Quick Start Function Summary Instructions for ASHCROFT GC52 Differential Pressure Transmitter Version 6.03 Rev. B

Similar documents
Installation and Maintenance Instructions for GC51 Rangeable Pressure Transmitter

User s Guide PX5100. Shop online at omega.com SM. Quick Start Function Summary Instructions for OMEGA PX5100 Rangeable Pressure Transmitter

Instruction Manual MODEL RSP SANITARY ELECTRONIC PRESSURE TRANSMITTER

T775U Series 2000 Electronic Stand-Alone Controller

GC30 Digital Differential Pressure Gauge Operation Manual

T775U Series 2000 Electronic Stand-Alone Controller

COMPANY. MX 9000 Process Monitor. Installation, Operating & Maintenance Manual AW-Lake Company. All rights reserved. Doc ID:MXMAN082416

Rosemount 1151 Smart Pressure Transmitter

GC61 Digital Pressure Gauge. Operation Manual

Signet 2250 Hydrostatic Level Sensor

LAUREL ELECTRONICS, INC.

TEK-LCD 7801A. NEMA 4X Loop-Powered Feet and Inches Level Meter. ACCESSORIES. Technology Solutions

T775L Series 2000 Electronic Stand-Alone Staging Controller

SCALE & WEIGHT DISPLAYS

T-Series "SMART" Sanitary Pressure Transmitter

ProVu PD6000 Process Meter

Smart-Encoder : Optical Incremental

LAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description

Process Transmitter RMA 422

Data Acquisition Networks. Installing and Configuring the DM01 Hardware

MF-PFT. Programmable differential pressure transmitter for pressure or flow measurement and control. DIL1 Output/Utsignal

REMOTE I/O R30 SERIES. PC CONFIGURATOR SOFTWARE Model: R30CFG Ver Users Manual

McCROMETER. RE100 Electronic Register. Programming Guide

800 Displaying Series Flowmeter

Operating Instructions

SC26 Magnetic Field Cancelling System

LVDT. Inductive Position Transducer - Hydraulic Series. SM-HYD Hydraulic Series. Key-Features:

HDBT Installation Guide

The measurements are stored in non-volatile memory, which retains data even when the power down.

2 WIRE - LOOP POWERED TRANSMITTER FOR PT100 AND NI100 PROBES

Weekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N

Distributed Design Series

UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load Cell

Installation and Setting up Instructions for the 990 Signal Conditioning Instrument

TABLE OF CONTENTS. Instructions:

Operating Instructions

Getting Started with the LabVIEW Sound and Vibration Toolkit

THE ASTRO LINE SERIES GEMINI 5200 INSTRUCTION MANUAL

EZ Encoder : Optical Incremental (P Series)

Short Manual. ZX2 Short Manual.doc Page 1 of 12

Operating instructions Electronic preset counter Type series 717

Ocean Sensor Systems, Inc. Wave Staff, OSSI F, Water Level Sensor With 0-5V, RS232 & Alarm Outputs, 1 to 20 Meter Staff

C200H-AD002/DA002 Analog I/O Units Operation Guide

PACSystems* RX3i Thermocouple Input Module, 12 Channels, IC695ALG412-CB

Commander 384. w w w. p r o l i g h t. c o. u k U S E R M A N U A L

DEX Fruit & Stem Growth Dendrometer User Manual

ELECTRICAL. DATA AND INDEX Not all complements shown A shown for reference. Index A leads B, CW (from shaft end) TERMINAL CONNECTIONS COM VCC CASE

Metric Series. PXM409 Differential Series. mv/v, 0 to 5 or 0 to 10 Vdc, or 4 to 20 ma Outputs Uni-Directional Ranges 0-25 mbar to 0-70 bar

RK-2 ENVIRONMENTAL DATA CONTACTLESS MAGNETOSTRICTIVE LINEAR POSITION TRANSDUCER WITH FLANGED HEAD. Main characteristics

LX3V-4AD User manual Website: Technical Support: Skype: Phone: QQ Group: Technical forum:

Digital Differential Pressure Gauge Switch 0.1 : 0.5 BAR USER GUIDE

EDL8 Race Dash Manual Engine Management Systems

Micro-DCI 53ML5100 Manual Loader

A summary of all menu lines available in self-diagnostic mode is shown below.

3M Distribution Box (DDB)

Quick Start Operating Instructions

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

F90 Series (Rate Indicators / Controllers) INSTRUCTION MANUAL

+GF+ SIGNET 8860 Dual Channel Conductivity/Resistivity Controller

Spectra Batten (Order code: LEDJ95)

K3NX Process Meter OPERATION MANUAL

Junior Max (JR Max ) Controller

VLC-3 USER'S MANUAL. Light Program Controller. M rev. 04 K rev. 00 & ( ( 5, 352*5$0 1 : $ 2 ' 6(77,1*6 )81&7,216

INSTRUCTION & OPERATION MANUAL. MODEL MMW-05 (5kW) MUROMACHI MICROWAVE FIXATION SYSTEM

AX 345. Process Indicator with Two Analogue Inputs, Calculations and Programmable Analogue Output. Operating Instructions for Model AX 346

Micro-Machined Silicon Transducers

UV Power Monitor. incident light 200 to 370 nm 300 C (Use at temperatures below the Fiber Unit s rated operating

Ambient SO 2 /H 2 S monitor APSA-H370 Instruction Manual

Troubleshooting. 1. Symptom: Status indicator (Red LED) on SSR is constant on. 2. Symptom: Output indicator (Yellow LED) on SSR is flashing.

Quick-Start for READ30

SLiC Fiber Aerial Closure System

Ambient NH 3 monitor APNA-370 Instruction Manual CODE:GZ

FOSC-600 C and D I N S T A L L A T I O N I N S T R U C T I O N

ORM0022 EHPC210 Universal Controller Operation Manual Revision 1. EHPC210 Universal Controller. Operation Manual

TeamWork Installation Guide

Pressure Sensor. Ordering Information. Mini-Cube Pressure Sensor with Easy-to-Read LED Display

Process transmitter RMA422

TeamWork Kits Installation Guide

FIELD MOUNTED RATE TOTALISER MODEL 202D

EchoSpan Two-Wire Ultrasonic Level Transmitter Model LU81/83/84 Owner s Manual

Ocean Sensor Systems, Inc. Wave Staff III, OSSI With 0-5V & RS232 Output and A Self Grounding Coaxial Staff

1. Safety precautions (Must Read)

Model IQ4-PC User Manual Revision Date:

Table of contents 1. INTRODUCTION GENERAL CONTENTS OF PACKAGE GENERAL USE OF THE EQUFLOW 6100 D/A CONVERTER STORAGE..

Contents: 1 LANsmart Pro Main Unit 4 Remote Unit: ID1, ID2, ID3, ID4

Inductive sensor. 2-wire, analog output BI8-M18-LI-EXI

PACSystems* RX3i. Isolated Thermocouple Input Module, 6 Channels, IC695ALG306-EB Isolated Thermocouple Input Module, 12 Channels, IC695ALG312-EB

User s Manual. Log Scale (/LG) GX10/GX20/GP10/GP20/GM10 IM 04L51B01-06EN. 3rd Edition

TECHNICAL MANUAL DRAW-WIRE DISPLACEMENT TRANSDUCER TYPE DWT

FOSC 450 C6 and D6 Closures

Sensopress LCD Special English

WECON LX3V-2TC2DA BD Board

2 CHANNEL RECEIVER DISPLAY POTENTIOMETER COM2 NC2 NO2

0.56" 4 Digital Blue LED Panel Meter (rescalable) User s Guide

JUMO extherm-at Type , explosion-proof surface-mounted thermostat for zones 1, 2, 21, and 22

FRQM-2 Frequency Counter & RF Multimeter

WECON LX3V-2PT2DA BD Board

1 Output 1 operation. 3 Pressure unit display. 4 Main display Large 4-character LCD display. 5 Sub-display Small 4-character LCD display.

Instructions. Cable with Armor F CAUTION. October Rev A

LadyBug Technologies, LLC LB5908A True-RMS Power Sensor

Transcription:

Quick Start Function Summary Instructions for ASHCROFT GC52 Differential Pressure Transmitter Version 6.03 Rev. B (See Complete I&M Manual for Further Detail) LOOK FOR THIS AGENCY MARK ON OUR PRODUCTS 2010 Ashcroft Inc., 250 East Main St., Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com All sales subject to standard terms and conditions of sale. I&M011-10164-GC52 Ver. 6.03 Rev. B 03/11

2

DISPLAY OVERVIEW Test Terminals Linear scaling mode Differential pressure unit monitor Total flow volume display (X1) CH+ In H2O GC52 CH 8.8.8.8.8.8. No function Scaling - Arbitrary unit monitor Measured data display Total flow volume display (X1000) Total flow volume display (X10) M MODE key DOWN key UP key Total flow volume display (X100) DESIGNATION Measured data display Differential pressure unit monitor Scaling; arbitrary unit monitor MODE key M DOWN key S UP key T Linear scaling mode No function to Total flow volume display FUNCTION Differential pressure, linear scaling value are displayed. When this unit monitor is ON, the differential pressure (in H 2O) is indicated on the measured data display. When this unit monitor is ON, the scaling value of an arbitrary unit (linear scaling), is indicated on the measured data display. This key is used to switch the setting mode and the measurement mode and to change the setting item. This key is used to change (decrease) and select the set value. This key is used to change (increase) and select the set value and to shift from the measurement mode to the zero adjustment mode. Change differential pressures into quantity None Accumulated volume calculated based on flow rate 3

1. UPON POWER-UP the unit enters Measure Mode displaying applied pressure. 2. TWO FUNCTION is available to the user in Measure Mode. A. Zero Adjustment Mode: In the measurement mode, the pressure connection is open to the atmosphere and $ key is pressed for more than 3 seconds in order to shift to zero adjustment mode for zero point adjustment of the differential pressure sensor If the zero point adjustment is performed correctly the message ADJ will be displayed for 2 seconds, and the display will return to the measurement mode. B. Key Lock Function Key Manual Indicator Setting of key lock MODE+$ one second LoC (Key invalidity) Release of key lock MODE+$ one second UnL (Key invalidity) Operation during keylock Function Key Manual Indicator Zero adjust. mode $ key greater than 3 sec LoC (Key invalidity) Hold value reset # key greater than 3 sec LoC (Key invalidity) 3. FIVE FUNCTIONS available to the User via Setting Mode. To enter the Setting Mode hold (M) key for more than 3 seconds. (See last page for complete Setting Mode menu.) A. Filter (Damping) The filter is based on the moving average of the pressure data to decrease display bounce and to smooth the analog output due to system pressure fluctuations at the user s discretion. Five selections: (0, 2, 4, 8 and 16 seconds), Use $ # keys to change value. If 0 is selected the filter is not applied. Note: Holding the 3 seconds returns to B. Re-scaling in inh 2 O units: Pressure Display Mode allows for zero (4mA) and span (20ma) adjustment of 10 to +110% Span respectively. Note: 1. See menu schematic on last page for detail. 2. Must be in Pressure Display Mode option within Setting Mode, this is noted on the screen by - n non Use $ #keys to move between Pressure Display Mode and Linear Display Mode which is for re-scaling in Arbitrary units. 4

3. To adjust Output Zero Point (4mA) and Output Span Point (20mA) the unit must be in the functional area as noted below while adjustment is via $ #keys. The value shown is a percentage of the pressure range (span) as noted on the product label (ex. If product was supplied as a 0-40 IWC range and the user desired the Output Zero Point (4mA) to be moved from 0 IWC to 20 IWC then Output Zero Point would be 50.0 which is 50%. Values shown below are from I&M manual.. Setting LCD Setting Setting Item Display Description Range Display Selection of non:pressure - n non mode pressure display display mode mode : non Lin: linear display mode Output Analog Pressure a 10.0 zero point output zero point range: 10 (4mA) : 10.0 (%Span) to 110% Span Output Analog Pressure span point output span point range: 10 a 90.0 (20mA) : 90.0 (%Span) to 110% Span Note: For setting of zero point and span point in the analog output, input the percent value over the pressure range. C. Re-scaling in Arbitrary units, Linear Display Mode. This function allows the user to establish a linear relationship from the standard inh 2 O unit to any user defined unit. Note: See menu schematic on last page. Unit must be in Linear Display Mode option within Setting Mode, this is noted on the screen by - n L;n Use $ #keys to move between Linear Display Mode and Pressure Display Mode. 5

Setting LCD Setting Setting Item Display Description Range Display mode Min. differential pressure n00l0n -- p0-20 Selection of linear display mode: Lin Min. differential pressure corresponding to OFFSET :20.0(inH 2 O) non: Differential pressure display mode; Lin: Linear display mode Differential pressure range: 0 to 75% Span Max. differential pressure p0-120 Decimal point position d0-001 Max. differential pressure corresponding to FULL SCALE :120(inH 2 O) Display after decimal point Number of digits: 1(digit) Differential pressure range: 25 to 100%Span 0,1,2,3 digit OFFSET d0-00.0 OFFSET corresponding min. differential pressure : 0.0 (m) 1999 to 1999 FULL SCALE d0-50.0 FULL SCALE corresponding to max. differential pressure :50.0 (m) 1999 to 1999 Output zero point a0-50.0 Analog output zero point : (4mA): 0.0 (%Span) Max. display span: 10 to 110% Span Output span point a0100.0 Analog output span point : (20mA): 100.0 (%Span) Max. display span: 10 to 110%Span Note: Values shown are from example in I&M manual. D. Flow Measurement/Square Root Extraction Mode Mode Square Square Root Display Mode Combining the sensing elements (orifice and pitot tube) with this product, the mode is used for the display of the momentary flow rate, integrated volume and for analog output corresponding to the momentary flow rate. (1) Momentary flow rate The momentary flow rate display has the maximum display span from zero to the maximum momentary flow rate. The Momentary flow rate display span depends on the setting of the zero point and span point of the analog output as shown in (2) analog output. It can display 0 to 105%F.S. display span. The scaling method of momentary flow rate can be performed only by setting the maximum momentary flow rate and then generate differential pressure using the following square root formula. Momentary flow rate Dx is expressed by the square root formula (a), and can be calculated only by measuring the generated differential pressure Px (percent value over the differential pressure range). (a) Dx = k x Px(%) 100(%) 6

In addition, the coefficient k is determined by substituting the maximum momentary flow rate Dm, which is measured from the formula (a), and the then generated differential pressure Pm into the formula (b). (b) k = Dm00 Pm 100 The differential pressure generated during the maximum momentary flow rate can be set in the range of 25 to 100%F.S. of the differential pressure range. The setting range for values of the maximum momentary flow rate is 0 to 1999. Note: The decimal point can be set arbitrarily. When the display resolution lowers and the wobbling of momentary flow rate increases in the low flow domain of the differential pressure flow meter, the domain (below the set value) will be forcedly indicated as zero by means of the low-cut for momentary flow rate. Moreover, the analog output has a fixed value of 4mA at the zero point. For setting of low-cut, input the percent value over the maximum display span. Its range is 0 to 30%F.S. and the decimal point position can be set up to one digit after decimal point as fixed point. (2) Analog output The zero point (4mA) and span point (20mA) of analog output can be set in the range of 0 to 110%F.S. of the maximum display span (0 to maximum momentary flow rate). The span between the zero point and the span point in this analog output is the momentary flow rate display span. (3) Integrated volume The units of integrated volume include two standards: Time factor and flow rate volume factor. The number of digits of integrated volume display is a maximum of 6 figures (999999); the display will return to 0 once the maximum reading has been met. clr overflows 0 999999 0 The zero reset of an integrated volume is executed by pressing S key for more than 3 seconds and displaying "clr" (clear) for 2 seconds. As backup in case of POWER OFF, the integrated volume value is stored in the nonvolatile memory for every hour. After power returns, integration starts from the integrated volume value stored in the memory. Integration is halted during the "FFF" display at the time of differential pressure range OVER. 7

The indicated value which is blinking is integrated during the "blink" display at the time of momentary flow rate display span OVER. Flow Measurement/Square Root Extraction Mode No. Setting Item LCD Display Setting Description Setting Range Default Display mode n~ Maximum differential selection 1 Flow rate decimal pt. position D 0 Max. momentary flow Low cut l Output zero point 2 Output span point 2 Time factor U Flow rate vol- 21 Display 22 switch setting 23 24 Selection for flow measurement/ square root extraction display mode Lin: Linear non: Differential pressure rot mode display mode Rot: Square root display mode p. 400 Maximum differential pressure relating to the flow rate D 1000 0.0 A 0.0 A100.0 SE[ Displays of value after decimal point, # of digits Max. momentary of flow using arbitrary units Forces display and output to zero 25 to 100% F.S. of sensor range 0,1,2,3 digit 0 to 1999 0.0 to 30.0% F.S. of max. display span non 100.0% of sensor range 0 1000 Momentary flow rate of analog output zero point (4mA): display span 0.0 10 to 100% F.S. of max. 100.0% F.S. Momentary flow rate of analog output zero point (20mA): 100.0% F.S. Measurement of max. momentary flow rate over time selected 0.0 10 to 100% F.S. of max. display span 100.0 Seconds, minutes or hours ume factor U 1 Flow rate x time selected 1,10,100,1000 1 s bt Switch time interval T 5 Loop check 3 c 0.0 Selection of display switching method of momentary flow rate and integrated volume Selection for ti: automatic Displays switching time interval in seconds Output check using arbitrary value displays pressure correlating to the 4 to 20mA signal ti = automatic bt = manual 1 to 10 seconds (10 stage) Display: momentary flow rate display span Analog output: 4 to 20mA 0.0 to 100.0% Sec bt 5 0 (4.0mA) (1) In the setting of a differential pressure the decimal point position is fixed for each differential pressure range. The max. differential pressure can be set from the value which is 25%F.S of the differential pressure range above the minimum differential pressure.the values under 25%F.S. cannot be increased or decreased by T, S key. (2) For setting zero point and span point of the analog output, input the percent value over the maximum display span (between OFFSET and FULL SCALE). Its decimal point position can be set up to one digit after the decimal point (xx.x). (3) Regardless of generated differential pressure or low-cut, the loop check can be changed arbitrarily linking the momentary flow rate display with the analog output using the T, S keys. This example of LCD display shows the display set to span point. 8

(4) Display switching method of momentary flow rate and integrated volume Display switching methods of momentary flow rate and integrated volume include the automatic switching display method to display them by turns at intervals of fixed time (1 to 10 seconds) and the manual switching display method to change the display by pressing (M) key. Complete Setting Mode Menu Setting Mode u 6.00 M f 2 M -n non M a -10.0 M a 90.0 M [ - 1.00 M M key for more than 3 seconds Version display Filter Differential pressure display mode setting (Re-scaling in inh 2O units) Differential pressure display mode Output zero point pressure Output span point pressure Loop check (zero point) Measurement Mode Basic key operation The setting item is changed by M key. The set value is changed or selected by key or key. When changing the value, it is increased or decreased by pressing key or key, respectively. (Refer to next page) Linear display mode setting (Re-scaling in arbitrary user defined units) n - l `n M p 20.0 M p 120.0 M d 1 M d 0.0 M d 50.0 M a 0.0 M a 100.0 M [ 50.0 M Linear display mode Min. pressure Max. pressure Decimal point position OFFSET Full scale Output zero point Output span point Loop check (span point) Flow Measurement Mode See Page 6 9

E. Loop Check: Use to send a 4-20mA signal meant to simulate applied pressure, can be accessed either through Pressure Display Mode or Linear Display Mode. See Complete Setting Mode Menu ; Loop Check is noted on the screen with a prefix (. The display is indicating in actual units and starts at the zero (4mA) point. If $ button is pressed, the linear display will auto increment by linkage between the linear display and the analog output. By continuing to press # button, auto decrement will occur. Release the button at the desired indication. Flow Measurement Mode (Square Root Extraction) Setting Refer to Section 14.3 N ROT M P. 4.00 M Flow Measurement / Square Root Extraction Mode Maximum Differential Selection d 0 d i d Z d 3 Flow Rate Decimal Point Position M D1000.0 100.0 M L 10.0 M a 0.0 Maximum Momentry Flow Low Cut Output Zero Point M a 100.0 Output Span Point M U SE( U n~in U hou Time Factor M U SE1 U 10 U 100 U 1000 21 Flow Rate Volume Factor M 22 5 Bt 5 ti M M 22 Display Switch Setting t 5 23 Switch Time Interval M c 0.0 24 Loop Check Returns to Setting Mode M 10

4. WIRING Power supply requirements, 12-36Vdc, note installation recommendations as follows: Terminal Strip: SMKDSP1.5/2-5.08 Phoenix contact A. Cable Requirements Two core shielded cable Cable outer diameter: 0.35 to 0.47 (9-12mm) Required for proper installation with cable gland option Wire Gauge: 14-22 AWG (multi-strand or solid) Transmission cable Receiver Power source Terminal box Shield Display (board) B. Wiring Instructions Do not run pressure transmitter cable / wires within the same conduit as high voltage (line power) line to reduce the potential for noise (interference). Use dedicated conduit on GC52 cables / wires for optimum results. Cable diameter, specified above, must be maintained when using the Cable Gland termination to retain environmental ratings. When connecting shield / drain wire, only connect one end which should be at the received ground. Wire stripping instructions; remove cable jacket 2-3 and strip wires 0.25. Shield / drain wire should not be exposed at the pressure transmitter termination. Inside sensor Line LCD holder DISPLAY CASE Notch Transmission cable (Twist) Sheath CAP 11

Remove cover and carefully remove the display to access the terminal strip, take care not to mishandle the display and associated electronics. Turn display over to expose terminal strip, make positive and negative connections; insert wire equal to the recommended strip length (0.25 ). After completing connections, align the retaining clips of the display with the housing s notches and carefully place into the housing. Be sure that the internal sensor ribbon cable does not cross the power supply lines just installed. Be sure to properly tighten the sealing grommet when using the Cable Gland before applying tension to the cable; the cable gland provides strain relief and environmental sealing. Tighten GC52 cover to maintain environmental rating. Connect to power source and receiver, than apply power to confirm correct wiring. Wire Power supply terminal block Turn with a screwdriver LCD clips (4) Wire terminals Display board Display Power Supply Requirements: Although the 4-20mA signal can travel over long distances, a very common issue to arise involves inadequate power at the pressure transmitter this results in voltage drop across the loop. Be sure to review the accompanying table to determine whether the 12-36Vdc has been received at the pressure transmitter. 12

Load Limitations 4-20mA Output Only Loop Resistance () 1020 1000 750 545 500 OPERATING REGION 250 0 0 10 12 20 24 30 32 LOOP SUPPLY VOLTAGE V min = 12V+[.022A*R L )] *Includes a 10% safety factor R L = R S + R W R L = Loop Resistance (ohms) R S = Sense Resistance (ohms) R W = Wire Resistance (ohms) 13

14

15

2010 Ashcroft Inc., 250 East Main St., Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com All sales subject to standard terms and conditions of sale. I&M011-10164-GC52 Ver. 6.03 Rev. B 03/11 16