B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines.
|
|
- Derek Robinson
- 5 years ago
- Views:
Transcription
1 PART 1 - GENERAL 1.1 SUMMARY A. This section includes: 1. Support Structures 2. Cable trays and ladder rack 3. Racks (including wire managers) 4. Cables (copper and optical fiber) 5. Jacks and faceplates 6. Terminations 7. Lightning protection 8. Termination hardware 9. Installation materials and method 1.2 QUALITY ASSURANCE AND STANDARDS A. All work, material or equipment shall comply with the codes, ordinances and regulations of the local government having jurisdiction, including the regulations of serving utilities and any participating government agencies having jurisdiction. B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines. C. All work shall comply with the California State University Telecommunication Information Planning Guidelines (TIP). D. Quality Assurance 1. Manufacturer s qualifications: All components shall be manufactured by an approved manufacturer. Specified system warranties are established between the cable manufacturer or installing contractor and the owner are not considered equal. 2. Installing contractor qualifications: Firms and their personnel must be regularly engaged in the installation of data networking cabling and equipment for systems of similar type and scope. The contractor must have a full service office able to respond to emergency callouts during the warranty period. The warranted system solutions for each manufacturer shall be proposed Category-6 certified warranties. The contractor must also provide complete installation of all wiring and devices or equipment. Subcontracts with electrical contractors or other warranted or nonwarranted contractors for supervised installation of any part of this system are not approved. All conduit and standard back boxes will be furnished and installed by the electrical contractor. Specialty boxes will be furnished by the equipment supplier and installed by the electrical contractor. 3. Equipment qualifications: It is the intent of these specifications that each bidder provides all hardware, components and installation services that are necessary to ensure a fully operational Category-6 wiring system proposed in the EIA/TIA Category-6 and the ISO Class E drafts. 4. Warranty: All components, installation, and Channel Performance Criteria shall be warranted by one of the approved manufacturers and shall be in compliance with the most current Category-6 standards. Warranty shall be to the customer for a minimum period of 25 years after Customer acceptance and sign-off of the completed system. The contractor shall provide documentation from one of the
2 1.3 SUBMITTALS approved manufacturers indicating their qualifications for installation of this system in compliance with the manufacturer s warranty requirements as a warranted contractor. A. Submit shop drawings for review including the following: 1. Racks (including wire managers) 2. Cable trays and ladder rack 3. Cables (copper and optical fiber) 4. Jacks and faceplates 5. Terminations 6. Lightning protection 7. Termination hardware 8. Installation materials and method B. In order to ensure project cohesion, a single point of contact is required to provide a TURNKEY solution. The work covered under this section of the specification consists of furnishing all labor, cabling, equipment; supplies; materials, and training. The Contractor will perform all operations necessary for the TURNKEY and fully completed installation in accordance with the specifications herein. As such, the successful Contractor must be factory trained on all aspects of system hardware. The successful Contractor shall be a California licensed C7 or C10 premise wiring contractor as defined in this specification. Subcontractors may not be utilized in the implementation of the plant wiring installation or certification process. C. The Design/Builder shall coordinate and design the most appropriate routing of all aboveceiling cable prior to bid. Where cables penetrate through walls a conduit sleeve shall be provided. Where cables pass through fire rated walls, the conduit sleeve shall be sealed to maintain the rating of the wall assembly. PART 2 - PRODUCTS 2.1 ALL TERMINATION EQUIPMENT, OUTLETS, FIBER OPTIC CABLE, UTP CABLE, AND REQUIRED HARDWARE SHALL BE AS MANUFACTURED BY THE APPROVED MANUFACTURER. PRODUCTS MAY ONLY BE USED TO COMPLY WITH WARRANTY GUIDELINES. 2.2 EQUIPMENT RACKS SHALL BE AS MANUFACTURED BY B-LINE, HOMACO OR CPI. RACKS OR OTHER COMPONENTS SPECIFICALLY CALLED FOR IN THE DRAWINGS SHALL BE PROVIDED AS SHOWN. 2.3 SUPPORT STRUCTURES A. As required by BICSI, and TIP,the engineer and building codes. 1. Includes but not limited to: conduit, supports, 2.4 MAIN DISTRIBUTION FRAME (MDF) A. The Building Distribution Frame shall be the central wiring and equipment location for the voice/data systems. The contractor shall include the following items at this location. B. Provide full perimeter 8 foot high by 3/ 4 inch thick, flame resistant plywood mounting backboard. Painted with fire resistant white paint or color to match
3 C. Fiber optic termination equipment rack (rack mounted), including all associated installation hardware. The equipment must have sufficient number of ports to connect all fibers in every cable terminated at this location. Provide 25% spare capacity for future wiring requirements. D. Category-6 Modular Patch panels (rack mounted) with RJ-45 style connectors, for terminating all twisted pair cable from each data outlet served from this location. Provide 48-port patch panels with jack inserts for all data station cabling. Provide 25% spare capacity for future wiring requirements. No more than (7) 48-port patch panels shall be installed in any rack. Panels will be center labeled. E. Provide Category type termination blocks for voice cabling. Mount termination blocks to plywood backboard. Identify cables with printed labels from template labels provided by the manufacturer. Termination blocks shall provide minimum 25% spare capacity. F. Fiber optic termination equipment (rack mounted), including all associated installation hardware for fiber optic connections. G. Provide a 19-inch equipment mounting rack or enclosure. Provide ladder rack bracing at top of rack back to wall and include seismic bolts to floor and wall. Each rack shall be furnished with the following accessories: 1. (1) grounding kit, connect grounding conductor to nearest ground buss bar. 2. Provide CPI CatRack full length vertical wire managers on each side of each rack section and horizontal wire managers between each patch panel and between electronics. The University Information Systems department shall supply quantity of switches to be installed. H. Additional items required for the BDF are as follows: 1. Provide (1) ground bus bar kit per closet or cabinet as detailed in the drawings. 2. Provide Category-6 patch panel patch cords, one for each data cable drop or port provided in the equipment racks. Verify with Customer all ports which will be activated. 3. Provide Category-6 Work Station patch cords, one for each data cable drop or port provided for on the drawings. 2.5 INTERMEDIATE DISTRIBUTION FRAME (IDF) A. The Intermediate Distribution Frame shall be a secondary wiring and equipment location for the data networking system. The contractor shall include the following items at this location. B. Provide full perimeter 8-0 high x ¾ thick, as detailed on drawings, flame resistant plywood mounting backboard. Painted with fire resistant white paint or color to match. C. Fiber optic termination equipment (rack mounted), including all associated installation hardware for fiber feed cables. The equipment must have sufficient number of ports to connect all fibers in every cable terminated at this location. D. Category-6 Modular Patch Panel (rack mounted) with RJ-45 style connectors, for terminating all twisted pair cable from each data outlet served from this location. Provide 48-port patch panels with jack inserts for all data station cabling. Provide 25% spare capacity for future wiring requirements. No more than (7) 48-port path panels shall be installed in any rack
4 E. Provide Category-6, 110-type termination blocks for voice cabling. Mount termination blocks to plywood backboard. Identify cables with printed labels from template labels provided by the manufacturer. Termination blocks shall provide minimum 25% spare capacity. F. Fiber optic termination equipment (rack mounted) type patch panel as detailed, including all associated installation hardware for fiber optic station outlets served from this location. Provide 25% spare capacity. This patch panel shall be physically isolated from the data networking fiber optic feed and station patch panels. The panel shall be for terminating station fiber cables only. G. Provide equipment mounting rack or enclosure as detailed in the drawings. Provide ladder rack bracing at top of rack back to wall and seismic bolting to the floor and wall. Rack shall be furnished with the following accessories: 1. (2) center weight equipment shelves for free standing equipment racks 2. (1) grounding kit, connect grounding conductor to nearest ground buss bar. 3. Provide CPI CatRack full length vertical wire managers on each side of each rack section and horizontal wire managers between each patch panel and between electronics. The University Information Systems department shall supply quantity of switches to be installed. H. Additional items at each IDF closet are as follows: 1. Provide Category-6 Patch Panel cords, one for each data cable drop or port provided in the equipment racks. 2. Provide Category-6 Work Station patch cords, one for each data cable drop or port provided for on the drawings. 3. Provide all other items as detailed on the drawings. 2.6 CAMPUS OUTDOOR FIBER OPTIC FEED CABLE A. Provide one continuous fiber optic cable routed from the Campus LAN/PBX in Building 37 to the Building Distribution Frame fiber patch panel. B. Fiber optic cable shall be rated for indoor applications. Construction shall consist of; all dielectric, stranded loose tube with central strength member, no more than twelve strands per tube, flame retardant PVC or PE jacket, water-blocking gel, and blank fillers as required. Central tube type fiber will not be considered equal. C. Fiber optic feeds shown as composite type may be run as separately jacketed cables. Cables shown as separate runs on the drawings may not be combined together. Contractor responsible for confirming all available conduits or pathways prior to opting for separate cables for multimode and single mode fibers. D. Cable shall contain one or all types of fibers listed below: 1. Multimode 62.5/125 micron strands, minimum Extended FDDI or Enhanced grade for dual mode operation at 850nm and 1300nm wave lengths. Minimum modal bandwidth testing at 200MHz and 500MHz respectively. Maximum attenuation at 850nm and 1300nm. Quantity of fibers as per detail drawings. 2. Single mode 8.3/125 micron strands, minimum High performance grade for dual mode operation at 1310nm and 1550nm wave lengths. Maximum attenuation at 1310nm and 1550nm. Quantity of fibers as per detail drawings
5 3. Refer to drawings for cable types required. Refer to acceptable cables section for additional information and approved manufacturers. E. Each fiber optic cable shall contain the quantity of strands of optical fibers as detailed in the drawings. A pull string shall be placed with all fiber cable at the time of installation. Outdoor rated fiber runs in excess of 150 feet shall be provided with a minimum 1/ 4 inch pull rope for future access. F. All fibers in a multi-fiber cable shall be fully operational within the required performance characteristics. If any individual fiber does not meet the minimum standards, the entire cable must be replaced, end to end, including connectors, without any additional expense to the University. All outdoor rated fiber shall be provided with Corning s Infinicor CL 1000 performance or CommScope s UltraFiber fiber optic glass. G. Acceptable Cables shall be: 1. Avaya 2. Pirelli 3. Corning 4. Commscope 2.7 INDOOR RISER FIBER OPTIC CABLE A. Provide one continuous fiber optic cable routed from the Main Distribution Frame fiber patch panel to each Intermediate Distribution Frame fiber patch panel. B. Fiber optic cable shall be rated for indoor applications. Construction shall consist of; all dielectric, tight buffer type 900um coating, Plenum rated jacket, and blank fillers as requested. Shall be OFNR or ONFP rated. C. Fiber optic feeds shown as composite type may be run as separately jacketed cables. Contractor responsible for confirming all available conduits or pathways prior to opting for separate cables for multimode and single mode fibers. D. Cable shall contain one or all types of fibers listed below: 1. Multimode 62.5/125 micron strands, minimum Extended FDDI or Enhanced grade for dual mode operation at 850nm and 1300nm wave lengths. Minimum modal bandwidth testing at 200MHz and 500MHz respectively. Maximum attenuation at 850nm and 1300nm. Quantity of fibers as per detail drawings. 2. Single mode 8.3/125 micron strands, minimum High Performance grade for dual mode operation at 1310nm and 1550nm wave lengths. Maximum attenuation at 1310nm and 1550nm. Quantity of fibers as per detail drawing. 3. Refer to drawings for cable types required. Refer to acceptable cables section for additional information and approved manufacturers. E. All indoor Plemum rated fiber shall be installed in riser rated innerduct, when not installed in conduit, a minimum of 1 in diameter. A pull string shall be placed with all fiber cable at the time of installation. Indoor rated fiber runs placed in conduit in excess of 150 feet shall be provided with a minimum 1/4 inch pull rope for future access. F. All fibers in a multi-fiber cable shall be fully operational within the required performance characteristics. If any individual fiber does not meet the minimum standards, the entire cable must be replaced, end to end, including connectors, without any additional expense to
6 the University. All indoor rated fiber shall be provided with Corning s Infinicor CL 1000 performance or CommScope s UltraFiber fiber optic glass. G. Acceptable cables shall be: 1. Avaya 2. Pirelli 3. Corning 4. Commscope H. Confirm requirements for outdoor cable fiber with riser drawings and site plans. Part number for composite style cable will vary greatly. Confirm part numbers with manufacturer. 2.8 STATION FIBER OPTIC CABLE A. Provide one continuous fiber optic cable from the Main Distribution Frame or Intermediate Distribution Frame fiber patch panel to the data or local origination outlet in each classroom. B. Multimode fiber optic cables shall contain 62.5/125 micron strands, minimum extended FDDI or Enhanced grade, for dual mode operations at 850nm and 1300nm wave lengths. C. Each cable shall have a minimum of four optical fibers in a round or oval construction cable. The fiber cable shall have an outer jacket of riser rated PVC. The fiber cable shall be OFNR rated for interior installation. D. All fibers in a multi-fiber cable shall be fully operational with the required performance characteristics. If any individual fiber does not meet minimum standards, the entire cable must be replaced, end to end, including connectors, without any additional expense to the University. E. Acceptable cables shall be: 1. Avaya 2. Pirelli 3. Corning 4. Commscope 2.9 DATA STATION CABLE A. Provide one Category-6, 4-pair, unshielded twisted pair (UTP) cable from the nearest MDF or IDF to each RJ-45 data outlet port indicated on the drawings. Data cable locations shall be identified with a different color jacket from the voice cables. B. Category-6 cables shall be copper wire, individually insulated and color coded. University shall determine color of data cables. C. The cables shall be UL or ETL rated and UL verified in compliance with proposed Category-6. D. Acceptable cables shall be: 1. Superior-Essex 2. Avaya 3. Commscope 4. Berktek 5. Leviton
7 2.10 MDF TO IDF VOICE FEED CABLES A. Provide multi-pair UTP category 3 cable from each IDF to the MDF as indicated on drawings. Cable must be 24 AWG, 22 AWG will not be approved as an acceptable equal. B. For voice feed cables, terminate all pairs on both ends of the cable on 110 type termination blocks. Follow standard voice color codes for termination. C. Ground and bond feed cables at one end of cable to aluminum shield with approved bullet bond type ground lug and #10 AWG green ground wire. Connect ground wire to closet ground bus bar. D. Acceptable manufacturers shall be: 1. Superior-Essex 2. Avaya 3. Commscope 4. Berktek 2.11 VOICE STATION CABLE A. Provide one Category-6, 4-pair unshielded twisted pair cable from the nearest MDF or IDF to each wall or desk telephone outlet port indicated on drawings. Dual outlets require two such cables. Voice cable locations shall be identified with a different color jacket from the data cables. Contractor will confirm voice requirements with customer contact prior to installation of cable. University shall determine color of voice cable jacket cables. B. Category-6 cables shall be copper wire, individually insulated and color coded. All IDF copper voice feed cables shall be riser rated. C. The cables shall be UL or ETL rated and UL verified in compliance with proposed Category- 6 standards. D. Acceptable cables shall be: 1. Superior-Essex 2. Avaya 3. Commscope 4. Berktek 5. Leviton 2.12 VOICE AND DATA OUTLETS A. Unshielded twisted pair data outlets shall be an RJ-45 Enhanced performance type 8- position/8 conductor modulator jacks, and shall comply with Category-6 performance requirements for data outlets. Voice outlets shall comply with Category-6 performance requirements. Outlets shall be provided as single port or multiple ports as required. All outlets shall be wired in an EIA/TIA 568B configuration. B. Fiber optic station outlets shall be SC Duplex type inserts and shall occupy the same faceplate as the data outlets. C. For single port data outlet or single port voice outlet locations, the faceplates shall have space for six (6) connections with one port fully operational for connection to all of the specified protocols. The remaining port shall be covered by a blank plate. This applies only to voice outlets intended for desk telephone connections
8 D. For triple port data outlet or any combination of voice and data totaling three ports, the faceplates shall have space for six (6) connections with three ports fully operational for connection to all of the specified protocols. The remaining ports shall be covered by a blank plate(s). This applies only to voice outlets intended for desk telephone connections. E. For single port voice outlet locations intended for wall telephone connections, a wall telephone type faceplate with attachment studs shall be provided. The wall telephone jack shall be 8-pin, RJ45 type and use IDC wire terminations only. Screw terminal type jacks will not be accepted as an alternative. F. All data outlet faceplates shall be (white) and shall have a unique sequential identification number applied to faceplate. Hand written labels are not permitted. Faceplates, with the exception of wall telephone outlets, shall include interchangeable colored icons or color coded port inserts. All color schemes shall be approved by the customer prior to installation. All faceplates shall allow for data jacks to be replaced without removing faceplate from wall. Contractor responsible for confirming faceplate color prior to installation. G. Acceptable jacks shall be: 1. Superior-Essex 2. Avaya 3. Leviton 4. Ortronics 2.13 EMERGENCY TELEPHONE INSTALLATION A. Provide one Category-6, 4-pair unshielded twisted pair cable from the nearest MDF or IDF to each Emergency Telephone location as indicated on drawings. Contractor will confirm voice requirements with customer contact prior to installation of cable. B. Category-6 cables shall be copper wire, individually insulated and color coded. C. The cables shall be UL or ETL rated and UL verified in compliance with Category-6 standards. D. Acceptable cables shall be: 1. Superior-Essex 2. Avaya 3. Commscope 4. Berktek 5. Leviton E. Emergency Telephones installed outside of the building shall be installed on a pole as indicated in the drawings. The telephone assembly and light assembly shall be surface mounted. Refer to manufacturer s recommended installation procedures for installation instructions. The data contractor shall furnish and install the pole assembly. The data contractor shall install the devices once the poles and service conduits are in place. F. Contractor shall confirm ring down assignments and programming requirements with CSUSM Campus Police. Emergency Telephone shall conform to existing campus requirements for height, visibility, and functionality
9 PART 3 - INSTALLATION 3.1 GENERAL A. Upon completion of 10% of the cabling installation, the contractor shall notify the Architect for an inspection of the project. The contractor shall give a minimum of 72 hours notification to the engineer for the inspection. The contractor will be given a written review of the findings, so if adjustments are required, the can be done before the project proceeds. B. Pull strings shall be provided with all cable runs including but not limited to; conduit stub ups, conduit sleeves, cable trays, open wiring routes, innerduct, and point-to-point conduits. Pull strings shall be free from cable bundles in open wiring routes. C. Velcro cable management straps are required on all Category-6 cable bundles, the last 20 feet or upon entry into equipment closet, a maximum of 12 apart. Cable bundles shall also be routed through cable management or D rings in the equipment closet. D. Velcro cable management straps are required on the rear of the equipment. Straps shall be a maximum of 12 apart. E. Every multimode and single mode fiber in every fiber optic cable must be terminated at both ends on a fiber patch panel in the IDF closet or on a faceplate in the classroom location. Termination shall be accomplished using Duplex SC type connectors with a long strain relief boot, except for fiber ran to station locations where a short boot shall be used. F. All SC connectors shall be of the same manufacture to ensure compatibility. Polarity of fiber strands must be observed at all times. 3.2 LABELING A. Each cable run shall be permanently labeled at each end with a unique sequential number which corresponds to a similar number provided for each data outlet and punch down point. A printed label shall be placed on the cable at the rear of the patch panel or termination block. A label will also be placed on each cable in the j-box behind the faceplate location. Hand written labels are not permitted. Where cable ID includes room number identification the contractor shall obtain written verification of actual final room numbers prior to beginning labeling (numbers on plans do not always match actual final room numbers). Cable puling cross reference lists will not be accepted with final documentation. B. Each patch panel port shall be identified with a unique sequential labeling scheme. Port identification labeling pattern shall be consistent throughout the project. The University Telecommunications Department must approve labeling scheme prior to implementation. C. All faceplates shall be identified with permanent printed labels. Labels must not be subject to removal by incidental contact. Contractor shall be responsible for replacing defective labeling for a period of one year from date of final sign-off of project. D. All fiber optic and UTP feed cables shall be identified with permanent, water resistant, printed labels. Labeling information shall include closest identifications, quantity of conductors (UTP) or strands (fiber) and house pair designations (UTP). E. Labeling will follow recommended EIA/TIA standards or as requested by the University. Contractor will confirm labeling pattern prior to final identification or testing. All test results will be identified by the final labeling scheme. University labeling guidelines are listed below:
10 1. Data jack labels in the communications room shall indicate the room number where the station jack is located. Data jack labels at the station location shall indicate the communications room number, patch panel letter, and D plus patch panel port number where the station cable is terminated. 2. Patch panels shall be lettered from top to bottom A, B, C, etc for rack 1. Patch panels shall be lettered from top to bottom H, I, J, etc for rack 2. this same lettering scheme shall continue until all patch panels are lettered. 3. Example for the data jack in room 346 connected to the 31st port on the second patch panel in the first rack in communications room 309 is: a. Patch panel label: 346 b. Station label: 309-B Voice jack labels in the communications room shall indicate the room number where the station jack is located. Voice jack labels at the station location shall indicate the communications room number, V plus sequential number from 000 to Example for the voice jack in room 346 connected in communications room 309, assuming it is the 38th cable terminated, is: a. Wallfield label: 346-V-038 b. Station label: 309-V-038 F. All fiber optic cables and/or innerduct shall be tagged with fiber optic warning tags in every manhole or pullbox. Fiber warning tags shall also be placed at each end of the cable in the termination closets in clear view. A minimum of (3) tags are required at each end. Fiber warning tags shall be placed on fiber optic cable and/or innerduct routed through open ceiling environments at increments no less than 15 feet apart. G. Where open wiring cables are run through the ceiling space (only permitted where specifically noted on the drawings), the wire shall be bundled together and supported above the ceiling. All cables must be fastened to the building structure via J hooks, or an approved Category-6 suspension system, and not directly in contact with any other system. Contractor shall submit suspension system to be used to the engineer prior to installation of cable. H. Where cables pass through a fire-resistant portion of the structure, conduit sleeves shall be provided to maintain the rating of the wall penetrated. Sealing of all penetrations with an approved fire barrier is required. Conduits and sleeves must remain accessible for future use. Permanent sealants may not be used to seal sleeves and conduits. I. Fiber optic cables connecting to equipment racks shall be installed with not less than 20 feet of slack cable between the rack and the terminal backboard. See drawings for fiber optic service loop requirements. Service loop shall be laid horizontally and attached to cable runway above each rack. J. Provide 6 inches of cable slack at computer data system outlets inside conduit box. K. In an accessible ceiling area, provide a 10 foot service loop above the data/voice outlet locations. Service loop must be tied up off of ceiling titles or ceiling surface. Neatly coil cable without exceeding minimum bend radius limitations. L. The minimum bending radius for all cables and the maximum pulling tension shall not exceed manufacturer s recommendations. M. Cables installed in manholes and pullboxes on terminal backboards shall be installed on wall mounted cable support racks
11 N. Provide a full 360 degree loop of cable around manhole and pullbox interiors. O. Cable pulling shall use a split mesh grip over the cable jacket. Connection directly to optical fibers and copper wire conductors shall not occur. P. When pulled through conduits, cable pulling lubricants shall be continuously applied to all cables and be specifically approved by the manufacturer. Q. Where cables are pulled through or pulled from a center of run, pull without splices or terminations, lead out the cables at all manholes, pullboxes, and conduits, taking care to feed them in again by hand for the next run. R. For each cable pull where a cable direction change is required, flexible feed-in tubes, pullout devices, multi-segmented sheaves, etc., shall be used to ensure proper cable pulling tensions and side wall pressures. Cables shall not be pulled directly around a short right angle bend. Any device or surface the cable comes in contact with when under pull-in tension shall have a minimum radius 50% greater than the final specified minimum installed cable bending radius. The maximum possible size radius sheaves and feed-in tubes, usable in the available working space, shall be provided in all situations, to ensure the minimum possible cable sidewall pulling pressure. Do not use devices with multi-segment roller type sheaves. S. Cable lengths over 250 feet shall be machine pulled, not hand pulled. Cables shall be pulled in a continuous, smooth operation without jerking or stop-start motion after initiation of pull. Maximum cable pulling speed shall be less than 50 feet per minute. Minimum pulling speed shall be greater than 15 feet per minute. T. When pulling cable through conduit, cables shall be pulled straight into or out of the raceway without bends at the raceway entrance or exit. Pull in cable from the end having the sharpest bend (i.e., bend shall be closest to the reel). Keep pulling tension to minimum by liberal use of lubricant, hand turning of reel, and slack feeding of cable into duct entrance. Employ not less than one man at reel and one at manhole or pullbox during this operation. Cables shall be pulled directly from cable reels. U. All cables shall be new and extend continuous from each MDF or IDF backboard or rack to all voice/data outlets or other equipment locations. V. Where cables are not installed in a conduit or other raceway system, they shall not be routed parallel with other line voltage equipment or wiring (120 volt and above) within 36 or within 12 of line voltage equipment or wiring where crossing. Where outdoor rated cables are routed exposed through ceilings for more than 50-0, install in EMT conduit system. W. The Contractor shall furnish to the University, a Microsoft Excel-based spreadsheet of the cable plant data for insertion in the Campus cable management software program. The spreadsheet shall be furnished by the University for completion by the Contractor. A sample of the spreadsheet format is provided below
12 Near End Backbone Data Media Far End Backbone Data Building Floor Comm Room *Patchpanel/ Connecting Block Identifier Starting Location on Connecting Block Cable Identifier Media Type (to include Total Pairs or Strands) Total Number of Pairs/Strands To Terminate Starting Pair/Strand Building Floor Comm Room Patchpanel/ Connecting Block Identifier Starting Location on Connecting Block CR01-04A trunk CWD-10A CR01-04B trunk CWD-10B FR06A MM R03B FR06A SM R03B CWD-06B trunk CWB-03B CWD-06C trunk CWB-03C CWB-04E Riser CWB-04E CWB-04F Riser CWB-04F 1 Columns A-D should match the id of the hardware Columns K-M should match the id of the hardware *110 Block Identifier Key 1st Identifier C=Copper F=Fiber 2nd Identifier W=Wall R=Rack 3rd Identifier A,B,C,D - which wall in room 01, 02 - which rack in room R01=first rack to left while facing A=first wall on right as you enter the door front of racks Column on wall (allow approx 4th Identifier 12"/column) Column in the rack 01 = first column to left as you face the wall 5th Identifier 110 block position 110 block position C=3rd physical block down *Patchpanel ID Key 1st Identifier: C=copper - F=fiber 2nd Identifier: rack number (R01 = first rack to left while facing front of racks)
13 Location Hardware Description Bldg Floor Room Identifier Purpose AMP 48 Port 2U RJ45 Patchpanel 568B R01D ATT 110AWI CWB-04C Horizontal Feed ATT 110AWI CWB-04E Feed from 1st Floor ATT 110AWI CWB-04A Feed from 1st Floor ATT 24 Port Fiber Panel R01B Fiber Riser ATT 110AWI CWB-03B Feed from MDF ATT 110AWI CWB-03C Feed from MDF ATT 110AWI CWB-04E Feed to 3rd Floor ATT 110AWI CWB-04F Feed to 3rd Floor ATT 24 Port Fiber Panel R01A ATT 110AWI CWD-06B Feed to BDF ATT 110AWI CWD-06C Feed to BDF ATT 110AWI CWD-10A Feed from CRA MDF ATT 110AWI CWD-10B Feed from CRA MDF ATT 72 Fiber Panel R03B Feed from CRA MDF ATT 110AWI R01F-04A Feed to 37 MDF ATT 110AWI R01F-04B Feed to 37 MDF ATT 72 Fiber Panel R06A Feed to 37 MDF
14 Patchpanel/Connecting Block Data Media Office Area Information Building Floor Comm Room *Patchpanel/110 block Space Identifier Location on PP or 110 Block Patchpanel Product Name Media Type Building Floor Room # of Office **Faceplate ID (location within room) ***Location on Faceplate Station Cable Identifier Faceplate Part Number CWB- 01C 38 ATT 110AWI-100 Cat A01 A V058 3 port wall CWB- 01C 26 ATT 110AWI-100 Cat B03 A V055 4 port wall C 21 AMP 48 Port Patchpanel 568B Cat A01 C D21 1 port wall C 22 AMP 48 Port Patchpanel 568B Cat X02 D D22 2 port beam CWB A 59 ATT 110AWI-100 Cat C01 A V015 3 port wall *110 Block Identifier Key 1st Identifier: C=copper - F=fiber 309-V015 2nd Idendifier: W=wall 3rd Identifier: A,B,C,D - which wall in room (A=1st wall on right as you enter door.) 4th Identifier: column on wall (01 = first column to left as you face the wall) 5th Identifier: 110 block position (C= 3rd block down in column) * Patch Panel Identifier Key 1st Identifier: location of patch panel on rack (A-G = rack 1: H-N = rack 2) ** Faceplate ID 1st Identifier: A-V = walls; X=beam; Y=Ceiling; Z=floor 2nd Identifier: = number of outlets on wall, floor, beam, etc (not to be confused with Cable ID) 309-C-D C-D
15 ***Location on Faceplate - Please see campus Network operations if faceplate different type than shown. A and B reserved for voice C and D reserved for Data E and F reserved for extra if needed END OF SECTION
REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus
REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus PART 1: GENERAL REQUIREMENTS A. Contractor Work 1. Provide and install (except as noted in this document), cable,
More informationUNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE
UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE Prepared in cooperation and approval from BICSI Building Industry Consulting Services International and
More informationSECTION COMMUNICATIONS HORIZONTAL CABLING
SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors including patch panels. 3. Cabling identification
More informationCalifornia Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.
PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated
More informationCoastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents
PART 1 - GENERAL 1.1 SUMMARY SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors. 3. Cabling system identification products. 1.2
More informationPre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017
Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM-2017-2 Date: 05/26/2017 Additional specification information for data communication to cameras and between Library
More informationBILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School
BILOXI PUBLIC SCHOOL DISTRICT Biloxi Junior High School Request for Proposals E-Rate 2014-2015 - Internal Connections Submit Proposals To: Purchasing Department Attn: Traci Barnett 160 St. Peter Street
More informationSTRUCTURED CABLE SYSTEM (SCS)
PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated
More informationSection Communications Optical Fiber Backbone Cabling
Part 1 1.1 Related Documents 1.1.1 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections apply to this Section. 1.2 Related
More informationSECTION FIBER OPTIC STATION CABLES
PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications shall include all labor necessary to perform and complete such construction, all materials and equipment incorporated
More informationA. All communications equipment rooms shall be installed in a neat and workmanlike manner.
SECTION 27 11 00 - COMMUNICATIONS EQUIPMENT ROOM FITTINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationMinimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE)
PART 1: GENERAL 1.01 Telecommunications Engineer Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) B. Registered Communications Distribution Designer
More informationTelecommunication Infrastructure Project September 20, 2002
PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Category rated UTP systems shall be provided and tested in accordance with the performance level established in Specification
More informationSPECIAL SPECIFICATION 8540 Telecommunication Cable
2004 Specifications CSJ 0914-00-307 & CSJ 0914-25-003 SPECIAL SPECIFICATION 8540 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing,
More informationSPECIAL SPECIFICATION 6559 Telecommunication Cable
2004 Specifications CSJ 0015-09-147, etc. SPECIAL SPECIFICATION 6559 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing, training,
More informationCABLING STANDARDS FOR
RFB for Wiring in the Outagamie County Courtrooms Attachment B September 1, 2016 CABLING STANDARDS FOR GENERAL The purpose of this document is to provide guidelines for all structured cable installations
More informationTender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab*
Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab* General Scope of Work: Supply and installation of Computer Laboratory setup in MIU Location of Installation:
More informationFollow The Leader In Shielded Technology
1970s Vampire Tap 1990s Shielded Modular Jack 190s 4 Position Data Connector Follow The Leader In Shielded Technology The new AMP-TWIST Jack is our latest shielded product evolution. It can be terminated
More informationTelecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5
Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5 1.0 INTRODUCTION Customer to define background and introduction to the project based on
More informationPublic Works Division Lighting District Fiber Optic Specifications April 2009
Public Works Division Lighting District Fiber Optic Specifications April 2009 7000 Florida Street Punta Gorda, Florida 33950 Tele: 941.575.3600 Fax : 941.637.9265 www.charlottecountyfl.com/publicworks
More informationAPPENDIX A Verify All Part Numbers (Partial List of Approved Products)
SECTION 16651 APPENDIX A Verify All Part Numbers (Partial List of Approved Products) SYSTIMAX SCS: OVER-VOLTAGE PROTECTION 1. Over-voltage Protection Device, 100-Pair with Enclosure, Product 489ACAI-100,
More informationSECTION TESTING, IDENTIFICATION AND ADMINISTRATION
PART 1 - GENERAL 1.1 SUMMARY SCOPE SECTION 25170 TESTING, IDENTIFICATION AND ADMINISTRATION 1. This section includes the minimum requirements for the testing, certification administration and identification
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD, applicable TC -, and CEHNC Design Guide 0-- (Standard is single UTOs and Double UTOs) B. Roads-Service, Lanes Adequate access is provided to the and AAR D. Testing Results-provided
More informationSECTION COMMUNICATIONS HORIZONTAL CABLING
SECTION 27 15 00 COMMUNICATIONS HORIZONTAL CABLING PART 1 GENERAL 1.1 RELATED DOCUMENTS AND SECTIONS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationTelecommunciations Infrastructure Project September 20, A. Broadband radio frequency active and passive components
PART 1 - GENERAL 1.1 SECTION INCLUDES A. Broadband radio frequency active and passive components B. Broadband optical active and passive components C. Coaxial cable and connectors D. Support and termination
More informationSECTION 7 -- CROSS-CONNECT SYSTEMS
DETAIL ENGINEERING REQUIREMENTS AT&T March, 2016 Section 7, ATT-TP-76400 Revised NA SECTION 7 -- CROSS-CONNECT SYSTEMS CONTENTS PAGE 1. GENERAL... 7-2 1.1. Introduction... 7-2 1.2. Cable Holes... 7-2 1.3.
More informationSECTION COMMUNICATIONS HORIZONTAL CABLING
(NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 - GENERAL 1.1 SECTION
More informationLiberty Mutual Structured Cabling Specification Bid and Build Structured Cabling Technical Specification for:
Bid and Build Structured Cabling Technical Specification for: Horizontal & Backbone Requirements Page 1 of 30 PUBLICATION RECORD Document Version Publication Date Primary Author Description Revision 1.0
More informationCHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT
CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT Purchasing and Warehouse Services Department October 1, 2007 Addendum No. 1 INVITATION FOR BID No. 08-09 Temporary Faculty Offices, Chabot College All Prospective
More informationSPECIAL SPECIFICATION 6191 Fiber Optic Cable
2004 Specifications CSJ 0014-02-014, etc SPECIAL SPECIFICATION 6191 Fiber Optic Cable 1. Description. Furnish, install, splice, field terminate, and test the fiber optic cables. 2. Materials. A. General
More informationSECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.
SECTION 33 71 49.23 MEDIUM VOLTAGE CABLE INSTALLATION PART 1 GENERAL 1.1 SCOPE A. Work included in this Section: Medium Voltage Cable (4 kv and 12 kv) Installation and Termination. Removal and return of
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationCOMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationDelaware County Community College Project # Marple Campus Renovation - Phase % Construction Documents November 23, 2011
SECTION 271323 - COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 - GENERAL 1.1 DESCRIPTION A. This section provides the specifications for the work related to the optical fiber system in the project.
More informationInformation Technology Services DESIGN AND INSTALLATION STANDARDS
Requirements and Guidelines for: New Construction, Renovations, Upgrades, and Retrofits. Revised: June 5, 2015 VIU ITS Network Services 2 TABLE OF CONTENTS 0 GENERAL... 5 1 FIBER OPTIC CABLING... 5 1.1
More informationMichigan State University Construction Standards EXTERIOR FIBER OPTIC CABLE SYSTEM PAGE
PAGE 271800-1 SECTION 271800 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSPECIAL SPECIFICATION 2284 Fiber Optic Cable (Self-Supporting)
2004 Specifications CSJ 0086-14-046 SPECIAL SPECIFICATION 2284 Fiber Optic Cable (Self-Supporting) 1. Description. Furnish, install, splice, field terminate, and test the fiber optic cables. 2. Materials.
More informationCable Installation Tips
Cable Installation Tips Campus Network Design & Operations Workshop These materials are licensed under the Creative Commons Attribution-NonCommercial 4.0 International license (http://creativecommons.org/licenses/by-nc/4.0/)
More informationSpecial Specification 6242 Special Fiber Optic Cable
Special Specification 6242 Special Fiber Optic Cable 1. DESCRIPTION 2. MATERIALS The contractor to install, splice, field terminate, test and document all fiber systems. A. General Requirements. Provide
More informationSTANDARDS SECTION (16651) COMMUNICATIONS DISTRIBUTION SYSTEM (Rev. Jun 2011)
PART 1 GENERAL 1.00 DESCRIPTION STANDARDS SECTION 271000 (16651) COMMUNICATIONS DISTRIBUTION SYSTEM (Rev. Jun 2011) A. Furnish and install a complete Communications (Telephone/Data) Distribution System
More informationDESIGN!!GUIDELINES!!!!!
DESIGNGUIDELINES 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 1. Testing General 1.1. For acceptance, 100% of the media
More informationDivision 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING
Revision 05/01/2017 Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING PART 1 GENERAL 1.1 SECTION INCLUDES A. Voice, Data, and Fiber Cable Product materials B. Voice, Data, and Fiber Cable Execution
More informationCable Installation Tips
Cable Installation Tips Campus Network Design & Operations Workshop These materials are licensed under the Creative Commons Attribution-NonCommercial 4.0 International license (http://creativecommons.org/licenses/by-nc/4.0/)
More informationNYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017
SECTION 27 15 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationMfgr. Berk Tek ea , Berk Tek ea , Berk Tek ea. Berk Tek ea ,350.
8. Pricing Schedule The undersigned has rd and understands all conditions and terms of RFP 336-, is authorized to submit this proposal on behalf of the company, and hereby offers to perform the services
More informationRequest for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points
Request for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points Due Date: Allowable Contract Date from Posted 470 The Palo Verde Elementary School District is requesting
More informationUNM IT/Telecommunications Guide Specification Labeling 11/07/
Labeling 1 PART 1: GENERAL 1.01 SCOPE OF WORK A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing
More informationSPECIAL SPECIFICATION 1438 Fiber Optic Cable (Single mode and Multimode)
1993 Specifications CSJ 0018-05-062, etc. SPECIAL SPECIFICATION 1438 Fiber Optic Cable (Single mode and Multimode) 1. Description. This Item shall govern for the furnishing and installation of fiber optic
More informationPREMIUM 5e F/UTP PRODUCTS
Siemon s end-to-end cabling system is guaranteed to provide transmission performance margins in excess of industry standards for category 5e parameters, while featuring excellent EMI resistance. has been
More informationRequest for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS
VOFP Cabling RFP 1 Request for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS For The Village of Franklin Park 2014 VOFP Cabling RFP 2 TABLE OF CONTENTS I. PROJECT DESCRIPTION
More informationSTATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE AND COMPONENTS. July 19, 2013
804.01 Description 804.02 General 804.03 Materials 804.04 Warranties 804.05 Fiber Optic Cable 804.06 Fan-Out Kit 804.07 Drop Cable 804.08 Fiber Optic Patch Cord 804.09 Fiber Termination Panel 804.10 Fusion
More informationHCS - HES Cabling Systems
HCS - HES Cabling Systems Installation Manual for HCS High-Capacity Fiber-Optic Rack-Mount Cabinets Be sure to read and completely understand this procedure before applying product. Be sure to select the
More informationSECTION CONTROL, COMMUNICATION AND SIGNAL WIRING
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 27 10 00 CONTROL, COMMUNICATION AND SIGNAL WIRING SPEC WRITER NOTES: 1. Edit this specification section between // //, to fit project, or delete if not applicable.
More informationSECTION TESTING OF COPPER CABLES
SECTION 27 08 13 TESTING OF COPPER CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction,
More information1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Fiber Optic Cable System
1993 Specifications CSJ 0008-12-071 SPECIAL SPECIFICATION ITEM 6540 Fiber Optic Cable System 1.0 Description. This item shall govern for the furnishing and installation of fiber optic cables in designated
More informationTHE OHIO STATE UNIVERSITY COMMUNICATIONS WIRING STANDARD
THE OHIO STATE UNIVERSITY COMMUNICATIONS WIRING STANDARD The objective of the standard wiring plan for the University is to provide an acceptable outlet for any communication device that requires connection
More informationTechnical Specifications Florida Gulf Coast University
Technical Specifications Florida Gulf Coast University 9/19/2018 Page 1 of 21 Approved Vendors (alphabetical order) Aztek (CIP) Certified Installer Plus Mr. Scott Coyne 4730 Enterprise Avenue Suite #308
More informationDescription: Pair Color Code Chart: Pair Color Chart 1 Brown White Brown 2 Orange White Orange 3 Green White Green 4 Blue White Blue.
Description: OZLINX CAT5e cable has a guaranteed performance; exceeds the Category 5e performance requirements and provides positive PSACR up to 155MHz for bandwidth requirement in the future. Product
More informationACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO
SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationMIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project
1.1.0 GENERAL The purpose of this specification is to establish a requirement for the installation of a voice, video and data cable network. The cable (copper), wire, hardware, equipment racks, jumpers,
More informationCATEGORY 6 CABLING SOLUTIONS
With over 20 years experience and know-how on communicating products design & developing, Premium Line has built maturity systems both in high tech develop and research center & complete structural quality
More informationRequest for Proposal (RFP)
Request for Proposal (RFP) Data Network for OCMS 017 Inquiries and requests regarding this RFP should be directed to: Michael Hale Technology Director Oconee County Schools PO Box 16 5-A School Street
More informationSECTION TELECOMMUNICATIONS FIBER OPTIC DISTRIBUTION
SECTION 16747 TELECOMMUNICATIONS FIBER OPTIC DISTRIBUTION PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: Requirements for installation and modification of fiber optic distribution systems by Tenants,
More informationA. The requirements of Section govern the work specified in this section.
SECTION 27 05 10 - COMMUNITY ANTENNA TELEVISION CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The requirements of Section 27 01 00 govern the work specified in this section. B. Refer to the following
More informationSTRUCTURED CABLING SYSTEMS (SCS)
STRUCTURED CABLING SYSTEMS (SCS) ModSecur - Structured Cabling Systems (SCS) A Structured Cabling System (SCS) is the backbone of any building, campus or site communication infrastructure. The sharp growth
More informationRequest for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling
Request for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling Due Date: Allowable Contract Date from Posted 470 The Clarkdale- Jerome School District is requesting
More informationSECTION O FIBER OPTICS
SECTION O FIBER OPTICS CONTENTS PAGE 1. GENERAL...O-2 1.1 Introduction...O-2 1.2 Definitions...O-2 1.3 Requirements...O-2 2. RUNNING, SECURING AND FIRESTOPPING FIBER OPTIC CABLE...O-3 2.1 Running Fiber
More informationADDENDUM NO. 2 This addendum consists of 8 pages. Kenai Peninsula Borough Purchasing & Contracting
KENAI PENINSULA BOROUGH Purchasing and Contracting 144 North Binkley Street Soldotna, Alaska 99669-7520 Toll-free within the Borough: 1-800-478-4441, Ext. 2260 PHONE: (907) 714-2260 FAX: (907) 714-2373
More informationSOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED.
Beaverton School District Capital Program Purchasing 16550 SW Merlo Road, Beaverton, OR 97006 Phone: 503-591-4539 SOLICITATION ADDENDUM NO. 1 ITB 15-0012 THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION
More informationMediacom Upgrade/Splicing Procedures (based on original document from Corporate dated 4/16/98)
Mediacom Upgrade/Splicing Procedures (based on original document from Corporate dated 4/16/98) 1. Splicing specifications are provided by Mediacom, but due to resplice conditions, many locations become
More informationFREEDM Loose Tube Interlocking Armored Cables
features and benefits Flexible, interlocking armor design Gel-free waterblocking technology Color-coded tubes and fibers UV-resistant, flameretardant jacket UV-Resistant Flame-Retardant Outer Jacket InterlockingArmor
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION TELECOMMUNICATIONS SYSTEM INFRASTRUCTURE
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. The intent of this standard is to describe the requirements of the telecommunications system infrastructure. Part of this system is the responsibility
More informationOASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices
OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices Berk-Tek recommends installing a well-designed structured cabling channel per the TIA standards. This includes up to 100
More informationSECTION COMMUNICATIONS STRUCTURED CABLING
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 27 15 00 COMMUNICATIONS STRUCTURED CABLING SPEC WRITER NOTES: 1. Edit this specification section between // //, to fit project, or delete if not applicable. 2.
More informationCATEGORY 5e CABLING SOLUTIONS
With the high speed data transmission requirement in LAN, 1998 IEEE ratified standard 802.3z defined protocol 1000BASE-T over Category 5e and higher level Ethernet cabling system. After that, with the
More informationProject No. # Page 1
PART 1 - GENERAL This section of the has references, products, procedures, processes, and work descriptions/summaries that are common to many Washington State University Pullman (WSUP) campus telecommunications
More informationBest Friends General Trading FZE
Welcome to Best Friends General Trading FZE Tel. +97 1 50-5426 202, Fax. +971 6 7407428, info@bestfgt.com, besttrd@eim.ae Infrastructure Product Guide Best fgt is UAE based company, operational for last
More informationMulti-Media Installation Guide
Multi-Media Installation Guide Coaxial Page 2 Data Plug Page 7 Data Jack Page 10 Telephone Page 13 Splicing Page 15 Cable Types Cable Types Two basic types of cable are used in multimedia installations.
More informationData Network Wiring Standard. Part 1: General Section Includes Publications and Standards
Part 1: General 1.01 Section Includes A. Fiber Optic Cable B. Fiber Optic Distribution Cabinets C. Interbuilding Fiber Optic Cabling/Patch Cords D. Fiber Optic Connectors E. Interbuilding Distribution
More informationDATA/TELECOMMUNICATIONS REQUEST FOR PRICING
Category 6A 10Gig DATA/TELECOMMUNICATIONS REQUEST FOR PRICING TABLE OF CONTENTS 1. GENERAL 3 1.1. Work Included... 3 1.2. Scope of Work... 3 1.3. Regulatory References... 4 1.4. Quality Assurance... 4
More informationCATEGORY 6A CABLING SOLUTIONS
10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Need of 10 Gigabit Service Application as
More informationNC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM
NC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM Content 1. General 5 2. The products of NC-1000 system 6 3. Mounting of the frame 8 4. Earthing of the frame 8 NC-1000 FIBRE OPTIC
More informationPreferred ordering guide for NETCONNECT
Preferred ordering guide for NETCONNECT MEA Region Contents Copper solutions Category 6A products 3 Category 6A and Category 7 shielded copper cables 3 Category 6A modular shielded panels 3 Category 6A
More informationCompact Module. Category 6 FTP Cabling System
Compact Module Shielded design for improved EMI performance Suitable for Gigabit Ethernet applications and beyond Ultra-slimline design Colour coded for quick and accurate termination Interchangeable with
More informationOptical Distribution Box 300 Installation Guide. Version : R0.0
Optical Distribution Box 300 Installation Guide Document No. : OD16-546-L-01 Version : R0.0 Date: 21-Mar-2018 IMPORTANT INSTRUCTIONS When using fiber optic equipment, basic precautions should always be
More informationCATEGORY 6A CABLING SOLUTIONS
10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Premium Line Category 6A Cabling Solutions
More informationWJHW, Inc. 6 April 2016 Texas Tech University Issue for CD Set Sports Performance Complex Lubbock, Texas
SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide materials, labor, and methods for telecommunications grounding and bonding system in accordance with
More informationIT/Telecommunications Technical and Wiring Standards. Phillips Exeter Academy
IT/Telecommunications Technical and Wiring Standards FOR Phillips Exeter Academy Exeter, NH No deviations will be permitted from these specifications without the express written consent of Phillips Exeter
More informationProject No. # Page 1
PART 1 - GENERAL This section of the has references, products, procedures, processes, and work descriptions/summaries that are common to many Washington State University Pullman (WSUP) campus telecommunications
More informationB. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.
SECTION 271300 - COMMUNICATIONS BACKBONE CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationCambria County Association for the Blind and Handicapped 175 Industrial Park Road Ebensburg, PA Prepared for: Prepared by:
Cable Management in Solar PV Arrays: A Review of Requirements in the National Electrical Code and how CAB Cable Rings and Saddles Meet These Requirements Prepared for: Cambria County Association for the
More informationMIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project
1.1.0 GENERAL MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project The purpose of this specification is to establish a requirement for the installation of
More information10G 6A UTP SYSTEM PRODUCTS 10G 6A UTP
0G A is Siemon s advanced, end-to-end augmented category UTP structured cabling system, designed to meet or exceed all 0GBASE-T performance requirements, including alien crosstalk. Siemon s full channel
More informationThe University of Texas at Austin September 30, 2011
SECTION 27 08 20 COPPER TESTING PART 1 - GENERAL 1.1 SUMMARY A. Test measurements shall be taken for all balanced-twisted pair cabling, including horizontal and backbone copper cables and wall-to-rack
More informationThe FiberMark1 offers an ideal solution for
Large Capacity Fiber Optic Splice Enclosure The Ideal Solution For Large Capacity Voice, Data, and Video Splicing Requirements. The FiberMark1 offers an ideal solution for larger fiber capacity voice,
More informationCABLE MANAGEMENT PRODUCTS Cable Managers & Accessories
CABLE MANAGEMENT PRODUCTS Cable Managers & Accessories Evolution Cable Management Page 5-3 Velocity Cable Management Page 5-8 Velocity Standard Pack Page 5-12 Vertical Cable Management Page 5-13 Global
More informationInformation & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008
Information & Communications Technology Group Standards June 2008 Appendix F UTP cabling Version 1.1 Appendix F UTP cabling 1. Introduction This Section details the required standards for Unshielded Twisted
More informationBrown University. Communications Standard Parts List
CIS - NTG Brown University Communications Standard Parts List All data installations must receive the 25-year Mission Critical Warrantee from Hubbell Premise Wiring. All fiber installations must receive
More information3M Fiber Optic Wall Mount Enclosure 8430 Series
3M Fiber Optic Wall Mount Enclosure 8430 Series Installation Instructions January 2014 3 78-0013-9429-1-A Table of Contents 1.0 Description...3 2.0 Parts...4 3.0 Assembly...4 4.0 Mounting the Enclosure...6
More informationSECTION TELECOMMUNICATIONS INFRASTRUCTURE
PART 1 - GENERAL 1.1 SUMMARY A. The telecommunications (telecom) infrastructure provides the basic infrastructure for the transport of voice and data signals throughout the facility. This is often regarded
More information