Installation instructions Roxtec CF 16 EMC and Roxtec CF 16 O EMC
|
|
- Verity Franklin
- 5 years ago
- Views:
Transcription
1 Safety information Roxtec recommends that all installations are performed without facility operation. Follow national regulations and installation codes. ny action affecting the routed service should be performed according to manufacturer recommendations. Installation instructions Roxtec CF 6 EMC and Roxtec CF 6 O EMC CF 6 EMC CF 6 O EMC Openable frame perture dimensions and conductive area Measurements in (mm) Ø. (x) Ø7 (x) T Maximum wall thickness is T: mm. : This area shall always be conductive and connected to ground. Tools needed Phillips screwdriver (not included) Torx key (included) Cable stripper tool. Recommended by the cable manufacturer (not included)
2 Components CF frame 6 7. Back plate. EMC plate. Cross recess screws. Torx screws. Cabinet/wall 6. Compression rubber 7. Front plate Roxtec Lubricant Roxtec CM ES module Roxtec CM PE module B B C C D B D B F G E F E E F : Environmental side B: Interior side C: Cable jacket D: Cable screen E: Plastic film F: Conductive tape G: Vertical ES screen : Environmental side B: Interior side C: Cable jacket D: Cable screen E: Plastic film F: Conductive tape Roxtec CM ES modules For cable/pipe outer diameter Module size Minimum Maximum CM w0/0 ES 0 0 CM 0w0/0 ES 0 0 CM w0 ES. 0. CM 0w0 ES. 6. CM 0w0 ES 0 CM 0 0- ES 9.. Roxtec CM PE modules For cable/pipe outer diameter Module size Minimum Maximum CM w0/0 PE 0 0 CM 0w0/0 PE 0 0 CM w0 PE. 0. CM 0w0 PE. 6. CM 0w0 PE 0 CM 0 0- PE 9.. Unused modules can be used as spare capacity. Center cores must always be present in unused modules.
3 Installation a b Clean the area in order to achieve good electrical conductivity between the counter frame and the inside of the structure. Route the cable through the compression rubber and front plate. Install the back plate and the EMC plate inside the cabinet. For openable frames, install the back plate and the EMC plate around the cables inside the cabinet. Mark where the outer jacket is to be removed to fit the conductive tape position (min mm). Cut and remove the outer jacket and any plastic foil to expose the screen/armor of the cable. Terminate the screen/armor according to the cable requirement. Suggestions for cable preparations are available on Correct placement of cable in EMC module.
4 Installation of Roxtec CM ES modules Remove the protection paper from the modules and fold back the tape. Note: Protection paper must be removed on spares also. dapt layers to outer jacket. dapt layers to cable screen. dapt vertical ES screen to cable screen chieve a gap of mm () between the module halves. If not, repeat step -. The halves may not differ by more than one layer. Ensure good electrical conductivity between the cable screen and module tape. Fold the adhesive conductive tape tightly inside the module half from one side along the inner layers. Lift the plastic film from the folded side. Fold the tape on the other side tightly inside the module half. There must be no air-pockets. 9 0 Fold the plastic film back inside the module half. Lubricate all modules sparsely with Roxtec Lubricant on inside and outside rubber surfaces only. Do not lubricate the plastic film. For spare modules, lubricate all inside sealing surfaces with Roxtec Lubricant. Do not lubricate the film. Remove the plastic film. Keep the tape clean. Note: Plastic film must be removed on spares also.
5 6 Insert the modules from the outside of the cabinet with the conductive tape inwards. Cable shall be installed so that eventual extra exposed cable screen runs into the cabinet. For openable frames, fit the compression gasket around the cables by using the pre-opened long side. Thoroughly lubricate the compression rubber on both outside and inside surfaces with Roxtec Lubricant Position the compression rubber around the modules. Position the front plate on the compression rubber. Tighten the torx screws alternately in small steps. lways start with the short sides. Recommended torque 8-0 Nm. Disassembly and reinstallation of Roxtec CM ES modules Untighten the torx screws alternately. lways start with the short sides. Remove the front plate. Remove the compression rubber. Push out the modules needed from the back side. Clean the void. dapt the removed module to the new cable according to the CM ES instructions.
6 Installation of Roxtec CM PE modules Remove the protection paper from the modules and fold back the tape. dapt layers to outer jacket. dapt layers to cable screen. chieve a gap of mm () between the module halves. If not, repeat step -. The halves may not differ by more than one layer. Ensure good electrical conductivity between the cable screen and module tape Fold the adhesive tape tightly inside the module half from one side along the inner layers. Lift the plastic film from the folded side. Fold the tape on the other side tightly inside the module half. There must be no air-pockets. Fold the plastic film back inside the module half. 9 0 Lubricate all modules sparsely with Roxtec Lubricant on inside and outside rubber surfaces only. Do not lubricate the film. For spare modules, lubricate all inside sealing surfaces with Roxtec Lubricant. Do not lubricate the film. Remove the plastic film. Keep the tape clean. Note: Plastic must be removed on spares also. Insert the modules from the outside of the cabinet. 6 Cable shall be installed so that eventual extra exposed cable screen runs into the cabinet. For openable frames, fit the compression gasket around the cables by using the pre-opened long side. Thoroughly lubricate the compression rubber on both outside and inside surfaces with Roxtec Lubricant. Position the compression rubber around the modules.
7 7 8 Position the front plate on the compression rubber. Tighten the torx screws alternately in small steps. lways start with the short sides. Recommended torque 8-0 Nm. Disassembly and reinstallation of Roxtec CM PE modules Untighten the torx screws alternately. lways start with the short sides. Remove the front plate. Remove the compression rubber. Push out the modules needed from the back side. Clean the void. dapt the removed module to the new cable according to the CM PE instructions.
8 Note For optimum reliability, wait hours or longer after installation before exposing the cables/pipes to strain or pressure. n incorrectly adapted module shall be replaced (layers shall not be reused). Cables shall go straight through the frame. Permitted Roxtec modules: CM ES and CM PE. Minimum diameter of cables:. mm. Maximum diameter of cables:. mm. pprovals or certificates may include amendments or limitations related to this application. The latest version of this and related documents are found at roxtec.com. DISCLIMER The Roxtec cable entry sealing system ( the Roxtec system ) is a modularbased system of sealing products consisting of different components. Each and every one of the components is necessary for the best performance of the Roxtec system. The Roxtec system has been certified to resist a number of different hazards. ny such certification, and the ability of the Roxtec system to resist such hazards, is dependent on all components that are installed as a part of the Roxtec system. Thus, the certification is not valid and does not apply unless all components installed as part of the Roxtec system are manufactured by or under license from Roxtec ( authorized manufacturer ). Roxtec gives no performance guarantee with respect to the Roxtec system, unless (I) all components installed as part of the Roxtec system are manufactured by an authorized manufacturer and (II) the purchaser is in compliance with (a), and (b), below. (a) During storage, the Roxtec system or part thereof, shall be kept indoors in its original packaging at room temperature. (b) Installation shall be carried out in accordance with Roxtec installation instructions in effect from time to time. The product information provided by Roxtec does not release the purchaser of the Roxtec system, or part thereof, from the obligation to independently determine the suitability of the products for the intended process, installation and/or use. Roxtec gives no guarantee for the Roxtec system or any part thereof and assumes no liability for any loss or damage whatsoever, whether direct, indirect, consequential, loss of profit or otherwise, occurred or caused by the Roxtec systems or installations containing components not manufactured by an authorized manufacturer and/or occurred or caused by the use of the Roxtec system in a manner or for an application other than for which the Roxtec system was designed or intended. Roxtec expressly excludes any implied warranties of merchantability and fitness for a particular purpose and all other express or implied representations and warranties provided by statute or common law. User determines suitability of the Roxtec system for intended use and assumes all risk and liability in connection therewith. In no event shall Roxtec be liable for indirect, consequential, punitive, special, exemplary or incidental damages or losses. Roxtec International B Box 0, 7 Karlskrona, SWEDEN PHONE , FX EMIL info@roxtec.com, rticle number: SS Document number: SS version D Roxtec and Multidiameter are registered trademarks of Roxtec in Sweden and/or other countries.
Installation instructions Roxtec CM PE systems
Safety information Roxtec recommends that all installations are performed without facility operation. Follow national regulations and installation codes. ny action affecting the routed service should be
More informationInstallation instructions Roxtec RM ES systems
Safety information Roxtec recommends that all installations are performed without facility operation. Follow national regulations and installation codes. ny action affecting the routed service should be
More informationInstallation instructions Roxtec RM BG B systems
Safety information Roxtec recommends that all installations are performed without facility operation. Follow national regulations and installation codes. ny action affecting the routed service should be
More informationInstallation instructions Roxtec RM BG systems
Safety information Roxtec recommends that all installations are performed without facility operation. Follow national regulations and installation codes. ny action affecting the routed service should be
More informationInstallation instructions Roxtec RM ES
Installation instructions Roxtec RM ES Environmental side Environmental side Pipe Cable screen/armor Layers Layers Cable sheath Vertical screen Plastic film Conductive tape Integrated environmental sealing
More informationInstallation instructions Roxtec RM PE
Installation instructions Roxtec RM PE Environmental side Environmental side Pipe Cable screen/armor Layers Layers Cable sheath Plastic film Conductive tape Integrated environmental sealing system for
More informationInstallation instructions Roxtec RM ES B
Installation instructions Roxtec RM ES B Environmental side Termination/ interior side Pipe Cable screen/armor Layers Termination/ interior side Cable sheath Layers Environmental side Vertical screen Plastic
More informationInstallation instructions Roxtec RM PE B
Installation instructions Roxtec RM PE B Environmental side Termination/ interior side Pipe Cable screen/armor Layers Termination/ interior side Cable sheath Layers Environmental side Plastic film Conductive
More informationInstallation instructions Cable transit device Roxtec RS ES Ex
General information Installation and maintenance: For European member countries of GENELEC, shall standard EN 60079-14 and EN 60079-17 be considered. For countries members of IECEx shall standard IEC 60079-14
More informationInstallation instructions Roxtec RS ES Ex
General information Installation and maintenance: For European member countries of GENELEC, shall standard EN 60079-14 and EN 60079-17 be considered. For countries members of IECEx shall standard IEC 60079-14
More informationInstallation instructions Ex frames
General information Installation and maintenance: For European member countries of GENELEC shall standard EN 60079-14 and EN 60079-17 be considered. For countries members of IECEx shall standard IEC 60079-14
More information3M SLiC 530/533/733-2 Port 0.61 Cable Entry Bracket 3M SLiC 530/533/733-2 Port-MSM 0.61 Cable Entry Bracket
3M SLiC 530/533/733-2 Port 0.61 Cable Entry Bracket 3M SLiC 530/533/733-2 Port-MSM 0.61 Cable Entry Bracket For use with 3M SLiC Free-Breathing Fiber Optic Closures and Terminals Instructions November
More information3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR
3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR 3M Cable Addition Kit 2181-XL and 2181-XL/FR Instructions September 2017 78-8130-5055-2-M 2 September 2017 78-8130-5055-2-M 1.0 Kit Contents 2.0 General...
More information3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR 3M Cable Addition Kit 2181-XL and 2181-XL/FR
3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR 3M Cable Addition Kit 2181-XL and 2181-XL/FR Instructions July 2010 3 1.0 Contents 1.0 General...3 2.0 Kit Contents...3 3.0 Cable Preparation...4 4.0
More information3M Better Buried Compound Compression Closure System
3M Better Buried Compound Compression Closure System Instructions March 2016 78-0015-2948-2-A Contents: 1.0 General...3 2.0 Kit Contents...3 3.0 Closure Selection Guide...4 4.0 LHS End Cap Installation...5
More information3M Fiber Optic Splice Closure 2178-XSB/XSB-FR & 2178-XLB/XLB-FR 3M Cable Addition Kit 2181-XB/XB-FR
3M Fiber Optic Splice Closure 2178-XSB/XSB-FR & 2178-XLB/XLB-FR 3M Cable Addition Kit 2181-XB/XB-FR Instructions July 2010 78-8135-0094-5-K 3 1.0 General 1.1 3M Fiber Optic Splice Closure 2178-XSB The
More information3M Distribution Box (DDB)
3M Distribution Box (DDB) Merged Copper and Fiber Pole/Post Mount Enclosure Installation Instructions November 2015 78-0015-2736-1-A 2 November 2015 78-0015-2736-1-A Contents 1.0 General 2.0 Enclosure
More informationMedium Box for Cable Termination
FIST-MB2-T I N S T A L L A T I O N I N S T R U C T I O N Medium Box for Cable Termination Contents 1 Introduction 1.1 Product description. 2 General 2.1 Tools 2.2 Kit contents 3 Installation and pre assembling
More information3M Better Buried Closures
3M Better Buried Closures Instructions March 2016 78-0015-2945-8-A Contents: 1.0 General... 3 2.0 Kit Contents... 3 3.0 Closure Selection Guide... 4 4.0 LHS End Cap Installation... 5 5.0 Cable Preparations...
More information2178-L/S Series Fiber Optic Splice Case with Gasket
2178-L/S Series Fiber Optic Splice Case with Gasket Instructions for: 2178-S Splice Case 2178-LS Splice Case 2178-LL Splice Case 2181-LS Cable Addition Kit May 1997 34-7041-9949-5-A 1 Table of Contents
More informationFIST-MB2-S. FIST Medium Box for Cable Splicing Only. 4 Cable installation. 1 Introduction. Contents. 2 General. 5. Fiber routing to individual trays
FIST-MB2-S I N S T A L L A T I O N I N S T R U C T I O N FIST Medium Box for Cable Splicing Only Contents 1 Introduction 1.1 Product description 2 General 2.1 Tools 2.2 Kit contents 3 Installation and
More informationInstructions. Cable with Armor F CAUTION. October Rev A
3M Single Conductor Accessory Breakout Kits (BOK's) for use with 3M Cable Accessories (Terminations, T-Bodies and Push-On Elbows) For Use With Single Conductor Accessories On Three-Core Conductor Cables
More information3M Better Buried Closure (with 3M Scotchlok Shield Bond Connector 4462-FN and 3M High Gel Re-enterable Encapsulant 8882)
3M Better Buried Closure (with 3M Scotchlok Shield Bond Connector 4462FN and 3M High Gel Reenterable Encapsulant 8882) Instructions April 2016 78813509979C Contents: 1.0 General... 1 2.0 Kit Contents...
More information3 SLiC Aerial Closure with Rubber End Seal
3 Aerial Closure with Rubber End Seal Instructions 1.0 General 1.1 This instruction bulletin describes the assembly of the 3M Aerial Closure with external bonding hanger brackets. These closures are suitable
More informationInstallation Instructions
TECP-30-260 Issue 2 July 2016 Installation Instructions OWB-S OWB-S Small Wall-mounted Box CONTENTS 1. Introduction 2. Kit content 3. Installation Instruction 3.1. Box installation 3.2. Conduit installation
More information3M Cold Shrink Foldback Splice Jacket Kit
3M Cold Shrink Foldback Splice Jacket Kit SJ-FB Instructions! CAUTION Working around energized systems may cause serious injury or death. Installation should be performed by personnel familiar with good
More information3 Foam Sealed Closure 2" (50 mm) with Compound Compression
3 Foam Sealed Closure 2" (50 mm) with Compound Compression Instructions 1.0 General 1.1 The 3M Foam Sealed Closure is designed to be used in the construction and maintenance of buried and underground PIC
More information3 Closure preparation 3.1 Work-stand 3.2. Opening FIST-GCOG2-Dx Preparing drop cable with micro-tubes
FIST-GCOG2-Dx24 I N S T A L L A T I O N I N S T R U C T I O N FTTH closure for micro-tubes and micro-cables Content 1 Introduction 2 Kit content 3 Closure preparation 3.1 Work-stand 3.2. Opening FIST-GCOG2-Dx24
More informationFOSC 450 C6 and D6 Closures
FOSC 450 C6 and D6 Closures I N S T A L L A T I O N I N S T R U C T I O N Fiber Optic Splice Closure 1. General Product Information The FOSC 450 C6 and D6 fiber optic splice closures use compressed gel
More information3M Scotchcast Reenterable Signal and Control Cable Splicing Kits 78-R Series
3M Scotchcast Reenterable Signal and Control Cable Splicing Kits 78-R Series Instructions Voltage Rating: 1000 V, Temperature Rating: 90 C Kit Contents 78-R1 78-R2 78-R3 78-R4 78-R5 Sleeve Set 1 1 1 1
More informationScotch Heavy Duty Vinyl Electrical Tape 22
Scotch Heavy Duty Vinyl Electrical Tape 22 Data Sheet July 2015 Description Agency Approvals & Self Certifications Scotch Heavy Duty Vinyl Electrical Tape 22 is a premium grade, 10-mil thick, vinyl insulating
More informationK & B Flame Retardant Building Riser Closures
K & B Flame Retardant Building Riser Closures September 1995 Issue 1, 34-7016-7030-8 1. General 1.1 3M Brand K&B Building Riser Closures are designed for use in building riser closets and may be positioned
More information3M Locator Plate N
M Locator Plate 44-107N Instructions for the assembly of.100 x.100 preassembled socket connectors 1.0 General The M Locator Plate 44-107N is designed to aid in the assembly of the preassembled socket connector
More information2179-CD Series Fiber Optic Splice Closure. Installation Instructions
2179-CD Series Fiber Optic Splice Closure Installation Instructions 1.0 Product Introduction The new 3M TM 2179-CD Series Fiber Optic Splice Closure can be used in buried, underground, aerial, and pedestal
More information2178 Fiber Optic Splice Case and 2181 Cable Addition Kit
2178 Fiber Optic Splice Case and 2181 Cable Addition Kit Instructions January 1994 Issue 1, 34-7029-6387-6 1 2 Contents: 1.0 General... 4 2.0 Specifications... 4 3.0 Kit Contents... 5 SECTION 1: 2178 Splice
More informationBacklight Replacement
Installation Instructions Backlight Replacement Catalog Numbers 2711P-RL7C, 2711P-RL7C2, 2711P-RL10C, 2711P-RL10C2, 2711P-RL12C, 2711P-RL12C2, 2711P-RL15C Topic Page About This Publication 1 Important
More informationFOSC-450D. Fiber Optic Splice Closure. 1 Introduction. Content. 5 Cable termination. 6 Fiber routing. 2 General. 7 Installation of the gel block
FOSC-450D I N S T A L L A T I O N I N S T R U C T I O N Fiber Optic Splice Closure Content 1 Introduction 2 General 2.1 Kit content 2.2 Tools 2.3 Accessories 2.4 Capacity 3 Preparation of the closure 4
More information3M Scotchcast Mine and Portable Cable Splice and Jacket Repair Kit M-40
3M Scotchcast Mine and Portable Cable Splice and Jacket Repair Kit M-40 Instructions 1 & 2 For Jacket Repair (pages 2 & 7) Supplemental Instructions for: Insulation Repair (page 12) Conductor Repair (page
More informationFOSC-600 C and D I N S T A L L A T I O N I N S T R U C T I O N
FOSC-600 C and D I N S T A L L A T I O N I N S T R U C T I O N In-line and butt version Cold applied re-usable fiber optic closure Contents 1 Introduction 1.1 Product description 1.2 Capacity 2 General
More informationENGINEERING COMMITTEE
ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 01 2015 Specification for F Port, Female, Outdoor NOTICE The Society of Cable Telecommunications Engineers (SCTE)
More information3M Cold Shrink Splice Kit QS-III 5515A
3M Cold Shrink Splice Kit QS-III 5515A for UniShield, Wire Shielded, Longitudinally Corrugated (LC), and Tape Shielded (Ribbon Shielded) Cable or Transitions to Concentric Neutral (CN)/Jacketed Concentric
More informationOPERATION AND MAINTENANCE MANUAL
OPERATION AND MAINTENANCE MANUAL SERIAL NUMBER CUSTOMER: SALES REP.: CONTENTS Mixer Installation / Assembly / Dimension Drawings Safety... 1 Customer Service Contact... 1 Initial Inspection... 2 Installation...2
More information3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT
3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT For Tape Over Wire (TOW) and Wire-Over-Tape (WOT) Shielded Cable For 250 2000 kcmil cable with 650-mil primary insulation thickness Instructions
More information27mm ECAM Double Cable Entry Port
27mm ECAM Double Cable Entry Port Instructions October 2006 1.0 Introduction The 3M 27mm ECAM Double Cable (External Cable Assembly Module) Entry Port is designed to accept fiber optic loose tube & central
More information3M Super 23 Electrical Tape
WEATHERPROOFING S CHEMICALS ET 3M SUPER 23 Features: Premium all-weather black electrical tape Remains conformable at -18 C /0 F 7mm thickness UV resistant Part # Size ET 3M Super 23 19mm x 9.15m WEATHERPROOFING
More information3M Cold Shrink Splice Kit QS-III 5514A
3M Cold Shrink Splice Kit QS-III 5514A for UniShield, Wire Shielded, Longitudinally Corrugated (LC), and Tape Shielded (Ribbon Shielded) Cable or Transitions to Concentric Neutral (CN)/Jacketed Concentric
More information3M Cold Shrink Splice Kit QS-III 5416A
3M Cold Shrink Splice Kit QS-III 5416A for Jacketed Concentric Neutral (JCN) and Concentric Neutral Cable Instructions IEEE Std. 404 15 kv Class 150 kv BIL CAUTION Working around energized systems may
More informationENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE Specification for F Connector, Male, Pin Type
ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 124 2011 Specification for F Connector, Male, Pin Type NOTICE The Society of Cable Telecommunications Engineers
More informationSPECIFICATION. Spec No : VSS-1402-CS603B
SPECIFICATION Spec No : VSS-1402-CS603B 1. INTRODUCTION 1.1. General This specification covers the design requirements and characteristics required of fiber optic splice closures to be used on fiber optic
More informationimac Intel 20" EMC 2133 and 2210 LCD Backlights (CCFL) Replacement
imac Intel 20" EMC 2133 and 2210 LCD Backlights (CCFL) Replacement The CCFL back lights are replaceable. I have pulled mine apart and documented my method. '''NOTE''' This is not for the feint hearted!
More information3M Fiber Optic Splice Tray 2527 with 3M PLC Optical Splitter
3M Fiber Optic Splice Tray 2527 with 3M PLC Optical Splitter Instructions January 2010 3 1.0 General 1.1 The 3M Fiber Optic Splice Tray 2527 with 3M PLC Optical Splitter(s) protects, organizes and stores
More informationSLiC Fiber Aerial Closure System
3 SLiC Fiber Aerial Closure System SLFC 533-SP SLFC 533-TS SLFC 733-SP Instructions May 2005 78-8135-4502-3-B N C H E S R A N G E M IL L IM E T E R S.4 10.6.8 A B C 15 20 I 1.0 Kit Contents Note: Examine
More informationINSTALLATION INSTRUCTIONS
LIGHTGUARD 350-20-WTC SEALED FIBER OPTIC CLOSURE VIEW ONLINE TABLE OF CONTENTS: GENERAL...2 SPECIFICATIONS...2 PACKAGE CONTENTS...3 PACKAGE CONTENTS: ACCESSORIES...3 RECOMMENDED TOOLS...3 ADD-ON COMPONENTS...4
More informationSPECIFICATION FIBER OPTIC SPLICE CLOSURE. Spec No : VSS-1007-BS403A-04A/SD. VSS-0107-BS403A-04A/SD R & D Center Manufacturing Division
SPECIFICATION FIBER OPTIC SPLICE CLOSURE Model Spec. No. Distribution Depts. VSOF-BS403A VSS-0107-BS403A-04A/SD R & D Center Manufacturing Division Sales Division Management Division Revision 10. 07 (Rev.4)
More information3M Fiber Closures BPEO
3M Fiber Closures BPEO 2 3M Fiber Closures BPEO The 3M Fiber Closures BPEO are designed with flexibility in application in mind. With a range of sizes, they can be deployed above grade (pole, facade) or
More information4320 SS-25 Self-Strip Terminating Block
4320 SS-25 Self-Strip Terminating Block Instructions May 2002 78-8130-7677-1 1.0 General The 3M 4320 SS-25 Self-Strip Terminating Block is a factory stubbed, self-stripping connecting block designed for
More informationIn-Wall Control Mount for ipod Touch
In-Wall Control Mount for ipod Touch INTRODUCTION The Mirage KP-iOS is an in-wall system that allows ipod touch (4th generation) to become a semi-permanent fixture in your wall. The system allows you to
More informationXS_-EU. M8 and M12 Sensor Connectors. Ordering Information
M8 and M Sensor Connectors XS_-EU For a wide range of applications the XS_-EU family of M8 and M sensor connectors provides the high performance and features making the family the ideal choice for standard
More informationHigh Density Block BRCP. HD BRCP- 128/192/256 pair. Installation Instructions
High Density Block BRCP HD BRCP- 128/192/256 pair Installation Instructions Product Introduction The BRCP block is the latest generation of MDF terminal blocks developed by 3M, specifically designed for
More informationDVDO VS4 HDMI Switch. User s Guide How to install, set up, and use your new DVDO product
DVDO VS4 HDMI Switch User s Guide How to install, set up, and use your new DVDO product TABLE OF CONTENTS Table of Contents... 1 Introduction... 1 Installation and Set-Up... 2 Remote Control Operation...
More informationHSK Mine and Portable Cable Splice
8096-4-HSK Mine and Portable Cable Splice Instructions 5 and 8 kv rated cables; Type SHD-GC Size 2/0 4/0 (connector max. length 2 1/2") 8096-4-HSK Mine and Portable Cable Splice 78-8119-6296-4-A 1 1.0
More information18mm ECAM Cable Entry Port
18mm ECAM Cable Entry Port Instructions October 2006 1.0 Introduction The 3M 18mm ECAM (External Cable Assembly Module) Cable Entry Port Kit is designed to accept fiber optic cables with external diameters
More informationLuminaire SIGNATURE SERIES
Luminaire SIGNATURE SERIES SIGNATURE SERIES Luminaire Do you need a lot of light? Is your application a sky sign? With maximum brightness and pitch this is the go-to module for oversized channel letters
More information1672A. Product Description. Product Specifications. Technical Specifications. Conductor. APAC Standard. Bend Radius.
1672A Part Number: 1672A 75 Ohm High-Frequency Cable Conformable Coax Cable Product Description 29 AW G solid.011" silver-coated copper-covered steel conductor, TFE Teflon insulation, copper-tin composite
More informationAtlona HDBaseT-Lite Transmitter over Single CAT5e/6/7
Atlona HDBaseT-Lite Transmitter over Single CAT5e/6/7 AT-HDTX User Manual Table of Contents 1. Introduction... 3 2. Package Contents... 3 3. Features... 3 4. Specifications... 3 5. Panel Descriptions a.
More information3M No Polish Jacketed SC/APC Connector
Communication Markets Division 3M No Polish Jacketed SC/APC Connector For use with 1.6 to 3.0 mm Jacketed Cable 3M No Polish SC/APC Connector enables fast, on-site termination of 1.6 mm to 3.0 mm jacketed
More informationCR-R880-BL: Indoor/Outdoor Proximity Reader with 10cm (4in) read range
CR-R880-BL: Indoor/Outdoor Proximity Reader with 10cm (4in) read range Installation Manual Table of Contents Basic Operation...2 CR-R880-BL Block Diagram...2 Technical Specifications...3 Features...4
More information2178 L/S Series Fiber Optic Splice Cases and Accessories
2178 L/S Series Fiber Optic Splice Cases and Accessories The 3M 2178 Fiber Optic Splice Case family has always given you great protection for fiber optic connections. Now, the addition of 3M 2178-L/S Series
More informationKVT Split cable glands
KVT Description Type Order Grommets Thread PU KVT is a circular split frame for quick and easy installation and sealing of cables with connectors or complete cable harnesses. 3 KVT 20** 34 24 M20. Polyamide
More informationCold Shrink Three-Conductor Splice Kit QS-III for use on Armor and Non-Armor Cables Instructions IEEE Std kv Class 250 kv BIL
Cold Shrink Three-Conductor Splice Kit QS-III for use on Armor and Non-Armor Cables Instructions IEEE Std. 404 35 kv Class 250 kv BIL Kit Number 5798A-MT Cable Range Requirements Cable Insulation O.D.
More informationLCC (Little Coaxial Connector) Installation Instructions)
LCC (Little Coaxial Connector) Installation Instructions) Content Page INTRODUCTION...1 Revision History...1 Trademark Information...1 1 TOOLS...2 1.1 Connection Tool Kit...2 1.2 Tool Illustrations...2
More informationSJOF-BS604B. Fiber Optic Splice Closure User Manual Rev.1
Fiber Optic Splice Closure 1. Introduction 1.1 General SAMJIN s SJOF-BS604B protects fiber optic splicing point in various installation conditions such as aerial, manholes, ducts, wall and direct buried
More informationDesk Mount Articulating Dual Monitor Arm with Cable Management & Height Adjust
Desk Mount Articulating Dual Monitor Arm with Cable Management & Height Adjust ARMDUAL *actual product may vary from photos DE: Bedienungsanleitung - de.startech.com FR: Guide de l'utilisateur - fr.startech.com
More informationQuante BPEO Splice-Protection Closure for Optical Fiber Cables. Features Advantages Benefits
3 Quante BPEO Splice-Protection Closure for Optical Fiber Cables BPEO: Fully Mechanical, Easy to Install, No Specific Tools BPEO is the newest generation of watertight spliceprotection closures for optical
More information3M Fiber Optic Closure System LL
3M Fiber Optic Closure System LL 3M Fiber Optic Closure System The 3M Fiber Optic Closure System LL provides a protective yet accessible environment for housing single or mass fusion fiber splices. The
More informationTECHNICAL SPECIFICATION
TECHNICAL SPECIFICATION (FIBER OPTIC SPLICE CLOSURE) Model Spec. No. Distribution Depts. VSOF-BS403A SJP-0609-403A-01A/SD Quality Assurance Team Manufacturing Division Sales Division Management Division
More informationOFDC-B8-72. Outdoor fiber distribution closure. 6 Closing. Content 1 Introduction. 7 Re-entry. 2 Kit content. 3 Closure preparation
OFDC-B8-72 I N S T A L L A T I O N I N S T R U C T I O N Outdoor fiber distribution closure Content 1 Introduction 2 Kit content 3 Closure preparation 4 Cable preparation 4.1 Feeder cable 4.2 Drop cable
More informationASSEMBLY, INSTALLATION, AND REMOVAL OF CONTACTS AND MODULES
ASSEMBLY, INSTALLATION, AND REMOVAL OF CONTACTS AND MODULES FOR 75 OHM AND 75 OHM HD COAXIAL CONTACTS AND MODULES Table of Contents SECTION 1 RECEIVER CONTACT ASSEMBLY INSTRUCTIONS SECTION 2 ITA CONTACT
More informationXW3D. Simple Wiring of Sensor Actuators. Connector Terminal Boxes. Specifications. Materials and Finish. Connection Combinations
Terminal Boxes XWD CSM_XWD_DS_E Simple Wiring of Sensor Actuators Greatly reduce wiring in combination with the Smartclick XS. Insert the connector and turn / of a turn to lock the connectors. Higher rated
More informationInterface Practices Subcommittee SCTE STANDARD SCTE Test Method for Drop Cable Center Conductor Bond to Dielectric
Interface Practices Subcommittee SCTE STANDARD SCTE 59 2018 Test Method for Drop Cable Center Conductor Bond to Dielectric NOTICE The Society of Cable Telecommunications Engineers (SCTE) / International
More informationVGA to DVI Extender over Fiber SET
VGA to DVI Extender over Fiber SET Model #: FO-VGA-DVI 2011 Avenview Inc. All rights reserved. The contents of this document are provided in connection with Avenview Inc. ( Avenview ) products. Avenview
More information3M No Polish Jacketed SC/APC Connector
Communication Markets Division 3M No Polish Jacketed SC/APC Connector For use with 1.6 to 3.0 mm Jacketed Cable 3M No Polish SC/APC Connector enables fast, on-site termination of 1.6 mm to 3.0 mm jacketed
More informationDisplayPort to VGA Converter
DisplayPort to VGA Converter Model #: C-DP-VGA 2010 Avenview Inc. All rights reserved. The contents of this document are provided in connection with Avenview Inc. ( Avenview ) products. Avenview makes
More information3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN
3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-500-1000 for Jacketed Concentric Neutral (JCN) and Flat Strap Neutral Cable Instructions IEEE Std. 404 15 kv Class 150 kv BIL F CAUTION Working around
More information3M Cold Shrink QS4 Integrated Splice Kit QS4-35TS
3M Cold Shrink QS4 Integrated Splice Kit QS4-35TS-350-1000 for Tape Shield, Wire Shield, UniShield, and Longitudinally Corrugated (LC) Cable Instructions IEEE Std. 404 35 kv Class 250 kv BIL F CAUTION
More information3M Coupling Tray FDTC-10S-COUPLINGTRAY
3M Coupling Tray FDTC-10S-COUPLINGTRAY for use with 3M Fiber Dome Closures FDC 10S Instructions July 2010 3 1.0 Introduction The 3M Coupling Tray FDTC-10S-COUPLINGTRAY can accommodate up to 10 loose tubes.
More information18W Low Energy Dusk-Dawn Bulkhead E-290B
18W Low Energy Dusk-Dawn Bulkhead E-290B INSTALLER GUIDE V1.0-12/06 IQ-ABH01-PH-18-PR IQ Europe Limited Sandbeck Lane, Wetherby LS22 7TW. Visit us at www.iq-europe.co.uk Installation helpline 0871 717
More informationAC Line Rated Disc Capacitors Class X1, 760 V AC, Class Y1, 500 V AC
AC Line Rated Disc Capacitors Class X1, 760 V AC, Class Y1, 500 V AC EATURES Complying with IEC 60384-14, 3 rd edition High reliability Vertical (inline) kinked or straight leads Material categorization:
More informationSC-C1M SiriusConnect TM Vehicle Tuner
SC-C1M SiriusConnect TM Vehicle Tuner For Special Market Applications Installation Guide Congratulations on the Purchase of your new SIRIUS SC-C1 SiriusConnect TM Vehicle Tuner. The SC-C1M is packaged
More informationWLS27 Multicolor LED Strip Light with EZ-STATUS
WLS7 Multicolor LED Strip Light with EZ-STATUS Instruction Manual Banner's WLS7 Multicolor LED Strip Light has a sturdy aluminum housing and is encased in a shatterproof, UV-stabilized, copolyester shell,
More informationCable installation guidelines
The Quality Connection Cable installation guidelines Business Unit Industrial Projects 2 Cable installation guidelines www.leoni-industrial-projects.com GENERAL Installation methods Many different methods
More informationPhotovoltaic Module Installation Manual (IEC)
Phono Solar Technology Co., Ltd. Add: No. 1 Xinghuo Rd., Nanjing Hi-tech Zone, Nanjing, China Tel: +86 25 5863 8000 Fax: +86 25 5863 8009 E-mail: support@phonosolar.com Website: www.phonosolar.com PHONO
More informationPhotovoltaic Module Installation Manual (IEC)
Phono Solar Technology Co., Ltd. Add: No. 1 Xinghuo Rd., Nanjing Hi-tech Zone, Nanjing, China Tel: +86 25 5863 8000 Fax: +86 25 5863 8009 E-mail: support@phonosolar.com Website: www.phonosolar.com PHONO
More informationSurface Mount Multilayer Ceramic Chip Capacitors for High Temperatures 200 C
Surface Mount Multilayer Ceramic Chip Capacitors for High Temperatures 200 C DESIGN TOOLS (click logo to get started) FEATURES Case size 0402, 0505, 0603, 0805, Available High frequency / high temperature
More informationInstallation Manual for New or Retrofit Installations
Installation Manual for New or Retrofit Installations Release Date: 24-August-2015 c Able Applied Technologies LTD. READ THE ENTIRE MANUAL COMPLETELY AND CAREFULLY BEFORE STARTING BEFORE YOU BEGIN ASSEMBLY
More informationENGINEERING COMMITTEE Interface Practices Subcommittee SCTE Test Method for Cable Weld Integrity
ENGINEERING COMMITTEE Interface Practices Subcommittee SCTE 178 2011 Test Method for Cable Weld Integrity NOTICE The Society of Cable Telecommunications Engineers (SCTE) Standards are intended to serve
More informationInstallation Manual SaVi Note Underwater LED Light
Installation Manual SaVi Note Underwater LED Light Model Numbers SAVI-NOTE7, SAVI-NOTE0 Table of Contents Safety Precautions...2 SaVi Note Install Instructions...3- M Instructions...- Warnings READ AND
More informationCommunication Markets Division. 3M Fiber Closures. Smart design makes your job easier.
Communication Markets Division 3M Fiber Closures Smart design makes your job easier. 2 Your connections deserve the best protection. No matter the size and configuration of your network, protecting its
More information3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500
3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500 for Jacketed Concentric Neutral (JCN) and Flat Strap Neutral Cable Instructions IEEE Std. 404 15 kv Class 150 kv BIL CAUTION Working around energized
More informationDetailed Specifications & Technical Data
For more information please call 1-800-Belden1 See Put-ups and Colors Related Documents: No.10 for Fiber Optic Cables.pdf Cable Characteristics: DESCRIPTION: 2 to 12 optical fibers, Central gel filling
More information