On-Line Monitoring of Cable Trench and Cable Pit by Using Metal Armored FBG Temperature Sensors

Similar documents
Broken Wires Diagnosis Method Numerical Simulation Based on Smart Cable Structure

BioTechnology. An Indian Journal FULL PAPER. Trade Science Inc.

Generator protection relay

INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 FIRE PREVENTION FOR CABLES, CABLE TRAYS AND CONDUITS

Cable installation guidelines

220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX

M4000 Diagnostic Test System For Power Apparatus Condition Assessment

Application of Measurement Instrumentation (1)

Detecting and Analyzing System for the Vibration Comfort of Car Seats Based on LabVIEW

Experimental Study on Dual-Wavelength Distributed Feedback Fiber Laser

Optical Receiver Manual. Transmitter OP-OR112R JⅢ. Shenzhen Optostar Optoelectronics Co., Ltd (Version 2)

Contrastive Analysis and Research on Negative Pressure Beam Tube System and Positive Pressure Beam Tube System for Mine Use

TERMINATIONS AND JOINTS FOR XLPE-INSULATED kv MEDIUM VOLTAGE CABLES

KRF EMC Filters Installation, Operation and Maintenance Manual

OCC Installation Conduit Guidelines Excerpt from Optical Cable Corporation s INSTALLATION GUIDE

Projectors EFFORTS FOR PROJECTOR QUALITY

SEL-3405 High-Accuracy IRIG-B Fiber-Optic Transceiver

Pelletizer Motor Bearing Damage Detection Based on Vibration Data. John J. Yu Carl Feng Wang Tony Wei Zhou Nicolas Péton Haibo Lin Jun Quan

Flygt Submersible Motor Cables

TABLE OF CONTENTS. Instructions:

High performance circuit breakers

EE028: Practical High Voltage Cable Jointing and Termination

Trends and Challenges of HV Cable Systems

ETSI ES V1.1.1 ( )

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES

SM-10 SAT Level Meter User s Manual

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Spec No.: ZTT Revision: 2 Date: Oct 3, Designer. Senior Technical Manager. Approver. Chief Technical Engineer

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

Fiber Optic. Foreword. Special Tips:

PSI-MOS-RS232/FO 850 E Serial to Fiber Converter

Optical Receiver Manual. Transmitter OP-OR212JSE. Shenzhen Optostar Optoelectronics Co., Ltd (Version 2)

EVERLIGHT ELECTRONICS CO.,LTD.

Description Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100

ModBox-1310nm-1550nm-28Gbaud-PAM nm & 1550 nm, 28 Gbaud PAM-4 Reference Transmitter

Protective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A

CC-Link IE Controller Network Compatible. CC-Link IE Controller Network Recommended Network Wiring Parts Test Specifications

TENDER SUMMARY. Tender Title:

Agilent 86120B, 86120C, 86122A Multi-Wavelength Meters Technical Specifications

LED MODULES READYLINE DL

ModBox-850nm-NRZ-series

ECONOMICAL 36 kv CABLE SYSTEM FOR THE BELGIAN NETWORK

Soft starter, 66 A, V AC, Us= 24 V DC, with control unit, Frame size N. Function Soft starter for three-phase loads, with control unit

Research on Control Strategy of Complex Systems through VSC-HVDC Grid Parallel Device

Micro duct Cable with HDPE Sheath for Installation by Blowing

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Process transmitter RMA422

XCOM1002JE (8602JE) Optical Receiver Manual

MN9320A. Optical Channel Drop Unit. Independent Test Access Tool for Comprehensive DWDM Measurements

High Voltage Cables kv. Handling and Operating Instructions

All-Optical Flip-Flop Based on Coupled SOA-PSW

Specification for Loose Tube Fiber Optic Cable (Non-Metallic, Dry Block, Figure-8) (G.652.D)

Industrial 10/100 Base-TX to 100 Base-FX Media Converter NS-200AFC-T/NS-200AFCS-T/NS-200AFCS-60T +12 ~ +48

UC FIBRE Optical Fibre Cable a fast, reliable and always available part of the Draka Datacom Solution. Be ready for the future: Draka Datacom Solution

TRF STEP-DOWN TRANSFORMER USER MANUAL

Emerging Subsea Networks

Nikon s DigiMicro Position Encoders Nanometer Resolution with Sub-Micron Accuracy

e-enterable Fiber Optic Splice Closure (Re-Enterable Aerial Closure for Access Service)

Wall-/Pipe-Mount Level Indicator

Six-Channel TDM Multiplexers for 3G, HD, SDI, and ASI. Installation and Operations. Manual

Model CB 60 CO 2 incubators with hot air sterilization and heat sterilizable CO 2 sensor

HOG 86. The incremental HeavyDuty encoder for highest demands

Bimetal Temperature Switch

Revision of Qualification Procedures for High Voltage and Extra High Voltage AC Extruded Underground Cable Systems

Process Transmitter RMA 422

Cladding Pumped Amplifier Using Seven-core EDF

Model KT 53 Cooling incubators with thermoelectric cooling

8000 Plus Series Safety Light Curtain Installation Sheet ( CD206A/ CD206B )

Bharat Heavy Electricals Limited HIGH PRESSURE BOILER PLANT, TIRUCHIRAPPALLI CONTROLS AND INSTRUMENTATION/FB

Fiber-Optic Sensor Amplifiers E3S-X3, E3X-NL and E3X-NM Discontinued March 2012; Revised Replacements

Model KT 115 Cooling incubators with thermoelectric cooling

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

Fiber Optic Splice Closure GPJ Instruction Manual

Power and Control T YPE BY RAVI GANATR November/December IAEI NEWS

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

LED Driver Linear / area fixed output

Model CB 160 CO 2 incubators with hot air sterilization and heat sterilizable CO 2 sensor

V9A01 Solution Specification V0.1

Model FP 240 Drying and heating chambers Classic.Line with forced convection and program functions

Mechanical Considerations in the Outer Tracker and VXD. Bill Cooper Fermilab

1.10mm Height 1210 Package. Bi-Color (Multi-Color) Chip LED. Technical Data Sheet. Part No: S155VBC-V12B-B41B

PRINCIPLES AND APPLICATIONS

OTX Optical Transmitter. Operation Instructions

Technical Data Sheet 0805 Package Chip LED (0.8mm Height)

ULTRALOW TEMPERATURE FREEZERS -86 C

Photovoltaic Module Installation Manual (IEC)

2179-CD Series Fiber Optic Splice Closure. Installation Instructions

EPU-400 -THERMOSTAT MANUAL- ENERPIA CO., LTD

Indoor Linear 80W Driver SI-C215280N2KR

EVERLIGHT ELECTRONICS CO.,LTD.

ELECTRICAL SAFETY INSPECTION REPORT

Features: Descriptions: Applications:

OPERATOR MANUAL OSD8865 DIGITAL TRIPLE VIDEO FIBER OPTIC RECEIVER

Assembly. Front view. LEDs. Parametrization interface. Power Bus

Non Magnetic Connectors

Real-time QC in HCHP seismic acquisition Ning Hongxiao, Wei Guowei and Wang Qiucheng, BGP, CNPC

LED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series

RLT 1550 d10. DWDM High Power, Ultra Wide Band CATV & SAT MHz Laser Optical Transmitter, with pre-correction, LAN remote control and alarms

Lt DELTA USA, Inc

Diagnostic & Testing Services

Transcription:

International Journal of Smart Grid and Clean Energy On-Line Monitoring of Cable Trench and Cable Pit by Using Metal Armored FBG Temperature Sensors Zhen Wang a,c, Min Cao b, Da-Da Wang b, Shao-Quan Zhang b, Chuan Li c *, Ying-Na Li c, Xiao-Long Li a,c a Graduate Workstations, Kunming University of Science and Technology & Yunnan Power Grid Corp Kunming 650217, China b Electric Power Research Inst., Yunnan Prov. Electric Power Test & Research Inst. (Group) Co., Ltd, Kunming 650217, China c Faculty of Information Engineering and Automation, Kunming University of Science and Technology, Kunming 650500, China Abstract Substation cable trench and cable pit lay many cables, which are used to connect electrical equipment. The longrunning of cable will probably cause insulation material aging, leakage sparking and local overheating occur, which eventually lead to a cable fire, the temperature of cable surface usually reflected the situation of the cable. Metal armored fiber Bragg grating temperature sensor are applying in a substation cable trench and cable pit, with four fiber trench it monitor the 60 cable temperature measuring point in current time. The 24-hours real-time monitoring indicates that the temperature of morning is the minimum, and the temperature of afternoon is the maximum. The temperature of cable surface ranges in the similar curve with ambient temperature. In the long-term of 479 days, the minimum of the average daily temperature range of 60 sensors is 21.24,detected at number 9 trench 1, The maximum is 37.43,detected at number 4 trench 2, which reached its maximum temperature 43.41 on July 3, 2010, and the minimum temperature is 4.37 on January 17, 2011,number 13 trench 1. The temperature of sensors changed in the same trend with seasons. Keywords: Fiber Bragg grating, power cable, on-line monitoring, cable trench, cable pit, environment temperature. a 1. Introduction Cable is an important part of electricity system. In the substation, cable is the connection of various electricity device, and links to the control room. It usually lays in cable bridge, cable tunnel, cable interlayer, cable ditch and cable shaft. The plenty of cables, long route, complicated trend and compact arrange. Especially in cable trench and cable pit, a relatively closed, dark and damp environment, cooling condition is poor, the long-term withstand high voltage, large current and heating, lead to the insulation material aging. In addition, as the electric circuit is used for a long time, lacks of regular maintenance and timely update, leakage ignition or local overheating would occur frequently, once the fire area is wide, the repair time is long, there will be a large loss [1], [2]. Temperature of high voltage cable surface reflects inside condition of the cable, whether overload operation or changes of cable operating environment or cable line fault (such as the various fault resulting from partial discharge of main insulation or the destruction of protecting layer) will cause the change of cable surface temperature therefore monitoring of cable surface temperature will timely detect the cable abnormal condition, then we take timely measures to avoid accidents [3], [4]. The wavelength shift of metal armored fiber Bragg grating temperature sensor Bragg is only sensitive to temperature and linearly changes with temperature, we use fiber Bragg grating sensor WDM technology, with 4 fiber trenches to do the timely on-line monitoring of 60 temperature monitoring point * Manuscript received July 14, 2012; revised August 15, 2012. Corresponding author. Tel.: +86-871-5916597; fax: +86-871-5916597; E-mail address: boatriver@eyou.com.

120 International Journal of Smart Grid and Clean Energy, vol. 2, no. 1, January 2013 and environmental temperature of Zhaotong Yanjin substation cable trench and cable pit. 2. Structure and Operation Principle Of Metal Armored Fiber Bragg Grating Temperature Sensor Fiber Bragg grating center wavelength is relative to the core of the effective refractive index n eff and the grid cycle Λ, changes of temperature, stress and strain can cause the refractive index n eff and raster cycle Λ change [5], which lead to the center wavelength λ B drifts. Mounted on the cable, fiber Bragg grating temperature sensor inevitably will be squeezed, bending, drawing and stress strain. The temperature measuring of cable fiber Bragg grating temperature sensor should resist traction during the rally and damage from bite of anti rodent animal. Insulating medium covers cable outer part, therefore, to make the sensor sensitive to temperature only and ensure the measuring accuracy, using a metal armored fiber Bragg grating temperature sensor which is not sensitive to external stress, its structure is shown in Fig. 1. Fig. 1. Structure of metal armored fiber Bragg grating temperature sensor. In the double layer tube structure, the main function of the outer tube is conducting temperature and eliminating the external stress strain impact on Bragg wavelength offset. As a result of the external stress strain impact, the outer tube longitudinal strain induced grating wavelength value offset is within, we can assume that the grating offset value is very small, and is within the allowable error range, it has little impact on the temperature induced Bragg wavelength offset. The temperature is uniformly transferred to the inner tube. Due to the temperature effect of grating in the inner tube, Bragg wavelength offset value changes, we can get the wavelength offset value by optical fiber AFC port to the spectrum analyzer. Wavelength variation caused by the change of temperature sensor is shown as in form (1) [6], ΔλB = ( α + ξ) Δ T = ST Δ T λ B Form (1), S T is temperature coefficient of sensor, ΔλB is the change of wavelength, α is coefficient of thermal expansion of the fiber, ξ is thermo-optical coefficient. Therefore, in the elimination of external stress strain field, metal armored fiber Bragg grating temperature sensor wavelength drift changes linearly with temperature, detecting the change of wavelength, so to measure temperature change. 3. Application of Metal Armored Fiber Bragg Grating Temperature Sensor in Cable Trench and Cable Pits The system is used in 220/110/35kV substation cable trench and cable pits of Yunnan power network of Zhaotong Power Supply Bureau Yanjin. When the power cable is installed on the cable trench and cable pits, it is difficult to measure the temperature by manual inspection, so temperature detection system based on the traditional telecommunication transmission can not meet the needs of application. Fiber Bragg grating real-time temperature monitoring is a distributed monitoring system, the position and (1)

Zhen Wang et al.: On-Line Monitoring of Cable Trench and Cable Pit by Using Metal Armored FBG Temperature Sensors 121 quantity of measuring point can be laid at needs, it holds high precision, fast response, far transmission distance, convenient installation, free of maintenance, harsh environment resistance, electromagnetic interference resistance, intrinsically safe and explosion-proof, has an obvious technical superiority. As shown in Fig. 2. (a) Fig. 2. (a) Cable Trench; (b) Cable Pit. (b) The cable temperature rise test has been done in the laboratory, to determine the initial temperature change and temperature distribution of the cable heat fault. Make site design site visits of transformer substation cable trench, cable pits According to a temperature measurement of a 4 core and 30 meters cable, the positioning accuracy is 1m, temperature resolution is 0.1, the effective measurement distance is up to 4 km. Following the 0.5 M per branch principles, we need 60 metal armored fiber optic Bragg grating temperature sensors in all. As shown in Fig. 3, the connecting box is placed in the 5 cable well, the 4 core cable communication cable ports, reached to the main control room then leads to No.5 well; 60 metal armored fiber optic Bragg grating temperature sensors are divided into 4 groups, respectively, occupy the 1~4 trench of fiber grating analyzer. The temperature sensors are respectively arranged: 1~15 sensors of 1 trench are arranged on the cable well 5, from 5 cable well to 35 kv cable trench high voltage interior, 35 kv cable trench high voltage interior; 1~15 sensors of 2 trench are arranged on the cable from the cable pit 5, cable pit 5 to the cable trench of main control room. 1~15 sensors of 3 trench are arranged on the cable trench from cable pit 3 to cable pit 5, cable pit 3, and the cable trench from cable pit 3 leading up to the main transformer (air cooling control box); 1~15 sensors of 4 trench are arranged on the cable pit 1, cable trench from cable pit 1 to the cable pit 5. Fig. 3. Cable trench and cable pit sensor layout figure. 4. On-Line Monitoring Data Analysis of Cable Trench and Cable Pit Fig. 4 shows the data change curve of cable trench and cable pit sensors with Yanjin environment temperature in 24 hours, at August 8, 2011. Curves are respectively got in cable trench, high voltage

122 International Journal of Smart Grid and Clean Energy, vol. 2, no. 1, January 2013 interior cable trench, cable pit and the real-time temperature monitoring Zhaotong Yanjin environment data. Fig. 4. data change curve of cable trench and cable pit sensors with Yanjin environment temperature in 24 hours In normal cable conditions of operation, the temperature changes of cable surface are mainly caused by the environment temperature change. Through the Fig. 5 data contrast curve we found that: The temperature of environment reached its lowest 22.2 at 7:00 in the morning, and reached its highest 30.5 at 16:00 in the afternoon; The cable trench sensors, reached its lowest 26.54 at 7:00, reached its highest 31.78 at 16:00; Cable trench sensors of high voltage chamber reached its lowest of 28.01 at 08:00, and reached its highest 29.25 at 00:00; The cable pit sensors reached its lowest 28.72 at 07:00, and reached its highest 35.01 at 17:00; The trend of cable surface temperature change and environmental temperature change is consistent, the data consequence is relatively stable. The temperature of cable pit sensor is 4 higher than that of cable trench on average, The temperature of cable trench sensors of high voltage chamber tend to be flat and is 2 higher than that of cable trench on average at 00:00 to 11:00, 3 lower than that of cable trench on average at 12~23. This is because the three teams of sensors laid on different locations, the ventilation performance, closure property of cable pit poorer than that in the trench, the temperature of pit is higher than the trench temperature; High voltage chamber of cable trench is indoor, plenty of equipments, and high quantity of heat production, little effect from external environment temperature, and little temperature change. The temperature sensor effectively monitors the temperature of a day. Fig. 5 shows the temperature change curve of sensors in cable trench and cable pit in 479 days. Fig. 6 shows the temperature change curve of Yanjin environment in 479 days, the time is from June 6, 2010 to September 28, 2011. Fig. 5. Temperature change curve of sensors in cable trench and cable pit in 479 days

Zhen Wang et al.: On-Line Monitoring of Cable Trench and Cable Pit by Using Metal Armored FBG Temperature Sensors 123 Fig. 6. Temperature change curve of Yanjin environment in 479 days As shown in Fig. 5, the summarizing of 60 metal armored optical fiber Bragg grating temperature sensor monitoring data, shows that the change trends of the basic temperature curve are consistent, the temperature curves of so many points are similar, there is no special point to deal with. In the long-term monitoring of 479 days, the minimum of the average daily temperature range of 60 sensors is 21.24, detected at number 9 trench 1, The maximum is 37.43, detected at number 4 trench 2, which reached its maximum temperature 43.41 on July 3, 2010, and the minimum temperature is 4.37 on January 17, 2011, detected at number 13 trench 1. As shown in Fig. 6, the environment temperature on January 19, 2011 reached its lowest 3.31, on October 15, 2011, reached its highest 33.36. Through the long-term monitoring, we see that the temperature change of metal armored fiber Bragg grating temperature sensor is consistent with the environment temperature change, which is influenced seriously by the season. There is no abnormalities or mutation in the temperature change, the change extent of the maximum and minimum value of temperature of cable trench and cable pit shows they are in normal working condition; According to the scope and the change of the long-term change trend, cable trench and cable pit temperature anomaly alarm function can be enabled. 5. Conclusion This article is about the armored optical fiber Bragg grating metal temperature sensor used in Yanjin substation in cable trench, able Cable pit, real-time online monitoring the operation situation of high voltage cables. Through the comparative analysis and monitoring of Yanjin environment within 24 hours and 479 days of temperature data change curves: cable surface temperature and environmental temperature change trend are consistent; the minimum of the average daily temperature range of 60 sensors is 21.24,detected at number 9 trench 1, The maximum is 37.43,detected at number 4 trench 2, which reached its maximum temperature 43.41 on July 3, 2010, and the minimum temperature is 4.37 on January 17, 2011,number 13 trench 1. Metal armored fiber Bragg grating temperature sensor temperature changes influenced by seasons; The temperature change has no abnormalities, mutation, the change extent of the maximum and minimum value of temperature of cable trench and cable pit shows they are in normal working condition. Cable surface temperature of cable and the carrying capacity have a certain relationship, but the cable carrying capacity, influenced by laying, operation conditions and the surrounding environment, is difficult to determine, according to the specific practical problems, we propose specific research contents and methods [7],[8]. Through the optical fiber Bragg grating sensor surface temperature of the cable to calculate the temperature of cable fiber core conductor, and then calculate the ampacities of cables, forecast the maximum load of cable, so that provide the technical basis for the electric power dispatching, to improve the cable of transmission capacity, make the cable work with its greatest potential [9].

124 International Journal of Smart Grid and Clean Energy, vol. 2, no. 1, January 2013 References [1] Zhang YJ, Kang RX, Lou JB, Wei B, Li J, Chen LJ, Su YL. Distributed temperature sensor based on fiber grating of cable. Laser & Infrared, 2010; 40(4):405-409. [2] Li J. Application of optical fiber grating temperature sensing system to on-line monitoring for power cables. East China Electric Power, 2005; 33(12):61-63. (in Chinese) [3] Peng C, Zhao JK, Miao FG. Distributed temperature system applied in cable temperature measurement. High Voltage Engineering, 2006; 32(8):43-45. [4] Zhu Y, Fu YM, Chen WM. Online deflection monitoring system for dafosi cable-stayed bridge. Journal of Intelligent Material Systems and Structures, 2006; 17:(8/9). [5] Li C, Zhang YM, Zhao YG, Li LJ, Fiber Grating: Principles, Techniques, and Applications, Beijing: Science Press; 2005. [6] Li C, You J, et al. Two-pipe fiber Bragg grating temperature sensor. Optical Technique, 2010: 36(2):1-4. [7] Fan YB, Zhang L, Meng SX, et al. Calculation of current rating for medium and low medium and low voltage XLPE cable in cluster laying. High Voltage Engineering, 2005; 31(10):59-60. [8] Zeng DX. A study of current-carrying capacity of drawlead cable in condenser bushing. IEEE Trans. on Power Delivery, 2000; 15(3):925-930. [9] Liu YG, Luo JH. Mathematical method of temperature calculation of power cable reachedor in real time. High Voltage Engineering, 2005; 31(5):52-54.