Installation instructions Roxtec RM BG B systems

Similar documents
Installation instructions Roxtec RM BG systems

Installation instructions Roxtec RM ES systems

Installation instructions Roxtec CM PE systems

Installation instructions Roxtec RM PE

Installation instructions Roxtec RM ES

Installation instructions Roxtec RM PE B

Installation instructions Roxtec RM ES B

Installation instructions Roxtec CF 16 EMC and Roxtec CF 16 O EMC

Installation instructions Cable transit device Roxtec RS ES Ex

Installation instructions Ex frames

Installation instructions Roxtec RS ES Ex

3M Better Buried Compound Compression Closure System

3M Distribution Box (DDB)

3M SLiC 530/533/733-2 Port 0.61 Cable Entry Bracket 3M SLiC 530/533/733-2 Port-MSM 0.61 Cable Entry Bracket

Instructions. Cable with Armor F CAUTION. October Rev A

FOSC 450 C6 and D6 Closures

3 Foam Sealed Closure 2" (50 mm) with Compound Compression

2178-L/S Series Fiber Optic Splice Case with Gasket

3M Better Buried Closures

Installation Instructions

3M Locator Plate N

3M Better Buried Closure (with 3M Scotchlok Shield Bond Connector 4462-FN and 3M High Gel Re-enterable Encapsulant 8882)

3 SLiC Aerial Closure with Rubber End Seal

SLiC Fiber Aerial Closure System

2178 Fiber Optic Splice Case and 2181 Cable Addition Kit

1672A. Product Description. Product Specifications. Technical Specifications. Conductor. APAC Standard. Bend Radius.

18mm ECAM Cable Entry Port

2179-CD Series Fiber Optic Splice Closure. Installation Instructions

3M Fiber Optic Splice Closure 2178-XSB/XSB-FR & 2178-XLB/XLB-FR 3M Cable Addition Kit 2181-XB/XB-FR

K & B Flame Retardant Building Riser Closures

3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR

27mm ECAM Double Cable Entry Port

MX-MOLDED READY VGA TO BNC CABLES MX-2076 MX MDR Electronics

3M Scotchcast Reenterable Signal and Control Cable Splicing Kits 78-R Series

FOSC-450D. Fiber Optic Splice Closure. 1 Introduction. Content. 5 Cable termination. 6 Fiber routing. 2 General. 7 Installation of the gel block

3M Cold Shrink Foldback Splice Jacket Kit

3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR 3M Cable Addition Kit 2181-XL and 2181-XL/FR

ENGINEERING COMMITTEE

SPECIFICATION. Spec No : VSS-1402-CS603B

DVDO VS4 HDMI Switch. User s Guide How to install, set up, and use your new DVDO product

Medium Box for Cable Termination

3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT

3 Closure preparation 3.1 Work-stand 3.2. Opening FIST-GCOG2-Dx Preparing drop cable with micro-tubes

Scotch Heavy Duty Vinyl Electrical Tape 22

RAIL D-SUB BACKSHELLS

MX-MOLDED READY VGA CABLES MX-2074, 2075, 2079,(LOW AND MID) MX-2987,(HIGH END) MDR Electronics

Instruction Guide February 2017

MX-VGA CABLE MX-2107 AND MX MDR Electronics

3M Super 23 Electrical Tape

User Manual. Model 979T and 979R Digital Audio Converters

VGA to DVI Extender over Fiber SET

3M Fiber Optic Splice Tray 2527 with 3M PLC Optical Splitter

3M No Polish Jacketed SC/APC Connector

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN

3M Fiber Closures BPEO

FIST-MB2-S. FIST Medium Box for Cable Splicing Only. 4 Cable installation. 1 Introduction. Contents. 2 General. 5. Fiber routing to individual trays

LCC (Little Coaxial Connector) Installation Instructions)

INSTALLATION INSTRUCTIONS

3M Scotchcast Mine and Portable Cable Splice and Jacket Repair Kit M-40

Photovoltaic Module Installation Manual (IEC)

High Density Block BRCP. HD BRCP- 128/192/256 pair. Installation Instructions

FOSC-600 C and D I N S T A L L A T I O N I N S T R U C T I O N

3M Cold Shrink Splice Kit QS-III 5416A

3M Cold Shrink Splice Kit QS-III 5515A

3M Scotchcast Flexible Power Cable Splice Kits 82-F Series

3M No Polish Jacketed SC/APC Connector

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE Specification for F Connector, Male, Pin Type

Cold Shrink Three-Conductor Splice Kit QS-III for use on Armor and Non-Armor Cables Instructions IEEE Std kv Class 250 kv BIL

3M Fiber Optic Closure System LL

3M Cold Shrink Splice Kit QS-III 5514A

Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

USER MANUAL. WARNING Read the instructions before using the machine. EN (Original Instruction) / 1704

Model Number Structure

Photovoltaic Module Installation Manual (IEC)

OPERATION AND MAINTENANCE MANUAL

Surface Mount Multilayer Ceramic Capacitors for RF Power Applications

Interface Practices Subcommittee SCTE STANDARD SCTE Test Method for Drop Cable Center Conductor Bond to Dielectric

E8Y. Micropressure Sensor with Easy-to-Read Digital Display. Differential Pressure Sensor. Ordering Information. Sensors

R87B. Box Fan. Comprehensive Lineup of Single, Double, and Triple Axial Fans with Easy One-step Mounting. Model Number Structure. Ordering Information

HSK Mine and Portable Cable Splice

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500

6000 Series Patch Panel Terminating Instructions

Quante BPEO Splice-Protection Closure for Optical Fiber Cables. Features Advantages Benefits

ASSEMBLY, INSTALLATION, AND REMOVAL OF CONTACTS AND MODULES

3M 8900 Single-mode SC Crimplok Connector

Surface Mount Multilayer Ceramic Capacitors for RF Power Applications

Sections 1. Application Equipment 2. Cable Preparation 3. Assembly 4. Termination Procedure 5. Inspection 6. Repair 7.

Multi-Media Card (MMC) DLL Tuning

VGA Extender over Single CAT 6 Cable with Audio Support. Model Extend both video and audio up to 1000 feet

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

In-Wall Control Mount for ipod Touch

Atlona HDBaseT-Lite Transmitter over Single CAT5e/6/7

KEL 24 Cable entry frames

3M Cold Shrink QS4 Integrated Splice Kit QS4-35TS

XS_-EU. M8 and M12 Sensor Connectors. Ordering Information

Surface Mount Multilayer Ceramic Chip Capacitors for High Frequency

3G/HD/SD-SDI to HDMI Converter

3M Sensored Termination (15 kv) QX-T15I-vi1-E

ENGINEERING COMMITTEE

CR-R880-BL: Indoor/Outdoor Proximity Reader with 10cm (4in) read range

Transcription:

Safety information Roxtec recommends that all installations are performed without facility operation. Follow national regulations and installation codes. ny action affecting the routed service should be performed according to manufacturer recommendations. Components Installation instructions Roxtec RM G systems Roxtec RM G module Roxtec RM G solid module Roxtec Lubricant Roxtec RM G modules measures in millimeters (mm) Roxtec RM G solid modules Module size For cable outer diameter min-max Module size RM 20 G 4-14.5 RM 20w40 G 3.5-16.5 RM 30 G 10-25 RM 30H90 G 10-25 RM 40 10-32 G 9.5-32.5 RM 40 G 21.5-34.5 RM 40H80 G 21.5-34.5 RM 20/0 G RM 30/0 G RM 40/0 G RM 60/0 G RM 30H90/0 G RM 40H80/0 G RM 10w120/0 G RM 60 24-54 G 24-54 RM 60 G 28-54 RM 80 G 48-71 RM 90 G 48-71 RM 120 G 67.5-99 Note: The range of the modules indicates the smallest diameter of the exposed cable screen to the largest diameter of the cable jacket. Modules with core can be used as spare parts.

Roxtec RM G module D F D D C E C E : Environmental side : Termination/interior side C: Removable layers D: Cable armor E: Module braid F: Cable jacket Recommended tools (not included) 13 mm spanner EMC marking tool Cable stripper tool. Continuity tester Roxtec Recommended by the cable installation tools manufacturer

Installation 1 2 3 4 ll G frames must be clean and have electrical contact with protective earth. National regulations apply. Hold the cable in its final position. Use the guide to mark where the cable jacket is to be removed. Remove the outer jacket and any plastic foil. The cable armor shall be clean and conductive. Secure the end of the cable armor. Suggestions for cable preparations are available on www.roxtec.com. 5 6 Packing space Frame size Frame height (H) Frame width (w) Packing height (h) 1 101 60 60 2 101 120 60 h H 3 160 60 120 4 160 120 120 5 218 60 180 6 218 120 180 7 278 60 240 w 8 278 120 240 Correct placement of a cable in a RM G module. The cable armor shall be visible outside the module. Measure your frame height (H) and check the corresponding packing height (h) in the table. Consider your packing height when inserting the modules. 7 8 9 10 Remove the core and fold out the braid. chieve a gap of 0.1-1.0 mm () between the module halves by peeling off layers. The cable armor shall be in contact with the braid. The number of layers may not differ () by more than one between the corresponding module halves. dapt the layers that are in contact with the cable jacket.

11 12 13 14 dapt the layers that are in contact with the cable armor. Fold the braid tightly inside the module half. Lubricate the sealing surfaces of all modules. void excess lubricant on the braid. Lubricate the sealing surfaces of the spare modules. Do not remove the core. 15 16 17 18 Lubricate the sealing surfaces of the solid modules. Lubricate the inside surfaces of the frame and especially its corners. Lubricate the area that will be in contact with the braid sparsely. Place modules according to your packing plan. When placing cables in modules, the cable armor shall be visible outside the module at the termination side. 19a 19b 20 21 Place cables and the corresponding module halves on top. For pass-through cables, cable armor shall be visible on the termination side. Insert a stayplate on top of every finished row of modules. The stayplate shall be clean and conductive. To simplify installation, the use of a pre-compression tool on every second module row is recommended.

22 23 24 2x 25 Ensure that the modules () are secured within the stayplate () edges. Separate the two stayplates and insert the final row of modules between the stayplates. 28 27 Use a Roxtec pre-compression tool to make space for the compression unit if required. 30 Turn the screws of the wedge counter clock-wise to full stop before inserting it. 31 Place the upper stayplate on top of the modules. 29 Lubricate both short sides of the wedge. 32 25 mm () of the screws shall be exposed. Insert the wedge so the stop flange () is in contact with the frame (). 33 Tighten the screws alternately until full mechanical stop, approx. 20 full revolutions per screw. Do not exceed 20 Nm. www.roxtec.com www.roxtec.com 26 efore inserting the final row of modules, insert two stayplates. ttach the wedge clip to the wedge screws to complete the installation. Completed installation.

34 Optional: Verify earth continuity from each cable armor to earth. Use a suitable instrument.

Disassembly and reinstallation 1 2 3 4 C Remove the wedge clip from the wedge. Loosen the screws alternately to full stop. Do not exceed 20 Nm. Insert a flat tool () between the wedge () and the stayplate (C) to simplify removal of the wedge. Roxtec tools are available. Remove modules and stayplates. 5 6 7 8 Note: Keep the rows sorted until it is time for reinstallation. If a module is damaged or replaced, all modules in that row must be replaced. The inside surfaces of the exposed packing space shall be clean and conductive. Lubricate the inside surfaces. Lubricate the area that will be in contact with the braid sparsely. Lubricate all corners carefully. Continue the reinstallation.

Roxtec RM G modules raid conductor properties Module size Total braid cross-section mm² pproximately equivalent WG RM 20 G 8 8 RM 20w40 G 4* 11 RM 30 G 13 6 RM 30H90 G 21 4 RM 40 10-32 G 21 4 RM 40 G 21 4 RM 40H80 G 42 1 RM 60 24-54 G 42 1 RM 60 G 42 1 RM 80 G 42 1 RM 90 G 42 1 RM 120 G 42 1 * Per cable rticle number: SS2006004801 Document number: SS2011002501 revision D Note Integrated environmental sealing system for bonding and grounding applications. For use with armored cables. For optimum reliability, wait 24 hours or longer after installation before exposing the cables or pipes to strain or pressure. Corrosion preventing primer must be removed to achieve electrical conductivity, where applicable. Cables shall go straight through the frame. pprovals or certificates may include amendments or limitations related to this application. The latest version of this and related documents are found at roxtec.com. Disclaimer The Roxtec cable entry sealing system ( the Roxtec system ) is a modular-based system of sealing products consisting of different components. Each and every one of the components is necessary for the best performance of the Roxtec system. The Roxtec system has been certified to resist a number of different hazards. ny such certification, and the ability of the Roxtec system to resist such hazards, is dependent on all components that are installed as a part of the Roxtec system. Thus, the certification is not valid and does not apply unless all components installed as part of the Roxtec system are manufactured by or under license from Roxtec ( authorized manufacturer ). Roxtec gives no performance guarantee with respect to the Roxtec system, unless (I) all components installed as part of the Roxtec system are manufactured by an authorized manufacturer and (II) the purchaser is in compliance with (a), and (b), below. (a) During storage, the Roxtec system or part thereof, shall be kept indoors in its original packaging at room temperature. (b) Installation shall be carried out in accordance with Roxtec installation instructions in effect from time to time. The product information provided by Roxtec does not release the purchaser of the Roxtec system, or part thereof, from the obligation to independently determine the suitability of the products for the intended process, installation and/or use. Roxtec gives no guarantee for the Roxtec system or any part thereof and assumes no liability for any loss or damage whatsoever, whether direct, indirect, consequential, loss of profit or otherwise, occurred or caused by the Roxtec systems or installations containing components not manufactured by an authorized manufacturer and/or occurred or caused by the use of the Roxtec system in a manner or for an application other than for which the Roxtec system was designed or intended. Roxtec expressly excludes any implied warranties of merchantability and fitness for a particular purpose and all other express or implied representations and warranties provided by statute or common law. User determines suitability of the Roxtec system for intended use and assumes all risk and liability in connection therewith. In no event shall Roxtec be liable for indirect, consequential, punitive, special, exemplary or incidental damages or losses. Roxtec International ox 540, 371 23 Karlskrona, SWEDEN Phone +46 455 36 67 00, Fax +46 455 820 12 Email info@roxtec.com, www.roxtec.com Roxtec and Multidiameter are registered trademarks of Roxtec in Sweden and/or other countries.