ZU 251. Incremental Counter Module With Analogue Output and Serial Interface. Operating Instructions. control motion interface

Similar documents
ZU 252. Incremental Counter Module With Analogue Output and Serial Interface. Operating Instructions. control motion interface

IV 251. Signal Converter SSI => Analogue and SSI => Serial. Operating Instructions. control motion interface

IV 251. Signal Converter SSI Analogue and SSI Serial. Operating Instructions. control motion interface

FS340 and FS641. High Performance Low Cost Controller for Flying Shears and Saws

AX 345. Process Indicator with Two Analogue Inputs, Calculations and Programmable Analogue Output. Operating Instructions for Model AX 346

GV 460 / GV 461 Impulse Splitters for Incremental Encoders with Potential Separation between Input and Outputs

CT340 and CT641. High Performance Low Cost Controller for Rotating Cutters and Printing Rolls. Operating Instructions

IX IX 348. SSI Indicators for Use with Single-Turn or Multi-Turn SSI Encoders

GV155, GV156 Electronic Cross Switchers for Encoder Signals and Analogue Signals

WDG 543XIOM, WDG 643XIOM WDG 743XIOM, WDG 843XIOM

Multifunction devices

BY 125 Low Cost Synchronous-Controller Operating Instructions for Operator Software OS3.x

Operating instructions Electronic preset counter Type series 717

touchmatrix Indicator IX350 / IX355 SSI indicator for absolute encoders, with touchscreen and graphic display

Vorne Industries. 87/719 Analog Input Module User's Manual Industrial Drive Itasca, IL (630) Telefax (630)

FS150 High Performance Flying Shear Control

DCP100 Digital Control Programmer Specifications

Industriefunkuhren. Technical Manual. IRIG-B Generator-Module for analogue / digital Signals of Type: IRIG-B / IEEE C / AFNOR NF S87-500

High Resolution Multicolor Contrast Scanner. Dimensioned drawing

Noise Detector ND-1 Operating Manual

Instruction Manual. Universal Flow Controller Model 261 / 261-EC-01

LAUREL ELECTRONICS, INC.

Product Information. EIB 700 Series External Interface Box

MICROMASTER Encoder Module

Industriefunkuhren. Technical Manual. OEM Sync-Module FE1000 (IRIG-B) ENGLISH

Preset counters, electronic

Operating Instructions (ed. 5.97) Electronic Preset Counter Type Series 904

medlab One Channel ECG OEM Module EG 01000

Operating Instructions

MC700 / MC720 Motion Control Firmware for Rotating Cutters and Printing Rolls. Cutting Pulse Sensor Optional: Print Mark Sensor

Operating Instructions

Absolute Encoders Multiturn

LWC Series LWC-80. Design. LWC Series Laser Wire Counters. Product name: Accessories: LWC-80

Troubleshooting. 1. Symptom: Status indicator (Red LED) on SSR is constant on. 2. Symptom: Output indicator (Yellow LED) on SSR is flashing.

FX-2DA SPECIAL FUNCTION BLOCK USER'S GUIDE

LAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description

PulseFlow FP100 Pulse to 4 20mA Flow Converter (Flow Rate Transmitter / Totalizer / Indicator)

RLS Series RLS-GD-20/20 -UV. Design. RLS-GD Series Gloss Detection Sensors. Accessories: (cf. page 9) Product name:

Z-D-IN. RS485 Modbus Module 5 Digital Inputs

Electronic Pulse Counter Combination device

C8000. sync interface. External sync auto format sensing : AES, Word Clock, Video Reference

MBUS 10 RS232 TO MBUS LEVEL CONVERTER

Ocean Sensor Systems, Inc. Wave Staff, OSSI F, Water Level Sensor With 0-5V, RS232 & Alarm Outputs, 1 to 20 Meter Staff

BY150. High Performance Synchronous Controller with Operator Software OS 3.2. Operating Instructions

Part No. ENC-LAB01 Users Manual Introduction EncoderLAB

Preset Counters. X e. X d 6.92 X. 0. IP khz Batch. LCD Preset Counters 1, 2, 4 or 6 Presets. Multifunction. Fast and user-friendly

Flexible Counter Series in DIN size 24 x 48 mm

48x24. Options ORDER NUMBER OF TYPE PFL B

Manual. Analog (U/I) Sendix M3661 / M3681. Sendix M3661R. Sendix M5861. Absolute multiturn encoder. Order code: 8.M36X1.XXXX.XX12

SPECTRO Series SPECTRO-3-50-UV-JR. Aufbau. SPECTRO-3 Series True Color Sensors. Product name: SPECTRO-3-50-UV-JR (incl. software SPECTRO3-Scope)

Capacitance Level Measurement Electronic insert FEC 12

C8188 C8000 1/10. digital audio modular processing system. 4 Channel AES/EBU I/O. features. block diagram. 4 balanced AES inputs

RK-2 ENVIRONMENTAL DATA CONTACTLESS MAGNETOSTRICTIVE LINEAR POSITION TRANSDUCER WITH FLANGED HEAD. Main characteristics

Single Axis Position Controller

Ocean Sensor Systems, Inc. Wave Staff III, OSSI With 0-5V & RS232 Output and A Self Grounding Coaxial Staff

R5 RIC Quickstart R5 RIC. R5 RIC Quickstart. Saab TransponderTech AB. Appendices. Project designation. Document title. Page 1 (25)

Re:connect M 203. RS232 Interface Revox. Dominating Entertainment. Revox of Switzerland. E 2.03

Operating Instructions

LX3V-4AD User manual Website: Technical Support: Skype: Phone: QQ Group: Technical forum:

UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load Cell

AES-402 Automatic Digital Audio Switcher/DA/Digital to Analog Converter

SPECTRO Series SPECTRO-3-50-FCL-JR. Design. SPECTRO-3 Series True Color Sensors. Product name: SPECTRO-3-50-FCL-JR (incl. software SPECTRO3-Scope)

Standard RS232 RS ma

MENU EXECUTE Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free

MODEL ED32i TTL LINEAR ENCODER

CSM Color sensors. Color sensors for the detection of a single color in restricted space conditions

Extra long-range RFID (proximity) card reader

Eaton Durant. Counters, process instruments and hour meters.

AES-404 Digital Audio Switcher/DA/Digital to Analog Converter

UDC100 Universal Digital Controller. Specification. Overview. Features. Features, continued /99 Page 1 of 4

MINI MCR-SL-F-UI-NC. Frequency transducers. Data sheet. 1 Description

O P E R A T I O N M A N U A L. RF-Reader. Stand-alone-Reader Leser 2plus with RS-232 interface

M203 LG. Multiroom Planer V2.00. Introduction. New features from software V2.00

THE ASTRO LINE SERIES GEMINI 5200 INSTRUCTION MANUAL

SPECTRO Series SPECTRO-3-30-UV. Design. SPECTRO-3 Series True Color Sensors. Product name: Accessories: (p. 9-10)

SCALE & WEIGHT DISPLAYS

Time meter electronic

Configuration Vestas VMP3500

MAGNETIC TAPE. Series MB. incremental scale. Key-Features:

AC182A 8 Input x 8 Output S-Video Matrix Switch with Audio

Flexible Counter Series in DIN size 24 x 48 mm

Step-Lok Manual V1.0 (preliminary) Last edited Feb 23 / 2015

Electronic Panel Meters DIGEM Preference Program Process control, automation & laboratory uses Class 0.01 to 1 Current, Voltage, Frequency,

DMP 331i DMP 333i. Precision Pressure Transmitter. Stainless Steel Sensor. accuracy according to IEC 60770: 0.1 % FSO

Material: Weight: Bearing Life: Shaft Speed: Storage Temp.: Shock: Vibration: Bump: Humidity: IP Rating: Cable: Connector: Flat Cable:

Material: Weight: Shaft Speed: Starting Torque: Storage Temp.: Shock: Vibration: Bump: Humidity: IP Rating: Cable: Connector: Flat Cable:

Dimensions. Model Number. Electrical connection. Features. Pinout Product information. Indicators/operating means. LGS25 Serie.

Working with CSWin32 Software

ED3. Digital Encoder Display Page 1 of 13. Description. Mechanical Drawing. Features

Netzer AqBiSS Electric Encoders

Material: Weight: IP Rating: Cable: Connector:

Process Transmitter RMA 422

Installation Guide. HDMI 4x1 Switcher

Operating Instructions Rev. No. 4.1 July 07, LTC and VITC Reader with Serial Interface TC 60 RLV

VLC-3 USER'S MANUAL. Light Program Controller. M rev. 04 K rev. 00 & ( ( 5, 352*5$0 1 : $ 2 ' 6(77,1*6 )81&7,216

Installation / Set-up of Autoread Camera System to DS1000/DS1200 Inserters

Special Applications Modules

UNIIQA+ NBASE-T Monochrome CMOS LINE SCAN CAMERA

COMPANY. MX 9000 Process Monitor. Installation, Operating & Maintenance Manual AW-Lake Company. All rights reserved. Doc ID:MXMAN082416

STX Stairs lighting controller.

Transcription:

control motion interface motrona GmbH Zwischen den Wegen 32 78239 Rielasingen - Germany Tel. +49 (0)7731-9332-0 Fax +49 (0)7731-9332-30 info@motrona.com www.motrona.com ZU 251 Incremental Counter Module With Analogue Output and Serial Interface Counter suitable for quadrature signals (A/B, 90º) as well as single channel inputs Counting inputs selectable to TTL/ RS422 format or to HTL / 10-30 volts format Maximum counting frequency 500 khz Analogue outputs +/-10 V, 0-20 ma and 4-20 ma, polarity following the sign of the internal counter Analogue conversion time 1 msec only RS 232 and RS 485 interfaces for serial readout of the counter Also suitable for conversion of the sum or the difference of two separate counts Facility for free linearization of the analogue output by 16 interpolation points Easy to set up by TEACH procedure, or by PC and Windows software Operating Instructions ZU25102A_e.DOC / Mrz-08 Page 1 / 26

Safety Instructions This manual is an essential part of the unit and contains important hints about function, correct handling and commissioning. Non-observance can result in damage to the unit or the machine or even in injury to persons using the equipment! The unit must only be installed, connected and activated by a qualified electrician It is a must to observe all general and also all country-specific and applicationspecific safety standards When this unit is used with applications where failure or maloperation could cause damage to a machine or hazard to the operating staff, it is indispensable to meet effective precautions in order to avoid such consequences Regarding installation, wiring, environmental conditions, screening of cables and earthing, you must follow the general standards of industrial automation industry - Errors and omissions excepted Version: ZU25101B/ HK/AF/ Nov.01 ZU25102A/ HK/AF/ Mar04 Description: Original version New parameters: Power-up-Mode, Protocol setting ZU25102A_e.DOC / Mrz-08 Page 2 / 26

Table of Contents 1. Introduction...4 2. Applicable encoders and sensors...5 3. Terminal Assignment...6 3.1. Incremental encoders TTL / RS 422...6 3.2. Incremental encoder HTL / 12-30V...7 3.3. Proximity switches, photocells etc...7 3.4. Analogue outputs...7 3.5. Serial interfaces...8 4. DIL switch settings...9 5. Setup Procedure...11 5.1. Operation as single channel counter (without direction signal) or as positional counter (with direction signal)...12 5.2. Operation as a summing or differential counter with two independent impulse inputs (A+B, A-B)...12 6. Readout of the actual counter state by serial communication...13 7. PC setup with use of the operator software OS3.x...14 8. Displays and Softkeys...15 9. Parameter Settings...16 10. Free Programmable Linearization...21 11. Test Functions...23 12. Dimensions...24 13. Technical Specifications...25 14. Parameter List...26 ZU25102A_e.DOC / Mrz-08 Page 3 / 26

1. Introduction ZU 251 represents a small and low-cost, but highly performing converter for industrial applications, where incremental counting of positions or events must be converted to either analogue format or serial data. The unit has been designed as a compact module with 12 screw terminals and a 9-position SUB-D connector (female). The housing is suitable for standard DIN rail mounting. The impulse input side provides channels A, B and also the inverted lines /A, /B which must be used with TTL/ RS422 input signals. The unit can count and convert the following formats to analogue and serial: a. Up/down count with quadrature input (A/B, 90 ). The polarity of the analogue output and the sign of the serial data depend on the sign of the actual counting result b. Single channel impulses on channel A. Input B sets the counting direction and therefore also the polarity of the output (LOW = negative, HIGH = positive). Please observe: Open NPN inputs are HIGH Open PNP inputs are LOW Open RS422 inputs are HIGH c. Dual count of fully independent events on channels A and B, where the output signal represents the sum or the difference of both counts. a. b. c. A B A B - + A B A and B, quadrature 90 A=impulse, B=static direction signal A and B: independant counting events The definitions for zero analogue output and full scale analogue output definition can be set over the full counting range of +/-8 decades (-99 999 999 to +99 999 999) ZU25102A_e.DOC / Mrz-08 Page 4 / 26

2. Applicable encoders and sensors The converter can accept the following impulse sources: Encoders with HTL level output (12 30V) and either PNP or NPN or Push-Pull or NAMUR characteristics, using quadrature output signals A and B TTL / RS422 encoders providing the output lines A, /A,B and /B Single channel sources like proximities or photocells, providing HTL output and PNP or NPN or NAMUR characteristics Single channel sources with TTL/ RS422 output, providing both, signal and inverted signal (differential operation) In general, HTL encoders will be supplied from the same source as the converter itself. For supply of TTL encoders, the unit provides an auxiliary output of 5.5 volts stabilized, (150 ma max.) For applications using single-ended TTL signals A, B only (i.e. without associated inverted signals /A, /B) : See successor model ZU252 ZU25102A_e.DOC / Mrz-08 Page 5 / 26

1 2 3 4 5 6 POWER 7 8 9 10 11 12 3. Terminal Assignment We recommend connecting the Minus wire of the power supply to earth potential. Please observe that, under poor earthing and grounding conditions, multiple earth connections of screens and GND terminals may cause severe problems. In such cases it may be better to have only one central earthing point for the whole system. GND terminals 4, 6 and 12 are connected internally. Depending on input voltage and load of the auxiliary voltage output, the total power consumption of the unit is approx. 150 ma (see specifications). 0-20mA / 4-20mA out Analogue out +/-10V TTL: Input /A HTL: n.c. TTL: Input /B HTL: n.c. TTL: Input A HTL: Input A TTL: Input B HTL: Input B Reset Aux. 5.5V out (max. 150 ma) GND ( - ) Analogue GND ( - ) +18...30 VDC (typ. 200 ma) GND ( - ) 3.1. Incremental encoders TTL / RS 422 If applicable, the encoder can be supplied from the ZU251 converter. Where the encoder is already supplied from a remote source, we recommend fully differential operation, with no GND connection between encoder and converter (see figures a. and b.) a) TTL encoder + A A B B - Screen ZU 251 converter 11 (+5.5V) A 8 A 9 B 2 B 3 12 (GND) b) TTL encoder + A A B B - +ext Screen ZU 251 converter 11 (+5.5V) A 8 A 9 B 2 B 3 12 (GND) -ext ZU25102A_e.DOC / Mrz-08 Page 6 / 26

3.2. Incremental encoder HTL / 12-30V The encoder may be supplied from the same source as the converter, or from another source. HTL encoder + A +24V Screen ZU 251 converter 9 B 3 GND 12 (GND) 3.3. Proximity switches, photocells etc. This connection is fully similar to a HTL incremental encoder. With single-channel operation, input B remains unconnected or can be used to select the output polarity. With use of two independent counting events for forming the sum or the difference, input B operates as the second counting input. For use of sensors providing 2-wire NAMUR characteristics: Set the inputs to HTL and NPN Connect the positive wire of the sensor to the corresponding input and the negative wire to GND. 3.4. Analogue outputs The unit provides a +/-10V voltage output and a 0-20 ma / 4-20 ma current output at a resolution of 14 bits, i.e. the voltage output operates in steps of 1.25 mv and the current output operates in steps of 2.5 μa. The nominal load of the voltage output is 2 ma, the current output accepts loads between 0 Ohms and 270 Ohms. The analogue ground uses a separate terminal, which however internally is connected to the GND potential of the power supply. Vout GND Iout 1 4 7 Screen +/- 10V (Imax = 2 ma) (R = 0-270 Ohms) 20 ma ZU25102A_e.DOC / Mrz-08 Page 7 / 26

9 8 7 6 5 4 3 2 1 5 4 3 2 1 9 8 7 6 3.5. Serial interfaces The unit provides a RS232 interface and a RS485 interface, however only one of the two can be used at a time. Serial communication allows to read out the counting result and to set parameters and variables by PC, according to need. +5V 5 4 3 2 1 GND int. RS485 T+ T- R+ R- TxD RxD RS232 Sub-D-9 (female on unit site) GND 5 4 3 2 1 9 8 7 6 TxD RxD 5 4 3 2 1 9 8 7 6 RS232: Please connect only pins 2, 3 and 5! PC ZU 251 T+ 120 Ohms 120 Ohms T- R+ 120 Ohms 120 Ohms R- T+ 9 8 7 6 RS485- Bus ( 4- wire ) T- R+ R- ZU 251 T+ 120 Ohms T- 120 Ohms RS485- Bus ( 2- wire ) ZU 251 ZU25102A_e.DOC / Mrz-08 Page 8 / 26

4. DIL switch settings The DIL switch located on the top site of the unit provides customer-specific settings of the desired operation modes. Changes of the switch settings will become active only after the next power-up cycle! ZU25102A_e.DOC / Mrz-08 Page 9 / 26

1 2345678 Unit loads default settings with every power up cycle No loading of default settings upon power-up HTL ( 12-30 V ) TTL / RS 422 Push button and LED operating in Teach mode Teach function disabled, LED testing inputs A and B NPN (switch to -) PNP (switch to +) VALUE" after power down Counter sets to RESET Counter stores actual data upon power down Quadrature A/B, 2x90 A + B A = impulse, B = direction RS 232 RS 485 The switch settings shown in the example are suitable for a quadrature encoder with HTL- and NPN characteristics. The power-down memory is switched off and the serial link is set to RS232 communication. After setup and commissioning, please set DIL switch position 6 to ON. If set to OFF, any inadvertently touch of the Teach button would overwrite your previous scaling input! *) These settings refer to the impulse inputs A/B only. The RESET input (terminal 10) however always uses HTL and PNP characteristics and you must apply a voltage of 12 to 30 volts to activate the Reset function. ZU25102A_e.DOC / Mrz-08 Page 10 / 26

5. Setup Procedure For all basic applications you can use the Teach feature for commissioning of the unit. Extended functions need a PC for setup and are described under section 7. As a first step it is advisable to check the input pulses by means of the LED marked Status. DIL switch 6 must be set to ON for this test. When you press the TEACH button one time, the yellow LED will be lit after the unit detected a pulse on input A. The LED will be OFF when no input pulse has been detected. When you press the TEACH button once more, you can also check input B (if applicable). With use of mode A+B and two independent impulse sources, again the yellow LED will be lit after a pulse has been detected on input B. With operation modes using input B to define the direction and polarity (quadrature or static), the yellow LED will indicate that the actual input signals provide a positive signal on the analogue output (LED on) or a negative signal (LED off). Where you like to get the other polarity, you must change the information of direction on A/B inputs ZU25102A_e.DOC / Mrz-08 Page 11 / 26

5.1. Operation as single channel counter (without direction signal) or as positional counter (with direction signal) Settings: Make sure that the DIL switch is set according to the encoder in use, and that DIL switch position 6 is OFF (Teach function active). Self test: Upon power up, both front LED s must be lit first, and the yellow status LED must switch off after the self-test has been concluded successfully (approx.1 sec.). Scaling of the analogue output with use of the Teach function: Press the Teach button one time. The status LED will blink in a slow sequence now while the unit waits for setting of the minimum counter state, this is the state where later you expect the analogue output to be zero (in general, this will be with counter=0). Please set the counter to the desired state or move the encoder to the desired position and reset the counter to zero. Then press the Teach button again. This stores your minimum counter definition. The LED will blink in a fast sequence now and the unit waits for setting of the maximum counter state, this is the state where later you expect full scale analogue output. Please get the counter to the desired state or move your encoder to the desired position. Then press the teach button once more. This stores your maximum counter definition and the LED will switch off. After this Teach procedure, your analogue output is set to 0 10 volts swing between the minimum and the maximum counter state. 5.2. Operation as a summing or differential counter with two independent impulse inputs (A+B, A-B) In principle, the Teach procedure is exactly the same as shown under 5.1, but the minimum and maximum counter states already refer to the sum or the difference of the count on both inputs. ZU25102A_e.DOC / Mrz-08 Page 12 / 26

6. Readout of the actual counter state by serial communication At any time you can read out the actual counter state and more values via serial link. For setting of serial communication parameters etc., you must however apply PC setup anyway, as shown later. ZU 251 uses the DRIVECOM communication protocol according to the ISO 1745 standard. Details about the protocol can be found in our document SERPRO.doc, available for download under www.motrona.com The following register codes are available for readout: C1 C2 Description : 8 Actual conversion result, scaled as % of full scale output, format xxx.xxx % *) : 9 Actual counting result ; 3 Actual output voltage of the analogue output, scaling 0 10 000 millivolts *) under consideration of the scaling operands as shown in section 9. Readout from <:8> = Counter result in % of full scale x xoperand /Operand + +/-Operand ZU25102A_e.DOC / Mrz-08 Page 13 / 26

7. PC setup with use of the operator software OS3.x You can apply the full set of functions when you use a PC and our operator software OS3.x for setup of the unit (actual software version is OS3.2). You can download this software and more instructions from our homepage www.motrona.com Connect your PC to the converter, using a serial RS232 cable like shown in section 3.5 of this manual. Make sure the cable only uses pins 2, 3 and 5. Pins 2 and 3 must be crossed. Run the OS3.x software and you will see the following screen: If your text and color fields remain empty and the headline says OFFLINE, you must verify your serial settings and the DIL switch setting. To do this, select Comms from the menu bar. Ex factory, all motrona units use the following serial standard settings: Unit No. 11, Baud rate 9600, 1 start/ 7 data/ parity even/ 1 stop bit If the serial settings of your unit should be unknown, you can run the SCAN function from the TOOLS menu to find out. ZU25102A_e.DOC / Mrz-08 Page 14 / 26

8. Displays and Softkeys The edit window for all unit parameters can be found on the left side of the screen. The INPUTS field shows the softkeys to switch the control commands on or off. Display boxes in the RS column indicate when the corresponding command is set to ON by PC. Display boxes in the PI/O column indicate that the corresponding command is ON by external hardware. The boxes in the OUTPUTS field provide information about the state of the unit, where Status A and Status B are especially useful to check the counting inputs: Status A is lit when a counting pulse is detected on input A Status B is lit when a counting pulse is detected on input B For input modes using direction information, Status B is lit when the actual direction of the input corresponds to forward count in the positive sense. The color bar graph displays the actual output state in a range of +/- 100 % of full scale. Control keys are available for readout, transmission and storage of parameters. ZU25102A_e.DOC / Mrz-08 Page 15 / 26

9. Parameter Settings Parameter Display Setting: x Operand / Operand +/- Operand Description These operands allow to convert the result to the desired engineering units. The conversion affects the numeric value for serial read out from register <:8> only, but not the scaling of the analogue output. With settings x operand = 1.0000 / operand = 1.0000 +/- operand = 0.0000 the readout from register < :8 > equals to the percentage result (xxx.xxx%), where 100,000% has been defined by the TEACH minimum and TEACH maximum settings Readout from <:8> = M easur ing result in % of f ull s cale x xoperand /Operand + +/-Operand General Setting Teach Minimum Teach Maximum This couple of settings define your minimum and maximum count for input A and input B (if applicable), where your analogue output moves from 0 V to 10 V. You can enter your minimum and maximum settings as follows: either by operating the Teach pushbutton (like described already under 5.1) or by entering the counter settings directly by keyboard to the parameter field of your screen, without using the TEACH function. When using summary or differential counting modes (A+B, A-B), these settings already refer to the sum or the difference of the counter. ZU25102A_e.DOC / Mrz-08 Page 16 / 26

Parameter Output Mode: V Description Selects the output format of the analogue outputs as shown: V ma ma Min. Encoder Max. Min. Encoder Max. Min. Encoder Max. Min. Encoder Max. Output Mode = 0-10V... 0... +10V Output Mode = 1 0... +10V Output Mode = 2 4... 20 ma Output Mode = 3 0... 20 ma Linearization Mode: Factor A Factor B: Sets the mode of linearization. 0: Linearization off, registers P1 to P16 do not affect the output characteristics. 1: Linearization in a range of 0 100% 2: Linearization over full range 100% to +100% See example under section Linearization Impulse scaling factors for the two counter inputs. Setting 1.0000 results in one increment with every input pulse, whereas setting 0.5000 would need 10 input pulses to increment by 5 etc. 1/4 Edge Mode: This setting, with use of quadrature A/B input, allows simple count (x1) or full quadrature count (x4), by either accepting rising edges from input A only, or all rising and falling edges from inputs A and B 0 = simple count (x1) 1 = quadrature count (x4) AB Mode: Reset Mode: Sets the counting mode with two independent single-channel inputs 0 = no combination 1 = sum A + B 2 = difference A B DIL switch positions 2 and 3 must be set correspondingly. Sets the behavior of the Reset input: 0 = static reset with high level 1 = dynamic reset by rising edge *) 2 = dynamic reset by falling edge *) 3 = dynamic reset by rising edge **) 4 = dynamic reset by falling edge **) Settings 1 and 3: Settings 2 and 4:. *) The duration between the active edge and the zero state of the analogue output is 5 msec. During this internal processing period the analogue output may make undefined jumps **) The duration between the active edge and the zero state of the analogue output is 10 msec, but there will be a defined zero approach with no jumps ZU25102A_e.DOC / Mrz-08 Page 17 / 26

Parameter Reset Value: Round Loop: Power up Mode: Set-Up-Settings: Description With every reset command, the counter presets to the datum set here (e.g. 000 000) and the analogue output follows the new counter state according to its output scaling. This register limits the counting range to a repeating loop. With setting of 1000, in upwards direction 999 is followed by to 000, and in downwards direction the counter sets to 1000 when reaching zero. Setting this register to 000 000 provides counting over the full range. Sets the action of the counter upon power up: 0 = Loads the previous value from power down memory 1 = sets counter to zero Analogue Offset: Allows adjusting the analogue zero output in a range of approx. +/- 100mV (respectively +/- 200 μa) if necessary. Analogue Gain: Sets the maximum output swing of the analogue output. Setting of 1000 results in a 10 volts respectively 20 milliamps output swing. Direction: Can be used to invert the polarity of the analogue output signal when converting quadrature A/B input signals or A=impulse and B=direction. 0 = no inversion of the polarity 1 = inversion of the polarity ZU25102A_e.DOC / Mrz-08 Page 18 / 26

Parameter RS232 / RS485 Setting: Unit Number: Serial Baud Rate: Serial Format: Protocol Setting: Description Especially with RS 485 applications it is necessary to attach a specific address to each unit, since up to 32 units can be connected to the same bus. You can choose any address number between 11 and 99. Factory setting = 11 The address must not contain a 0 because these numbers are reserved for collective addressing. Setting Baud 0* 9600 1 4800 2 2400 3 1200 4 600 5 19 200 6 38 00 * = Factory setting Setting Data bits Parity Stop bits 0* 7 even 1 1 7 even 2 2 7 odd 1 3 7 odd 2 4 7 none 1 5 7 none 2 6 8 even 1 7 8 odd 1 8 8 none 1 9 8 none 2 * = Factory setting The serial port of the unit can operate in either PC-Mode or in Printer Mode. With PC-Mode, the unit waits for a request string and responds with a corresponding data string. For details of the protocol see description SERPRO. With Printer Mode the unit sends data without any request and under Timer control as described subsequently. As soon as the unit receives a character, it automatically switches to PC Mode and operates according to protocol. When for a period of 20 sec. no character has been received, the unit switches automatically to Printer Mode and starts cyclic data transmission. ZU25102A_e.DOC / Mrz-08 Page 19 / 26

The following register settings control the automatic cyclic transmission of internal register values by serial interface to peripherals like printers or displays. Parameter Serial Protocol: Description This register selects the serial protocol for the cyclic transmission. When set to 0, the string starts with the serial address of the unit ( Unit Number ), followed by a space and the value of the register to be read out. The string ends with a Line Feed character and a Carriage Return character. When set to 1, the unit number is omitted and the string starts with the register value directly. This allows a little faster transmission because of the shorter transmission time. Unit No. Serial Protocol = 0 : 1 1 +/- X X X X X X LF CR Serial Protocol = 1 : +/- X X X X X X LF CR Serial Timer: Register Code: Backup Value: This register determines the cycle time in seconds for the cyclic transmission. E. g. with a setting of 0.100 the selected register value will be transmitted every 100 ms. The Accuracy of the timer is +/-500 μs. Selects the register to be transmitted cyclically. Setting of 00 selects register code :0, setting of 01 selects register code :1 etc. Upon power down, this register stores the last actual count. When the unit is powered up again, the counter re-loads this register value, provided the storage function has been enabled by parameter Power up. ZU25102A_e.DOC / Mrz-08 Page 20 / 26

10. Free Programmable Linearization This programmable feature allows the user to convert the linear counting process to a nonlinear analogue output. There are 16 programmable interpolation points available, which can be set in any desired distance over the full conversion range. Between two coordinates, the unit uses linear interpolation. Therefore it is advisable to use more points in a range with strong curves and only a few points where the curvature is less. To specify your desired linearization curve, you must first set the Linearization Mode register to either 1 or 2. Use registers P1(x) to P16(x) to specify the coordinates on the x-axis. These are the analogue output values that the unit normally would generate according to the actual count. The settings are in % of full scale. Now enter the attached values to registers P1(y) to P16(y). These are the values that the analogue output will generate instead of the x- values Example: the value set to register P2(y) will substitute original value P2(x) etc. x-registers must use continuously increasing settings, i.e. P1(x) must have the lowest and P16(x) must have the highest setting All entries use a percentage format of xx.xxx% full scale. Setting 0.000% means zero output and setting 100.000% means full scale output. With Linearization Mode set to 1, it is a must to set P1(x) to 0% and P16(x) to 100%. Linearization is defined in the positive range only and the negative range will be a mirror image of the positive range with reference to zero. With Linearization Mode set to 2, it is a must to set P1(x) to 100% and P16(x) to +100%. This enables the user to set curves which are not symmetric to the zero position. *) Output mode = 0 *) y P1(x)= 0% P1(y)=10% Linearisation Mode = 1 P1(x)= -100% P1(y)= 95% P16(x)=100% P16(y)= 80% x P8(x)= 0% P8(y)= 80% y Linearisation Mode = 2 x P16(x)=+100% P16(y)= -60% ZU25102A_e.DOC / Mrz-08 Page 21 / 26

You can visualize your curve on the PC screen or by means of an external oscilloscope. For this, select TOOLS, then TEST and there Analogue Voltage Function. The unit will now simulate a repeating counting cycle over the full range and generate the analogue signal accordingly. When you use the Scope function of the operator software, you must set the serial code :1 to record the analogue output. ZU25102A_e.DOC / Mrz-08 Page 22 / 26

11. Test Functions When you select TEST from the TOOLS menu, you are able to verify the following data, by clicking to the corresponding field: Actual counter value DIL switch settings Internal supply voltages Analogue output state ZU25102A_e.DOC / Mrz-08 Page 23 / 26

12. Dimensions 40 mm (1.575 ) 91mm (3.583 ) 74 mm (2.913 ) 79 mm (3.110 ) Front view Side view Top view ZU25102A_e.DOC / Mrz-08 Page 24 / 26

13. Technical Specifications Power Supply : 18...30 VDC Power consumption : approx. 170 ma at 18 V approx. 120 ma at 30 V (+5.5V uncharged) Encoder supply : +5.5V +/- 5% (max. load: 150mA) Inputs RS422 and TTL : TTL differential, RS 422 standard Inputs HTL and Reset : High > 10 V, Low < 3 V Analogue outputs : +/- 10 V (> 5 kohm) 0-20 ma / 4-20 ma (< 270 Ohm) Step width of analogue outputs : 1.25 mv / 2.5 μa Analogue resolution : 14 bits (+ 10V / +20mA... -10V/ -20mA) Accuracy of analogue output : 0.1% +/- 1 digit Response time counter => analogue (normal operation): : approx. 1 msec Reset time of the analogue output upon external reset command : approx. 5 msec or 10 msec (see Reset Mode ) Minimum Reset pulse duration : 5 msec Temperature range Weight : Operation: 0... +45 C (+32 +113 F) Storage: -25 +70 C (-13 +158 F) : approx. 190 g Conformity and standards : EMC 89/336/EEC: EN 61000-6-2 EN 61000-6-3 LV73/23/EEC: EN 61010-1 ZU25102A_e.DOC / Mrz-08 Page 25 / 26

14. Parameter List Parameter Min. value Max. value Default Digits Decimal Serial Code positions *Operand -99 999 99 999 10 000 +/- 5 4 00 /Operand 1 99 999 10 000 5 4 01 +/- Operand -100 000 000 100 000 000 0 +/- 9 0 02 Teach Minimum A -100 000 000 100 000 000 0 +/- 9 0 03 Teach Maximum A -100 000 000 100 000 000 10 000 +/- 9 0 04 Factor A 1 99 999 10 000 5 4 05 Factor B 1 99 999 10 000 5 4 06 Output Mode 0 3 0 1 0 07 Linearization Mode 0 2 0 1 0 08 ¼ Edge Mode 0 1 0 1 0 09 AB Mode 0 2 0 1 0 10 Reset Mode 0 4 0 1 0 11 Reset Value -100.000 000 100 000 000 0 +/- 9 0 12 Round Loop 0 1 000 000 0 7 0 13 Power up Mode 0 1 0 1 14 P1 (x) -100 000 100 000 100 000 +/- 6 3 A0 P1 (y) -100 000 100 000 100 000 +/- 6 3 A1 P2 (x) -100 000 100 000 100 000 +/- 6 3 A2 P2 (y)... -100 000 100 000 100 000 +/- 6 3 A3...(A9)...(B0) P16 (x) -100 000 100 000 100 000 +/- 6 3 D0 P16 (y) -100 000 100 000 100 000 +/- 6 3 D1 Direction 0 1 0 1 0 46 Analog Offset -99 99 0 +/- 2 0 47 Analog Gain 0 10 000 1 000 5 0 48 Unit Number 0 99 11 2 0 90 Serial Rate 0 6 0 1 0 91 Serial Format 0 9 0 1 0 92 Serial Protocol 0 1 0 1 0 30 Serial Timer 5 99 999 100 5 3 31 Register Code 0 19 0 2 0 32 Backup Encoder A -100 000 000 +100 000 000 0 +/- 9 0 33 Backup Encoder B -100 000 000 +100 000 000 0 +/- 9 0 34 Backup Rest A -10 000 +10 000 0 +/- 5 0 35 Backup Rest B -10 000 +10 000 0 +/- 5 0 36 ZU25102A_e.DOC / Mrz-08 Page 26 / 26