM-108 Matrix Fiber Interface Instruction Manual 2003 Clear-Com Intercom Systems All Rights Reserved Part Number 810291 Rev. A Clear-Com Intercom Systems

More information

Multi-Media Installation Guide

Multi-Media Installation Guide Multi-Media Installation Guide Coaxial Page 2 Data Plug Page 7 Data Jack Page 10 Telephone Page 13 Splicing Page 15 Cable Types Cable Types Two basic types of cable are used in multimedia installations.

More information

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE Prepared in cooperation and approval from BICSI Building Industry Consulting Services International and

More information

VCF-HCFB01TXRX SD/HD/3G-SDI Optical Transceiver with Independence audio

VCF-HCFB01TXRX SD/HD/3G-SDI Optical Transceiver with Independence audio User Manual VCF-HCFB01TXRX SD/HD/3G-SDI Optical Transceiver with Independence audio NOTE: The casing design is subject to change without notice. SD/HD/3G-SDI Optical Transceiver is a perfect and economic

More information

INSTALLATION MANUAL. ION Series FIBER OPTIC ILLUMINATOR IP67 OUTDOOR RATED

INSTALLATION MANUAL. ION Series FIBER OPTIC ILLUMINATOR IP67 OUTDOOR RATED ION Series FIBER OPTIC ILLUMINATOR IP67 OUTDOOR RATED ION-8000-WW (Warm White) ION-8000-CW (Cool White) ION-8000-B (Blue) ION-8000 RGB ION-8000 RGBW ION-8000 WW-CW Class 2 E359853 10.08.2014 FIBER HEAD

More information

GE Interlogix Fiber Options S700V & S702V. Instruction Manual FIBER-OPTIC VIDEO TRANSMISSION SYSTEM

GE Interlogix Fiber Options S700V & S702V. Instruction Manual FIBER-OPTIC VIDEO TRANSMISSION SYSTEM g GE Interlogix Fiber Options Instruction Manual S700V & S702V FIBER-OPTIC VIDEO TRANSMISSION SYSTEM Federal Communications Commission and Industry Canada Radio Frequency Interference Statements This equipment

More information

HD Flex Patch Panel. ASSEMBLY VIEW (FLEX1UPN** shown) FS128B. CONTENTS: (#) indicates FLEX4UPN** quantity

HD Flex Patch Panel. ASSEMBLY VIEW (FLEX1UPN** shown) FS128B. CONTENTS: (#) indicates FLEX4UPN** quantity HD Flex Patch Panel Part Numbers: FLEX1UPN**, FLEX2UPN**, FLEX4UPN** Panduit Corp. 2018 INSTALLATION INSTRUCTIONS Note: HD Flex Patch Panels are compatible with HD Flex Fiber System Components. HD Flex

More information

Kwangil Electronic Introduction

Kwangil Electronic Introduction www.kicable.com Introduction Dear Valuable customs of Kwang IL Wire & Cable Co, Inc. First of all, I d like to appreciate all the supports and cooperations given to us, and we sincerely hope all of you

More information

HDMI Technology. HDMI Over Category 6 HDBaseT Signal Extenders

HDMI Technology. HDMI Over Category 6 HDBaseT Signal Extenders Product Bulletin PB 494 Belden HDMI Connectivity Solutions Belden now offers a complete solution for sending HDMI signals over long distances without a reduction in signal quality. Whether using Category

More information

The world's first POF AOC manufacturer. Compare to copper cable

The world's first POF AOC manufacturer. Compare to copper cable UNIVE UNIVE, the world s first POF AOC manufacturer, was founded as SoC design and IP service company in 2003. Based on our business motto on the creation of differentiated values for customer s satisfaction,

More information

Interface Practices Subcommittee SCTE STANDARD SCTE Specification for Mainline Plug (Male) to Cable Interface

Interface Practices Subcommittee SCTE STANDARD SCTE Specification for Mainline Plug (Male) to Cable Interface Interface Practices Subcommittee SCTE STANDARD Specification for Mainline Plug (Male) to Cable Interface NOTICE The Society of Cable Telecommunications Engineers (SCTE) / International Society of Broadband

More information

SD/HD/3G-SDI Video + Power + Data RS-485 Transmission over Coax Kit

SD/HD/3G-SDI Video + Power + Data RS-485 Transmission over Coax Kit User Manual SD/HD/3G-SDI Video + Power + Data RS-485 Transmission over Coax Kit HD-SDE-VDK Tx Camera Side Rx DVR Side HD-SDE-VDT SD-6b SD-6a The power are only for the devices, not for camera. Repeater

More information

Section Communications Optical Fiber Backbone Cabling

Section Communications Optical Fiber Backbone Cabling Part 1 1.1 Related Documents 1.1.1 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections apply to this Section. 1.2 Related

More information

Follow The Leader In Shielded Technology

Follow The Leader In Shielded Technology 1970s Vampire Tap 1990s Shielded Modular Jack 190s 4 Position Data Connector Follow The Leader In Shielded Technology The new AMP-TWIST Jack is our latest shielded product evolution. It can be terminated

More information

DISTRIBUTION AMPLIFIER

DISTRIBUTION AMPLIFIER MANUAL PART NUMBER: 400-0045-005 DA1907SX 1-IN, 2-OUT VGA/SVGA/XGA/UXGA DISTRIBUTION AMPLIFIER USER S GUIDE TABLE OF CONTENTS Page PRECAUTIONS / SAFETY WARNINGS... 2 GENERAL...2 GUIDELINES FOR RACK-MOUNTING...2

More information

Precision Interconnects High-Performance Video and Audio Cables

Precision Interconnects High-Performance Video and Audio Cables High-Performance Video and Audio Cables DVDO Home Theater Products by Anchor Bay Technologies, Inc. 300 Orchard City Drive, Mailstop 131 Campbell, California 95129 Toll-Free 1.866.423.DVDO Fax 408.379.3845

More information

W-2x2 2x2, 1x3 or 1x4 Video Wall. Low Resolution. Monitor Output. CATx Extender Output) Low Resolution. Monitor Output (HDMI, DVI

W-2x2 2x2, 1x3 or 1x4 Video Wall. Low Resolution. Monitor Output. CATx Extender Output) Low Resolution. Monitor Output (HDMI, DVI WALL Video Walls Plug and play - no software required for operation Color temperature adjustments Pure hardware architecture, not a PC Can be configured in a x mode to be used with a x 4K monitor Can be

More information

Structured Cabling Introduction & Installation Guide

Structured Cabling Introduction & Installation Guide Structured Cabling Introduction & Installation Guide Structured Cabling Overview General Structure - Cat5e/Cat6 Cabling The structure illustrated has the following key points: Face plates present outlet

More information

UCR 2008, Change 3, Section 5.3.7, Video Distribution System Requirements

UCR 2008, Change 3, Section 5.3.7, Video Distribution System Requirements DoD UCR 2008, Change 3 Errata Sheet UCR 2008, Change 3, Section 5.3.7, Video Distribution System Requirements SECTION 5.3.7.2.2 CORRECTION IPv6 Profile requirements were changed to a conditional clause

More information

Continuous High-Flex Cable for Automated Systems

Continuous High-Flex Cable for Automated Systems Take advantage of the proven,10 million flex cycle capabilities of any of flexlife-10 cable designs and eliminate the risk of plant downtime due to cable failure. Continuous High-Flex Cable for Automated

More information

3G-SDI Extender via Single Mode Fiber LC Simplex Connector Extends 3G-SDI Link Up To 20 Kilo Meters

3G-SDI Extender via Single Mode Fiber LC Simplex Connector Extends 3G-SDI Link Up To 20 Kilo Meters Description 3G-SDI (3G Serial Digital Interface) recently has become increasingly popular in the application of video and audio transmission system. However, the traditional copper wire cable imposes limits

More information

HI-DEX PRODUCT SET DATASHEET

HI-DEX PRODUCT SET DATASHEET APPLICATION HI-DEX is an ultra high-performance, pre-terminated and modular optical fibre cabling system based on MT ferrule connector technology. This product set is designed for installationn in the

More information

PLU-TV & AT&T CATV CLASSROOM/OFFICE BUILDING EQUIPMENT LISTS & DIAGRAMS CLT CATV.doc CENTER FOR LEARNING & TECHNOLOGY (CLT)

PLU-TV & AT&T CATV CLASSROOM/OFFICE BUILDING EQUIPMENT LISTS & DIAGRAMS CLT CATV.doc CENTER FOR LEARNING & TECHNOLOGY (CLT) Page 1 08-21-01 PLU-TV & AT&T CATV CLASSROOM/OFFICE BUILDING EQUIPMENT LISTS & DIAGRAMS CLT CATV.doc CENTER FOR LEARNING & TECHNOLOGY (CLT) The following is a list of equipment needed to cable and provide

More information

ADDENDUM NO. 2 This addendum consists of 8 pages. Kenai Peninsula Borough Purchasing & Contracting

ADDENDUM NO. 2 This addendum consists of 8 pages. Kenai Peninsula Borough Purchasing & Contracting KENAI PENINSULA BOROUGH Purchasing and Contracting 144 North Binkley Street Soldotna, Alaska 99669-7520 Toll-free within the Borough: 1-800-478-4441, Ext. 2260 PHONE: (907) 714-2260 FAX: (907) 714-2373

More information

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus PART 1: GENERAL REQUIREMENTS A. Contractor Work 1. Provide and install (except as noted in this document), cable,

More information

How Wire Fails Originally presented to the Society of Motion Picture and Television Engineers Convention, Sydney, Australia, on Friday, July 4, 1997.

How Wire Fails Originally presented to the Society of Motion Picture and Television Engineers Convention, Sydney, Australia, on Friday, July 4, 1997. How Wire Fails Originally presented to the Society of Motion Picture and Television Engineers Convention, Sydney, Australia, on Friday, July 4, 1997. ABSTRACT: By Stephen H. Lampen Technology Development

More information

Digamber Telecom.

Digamber Telecom. +91-8048409600 Digamber Telecom https://www.sancharcable.com/ We are a reputed manufacturer and supplier of Telecom Industrial Products & Cables that is working hard from over many years to achieve utmost

More information

CUSTOM COLLECTION. Welcome to the Tributaries Custom Collection.

CUSTOM COLLECTION. Welcome to the Tributaries Custom Collection. CUSTOM COLLECTION Welcome to the Tributaries Custom Collection. Inside, you will find information about our growing line of connectors, cables and award winning accessories all designed especially for

More information

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 102 2010 Cable Retention Force Testing of Trunk & Distribution Connectors NOTICE The Society of Cable Telecommunications

More information

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project 1.1.0 GENERAL The purpose of this specification is to establish a requirement for the installation of a voice, video and data cable network. The cable (copper), wire, hardware, equipment racks, jumpers,

More information

Extender for HDMI over one CAT5

Extender for HDMI over one CAT5 1080P Extender for HDMI over one CAT5 GTV-HDBT-CAT5 User Manual gefentv.com ASKING FOR ASSISTANCE Technical Support: Telephone (818) 772-9100 (800) 545-6900 Fax (818) 772-9120 Technical Support Hours:

More information

RAPIDRUN. Saves Time & Money Offers High Performance & Quality Allows For Easy Upgrades Provides The Total Solution Fast, Complete A/V System Do More!

RAPIDRUN. Saves Time & Money Offers High Performance & Quality Allows For Easy Upgrades Provides The Total Solution Fast, Complete A/V System Do More! RAPIDRUN Saves Time & Money Offers High Performance & Quality Allows For Easy Upgrades Provides The Total Solution Fast, Complete A/V System Do More! RapidRun is the most complete audio/video cabling system

More information

Introduction. Fiber Optics, technology update, applications, planning considerations

Introduction. Fiber Optics, technology update, applications, planning considerations 2012 Page 1 Introduction Fiber Optics, technology update, applications, planning considerations Page 2 L-Band Satellite Transport Coax cable and hardline (coax with an outer copper or aluminum tube) are

More information

CABLING STANDARDS FOR

CABLING STANDARDS FOR RFB for Wiring in the Outagamie County Courtrooms Attachment B September 1, 2016 CABLING STANDARDS FOR GENERAL The purpose of this document is to provide guidelines for all structured cable installations

More information

2090-Series Kinetix 6000M Integrated Drive-Motor Cables

2090-Series Kinetix 6000M Integrated Drive-Motor Cables 2090-Series Kinetix 6000M Integrated Drive-Motor Cables cables with rugged SpeedTec connectors, and network cables with straight and right-angle connector options, are available for connecting your Kinetix

More information

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 48-3 2011 Test Procedure for Measuring Shielding Effectiveness of Braided Coaxial Drop Cable Using the GTEM Cell

More information

HVWIP-Series (HVWIP-T + HVWIP-R)

HVWIP-Series (HVWIP-T + HVWIP-R) HVWIP-Series ( + ) The AG Neovo HVWIP-Series ( + ) LAN video wall matrix extender for digital signage applications. Features > Support 1080P@60Hz up to 100meters in Point-to-Point mode. > Support seamless

More information

www.comprehensiveco.com/gopro Pro AV/IT Heavy Duty Certified 18G 4K HDMI Cables Comprehensive s Pro AV/IT Certified 18G 4K (End to End) HDMI Cables are full UHD with Deep Color and High Dynamic Range support

More information