A guide to Woolworths Limited additional requirements. for the testing of twisted pair and fibre installation.

Size: px
Start display at page:

Download "A guide to Woolworths Limited additional requirements. for the testing of twisted pair and fibre installation."

Transcription

1 22 nd August 2013 A guide to Woolworths Limited additional requirements for the testing of twisted pair and fibre installation. Background This document has been prepared by VTI Services and approved by Woolworth s Limited to provide guidelines to the additional requirements for the testing of Woolworth s Limited sites. Document Limitation This document is provided for guidance only. All care has been taken in the creation of the document; however no claim that any or all issues have been identified and no responsibility will be accepted for its use. This document reflects VTI Services understanding of Woolworth s Limited requirements at the time of publication; however should there be conflict between this document and the Woolworth s Limited requirements, Woolworth s Limited requirements takes precedence. The testing requirements of Woolworth s Limited may change at any time without notice. Specifications should be read to determine testing requirements before testing is undertaken. General Requirements Independent test result analysis In the interests of ensuring compliance of the performance of the installed cabling system against Australian/New Zealand and specific Woolworth s Limited standards, it is a requirement that all SCS cabling test data be verified by an approved NATA Inspection Body. This effects all installations, irrespective of the communication contractor or structured cabling system vendor installing communication cabling systems within Woolworth s Limited locations. CR004-Woolworths- Testing Guide V1.9 Page 1 of 5

2 Woolworth s Limited require on nominated projects that the fibre and twisted pair test results be submitted to an approved NATA accredited inspection body for evaluation. The associated Statement of Compliance and report form part of the acceptance requirements of the project. Woolworth s Limited s approved NATA Inspection body VTI Services 16 Banbury Crescent Chipping Norton.NSW.2170 Telephone: office@vti.net.au Contact: Murray Teale Woolworth s Limited requires the verification of test data to Australian and New Zealand Standards along with specified additional Woolworth s requirements Woolworth s Limited additional requirements form part of the compliance of the report and may include additional elements not associated directly with testing. 1. It is a Woolworth s Limited requirement that all reports generated against Woolworth s Limited requirements be issued from the inspection body directly to Woolworth s Limited at the time of creation This provides Woolworth s Limited a mechanism to carry out a risk assessment of a site and allow for the installation to be accepted before a Statement of Compliance has been issued. This acceptance before a Statement of Compliance has been issued minimises the potential delay in practical completion and/or acceptance of a project Test Equipment All test equipment shall be in calibration at time of testing CR004-Woolworths- Testing Guide V1.9 Page 2 of 5

3 Twisted Pair Requirements Test Requirements Permanent link testing shall be carried out to the compliance requirements of AS/NZS3080 Permanent Links. Correct adaptors shall be used for all testing (Channel adaptors are unacceptable for permanent link testing). Marginal/Conditional Passes (Pass*) are not acceptable Full Plot Data shall be present. Test results shall be provided electronically. Approved Testers Twisted pair testers utilised for testing of Woolworth s Limited installations shall meet defined requirements. Testers meeting these requirements which have been approved by Woolworth s Limited include: o Fluke DTX1200-Fluke DTX1800. o Wirescope 350 and Wirescope PRO. Fibre Requirements Permanent link testing shall be carried out to the compliance requirements of AS/NZS3080 for all fibre cores. LSPM testing shall be carried out in two directions and at two wavelengths on all installed links. LSPM Test results will be provided electronically in the testers native format along with VTI Services fibre reporting sheet. The Woolworth s fibre reporting sheet forms part of the Additional Criteria Form and is available on VTI Services Website under downloads. Optical fibre mated connectors shall meet the following minimum optical return loss requirements. o 20 db for Multi-mode. o 35 db for Single-mode. o Testing of ORL is not required outside of visual inspection of the interface connector. The pass fail criteria will be that specified within AS/NZS ISO/IEC CR004-Woolworths- Testing Guide V1.9 Page 3 of 5

4 Woolworth s Limited Specific Requirements Necessary reporting including Woolworths additional information, Fibre reporting Sheet and TCA1 Form, shall be provided along with Test results. Without this information assessment of test data cannot take place; deeming the site as Non- Compliant. The Woolworth s Additional Criteria Form is available on VTI Services Website under downloads. Any Backbone and MDF/IFD/TPF to BD tie cables shall be tested for wire map and the results submitted for verification. All new projects depending on store types require backbone test results be provided (This is for groups of results not individual tests). Please note- Required TP Backbone : Store type 1 -nil. Store type 2- nil. Store type 3 - Backbone 25pr (1 group of 6 [4pr] cables) Store type 4 - Backbone 25pr (2 groups of 6 [4pr] cables) Store type 5 - Backbone 25pr (3 groups of 6 [4pr] cables) Store type 6 - Backbone 25pr (4 groups of 6 [4pr] cables) Backbone will be assessed against: Wire-map. Length. Continuity. All new projects require tie cabling test results to be provided The tie cable shall be tested as single pairs. Each single pair that connects MDF/IFD/TPF to BD shall be tested for: Wire-map. Continuity. The SCS BD side of 25-pair UTP MDF/IDF/TPF Tie cables shall be terminated within the SCS BD onto a CAT6 patch panel, with each pair of the 25-pair cable terminated on a port on the CAT6 patch panel, As shown in the below table; *Please note: The 25 th Pair is required to be terminated CR004-Woolworths- Testing Guide V1.9 Page 4 of 5

5 25-Pair number Mate Colour CAT6 Patch panel 1 White Blue Port 1 Pin 4/5 2 White Orange Port 2 Pin 4/5 3 White Green Port 3 Pin 4/5 4 White Brown Port 4 Pin 4/5 5 White Grey Port 5 Pin 4/5 6 Red Blue Port 6 Pin 4/5 7 Red Orange Port 7 Pin 4/5 8 Red Green Port 8 Pin 4/5 9 Red Brown Port 9 Pin 4/5 10 Red Grey Port 10 Pin 4/5 11 Black Blue Port 11 Pin 4/5 12 Black Orange Port 12 Pin 4/5 13 Black Green Port 13 Pin 4/5 14 Black Brown Port 14 Pin 4/5 15 Black Grey Port 15 Pin 4/5 16 Yellow Blue Port 16 Pin 4/5 17 Yellow Orange Port 17 Pin 4/5 18 Yellow Green Port 18 Pin 4/5 19 Yellow Brown Port 19 Pin 4/5 20 Yellow Grey Port 20 Pin 4/5 21 Violet Blue Port 21 Pin 4/5 22 Violet Orange Port 22 Pin 4/5 23 Violet Green Port 23 Pin 4/5 24 Violet Brown Port 24 Pin 4/5 25* Violet Grey Port 24 Pin 1/2 CR004-Woolworths- Testing Guide V1.9 Page 5 of 5

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION PART 1 - GENERAL 1.1 SUMMARY SCOPE SECTION 25170 TESTING, IDENTIFICATION AND ADMINISTRATION 1. This section includes the minimum requirements for the testing, certification administration and identification

More information

Excel recommends Fluke Networks, this section is written around the use of this range of test equipment.

Excel recommends Fluke Networks, this section is written around the use of this range of test equipment. Testing Excel recommends Fluke Networks, this section is written around the use of this range of test equipment. Twisted Pair Copper This section describes and sets out the requirements for Class D (Cat

More information

1.0 GENERAL. 1.2 SUMMARY.1 Section Includes:

1.0 GENERAL. 1.2 SUMMARY.1 Section Includes: 1.0 GENERAL 1.1 DOCUMENTS.1 This section of the Specification forms part of the Contract Documents and is to be read, interpreted, and coordinated with all other parts. 1.2 SUMMARY.1 Section Includes:

More information

The University of Texas at Austin September 30, 2011

The University of Texas at Austin September 30, 2011 SECTION 27 08 20 COPPER TESTING PART 1 - GENERAL 1.1 SUMMARY A. Test measurements shall be taken for all balanced-twisted pair cabling, including horizontal and backbone copper cables and wall-to-rack

More information

DESIGN!!GUIDELINES!!!!!

DESIGN!!GUIDELINES!!!!! DESIGNGUIDELINES 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 1. Testing General 1.1. For acceptance, 100% of the media

More information

ISO/IEC testing LC to LC (Duplex Multimode) DTX-MFM

ISO/IEC testing LC to LC (Duplex Multimode) DTX-MFM Page 1 of 5 ISO/IEC 14763-3 testing LC to LC (Duplex Multimode) DTX-MFM ISO/IEC 11801 now refers fibre testing to ISO/IEC 14763-3. More importantly, the limits have changed and we'll show you how in this

More information

RCIT Cable Certification Testing Revised 10/2017

RCIT Cable Certification Testing Revised 10/2017 RCIT Testing Revised 10/2017 General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall

More information

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards.

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards. 27 08 00 Certification and Commissioning of Communication Systems (Revision date: 7/3/12) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 - GENERAL 1.1 SECTION

More information

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017 Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM-2017-2 Date: 05/26/2017 Additional specification information for data communication to cameras and between Library

More information

LCS2 Cat. 6 RJ 45 Patch panels and units

LCS2 Cat. 6 RJ 45 Patch panels and units 87045 LIMOGES Cedex Telephone: 33 0 5 55 06 87 87 - Fax: 33 0 5 55 06 88 88 LCS2 Cat. 6 RJ 45 CONTENTS Page 1. General characteristics....1 2. Presentation...2 3. Installation...2 4. Technical characteristics...2

More information

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall obtain authorization from

More information

SECTION TESTING OF COPPER CABLES

SECTION TESTING OF COPPER CABLES SECTION 27 08 13 TESTING OF COPPER CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction,

More information

Challenges for testing 10GBASE-T

Challenges for testing 10GBASE-T Challenges for testing 10GBASE-T Adrian Young Customer Support Manager adrian.young@flukenetworks.com Check list Category 6A component compliant connector Category 6A compliant cable Perfect terminations

More information

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus PART 1: GENERAL REQUIREMENTS A. Contractor Work 1. Provide and install (except as noted in this document), cable,

More information

How to Specify MTP Pre-terminated Optical Cabling. January White Paper. Published

How to Specify MTP Pre-terminated Optical Cabling. January White Paper. Published White Paper How to Specify MTP Pre-terminated Optical Cabling Published January 2009 The benefits of pre-terminated cabling The two principal advantages of pre- terminated cabling are reduced time on site

More information

The need for Encircled Flux, real or imaginary?

The need for Encircled Flux, real or imaginary? Version 1.7 The need for Encircled Flux, real or imaginary? Harley Lang, RCDD Fluke Networks 14 March, 2013 Presentation agenda What s the issue Mandrels are they needed? Review of standards Coupled Power

More information

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008 Information & Communications Technology Group Standards June 2008 Appendix F UTP cabling Version 1.1 Appendix F UTP cabling 1. Introduction This Section details the required standards for Unshielded Twisted

More information

Term 1 Grade 11 -Task Sheet 2. Group: N/A (Not Applicable) Finishing Time: Make a CAT5 cable. Picture 1. Picture 2

Term 1 Grade 11 -Task Sheet 2. Group: N/A (Not Applicable) Finishing Time: Make a CAT5 cable. Picture 1. Picture 2 Term 1 Grade 11 -Task Sheet Name: SIS No Group: N/A (Not Applicable) Signed Date: Grade Start Time: Finishing Time: Make a CAT5 cable Picture 1 Picture Task Sheet Unit OBJECTIVE Understand the steps to

More information

Robert Burén. Product Manager. Nexans Cabling Solutions. 10G Solutions

Robert Burén. Product Manager. Nexans Cabling Solutions. 10G Solutions Robert Burén Product Manager 10G Solutions Nexans Cabling Solutions 1 10 Gigabit Ethernet.Performance 30 GByte can be transmitted within 24 seconds Example: MRI-scan size is 30GB as average A memory device

More information

Mar11 Rev E

Mar11 Rev E Product Specification 108-1832 11Mar11 Rev E MT-RJ Patch Panel and Outlet Jacks (Standard, XG, SECURE and SECURE XG) 1. SCOPE 1.1. Content This specification, which meets the Optical Fiber Cabling Components

More information

How to accelerate your cabling system approvals

How to accelerate your cabling system approvals How to accelerate your cabling system approvals Adrian Young Fluke Networks November, 2013 Singapore Objectives for this session Resolve field failures on the spot Look at real world examples of fault

More information

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project 1.1.0 GENERAL The purpose of this specification is to establish a requirement for the installation of a voice, video and data cable network. The cable (copper), wire, hardware, equipment racks, jumpers,

More information

LEGRAND CABLING SYSTEM 2 PERFORMANCE FROM TECHNICAL ROOM TO WORKSTATION

LEGRAND CABLING SYSTEM 2 PERFORMANCE FROM TECHNICAL ROOM TO WORKSTATION LEGRAND CABLING SYSTEM 2 PERFORMANCE FROM TECHNICAL ROOM TO WORKSTATION 14 LCS 2 Copper A complete system for higher performance Connectors See pages 16 to 19 LCS 2 copper Patch panels See pages 21 to

More information

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents PART 1 - GENERAL 1.1 SUMMARY SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors. 3. Cabling system identification products. 1.2

More information

AS/NZS 1367:2016. Australian/New Zealand Standard

AS/NZS 1367:2016. Australian/New Zealand Standard AS/NZS 1367:2016 Australian/New Zealand Standard Coaxial cable and optical fibre systems for the RF distribution of digital television, radio and in-house analog television signals in single and multiple

More information

CAT6Plus System. Brand-Rex Limited

CAT6Plus System. Brand-Rex Limited Brand Rex introduces it's New CAT6Plus Cabling Solution, designed to deliver an optimum performance cabling system. All products in the CAT6Plus system have 3rd party approval* and therefore either meet

More information

Connectix Cabling Systems

Connectix Cabling Systems Connectix Cabling Systems Cabling Standards and CPR Update Connectix CEP Fibre Optic Solutions Jason Holroyd CNID Director of Business Development Types of fibre Agenda Introduction Uses Construction Transmission

More information

Volition TM RJ45 K5e Jacks

Volition TM RJ45 K5e Jacks Volition TM RJ45 K5e Jacks Part of our 3M Volition Network Solutions, the new K5e range is our ultimate Category 5e hardware component (ISO/IEC 11801, EN 50173 and ANSI/TIA/EIA-568). The K5e jack is a

More information

Follow The Leader In Shielded Technology

Follow The Leader In Shielded Technology 1970s Vampire Tap 1990s Shielded Modular Jack 190s 4 Position Data Connector Follow The Leader In Shielded Technology The new AMP-TWIST Jack is our latest shielded product evolution. It can be terminated

More information

Compact Module. Category 6 FTP Cabling System

Compact Module. Category 6 FTP Cabling System Compact Module Shielded design for improved EMI performance Suitable for Gigabit Ethernet applications and beyond Ultra-slimline design Colour coded for quick and accurate termination Interchangeable with

More information

HighBand 25. TrueNet Category 6 Solutions

HighBand 25. TrueNet Category 6 Solutions HighBand 25 TrueNet Category 6 Solutions The highest performing cross-connect system in the world. A unique high-density solution with superior cable management. ADC KRONE s HighBand 25 cross connect solution

More information

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE Prepared in cooperation and approval from BICSI Building Industry Consulting Services International and

More information

Cable harness for bodywork functions

Cable harness for bodywork functions General information General information This document describes 2 different cable harnesses for bodywork functions, see illustration. C486 C487 C488 C494. Cable harness from cab to frame (variant family

More information

The Road to Single Mode: Direction for choosing, installing and testing single mode fiber

The Road to Single Mode: Direction for choosing, installing and testing single mode fiber The Road to Single Mode: Direction for choosing, installing and testing single mode fiber Adrian Young Leviton Network Solutions Jim Davis Fluke Networks Adrian Young, Sr. Applications Engineer Leviton

More information

LAN Network Tester. Operating Manual. Part No TRIAX - your ultimate connection

LAN Network Tester. Operating Manual. Part No TRIAX - your ultimate connection LAN Network Tester Part No. 157011 Operating Manual TRIAX - your ultimate connection Safety and Disposal The LAN Network Tester operates off 6V DC only. Only use the internal, battery powered, 6V power

More information

The current state of multimode OTDR and Light Source and Power Meter (LSPM) Insertion Loss (IL) testing is as follows:

The current state of multimode OTDR and Light Source and Power Meter (LSPM) Insertion Loss (IL) testing is as follows: APPLICATION NOTE Meeting the Encircled Flux Launch Standard Scope: Guidance on how to test to the Encircled Flux (EF) multimode launch standard using existing optical test equipment and the Optronics Encircled

More information

SC8108-A. NetWork Cable Tester. User Operation Manual. Taking Its Source At Sanling Science & Technology Good helper to network

SC8108-A. NetWork Cable Tester. User Operation Manual. Taking Its Source At Sanling Science & Technology Good helper to network SC8108-A NetWork Cable Tester User Operation Manual Taking Its Source At Sanling Science & Technology Good helper to network 1. The tester uses 6V DC as the power supply only. 2. Never attempt to connect

More information

MT-RJ SECURE Product Expansion Now 10 Variants of the MT-RJ SECURE Products

MT-RJ SECURE Product Expansion Now 10 Variants of the MT-RJ SECURE Products MT-RJ Product Expansion Now 0 Variants of the MT-RJ Products In response to several customers, the MT-RJ product line has been expanded with an additional six color/key versions. In addition to the original

More information

Specification of Fusion Splice Loss - FIA TSD Mike Gilmore FIA Technical Director

Specification of Fusion Splice Loss - FIA TSD Mike Gilmore FIA Technical Director Specification of Fusion Splice Loss - FIA TSD-2000-4-1-1 Mike Gilmore FIA Technical Director Mike Gilmore Standards Activities Member: ISO/IEC JTC1 SC25 WG3: Generic Cabling ISO/IEC JTC1 SC25 Project Team:

More information

CAT6 Cable Tester. Operating Manual. Part No TRIAX - your ultimate connection

CAT6 Cable Tester. Operating Manual. Part No TRIAX - your ultimate connection CAT6 Cable Tester Part No. 157010 Operating Manual TRIAX - your ultimate connection Application For checking CAT 5e and CAT 6 cables, (UTP and STP). Can also be used with BNC coaxial cable and modular

More information

Datasheet: MultiFiber Pro Update

Datasheet: MultiFiber Pro Update Datasheet: MultiFiber Pro Update Datasheet: MultiFiber Pro Update First MPO tester to support both Singlemode and Multimode MPO fiber testing Data centers are growing, fueled by the proliferation of media,

More information

INSTALLATION MANUAL FT-FOTR-8VD-ST-S. 8-Channel Digital Duplex Baseband Video Transmitter and Receiver With Reverse Data Transmission for PTZ Cameras

INSTALLATION MANUAL FT-FOTR-8VD-ST-S. 8-Channel Digital Duplex Baseband Video Transmitter and Receiver With Reverse Data Transmission for PTZ Cameras INSTALLATION MANUAL FT-FOTR-8VD-ST-S 8-Channel Digital Duplex Baseband Transmitter and Receiver With Reverse Transmission for PTZ Cameras v1.0 4/5/11 1 PACKAGE CONTENTS This package contains: One each

More information

Australian and New Zealand Energy Performance and Marking Requirements for External Power Supplies

Australian and New Zealand Energy Performance and Marking Requirements for External Power Supplies FACT SHEET October 2008 Australian and New Zealand Energy Performance and Marking Requirements for External Power Supplies Minimum Energy Performance Standards (MEPS) Implementation dates Australia - 1

More information

SMART CLASSix 48 UTP Patch Panels (with patching switches) -

SMART CLASSix 48 UTP Patch Panels (with patching switches) - Features Front-mounted Patching Switches connect ports internally, dramatically reducing the need for patch cords Compatible to Unshielded Twisted Pairs (UTP) cabling systems High performance panel that

More information

HI-DEX PRODUCT SET DATASHEET

HI-DEX PRODUCT SET DATASHEET APPLICATION HI-DEX is an ultra high-performance, pre-terminated and modular optical fibre cabling system based on MT ferrule connector technology. This product set is designed for installationn in the

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) Datasheet: MultiFiber Pro Optical Power Meter and Fiber Test Kits Data centers are growing, fueled by the proliferation

More information

Datasheet: MultiFiber Pro

Datasheet: MultiFiber Pro Datasheet: MultiFiber Pro First MPO tester to support both Singlemode and Multimode MPO fiber testing Data centers are growing, fueled by the proliferation of media, virtualization and the need for more

More information

Do you know if your Cat. 6 patch cord has been tested according to standards?

Do you know if your Cat. 6 patch cord has been tested according to standards? White Paper 02. Juli 2002 Andreas Clauser Hauptsitz Binzstrasse 31 CH-8622 Wetzikon Tel +41 1 933 8375 Fax +41 1 930 49 41 Internet www.rdm.com Do you know if your Cat. 6 patch cord has been tested according

More information

CC-Link IE Controller Network Compatible. CC-Link IE Controller Network Recommended Network Wiring Parts Test Specifications

CC-Link IE Controller Network Compatible. CC-Link IE Controller Network Recommended Network Wiring Parts Test Specifications Model Title CC-Link IE Controller Network Compatible CC-Link IE Controller Network Recommended Network Wiring Parts Specifications Management number: BAP-C0401-028-A CC-Link Partner Association (1/31)

More information

Fiber Optic Meter Fiber Optic Source

Fiber Optic Meter Fiber Optic Source FOM/FOS Fiber Optic Meter Fiber Optic Source Warning To avoid injury: do not service the FOM or FOS unless you are qualified to do so. The service information provided in this document is for the use of

More information

HARTING Ethernet cabling cables and connectors, 4 wire

HARTING Ethernet cabling cables and connectors, 4 wire Industrial Cat. 5e Standard cable, 4-wire Type A for permanent installation or to build-up PROFINET system cables PVC X 8 wire X Cat. 5e X Cat. 6 Cat. 6 A Cat. 7 Cable structure Core structure Wire insulation

More information

What really changes with Category 6

What really changes with Category 6 1 What really changes with Category 6 Category 6, the standard recently completed by TIA/EIA, represents an important accomplishment for the telecommunications industry. Find out which are the actual differences

More information

OLP-87/87P. SmartClass Fiber PON Power Meter and Microscope

OLP-87/87P. SmartClass Fiber PON Power Meter and Microscope OLP-87/87P SmartClass Fiber PON Power Meter and Microscope The Viavi Solutions OLP-87 is an FTTx/PON power meter for use in qualifying, activating, and troubleshooting B-PON, E-PON, G-PON, and next-generation,

More information

3M 8900 Single-mode SC Crimplok Connector

3M 8900 Single-mode SC Crimplok Connector 3M 8900 Single-mode SC Crimplok Connector Technical Report June 1999 80-6110-1441-8 1 1.0 Product Description & Requirements The 3M SC Single-mode Crimplok Connector is designed to provide the customer

More information

NAVSEA STANDARD ITEM. 1.1 Title: Fiber Optic Component; remove, relocate, repair, and install

NAVSEA STANDARD ITEM. 1.1 Title: Fiber Optic Component; remove, relocate, repair, and install NAVSEA STANDARD ITEM ITEM NO: 009-123 DATE: 18 NOV 2016 CATEGORY: II 1. SCOPE: 1.1 Title: Fiber Optic Component; remove, relocate, repair, and install 2. REFERENCES: 2.1 Standard Items 2.2 MIL-STD-1678,

More information

HDBT Installation Guide

HDBT Installation Guide KRAMER ELECTRONICS LTD. HDBT Installation Guide MODELS: Kramer HDBT Cable Recommendations for Usage and Termination Guidelines For the latest information on our products and a list of Kramer distributors,

More information

Draft for Public Comment

Draft for Public Comment Draft for Public Comment Form 36 Version 6.1 DPC: 03/302646 DC Head Office 389 Chiswick High Road London W4 4AL Telephone: +44(0)20 8996 9000 Fax: +44(0)20 8996 7001 Date: 27 March 2003 Origin: National

More information

Enterprise Networks. Comms Room and Backbone. in DETAIL

Enterprise Networks. Comms Room and Backbone. in DETAIL Enterprise Networks Comms Room and Backbone in DETAIL 31 Patch Panels 33 CAT 6 CL 16 WAY PATCH PANEL 19 1U Category 6 performance patch panel. Jacks are fitted. Integral cable management and reusable label

More information

Telecommunication Infrastructure Project September 20, 2002

Telecommunication Infrastructure Project September 20, 2002 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Category rated UTP systems shall be provided and tested in accordance with the performance level established in Specification

More information

Section Communications Optical Fiber Backbone Cabling

Section Communications Optical Fiber Backbone Cabling Part 1 1.1 Related Documents 1.1.1 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections apply to this Section. 1.2 Related

More information

3M Telecommunications. Solutions for Networks. 3M MPO solutions. High Density Networks. Technology built for business

3M Telecommunications. Solutions for Networks. 3M MPO solutions. High Density Networks. Technology built for business 3M Telecommunications Solutions for Networks 3M MPO solutions High Density Networks Technology built for business 2 3M Telecommunications Solutions for Networks 3M Telecommunications Solutions for Networks

More information

TP-5290 TRBO PANEL Emergency Display Panel

TP-5290 TRBO PANEL Emergency Display Panel TP-5290 TRBO PANEL Emergency Display Panel >>>> USER HANDBOOK ACMA Supplier Code N468 ISO9001 Certified Document G13214 Issue 1.4, 26/08/2013 FOR Motorola Solutions Australia Design Two Thousand Pty Ltd

More information

D131x-apbpmslc TECHNICAL DATA. Fiber Optic Patch Cords Simplex LSZH. Description. Features & Benefits

D131x-apbpmslc TECHNICAL DATA. Fiber Optic Patch Cords Simplex LSZH. Description. Features & Benefits Description DME PROLINK s patch cords are state-of-art product which are made through advanced polishing and assembly procedures. The multimode patch cords are offered with a Physical Contact (PC) polish

More information

LCS3 3 DIMENSIONS OF EXCELLENCE PERFORMANCE SCALABILITY EFFICIENCY DATA CENTRE LOCAL AREA NETWORK POWERED BY SPECIALISTS

LCS3 3 DIMENSIONS OF EXCELLENCE PERFORMANCE SCALABILITY EFFICIENCY DATA CENTRE LOCAL AREA NETWORK POWERED BY SPECIALISTS LCS3 3 DIMENSIONS OF EXCELLENCE PERFORMANCE SCALABILITY EFFICIENCY DATA CENTRE LOCAL AREA NETWORK POWERED BY SPECIALISTS Global strength built on local knowledge Legrand is the global specialist in electrical

More information

Telecommunciations Infrastructure Project September 20, A. Broadband radio frequency active and passive components

Telecommunciations Infrastructure Project September 20, A. Broadband radio frequency active and passive components PART 1 - GENERAL 1.1 SECTION INCLUDES A. Broadband radio frequency active and passive components B. Broadband optical active and passive components C. Coaxial cable and connectors D. Support and termination

More information

Project No. # Page 1

Project No. # Page 1 PART 1 - GENERAL This section of the has references, products, procedures, processes, and work descriptions/summaries that are common to many Washington State University Pullman (WSUP) campus telecommunications

More information

Field Testing and Troubleshooting of PON LAN Networks per IEC Jim Davis Regional Marketing Engineer Fluke Networks

Field Testing and Troubleshooting of PON LAN Networks per IEC Jim Davis Regional Marketing Engineer Fluke Networks Field Testing and Troubleshooting of PON LAN Networks per IEC 61280-4 Jim Davis Regional Marketing Engineer Fluke Networks Agenda Inspection and Cleaning APC vs UPC PON basics Wavelengths Architecture

More information

Start Up or Shut Down Hunting Function. Using the Receiver. If there is a short circuit in the cable, it will display as follows:

Start Up or Shut Down Hunting Function. Using the Receiver. If there is a short circuit in the cable, it will display as follows: If there is a short circuit in the cable, it will display as follows: Push key (No) to exit calibration function. Push key (Yes) to repeat measurement process. 11 Note: The calibration will recover the

More information

Datasheet: SimpliFiber Pro

Datasheet: SimpliFiber Pro Datasheet: SimpliFiber Pro Datasheet: SimpliFiber Pro SimpliFiber Pro makes testing simple Fluke Networks' SimpliFiber Pro Optical Power Meter incorporates new and innovative features to give technicians

More information

Instalaciones de fibra optica en entornos de centro de datos y campus para suportar 40, 100G y mas

Instalaciones de fibra optica en entornos de centro de datos y campus para suportar 40, 100G y mas Instalaciones de fibra optica en entornos de centro de datos y campus para suportar 40, 100G y mas Jim Davis Regional Marketing Engineer Fluke Networks Agenda Inspection and Cleaning Loss Budgets TIA (Cabling)

More information

Copper Cabling Troubleshooting Handbook

Copper Cabling Troubleshooting Handbook NETWORKSUPERVISION Copper Cabling Troubleshooting Handbook NETWORKSUPERVISION Table of Contents Introduction 2 Troubleshooting Basics 3 Link Models 4 The automated DTX Series diagnostics 5 Causes of Cabling

More information

IEEE 802.3af Power via MDI Standard Compliant Mid-Span Insertion Solution. Presented by PowerDsine: David Pincu -

IEEE 802.3af Power via MDI Standard Compliant Mid-Span Insertion Solution. Presented by PowerDsine: David Pincu - IEEE 802.3af Power via MDI Standard Compliant Mid-Span Insertion Solution Presented by PowerDsine: David Pincu - davidp@powerdsine.com Objectives! Investigate the Channel /Link options! Identify the requirements

More information

T-BERD /MTS 5800 Network Tester Fiber Channel Layer 2 Traffic

T-BERD /MTS 5800 Network Tester Fiber Channel Layer 2 Traffic Quick Card T-BERD /MTS 5800 Network Tester Fiber Channel Layer 2 Traffic This quick card outlines how to configure and run a Fiber Channel Layer 2 Traffic Test with a recommended test suite of Throughput,

More information

TB806AUX Class E A / Cat.6A UTP Keystone Jack (Auto press-fit)

TB806AUX Class E A / Cat.6A UTP Keystone Jack (Auto press-fit) TB806AUX / Cat.6A UTP Keystone Jack (Auto press-fit) Cable holder with Strain Relief (SR) function: secure the cable with cable tie, and not wiggle to affect the termination and transmission. Cap: easy

More information

Preparing a home for TransACT fibre-to-the-premise (FTTP) services

Preparing a home for TransACT fibre-to-the-premise (FTTP) services Preparing a home for TransACT fibre-to-the-premise (FTTP) services A guide for builders, telecommunications cablers and home owners transact.com.au For more information call TransACT s FTTP Sales Manager,

More information

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School BILOXI PUBLIC SCHOOL DISTRICT Biloxi Junior High School Request for Proposals E-Rate 2014-2015 - Internal Connections Submit Proposals To: Purchasing Department Attn: Traci Barnett 160 St. Peter Street

More information

STRUCTURED CABLING SYSTEMS (SCS)

STRUCTURED CABLING SYSTEMS (SCS) STRUCTURED CABLING SYSTEMS (SCS) ModSecur - Structured Cabling Systems (SCS) A Structured Cabling System (SCS) is the backbone of any building, campus or site communication infrastructure. The sharp growth

More information

CASS COUNTY, MICHIGAN CASSOPOLIS, MI REQUEST FOR PROPOSAL SPECIFICATIONS

CASS COUNTY, MICHIGAN CASSOPOLIS, MI REQUEST FOR PROPOSAL SPECIFICATIONS CASS COUNTY, MICHIGAN CASSOPOLIS, MI REQUEST FOR PROPOSAL SPECIFICATIONS Cass County, Michigan invites qualified vendors to submit proposals for the purchase, installation, and programming of a centralized

More information

MT Connect Pre-Terminated Fibre Cabling Systems

MT Connect Pre-Terminated Fibre Cabling Systems MT Connect Pre-Terminated Fibre Cabling Systems fibreplus A trusted voice in a world of confusion Brand-Rex has developed the enviable position of being Europe s premier, home based provider of best in

More information

Arista 40G Cabling and Transceivers: Q&A

Arista 40G Cabling and Transceivers: Q&A Arista 40G Cabling and Transceivers: Q&A 40G Cabling Technical Q&A Document 40Gigabit Cables and Transceivers Q. What 40G cables and transceivers are available from Arista? A. Arista supports a full range

More information

STRUCTURED CABLE SYSTEM (SCS)

STRUCTURED CABLE SYSTEM (SCS) PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

ETSI ES V1.1.1 ( )

ETSI ES V1.1.1 ( ) ES 202 319 V1.1.1 (2004-06) Standard Transmission and Multiplexing (TM); Passive optical components and cables; Optical fibre cables to be used for patchcord applications for single-mode optical fibre

More information

LCS 2 RJ 45 Cat. 6A HD panels and units

LCS 2 RJ 45 Cat. 6A HD panels and units 87045 LIMOGES Cedex Telephone: (+33) 05 55 06 87 87 - Fax: +33 (0)5 55 06 88 88 Page 0 335 85/86 1. General characteristics....1 2. Presentation...1 3. Positioning...1 4. Technical characteristics...1

More information

LANmark PCB patch panel, 1HU INSTALLATION GUIDE. LANmark PCB patch panel, 1 HU

LANmark PCB patch panel, 1HU INSTALLATION GUIDE. LANmark PCB patch panel, 1 HU LANmark PCB patch panel, 1HU INSTALLATION GUIDE LANmark PCB patch panel, 1 HU Document information Document reference Release September 2001 Published by Contact address BRO-009 LANmark PP 1HU 0701 Nexans

More information

Structured Cabling Introduction & Installation Guide

Structured Cabling Introduction & Installation Guide Structured Cabling Introduction & Installation Guide Structured Cabling Overview General Structure - Cat5e/Cat6 Cabling The structure illustrated has the following key points: Face plates present outlet

More information

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1. PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

About Nexans 3. About Berk-Tek 4. Hyper Plus 5e Cat 5e UTP 5. HyperPlus 5e Plenum 6. Hyper Plus 5e Riser 10. HyperPlus 5e Patch 14

About Nexans 3. About Berk-Tek 4. Hyper Plus 5e Cat 5e UTP 5. HyperPlus 5e Plenum 6. Hyper Plus 5e Riser 10. HyperPlus 5e Patch 14 Table of contents About Nexans 3 About Berk-Tek 4 Hyper Plus 5e Cat 5e UTP 5 HyperPlus 5e Plenum 6 Hyper Plus 5e Riser 10 HyperPlus 5e Patch 14 HyperPlus 5e OSP 18 22 7/10/07 - http://www.berktek.com Page

More information

Platinum Tools Inc. All rights reserved. 5/12 Voice, Data, Video + Length GENERAL SPECIFICATIONS WARNINGS

Platinum Tools Inc. All rights reserved. 5/12 Voice, Data, Video + Length GENERAL SPECIFICATIONS WARNINGS Voice, Data, Video + Length Instruction Sheet: P/N T9 GENERAL SPECIFICATIONS The Platinum Tools, VDV MapMaster.0 is a portable voice-data-video cable tester with length measurement. It tests and troubleshoots

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors including patch panels. 3. Cabling identification

More information

Fiber Optic Testing. The FOA Reference for Fiber Optics Fiber Optic Testing. Rev. 1/31/17 Page 1 of 12

Fiber Optic Testing. The FOA Reference for Fiber Optics Fiber Optic Testing.   Rev. 1/31/17 Page 1 of 12 Fiber Optic Testing Testing is used to evaluate the performance of fiber optic components, cable plants and systems. As the components like fiber, connectors, splices, LED or laser sources, detectors and

More information

AES standard for audio connectors - Modified XLR-3 Connector for Digital Audio. Preview only

AES standard for audio connectors - Modified XLR-3 Connector for Digital Audio. Preview only Reaffirmed 2017 AES standard for audio connectors - Modified XLR-3 Connector for Digital Audio Published by Audio Engineering Society, Inc. Copyright 2011 by the Audio Engineering Society Abstract This

More information

LAN Network Tester LAN Network Tester

LAN Network Tester LAN Network Tester LAN Network Tester Model Item no. LAN Network Tester 157011 Version EN triax.com Safety and Disposal The LAN Network Tester operates off 6V DC only. Only use the internal, battery powered, 6V power supply

More information

TEST REPORT NO.: CRT-081 RENDERED TO: Hubbell Premise Wiring 14 Lord s Hill Road Stonington, CT

TEST REPORT NO.: CRT-081 RENDERED TO: Hubbell Premise Wiring 14 Lord s Hill Road Stonington, CT 3933 US ROUTE 11, CORTLAND, NEW YORK 1345, U.S.A. Phone Number: 1-8-345-3851 Fax Number: 67-758-3648 PROJECT NO.: 322866-311 DATE: February 19, 29 TEST REPORT NO.: 322866CRT-81 RENDERED TO: Hubbell Premise

More information

Viavi T-BERD 5800 CPRI Testing Guide with ALU BBU Emulation

Viavi T-BERD 5800 CPRI Testing Guide with ALU BBU Emulation Viavi T-BERD 5800 CPRI Testing Guide with ALU BBU Emulation Scope Version 4 January 2018 Firmware 26.0.0.6c1973b or Later REQUIRED! This document describes Common Public Radio Interface (CPRI) testing

More information

Class E A / Cat.6A Screened Coupler

Class E A / Cat.6A Screened Coupler Class E A / Cat.6A Screened Coupler Patented Qualified Class E A / Cat.6A (500MHz) of ANSI/TIA-568-C.2 IEC 60603-7-51 AMD 2,Class E A CENELEC EN 50173-1 Specification Specification: Qualified Screened

More information

PREMIUM 5e F/UTP PRODUCTS

PREMIUM 5e F/UTP PRODUCTS Siemon s end-to-end cabling system is guaranteed to provide transmission performance margins in excess of industry standards for category 5e parameters, while featuring excellent EMI resistance. has been

More information

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices Berk-Tek recommends installing a well-designed structured cabling channel per the TIA standards. This includes up to 100

More information

Monash University. Communications Cabling Manual. (Sites running legacy PABXs)

Monash University. Communications Cabling Manual. (Sites running legacy PABXs) Monash University Communications Cabling Manual (Sites running legacy PABXs) Communications & Networks Information Technology Services Monash University Monash Cabling Specifications (PABX sites)doc Page

More information

Magic Patch Patch Leads & Accessories

Magic Patch Patch Leads & Accessories Magic Patch Patch Leads & Accessories T: 01376 346600 F: 01376 346620 www.connectixcablingsystems.com Issue 1.1 Magic Patch Cabling Systems TM Magic Patch Connectix Cabling Sytems TM range of patch leads,

More information