Specification of Fusion Splice Loss - FIA TSD Mike Gilmore FIA Technical Director
|
|
- Sheryl Phillips
- 5 years ago
- Views:
Transcription
1 Specification of Fusion Splice Loss - FIA TSD Mike Gilmore FIA Technical Director
2 Mike Gilmore Standards Activities Member: ISO/IEC JTC1 SC25 WG3: Generic Cabling ISO/IEC JTC1 SC25 Project Team: SOHO Convenor: ISO/IEC JTC1 SC25 WG3 IPTG: Industrial Premises Cabling Convenor: CENELEC TC215 WG1: IT Cabling CENELEC TC215 WG1 PT Industrial Premises Cabling Secretary: CENELEC TC215 WG1 PT Data Centre Cabling Mike Gilmore Senior Partner, The Cabling Partnership Managing Director e-ready Building Chairman: BSI TCT7/-/1: IT Cabling BSI TCT7/-/3: IT Cabling Support Group Technical and Standards Director: Fibreoptic Industry Association Mobile: +44 (0)
3 Existing Standards for OF Cabling Components ISO/IEC Ed. 2 (2002) AND (BS) EN (2002) CABLED OPTICAL FIBRE Attenuation coefficient (dbkm -1 max) Wavelength 850nm 1300nm 50/125 or 62.5/125 50/125 OM1 OM2 OM3 Wavelength OS1 3,5 1310nm 1,0 1,5 1550nm 1,0 OS2* OS1 1,0 0,4 1,0 0,4 MMF SMF ISO/IEC Ed. 2 (2002) AND (BS) EN (2002) CONNECTING HARDWARE Attenuation (db max) Wavelength All OM1, OM2, OM3 Connection Splice 95%<0,5 100%<0,75 100%<0,3 OS1, OS2* Wavelength Connection Splice All 95%<0,5 100%<0,75 100%<0,3 ANSI/TIA/EIA-568-B.3 CONNECTING HARDWARE Wavelength Connection Splice Wavelength Connection Splice Attenuation (db max) All 100%<0,75 100%<0,3 All 100%<0,75 100%<0,3 * standard in development
4 Premises Cabling TO CP FD BD CD PREMISES CABLING ISO/IEC (BS) EN Telecommunications Outlet Consolidation Point Floor Distributor Building Distributor Campus Distributor TO TO TO TO TO CP Horizontal cabling FD FD Building backbone cabling BD Campus backbone cabling CD CC = Crossconnect Panel PP= Patch Panel Transmission channel BD CD CC PP PP CC FD BD Building backbone cabling Campus backbone cabling CC PP PP CC
5 WAN Cabling - Singlemode Technology Transmission channel CC PP PP CC Attenuation Wavelength 1310nm 1550nm OS2* OS1 0,4 dbkm 1,0-1 0,4 dbkm 1,0-1 Splice 0,3 db Based on a splice every 1000 metres then 75% of loss comes from splices UNACCEPTABLE
6 Which singlemode would you like, Sir? Chromatic Dispersion Coefficient +ve -ve ITU-T G.652 ITU-T G.655 ITU-T G Wavelength (nm) G Characteristics of a single-mode optical fibre cable G Characteristics of a dispersion-shifted single-mode optical fibre cable G Characteristics of a cut-off shifted single-mode optical fibre cable G Characteristics of a non-zero dispersion shifted single-mode optical fibre cable IEC TYPE B1.1 TYPE B1.2 TYPE B1.3 TYPE B2 TYPE B4 equivalent to G652a G654a G652c G653a G655a G656 G652b G654b G652d G653b G655b G654c G655c
7 Mode Field Diameter MODE FIELD DIAMETER (µm) Limit +/- tolerance Extreme limits Wavelength Minimum OS1 Maximum OS1 Minimum OS1 Maximum OS1 B nm 8,6 1,0 +/- 0,7 9,5 1,0 +/- 0,7 1,0 7,9 10,2 1,0 B nm 8,6 1,0 +/- 0,7 9,5 1,0 +/- 0,7 1,0 7,9 10,2 1,0 Wavelength Minimum OS1 Maximum OS1 Minimum OS1 Maximum OS1 B nm 9,5 1,0 +/- 1,0 13,0 +/-1,0 1,0 8,5 14,0 1,0 B2 1550nm 7,8 1,0 +/- 0,8 8,5 1,0 +/- 0,8 1,0 7,0 1,0 9,3 B4 1550nm 8,0 1,0 +/- 0,7 11,01,0 +/- 0,7 1,0 7,3 11,7 1,0 B1.1 B1.3 B1.2 B2 B4 7,0 8,0 9,0 10,0 11,0 12,0 13,0 14,0
8 Splicing Technology Options CORE ALIGNMENT SPLICING TECHNOLOGY Mode Field Diameter (MFD) Splice loss = MFD mismatch + processing variations CLADDING ALIGNMENT SPLICING TECHNOLOGY Splice loss = MFD mismatch + processing variations + core concentricity error
9 Mode Field Diameter Mismatch FIBRE 1 FIBRE 2 d 1 Splice loss (MFD) d 2 = log 10 (d 1 /d 2 + d 2 /d 1 ) MFD 1 MFD 2 Splice loss (db) MFD 1 MFD 2 8,0 +/- 0,7 9,0 +/- 0,7 10,0 +/- 0,7 11,0 +/- 0,7 12,0 +/- 0,7 13,0 +/- 0,7 14,0 +/- 0,7 8,0 +/- 0,7 9,0 +/- 0,7 10,0 +/- 0,7 11,0 +/- 0,7 12,0 +/- 0,7 13,0 +/- 0,7 14,0 +/- 0,7 RESULTING INDIVIDUAL SPLICE LOSS (db max.) 0,14 0,28 0,11 0,22 > 0,3 0,08 0,19 0,08 0,17 0,08 0,15 0,08 0,25 0,13 0,07
10 Incompatibility MODE FIELD DIAMETER (µm) Limit +/- tolerance Extreme limits Wavelength Minimum OS1 Maximum OS1 Minimum OS1 Maximum OS1 B nm 8,6 1,0 +/- 0,7 9,5 1,0 +/- 0,7 1,0 7,9 10,2 1,0 B nm 8,6 1,0 +/- 0,7 9,5 1,0 +/- 0,7 1,0 7,9 10,2 1,0 Wavelength Minimum OS1 Maximum OS1 Minimum OS1 Maximum OS1 B nm 9,5 1,0 +/- 1,0 13,0 +/-1,0 1,0 8,5 14,0 1,0 B2 1550nm 7,8 1,0 +/- 0,8 8,5 1,0 +/- 0,8 1,0 7,0 1,0 9,3 B4 1550nm 8,0 1,0 +/- 0,7 11,01,0 +/- 0,7 1,0 7,3 11,7 1,0 B1.1 B1.3 B1.2 B2 B4 7,0 8,0 9,0 10,0 11,0 12,0 13,0 14,0
11 A Specification Minefield SPLICE TYPE SAME PRODUCT SAME TYPE SPLICE DEFINITION Two optical fibres from a single IEC Type with: the same nominal MFD; subject to the applicable tolerances. Two optical fibres from a single IEC Type A low loss specification can be applied A higher loss specification can be applied - but only for specific Types DIFFERENT TYPE UNKNOWN Two optical fibres known but different IEC Types Two optical fibres of unknown provenance A specification can be applied - but only for specific products within each Type SAME MFD Two optical fibres from different IEC Types with: the same nominal MFD; subject to the applicable tolerances. No loss specification can be applied A low loss specification can be applied - after ensuring that wavelength conversation has been applied to the MFD values
12 Specification of Individual Splice Loss Transmission channel CC PP PP CC Splice loss (db) Low loss limit Controls workmanship Poor Yield High Re-work High loss limit Allows poor workmanship 100% Yield 0% Re-work
13 Specification of Average Splice Loss Transmission channel CC PP PP CC Individual splice loss (db) 0,0 db 0,15 db Average splice loss (db) 0,0 db 0,06 db
14 Behaviour of Average Splice Loss Max. average splice loss (db) No. of splices
15 FIA Technical Support Documents TSD DESIGN OPERATION INSTALLATION SAFETY OPTICAL FIBRE CABLING: LAN APPLICATION SUPPORT GUIDE POLARITY MAINTENANCE INSTALLATION PRACTICE: SPLICING TESTING OF INSTALLED CABLING: ATTENUATION USING LSPM EQUIPMENT TESTING OF INSTALLED CABLING: ATTENUATION USING OTDR EQUIPMENT OPTICAL POWER: SAFETY LEVELS OPTICAL FIBRE: HANDLING OF PROCESSING CHEMICALS OPTICAL FIBRE: DISPOSAL OF WASTE
16 FIA Recommended Limits - Single Splices CORE ALIGNMENT SPLICING TECHNOLOGY MMF SMF ISO/IEC Ed. 2 (2002), (BS) EN (2002) and ANSI/TIA/EIA-568-B.3 Attenuation (db max) Wavelength All Splice 100%<0,3 Wavelength All Splice 100%<0,3 CLADDING ALIGNMENT SPLICING TECHNOLOGY
17 FIA Recommended Limits - Multiple Splices CORE ALIGNMENT SPLICING TECHNOLOGY Single splice (db max.) Average for 2 splices (db max.) Average for 3 splices (db max.) Average for 4 splices (db max.) Average for 5 splices (db max.) Average for 10 splices (db max.) G652 G655 a, b, c, d a, b and c B1.1 B1.3 B4 1310nm 1550nm 0,3 0,3 0,09 1,0 0,08 1,0 0,08 1,0 0,07 0,12 1,0 0,10 1,0 0,09 1,0 0,08 0,06 0,08 ITU-T IEC Wavelength CLADDING ALIGNMENT SPLICING TECHNOLOGY
18 A Question of Measurement FIA IEC and FIA-TSD Bi-directional measurement required AVERAGE SPLICE LOSS A-H = (Y 1 -(A 1 +B 1 +C 1 +D 1 +E 1 +F 1 +G 1 +H 1 ))/7 AVERAGE SPLICE LOSS H-A = (Y 2 -(A 2 +B 2 +C 2 +D 2 +E 2 +F 2 +G 2 +H 2 ))/7 AVERAGE SPLICE LOSS = 0.5 [(AVERAGE SPLICE LOSS A-H) + (AVERAGE SPLICE LOSS H-A)] A 1 H 2 B 1 G 2 C 1 F 2 Y 1 (db) D 1 Y 2 (db) E 2 E 1 D 2 F 1 C 2 G 1 B 2 H 1 A 2
19 Splicing Technology Options CORE ALIGNMENT SPLICING TECHNOLOGY Mode Field Diameter (MFD) Splice loss = MFD mismatch + processing variations CLADDING ALIGNMENT SPLICING TECHNOLOGY Splice loss = MFD mismatch + processing variations + core concentricity error
20 Commercial Viability THE CLIENTS PERSPECTIVE Excessively low splice loss specifications can result in: delays to project completion; additional costs (labour resource) in meetings, re-negotiation or arbitration of outcomes; additional costs associated with attenuation of system components. Unclear splice loss specifications can result in: delays to project completion; additional costs (labour resource) in meetings, re-negotiation or arbitration of outcomes. THE INSTALLERS PERSPECTIVE Excessively low and/or unclear splice loss specifications can result in: delays to project completion; additional costs (labour resource) in rework of completed splice closures: additional costs (labour resource) in meetings, re-negotiation or arbitration of outcomes; reduction in profit due to late payment; delayed onset of other work; damage to reputation. EVERYONE S PERSPECTIVE It is in everyone s interest to agree a clear, technically feasible and commercially viable set of limits
21 Rework Levels CORE ALIGNMENT SPLICING TECHNOLOGY 25 G655 a, b and c Type B4 SMF 20 % Rework G652 a, b, c and d Type B1.1, B1.3 SMF 5 PLEASE NOTE: FIGURES ARE INDICATIVE ONLY ERROR MAY EXCEED 5% Max. allowed loss db (10 splice average)
22 Rework Levels CLADDING ALIGNMENT SPLICING TECHNOLOGY 25 G655 a, b and c Type B4 SMF 20 % Rework G652 a, b, c and d Type B1.1, B1.3 SMF 5 PLEASE NOTE: FIGURES ARE INDICATIVE ONLY ERROR MAY EXCEED 5% Max. allowed loss db (10 splice average)
23 Cost of Rework SYSTEM TOPOLOGY Example of 8% rework a 12-element cable might require every splice closure to be reworked a 4-element cable might only could require every third splice closure to be reworked RESOURCE ALLOCATION Rework requires continuous presence of both splicing and testing team COST PER SPLICE Can easily exceed original installation cost
24 Technical Checklist INSTALLERS PREPARE THE WORK AREA PREPARE THE FUSION SPLICING EQUIPMENT DO PREPARE AND CLEAN CABLE ELEMENTS APPLY THE SPLICE PROTECTION SLEEVE PREPARE THE PRIMARY COATING STRIPPING TOOL REMOVE OPTICAL FIBRE PRIMARY COATING DO CLEAN THE FIBRE TO REMOVE REMAINING COATING DEBRIS, CABLE GEL RESIDUE ETC. CLEAVE THE FIBRE SPLICE THE FIBRE DO cleave angle: cracks: roll-off or lip: dust contamination: splice programme: PROTECT THE SPLICE
25 Conclusions INSTALLATION INSTALLATION PRACTICE: SPLICING GUIDELINES TO SPECIFIERS specify incompatible fibres! DON T specify maximum individual splice losses of less than 0,3dB set unrealistic average splice loss requirements - design systems with realistic power budgets include specifications for the MFD of the fibre to be used as well as the generic type. DO use the FIA guidelines to set maximum average splice losses be clear about the meaning of average splice loss - only specify average losses for splices in the same segment or channel (i.e. do not specify an average splice loss per joint closure) GUIDELINES TO INSTALLERS DON T DO quote for contracts where the optical fibres involved are not fully specified consider the system topology calculate the amount of rework and its cost before quoting for a contract. adopt best practices when using splicing equipment
26 Acknowledgements INSTALLATION INSTALLATION PRACTICE: SPLICING Fibreoptic Industry Association Optilan TRITEC Developments Limited Mike Gilmore John Colton Mike Haynes Andy Toal Brendan Ward David Myers Furukawa Electric Europe Limited Fujikura Europe Limited Sumitomo Electric Europe Limited Adrian Wood Ian Tweedle David Randall Yakeen Patel
40/100 Gb ETHERNET CABLING - A PERFECT STORM?
40/100 Gb ETHERNET CABLING - A PERFECT STORM? Mike Gilmore Mike Gilmore Mike Gilmore, Fellow IET Managing Director e-ready Building Standards Activities Member JTC1 SC25 WG3: Generic Cabling Convenor JTC1
More informationHow to Speak Fiber Geek Article 4: Single-Mode Optical Fiber Geometries
Welcome back, Fiber Geeks! The first article in this series highlighted some bandwidth demand drivers and introductory standards information. Article 2 then focused on attenuation and Article 3 followed
More information40GBASE-ER4 optical budget
40GBASE-ER4 optical budget Pete Anslow, Ciena SMF Ad Hoc, 21 August 2012 1 Introduction The Next Generation 40 Gb/s and 100 Gb/s Optical Ethernet Study Group has an adopted objective: Define a 40 Gb/s
More informationTENDER SUMMARY. Tender Title:
TENDER SUMMARY Tender Title: Tender Ref: Closing Date: OPEN TENDER FOR THE SUPPLY OF FIBER OPTIC CABLE 384 CORE LOOSE TUBE ( FOC 384C ) FOR TELEKOM MALAYSIA BERHAD ( TM ) LPM/2018/T/02/FOC 384C 23 February
More informationDelaware County Community College Project # Marple Campus Renovation - Phase % Construction Documents November 23, 2011
SECTION 271323 - COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 - GENERAL 1.1 DESCRIPTION A. This section provides the specifications for the work related to the optical fiber system in the project.
More information40G SWDM4 MSA Technical Specifications Optical Specifications
40G SWDM4 MSA Technical Specifications Specifications Participants Editor David Lewis, LUMENTUM The following companies were members of the SWDM MSA at the release of this specification: Company Commscope
More information400G-FR4 Technical Specification
400G-FR4 Technical Specification 100G Lambda MSA Group Rev 1.0 January 9, 2018 Chair Mark Nowell, Cisco Systems Co-Chair - Jeffery J. Maki, Juniper Networks Marketing Chair - Rang-Chen (Ryan) Yu Editor
More informationRecommended Changes to Optical PMD Proposal
Recommended Changes to Optical PMD Proposal Steve Swanson Corning Incorporated 607 974 4252 tel 607 974 4941 fax swansonse@corning.com Paul Kolesar Lucent Technologies 908 957 5077 tel 908 957 5604 fax
More informationSSA Fibre-Optic Extender 160 Fibre Installation Guidelines Version 1.2
SSA Fibre-Optic Extender 160 Version 1.2 0.1 Introduction This document provides information on the specification and installation of optical fibre networks to support SSA optical extender products. SSA
More informationPart 1: How to Avoid Confusion When Testing Insertion Loss According to TIA/EIA-568 B.1 and B.3
Fiber Optic Services And Products EYE ON FIBER Volume 1, Issue 2 August 2002 Part 1: How to Avoid Confusion When Testing Insertion Loss According to TIA/EIA-568 B.1 and B.3 I have been reviewing a Draft
More information40G SWDM4 MSA Technical Specifications Optical Specifications
40G SWDM4 MSA Technical Specifications Specifications Participants Editor David Lewis, LUMENTUM The following companies were members of the SWDM MSA at the release of this specification: Company Commscope
More informationTech Breakfast: Fibre Optic Cabling
Tech Breakfast: Fibre Optic Cabling An introduction phil.crawley@jigsaw24.com @IsItBroke on Twitter http://www.root6.com/author/phil Fibre optic cabling Applications within Film & TV Single mode vs. Multi
More informationDESIGN!!GUIDELINES!!!!!
DESIGNGUIDELINES 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 1. Testing General 1.1. For acceptance, 100% of the media
More informationSMF Ad Hoc report. Pete Anslow, Ciena, SMF Ad Hoc Chair. IEEE P802.3bm, Geneva, September 2012
SMF Ad Hoc report Pete Anslow, Ciena, SMF Ad Hoc Chair IEEE P802.3bm, Geneva, September 2012 1 Introduction The Next Generation 40 Gb/s and 100 Gb/s Optical Ethernet Study Group SMF Ad Hoc has: Held two
More informationOPTICAL FIBRE CABLE NETWORK 2004/1
OPTICAL FIBRE CABLE NETWORK 2004/1 HELKAMA OPTICAL FIBRE CABLES Cabled optical fibre characteristics OS1 singlemode fibre SM ITU-T G.652 Mode field diameter 1310nm 9.3+/-0.5µm Mode field eccentricity 1.0
More information100G-FR and 100G-LR Technical Specifications
100G-FR and 100G-LR Technical Specifications 100G Lambda MSA Rev 1.0 January 9, 2018 Chair Mark Nowell, Cisco Systems Co-Chair - Jeffery J. Maki, Juniper Networks Marketing Chair - Rang-Chen (Ryan) Yu,
More informationSPECIFICATION 96F SM LOOSE TUBE, DRY CORE MINI CABLE
Revision No.:01 Date: 07.10.06 SPECIFICATION OF 96F SM LOOSE TUBE, DRY CORE MINI CABLE PART NO.:D-96/SM/MTY(F)-MFN-O6.3 Checked By: Pavan Maheshwari Process Associate Design & Development Team Approved
More informationWe will look first at the cable, and then the transceivers (which act as both transmitter and receiver on each end of the fiber cable).
Nuclear Sensors & Process Instrumentation Fiber Cable Basics Fiber-optic communication is a method of transmitting information from one place to another by sending light through an optical fiber. The light
More informationStandard FTTH Drop Cable. FTTH DROP - nb6a1/g657a1
Optical Fibre Cable Technical Specification Standard FTTH Drop Cable FTTH DROP - nb6a1/g657a1 NextraCom Optical Fibre Cable All rights reserved 1.Scope This Specification covers the design requirements
More information3M Telecommunications. Solutions for Networks. Design Planning and Installation Manual. for Fibre and Copper Cabling Systems.
3M Telecommunications Solutions for Networks Design Planning and Installation Manual for Fibre and Copper Cabling Systems Innovation Design, Planning and Installation of the Volition Cabling System Design
More informationHES HACILAR ELEKTRİK SANAYİ VE TİC.A.Ş.
Technical Specification Revision/Date: 04/04.15 By N.KARAAĞAÇ Date : 27 February 2015 Cable Type HES Cable Product Number :, Outdoor F/O Cable :FOZZXXXSJSA41JYY (ZZ: fiber type G652=SD, G657 A1 = A1, G657
More informationSPECIFICATION 192F SM LOOSE TUBE, DRY CORE MINI CABLE
Revision No.:00 Date: 08.03.2010 SPECIFICATION OF 192F SM LOOSE TUBE, DRY CORE MINI CABLE PART NO.:D-192/SM/MTY(F)-MFN-O9.1 Checked By: Pavan Maheshwari Process Associate Design & Development Team Approved
More informationHERA RETICULATION FIBRE CABLE PRODUCT REQUIREMENTS
Organisation : NRF (National Research Foundation) Facility : SARAO (South African Radio Astronomy Observatory) Project : HERA (Hydrogen Epoch of Reionization Array) Document Type : PRD (Product Requirements
More informationOptical Fibre Cable Technical Specification. Duct Cable GYFTY-24,48,72,144,216B1.3
Version GYFTY-V1.0 Optical Fibre Cable Technical Specification Duct Cable GYFTY-24,48,72,144,216B1.3 Yangtze Optical Fibre and Cable Joint Stock Limited Company All rights reserved 1. Scope This Specification
More informationLD Series High Performance Loose Tube Fiberoptic Cables
Fiberoptic Cables Catalog LD Series High Performance Loose Tube Fiberoptic Cables APPLICATIONS Long-distance outside plant telephone, CATV as well as data communications Direct burial and installation
More informationThe Road to Single Mode: Direction for choosing, installing and testing single mode fiber
The Road to Single Mode: Direction for choosing, installing and testing single mode fiber Adrian Young Leviton Network Solutions Jim Davis Fluke Networks Adrian Young, Sr. Applications Engineer Leviton
More informationDetailed Specifications & Technical Data
For more information please call 1-800-Belden1 See Put-ups and Colors Related Documents: No.10 for Fiber Optic Cables.pdf Cable Characteristics: DESCRIPTION: 2 to 12 optical fibers, Central gel filling
More informationFiber Optic Testing. The FOA Reference for Fiber Optics Fiber Optic Testing. Rev. 1/31/17 Page 1 of 12
Fiber Optic Testing Testing is used to evaluate the performance of fiber optic components, cable plants and systems. As the components like fiber, connectors, splices, LED or laser sources, detectors and
More informationISO/IEC testing LC to LC (Duplex Multimode) DTX-MFM
Page 1 of 5 ISO/IEC 14763-3 testing LC to LC (Duplex Multimode) DTX-MFM ISO/IEC 11801 now refers fibre testing to ISO/IEC 14763-3. More importantly, the limits have changed and we'll show you how in this
More informationSelection of a cable depends on functions such as The material Singlemode or multimode Step or graded index Wave length of the transmitter
Fibre Optic Communications The greatest advantage of fibre cable is that it is completely insensitive to electrical and magnetic disturbances. It is therefore ideal for harsh industrial environments. It
More informationGUXT. Mini-Breakout Cables (Distribution) Universal Indoor/ Outdoor A/I-VQ(ZN)BH Improved Rodent Protection. Ordering Information.
GUXT Mini-Breakout Cables (Distribution) Universal Indoor/ Outdoor A/I-VQ(ZN)BH Improved Rodent Protection Ordering Information Belden European Part Numbers Fibre type / count 4 6 8 12 16 24 62.5/125-OM1
More informationOPTICAL FIBER CABLE, ALL DIELECTRIC SELF SUPPORTING CABLE
SPEC NO. TEC-OPTIC-81101A(Rev.4)-2014.07 TECHNICAL PROPOSAL FOR OPTICAL FIBER CABLE, ALL DIELECTRIC SELF SUPPORTING CABLE ( Span length : Max. 100m ) APPROVED BY : J.Y. LEE / HEAD OF TEAM ENGINEERING TEAM
More informationSpec No.: ZTT Revision: 2 Date: Oct 3, Designer. Senior Technical Manager. Approver. Chief Technical Engineer
Spec No.: ZTT 45012 Revision: 2 Date: Oct 3, 2014 TECHNICAL SPECIFICATION Optical Fiber Cable (Reference: NBR 14566) Designer Senior Technical Manager Approver Chief Technical Engineer Jiangsu Zhongtian
More informationRFP LC Uniboot to RFP LC Uniboot Patch cord, 2 fibres, Interconnect tight-buffered cable, LSZH
1 1 9.41 115 0 Pretium EDGE 143 RFP LC Uniboot to RFP LC Uniboot Patch Pretium EDGE Solutions jumpers are integrated reverse -polarity uniboot duplex assemblies that meet the high -density space requirements
More informationMicro duct Cable with HDPE Sheath for Installation by Blowing
Optical Fiber Cable Technology Specification INTERNAL Optical Fiber Cable Specification Micro duct Cable with HDPE Sheath for Installation by Blowing GCYFY-12/24/36/48/72/96/144/288/432/576B1.3 V7.0 2018-3-20,CCopyright.
More informationMulti Core fibers and other fibers for the future.
Multi Core fibers and other fibers for the future. Ole Suhr Senior Account Manager. FIA Summer Seminar, June 2017 1 Your Optical Fiber Solutions Partner Copyright OFS 2017 Market for optical fibers: Recently
More informationProduct information. OpDAT VIK with breakout cable. Product description. Illustrations. Page 1/7
Page /7 Illustrations Product description Pre-terminated installation cables (VIK) are fiber optic cables with connectors on one or both ends that are made in manual singleitem production at METZ CONNECT
More informationRevision No. 4 Page No. Page 1 of 7
Page No. Page 1 of 7 Single Mode Optical Fibre Cables With Loose Fibres in Stranded Tubes And Corrugated Steel tape Armouring For Duct Applications LITE KABEL SDN. BHD. reserves the right to make changes
More informationGUWN. Central Loose Tube Cables Universal Indoor/Outdoor, Steel Wire Armor (SWA) A/I-DQ(ZN)HBH Full Rodent Protection. Ordering Information
GUWN Central Loose Tube Cables Universal Indoor/Outdoor, Steel Wire Armor (SWA) A/I-DQ(ZN)HBH Full Rodent Protection Ordering Information Belden European Part Numbers Fibre type / count 4 6 8 12 16 24
More informationField Testing and Troubleshooting of PON LAN Networks per IEC Jim Davis Regional Marketing Engineer Fluke Networks
Field Testing and Troubleshooting of PON LAN Networks per IEC 61280-4 Jim Davis Regional Marketing Engineer Fluke Networks Agenda Inspection and Cleaning APC vs UPC PON basics Wavelengths Architecture
More informationSINGLE MODE OPTICAL FIBER CABLE SPECIFICATION (ARSS)
SINGLE MODE OPTICAL FIBER CABLE SPECIFICATION (ARSS) No. FT-S16274 Version: A (ITU-T Rec. G.652.D) Futong Group Communication Technology (Thailand) Co., Ltd. All Right Reserved Add: No.7/324, Moo 6, T.Mabyangporn
More informationConnectix Cabling Systems
Connectix Cabling Systems Cabling Standards and CPR Update Connectix CEP Fibre Optic Solutions Jason Holroyd CNID Director of Business Development Types of fibre Agenda Introduction Uses Construction Transmission
More informationRFP LC Uniboot to RFP LC Uniboot Patch cord, 2 fibres, Interconnect tight-buffered cable, LSZH
1 1 9.41 115 0 Pretium EDGE 143 RFP LC Uniboot to RFP LC Uniboot Patch Pretium EDGE Solutions jumpers are integrated reverse -polarity uniboot duplex assemblies that meet the high -density space requirements
More informationAssembly code page 46. Cable code page 47. Assembly classes page 48. Polarization maintaining assemblies page 52
cable assemblies Assembly code page 46 Cable code page 47 Assembly classes page 48 Polarization maintaining assemblies page 52 45 Assembly: Ordering code Description cable type 27H01CD0- see cable code
More informationThe current state of multimode OTDR and Light Source and Power Meter (LSPM) Insertion Loss (IL) testing is as follows:
APPLICATION NOTE Meeting the Encircled Flux Launch Standard Scope: Guidance on how to test to the Encircled Flux (EF) multimode launch standard using existing optical test equipment and the Optronics Encircled
More informationIntroduction to Fibre Optics
Introduction to Fibre Optics White paper White Paper Introduction to Fibre Optics v1.0 EN 1 Introduction In today s networks, it is almost impossible to find a network professional who has never been in
More informationHow to Specify MTP Pre-terminated Optical Cabling. January White Paper. Published
White Paper How to Specify MTP Pre-terminated Optical Cabling Published January 2009 The benefits of pre-terminated cabling The two principal advantages of pre- terminated cabling are reduced time on site
More informationSpecification for Loose Tube Fiber Optic Cable (Non-Metallic, Dry Block, Figure-8) (G.652.D)
2-3, Marunouchi 2-chome, Chiyoda-ku, Tokyo 100-8322, Japan No. FB-KL4001C for Loose Tube Fiber Optic Cable (Non-Metallic, Dry Block, Figure-8) (G.652.D) Aug 2014 1 1. General This specification describes
More informationThe need for Encircled Flux, real or imaginary?
Version 1.7 The need for Encircled Flux, real or imaginary? Harley Lang, RCDD Fluke Networks 14 March, 2013 Presentation agenda What s the issue Mandrels are they needed? Review of standards Coupled Power
More informationCOPYRIGHT 2011 AXON DIGITAL DESIGN B.V. ALL RIGHTS RESERVED
Fiber connectivity GEP100 - HEP100 Fiber optic connections: an alternative to coaxial 3Gb/s, HD, SD embedded domain Dolby E tocables PCM decoder with audio shuffler A A product application note Quad speed
More informationGYFTY TECHNICAL SPECIFICATIONS FOR GYFTY CABLE
TECHNICAL SPECIFICATIONS FOR GYFTY CABLE 1 1. Product Description This specification covers the general requirements and performance of cable, which FOC offered including optical characteristics, mechanical
More informationØ 1000 * 588 mm 50 kg
GOCN Central Loose Tube Cables Outdoor Corrugated Steel Tape Armor (CST) A-DQ(ZN)(SR)2Y Full Rodent Protection Ordering Information Belden European Part Numbers Fibre type / count 4 6 8 12 16 24 62.5/125-OM1
More information100GBASE-DR2: A Baseline Proposal for the 100G 500m Two Lane Objective. Brian Welch (Luxtera)
100GBASE-DR2: A Baseline Proposal for the 100G 500m Two Lane Objective Brian Welch (Luxtera) Supporters Rob Stone (Broadcom) IEEE 802.3cd Task Force, July 2016 2 100G-DR2 Configuration: A 2x50 Gb/s parallel
More informationLIIN-25 FO Pigtail FC (0.9mm)
LIIN25 FO Pigtail FC (0.9mm) Features Single and Multi Mode ISO900, RoHS Compliant Test Certificate for each item Batch number tracking Standards of reference and applications ITU.T G652.D, ISO/IEC 80,
More informationFREEDM Loose Tube Interlocking Armored Cables
features and benefits Flexible, interlocking armor design Gel-free waterblocking technology Color-coded tubes and fibers UV-resistant, flameretardant jacket UV-Resistant Flame-Retardant Outer Jacket InterlockingArmor
More informationRFP LC Uniboot to RFP LC Uniboot Patch cord, 2 fibres, Interconnect tight-buffered cable, LSZH
1 1 9.41 115 0 Pretium EDGE 143 RFP LC Uniboot to RFP LC Uniboot Patch Pretium EDGE Solutions jumpers are integrated reverse -polarity uniboot duplex assemblies that meet the high -density space requirements
More informationHI-DEX PRODUCT SET DATASHEET
APPLICATION HI-DEX is an ultra high-performance, pre-terminated and modular optical fibre cabling system based on MT ferrule connector technology. This product set is designed for installationn in the
More information200GBASE-DR4: A Baseline Proposal for the 200G 500m Objective. Brian Welch (Luxtera)
200GBASE-DR4: A Baseline Proposal for the 200G 500m Objective Brian Welch (Luxtera) IEEE 802.3bs Task Force, May 2016 Supporters Tom Issenhuth (Microsoft) Rob Stone (Broadcom) Eric Baden (Broadcom) Steve
More informationBendBright XS Single Mode Optical Fibre
Draka Comteq Optical Fibre Issue date: 11/07 Supersedes: 03/07 Single Mode Optical Fibre Enhanced low macrobending sensitive, low water peak fibre Product Type: G.652D, G.657A&B Coating Type: ColorLock
More informationfor FOSTEC INC. 1/ 15
TECHNICAL SPECIFICATION for OPTICAL FIBER PATCH CORD / PIGTAIL FOSTEC / 5 . Scope: This specification is applicable to optical fiber patch cord, pigtail and with w optical connectors. The pigtail is single
More informationInstallation of Optical Fiber
Application Notes Installation of Optical Fiber Author Mr. Prasanna Pardesi This procedure describes general information for installation of optical fiber cable pulled or blown in HDPE ducts. Keywords
More informationMembership: At the previous meeting I reported the m/ship number of 201 (inc. temp members not coverted to full members) - Changes since then:
FIA Secretariat Report Council meeting Tuesday 18 th March 2008 Actions: Actions completed from previous meeting 1 st February 2008 Membership: At the previous meeting I reported the m/ship number of 201
More informationGBRE. Multi Loose Tube Cables Outdoor A-DQ(ZN)B2Y Improved Rodent Protection. Ordering Information. Applications. Features & Benefits
GBRE Multi Loose Tube Cables Outdoor A-DQ(ZN)B2Y Improved Rodent Protection Ordering Information Belden European Part Numbers Fibre type / count 84 96 62.5/125-OM1 GBRE184 GBRE196 -OM2 BW /1200 GBRE284
More informationJob Aid Server and CSS Separation Avaya S8700 Media Server
Overview of server separation Job Aid and CSS Separation Avaya S8700 Media This job aid provides information regarding the separation of S8700 Media s and the Separation of duplicated Center Stage Switch
More informationA guide to Woolworths Limited additional requirements. for the testing of twisted pair and fibre installation.
22 nd August 2013 A guide to Woolworths Limited additional requirements for the testing of twisted pair and fibre installation. Background This document has been prepared by VTI Services and approved by
More informationMTS/T-BERD Platforms WDMPMD Module
ACTERNA TEST & MEASUREMENT SOLUTIONS MTS/T-BERD Platforms WDMPMD Module Key Features A unique solution combining OSA, PMD, and SA test functions in one plug-in module The most compact PMD/WDM/SA test solution
More informationIntroduction to Fiber Optic Cable Technology Jerry Bednarczyk, PE Course Content
Introduction to Fiber Optic Cable Technology Jerry Bednarczyk, PE Course Content Page 1 of 10 GENERAL A fiber optic cable system is very similar to a copper wire system in that it is used to transmit data
More informationETSI ES V1.1.1 ( )
ES 202 319 V1.1.1 (2004-06) Standard Transmission and Multiplexing (TM); Passive optical components and cables; Optical fibre cables to be used for patchcord applications for single-mode optical fibre
More informationCable Jacket - The outermost layer of the fiber cable. Application: Types Single mode Multi mode. Simplex or Duplex available
Fiber Optic Products FIBER OPTIC PRODUCTS FIBER OPTIC PATCH CORD CABLE The Construction of a Fiber-Optic Cable Cable Jacket - The outermost layer of the fiber cable. Strengthening fibers - The strengthening
More informationCable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification
General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall obtain authorization from
More informationScope: Using Wave Division Multiplexing (WDM) for the Protection Data Interface (PDI) of the 7SD5 / 7SD61.
Page 1 of 10 Using Technology for the PDI of the and 7SA522/7SA6 Scope: Using Wave Division Multiplexing () for the Protection Data Interface (PDI) of the 7SD5 /. Two important issues related to differential
More informationTECHNICAL SPECIFICATION
ISSUED : OCT. 02, 2006 PAGE : 1 OF 9 REV. : 1 TECHNICAL SPECIFICATION FOR GST 2006-043A LOOSE TUBE DRY CORE CABLE SINGLE JACKET/SINGLE ARMOR (SJSA CABLE) Prepared By : Oh-Heoung Kwon Engineer Optical Technical
More informationHigh Speed Data Connector (HSSDC) For 100 MBit/Sec Token Ring. John L. Hill AMP Incorporated July, 1998
High Speed Data Connector (HSSDC) For 100 MBit/Sec Token Ring John L. Hill AMP Incorporated July, 1998 High Performance Cable Assembly Characteristics Controlled/Matched Impedance Connectors and Cables
More informationSOLO ADSS Short-Span Cables, Fibers
features and benefits Loose tube design Self-supporting Track-resistant jacket available Innovative waterblocking cable core SOLO ADSS Cable Drawing ZA-2615 Stable performance and compatibility with all
More informationUniprise Solution Brochure. North America/CALA.
Uniprise Solution Brochure North America/CALA Exceptional Value. Headroom to Standards. Simplicity by Design. Uniprise delivers quality, easy-to-use solutions that work from day one to support customer
More informationPre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017
Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM-2017-2 Date: 05/26/2017 Additional specification information for data communication to cameras and between Library
More informationPublic Works Division Lighting District Fiber Optic Specifications April 2009
Public Works Division Lighting District Fiber Optic Specifications April 2009 7000 Florida Street Punta Gorda, Florida 33950 Tele: 941.575.3600 Fax : 941.637.9265 www.charlottecountyfl.com/publicworks
More informationThe advantages of using reduced coating diameter optical fibers (200µm) in ADSS cables for deployment in FTTx networks
The advantages of using reduced coating diameter optical fibers (200µm) in ADSS cables for deployment in FTTx networks Paul van Zyl CBI Electric Telecom Cables Brits, South Africa +27-12-381-1498 pvzyl@cbitele.com
More informationSPECIAL SPECIFICATION 6191 Fiber Optic Cable
2004 Specifications CSJ 0014-02-014, etc SPECIAL SPECIFICATION 6191 Fiber Optic Cable 1. Description. Furnish, install, splice, field terminate, and test the fiber optic cables. 2. Materials. A. General
More informationSPECIAL SPECIFICATION 2284 Fiber Optic Cable (Self-Supporting)
2004 Specifications CSJ 0086-14-046 SPECIAL SPECIFICATION 2284 Fiber Optic Cable (Self-Supporting) 1. Description. Furnish, install, splice, field terminate, and test the fiber optic cables. 2. Materials.
More informationUNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE
UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE Prepared in cooperation and approval from BICSI Building Industry Consulting Services International and
More informationInstalaciones de fibra optica en entornos de centro de datos y campus para suportar 40, 100G y mas
Instalaciones de fibra optica en entornos de centro de datos y campus para suportar 40, 100G y mas Jim Davis Regional Marketing Engineer Fluke Networks Agenda Inspection and Cleaning Loss Budgets TIA (Cabling)
More informationFiber Optic Meter Fiber Optic Source
FOM/FOS Fiber Optic Meter Fiber Optic Source Warning To avoid injury: do not service the FOM or FOS unless you are qualified to do so. The service information provided in this document is for the use of
More informationMining and Petrochemical Fiber Optic Cables
Features and Benefits Loose construction Stable and highly reliable transmission parameters Waterblocking technology Allows efficient and craft-friendly cable preparation in outdoor or indoor/outdoor applications
More informationPluggable Transceivers Installation Guide
Pluggable Transceivers Installation Guide 121140-04 Published November 2017 Copyright 2017 Extreme Networks, Inc. All rights reserved. Legal Notice Extreme Networks, Inc. reserves the right to make changes
More informationCC-Link IE Controller Network Compatible. CC-Link IE Controller Network Recommended Network Wiring Parts Test Specifications
Model Title CC-Link IE Controller Network Compatible CC-Link IE Controller Network Recommended Network Wiring Parts Specifications Management number: BAP-C0401-028-A CC-Link Partner Association (1/31)
More informationNumber of Fiber 6 Core 12 Core. Part Number
Order Information OUTDOOR OFC-Drop Wire, MM (OM2) (50/125) LOOSE TUBE BLACK Number of Fiber 6 Core 12 Core Part Number 74550006 74550012 1. General 1. Scope 2. Quality Assurance This specification covers
More informationEVLA Fiber Selection Critical Design Review
EVLA Fiber Selection Critical Design Review December 5, 2001 SJD/TAB 1 Fiber Selection CDR Decision about what fiber to install Select cable Jan 2002 Order cable Jan 2002 Receive cable May 2002 Start installation
More information50 Gb/s per lane MMF baseline proposals. P802.3cd, Whistler, BC 21 st May 2016 Jonathan King, Finisar Jonathan Ingham, FIT
50 Gb/s per lane MMF baseline proposals P802.3cd, Whistler, BC 21 st May 2016 Jonathan King, Finisar Jonathan Ingham, FIT 1 Supporters Chris Cole, Finisar Doug Coleman, Corning Scott Kipp, Brocade Kent
More informationWhat really changes with Category 6
1 What really changes with Category 6 Category 6, the standard recently completed by TIA/EIA, represents an important accomplishment for the telecommunications industry. Find out which are the actual differences
More information3M Telecommunications. Solutions for Networks. 3M MPO solutions. High Density Networks. Technology built for business
3M Telecommunications Solutions for Networks 3M MPO solutions High Density Networks Technology built for business 2 3M Telecommunications Solutions for Networks 3M Telecommunications Solutions for Networks
More information500 m SMF Objective Baseline Proposal
500 m SMF Objective Baseline Proposal Jon Anderson, Oclaro John Petrilla, Avago Technologies Tom Palkert, Luxtera IEEE P802.3bm 40 Gb/s & 100 Gb/s Optical Ethernet Task Force SMF Ad Hoc Conference Call,
More informationOCC Installation Conduit Guidelines Excerpt from Optical Cable Corporation s INSTALLATION GUIDE
Installation Conduit Guidelines Excerpt from Optical Cable Corporation s INSTALLATION GUIDE Conduit Installation A conduit cable installation involves placement of one or more optical cables inside a preinstalled
More information100G CWDM Link Model for DM DFB Lasers. John Petrilla: Avago Technologies May 2013
100G CWDM Link Model for DM DFB Lasers John Petrilla: Avago Technologies May 2013 Background: 100G CWDM Link Attributes Since the baseline proposal for the 500 m SMF objective based on CWDM technology
More information10GBASE-LRM Interoperability & Technical Feasibility Report
10GBASE-LRM Interoperability & Technical Feasibility Report Dan Rausch, Mario Puleo, Hui Xu Agilent Sudeep Bhoja, John Jaeger, Jonathan King, Jeff Rahn Big Bear Networks Lew Aronson, Jim McVey, Jim Prettyleaf
More information64G Fibre Channel strawman update. 6 th Dec 2016, rv1 Jonathan King, Finisar
64G Fibre Channel strawman update 6 th Dec 2016, rv1 Jonathan King, Finisar 1 Background Ethernet (802.3cd) has adopted baseline specs for 53.1 Gb/s PAM4 (per fibre) for MMF links 840 to 860 nm VCSEL based
More information3M 8900 Single-mode SC Crimplok Connector
3M 8900 Single-mode SC Crimplok Connector Technical Report June 1999 80-6110-1441-8 1 1.0 Product Description & Requirements The 3M SC Single-mode Crimplok Connector is designed to provide the customer
More informationCisco 10GBASE Dense Wavelength-Division Multiplexing SFP+ Modules
Data Sheet Cisco 10GBASE Dense Wavelength-Division Multiplexing SFP+ Modules Use Dense Wavelength-Division Multiplexing (DWDM) SFP+ modules to integrate WDM transport directly into your Cisco 10 Gigabit
More information100G SR4 Link Model Update & TDP. John Petrilla: Avago Technologies January 2013
100G SR4 Link Model Update & TDP John Petrilla: Avago Technologies January 2013 100G 100m Transceivers Summary Presentation Objectives: Provide an update of the example link model for 100G 100m MMF Discuss
More informationProduct Catalogue. Fibre Optic Cable
Product Catalogue Fibre Optic Cable version 2017 Empowering businesses through innovative network solutions. We have been pushing boundaries and providing innovative products and solutions to clients around
More information