Aging test: integrated vs. non-integrated splices shield continuity systems.

Similar documents
3M Cold Shrink Splice Kit QS-III 5416A

3M Cold Shrink Splice Kit QS-III 5514A

3M Cold Shrink Splice Kit QS-III 5515A

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN

3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500

3M Cold Shrink QS4 Integrated Splice Kit QS4-35TS

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-2-4/0

3M Cold Shrink QS4 Integrated Splice Kit QS4-15SP-2-4/0

Quick Term III. 3M Cold Shrink 3 Core Indoor Termination. 3.3 kv mm 2

HSK Mine and Portable Cable Splice

3M Cold Shrink QS-III Splice Kit 5467A(S)-WF

Cold Shrink Straight Joint

Cold Shrink Three-Conductor Splice Kit QS-III for use on Armor and Non-Armor Cables Instructions IEEE Std kv Class 250 kv BIL

Instructions. Cable with Armor F CAUTION. October Rev A

3M Cold Shrink Foldback Splice Jacket Kit

F CAUTION. Jacketed Concentric Neutral (JCN) Cable. Concentric Neutral (CN) Cable. IEEE Std. No. 48 Class 1 Termination 15 kv Class 110 kv BIL

3M Cold Shrink Rubber Splicing Kit 5552

Industrial Loadbreak Elbow

3M Motor Lead Inline Splice 5331, 5332, 5333 & 5334

3M Sensored Termination (15 kv) QX-T15I-vi1-E

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES

Selecting Cables for Power over Ethernet

TFT-150R-G. Tape Shield Cable (page 2) Suggested Installation Equipment (not supplied with kit) Wire Shield Cable (page 7)

Cold Shrink Silicone Rubber Termination QT-II

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

Quick Term II. Cold Shrink Silicone Rubber Termination (With High-K Stress Relief) Instruction Sheet. Quick Term II. Silicone Rubber Termination Kits

2179-CD Series Fiber Optic Splice Closure. Installation Instructions

Built tough for long-term connections

Quick Term II Silicone Rubber Termination Kits for Shielded Cables Instruction Sheet

3M Better Buried Closures

2016 Cable Splicing Courses

High Temperature Operation of Extruded Distribution Cable Systems. White Paper

3M Scotchcast Flexible Power Cable Splice Kits 82-F Series

Safety Codes Council Conference Banff C Panel Discussion

PEM1124ENG ENGLISH. STK TERMINATION KIT FOR PLASTIC CABLE WITHOUT ARMOURING 1 kv STKR TERMINATION KIT FOR PLASTIC CABLE WITH ARMOURING 1 kv

Built tough for long-term connections

STRAIGHT TWO WAY JOINT3/C, PAPER INSULATED, SHIELDED, LEAD COVERED CABLE. Revised: October 10, 2008 Revised By: SGL Approved By: RHS SPLICES

3M Scotchcast Reenterable Signal and Control Cable Splicing Kits 78-R Series

Cable Retention Force Testing of Trunk & Distribution Connectors

3 Foam Sealed Closure 2" (50 mm) with Compound Compression

3M Better Buried Compound Compression Closure System

SECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.

Communication Markets Division 3M Scotchlok Connectors and Tools. Proven. Solutions for. Today s Applications

FLUID VIEW 12V LED TAPE LIGHT

3 Cold Shrink Products

Low Voltage Splices, 1000 V or less

INSTALLATION INSTRUCTION PEM1368ENG ENGLISH

Scotch Heavy Duty Vinyl Electrical Tape 22

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

K & B Flame Retardant Building Riser Closures

PEM1126ENG ENGLISH STPKR. TERMINATION KIT FOR PAPER CABLE WITH LEAD SHEATH 1 kv INSTALLATION INSTRUCTION

Scotchlok Connectors and Tools

COOPER POWER SERIES. 600 A 15/25 kv class DT625 T-body installation and cable preparation instructions. Deadbreak Apparatus Connectors MN650017EN

3M Better Buried Closure (with 3M Scotchlok Shield Bond Connector 4462-FN and 3M High Gel Re-enterable Encapsulant 8882)

3M Scotchcast Mine and Portable Cable Splice and Jacket Repair Kit M-40

Aruba Outdoor AP Antenna Weatherproofing

INSTALLATION INSTRUCTION PEM1423ENG ENGLISH

LEGEND POWER SYSTEMS

Coaxial Cable Feedline Choke Kit - 50 Ω

2178 Fiber Optic Splice Case and 2181 Cable Addition Kit

Crimplok. Connectors. 3M Crimplok ST* Connector Multimode 1. 3M Crimplok SC Connector Single-mode 2

MOTOR LEAD TO DOWN HOLE CABLE SPLICE PROCEDURE

THE EFFECT OF LOOSE CONNECTORS ON SHIELDING EFFECTIVENESS

2178-L/S Series Fiber Optic Splice Case with Gasket

VITALink Taped Splice Straight Through Crimp

Weatherproofing Coaxial Cable Connections

3M SLiC 530/533/733-2 Port 0.61 Cable Entry Bracket 3M SLiC 530/533/733-2 Port-MSM 0.61 Cable Entry Bracket

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

Cambria County Association for the Blind and Handicapped 175 Industrial Park Road Ebensburg, PA Prepared for: Prepared by:

HIGH VOLTAGE CABLE ACCESSORIES - Application, Design, Installation, Testing - Ivan Jovanovic G&W Electric Company

SnapStak Stackable Snap-In Cable Hanger Electrical and Mechanical Testing Performance

A Comparison of Dry Versus Gel Filled Optical Cables

SLiC Fiber Aerial Closure System

Automatic Connector MHV Connectors MHV Introduction MHV series connectors Contents Polarized mating interfaces Anti-Rock mating interfaces

SPECIFICATION. Spec No : VSS-1402-CS603B

Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

MPI Cable Selection Guide

3M Super 23 Electrical Tape

3M Mini D Ribbon (MDR) Cable Assembly

Installation instructions Roxtec RM ES systems

Jul03 Rev C EC

Test Report: Gamma Vibration & Shock

HN Connectors. Automatic Connector. Introduction. Contents. 631/ FAX 631/

3M - A Global, Diversified Technology Company

GPS4000. GPS Time Receiver System. User Manual Version 1.1. World Time Solutions. World Time Solutions Limited

Student Services & Classroom Addition

Installation instructions Roxtec CM PE systems

3 SLiC Aerial Closure with Rubber End Seal

Installation instructions Roxtec RM PE B

Installation instructions Roxtec RM BG B systems

Multi-Media Installation Guide

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

TE Connectivity DEUTSCH DL Series MIL-DTL Series III Connectors

Surface Mount Multilayer Ceramic Capacitors for RF Power Applications

3M Distribution Box (DDB)

PT9420 Cable Actuated Sensor Industrial ma 0..20mA

Installation instructions Roxtec RM ES B

FOSC-600 C and D I N S T A L L A T I O N I N S T R U C T I O N

ASSEMBLY, INSTALLATION, AND REMOVAL OF CONTACTS AND MODULES

Transcription:

Aging test: integrated vs. non-integrated splices shield continuity systems. George Fofeldea Power Engineer, 3M Canada November 2018

Abstract To maximize long-term splice performance, the implications of the field conditions must be understood before an application is chosen, including the shield continuity connection. Currently, there is no technical comparison between a crimped and noncrimped shield connection. Testing in a lab against standard field conditions doesn t tell us the full story when evaluating the reliability of an electrical splice and its shield connection. In fact, our tests show that you should strongly consider the environment before choosing your splicing solution. 2

Table of contents Introduction... page 4-5 Materials and methods... page 5-7 Test setup... page 6 Test procedure... page 7 Study methodology... page 7 Results... page 7-9 Table 1: Accelerated aging test... page 9 Discussion... page 10 Conclusion... page 11 References... page 12 3

Introduction Traditionally, the utility industry has rebuilt the shielding continuity of jacketed concentric neutral (JCN) cables by bundling up the concentric neutral (CN) wires and crimping them with one or two connectors. In certain special applications, such as steel-wire armour submarine cables, each individual concentric neutral wire is connected with one connector to the concentric neutral wire of the other cable. Most splicing solutions offered by manufacturers today involve re-jacketing for mechanical and environmental protection. This type of bundled and crimped connection has been used for decades by utilities and industrial customers with very good results. Crimp sleeve Bundled neutral wires Splice body Neutral pad Figure 1: Shows bundled and crimped wires over a splice body. Today, JCN cables are used most often, but in the past, unjacketed CN cables were also used. From a shield continuity perspective, crimped and bundled neutral wires have proven to perform well in the field, even with unjacketed cables that are exposed to the environment. The crimped shield connection was and still is being used in various environments (e.g., heavy salt, different de-icing substances, water, etc.) with both jacketed and un-jacketed distribution cables. 1 Heavy Different de-icing salt substances Water accumulated in the cable chambers However, recently the utility industry introduced integrated joints. 1 The integrated joint design requires the CN wires to be cut and the shielding sleeve (that provides electric continuity) to be attached by constant force springs to the CN wires, on both sides of the splice. Manufacturers, like 3M, have tested this assembly in the lab with very good results. For example, a 3M laboratory test (see Chart 1) shows that after 550 current cycles (three-hours on : three-hours off ) at an applied current of approximately 250A, the connections remained stable and the temperatures of the constant force springs stayed in the range of 31-34 C (recorded jacket temperatures in the range of 29-30 C). 2 4

Chart 1 Results from laboratory test 40.00 275.00 Constant Force Spring Connection 1 35.00 225.00 Constant Force Spring Connection 2 Cable Jacket 30.00 Applied Current Temperature ( C) 25.00 20.00 15.00 10.00 175.00 125.00 75.00 Current (A) This is an example of a typical lab test to assess the integrity of a certain connection, which helps engineers optimize design and select final splice solutions in terms of shielding components. 5.00 25.00 0.00-25.00 0 1 2 3 4 5 6 Cycle Point (Hour) Once a splice is installed in the field, it could be subject to non-standard service conditions and/or adverse environments, some of which are outside the control of the installers, owner-operators, or splice manufacturers. These installation inconsistencies can affect the long-term performance and life expectancy of an installed splice. Examples of such elements include corrosive water, higher or lower circulating currents through the shielding system, system transients, deviations from the recommended installation instructions, etc. As a result, a laboratory test was designed to assess some of the non-standard conditions that may occur in certain environments, such as underground cable chambers and vaults, windfarms, or other industrial locations. The goal of this technical comparison test is to equip the reader with the research to help answer: which splice is right for my field condition(s)? Materials and methods A test was conducted in a controlled laboratory environment to determine which splicing method integrated connection or traditional crimp connection is most effective when the splice is exposed to non-standard conditions. Effectiveness was determined using two measures: speed of degradation and temperature. The comparison: A shield connection that uses taped and non-taped constant force springs attached to a shielding sleeve overlapping CN wires versus a connection that uses the traditional crimped connector method of the CN shield wires. 5

Test setup Loop configuration 1 assembly shielding sock with constant force springs, covered with vinyl electric tape* (see Figure 2) 1 assembly shielding sock with constant force springs, not covered with vinyl electric tape* (see Figure 3) 1 crimped connector connecting the CN wires. The connector used is 10006 2/0 CU (see Figure 4) (e.g., traditional crimp connection) Figure 2: Assembly shielding sock with constant force springs, covered with vinyl electrical tape * Figure 3: Assembly shielding sock with constant force springs, not covered with vinyl electrical tape * Note: the shielding sock has been connected to the CN wires of a 4/0 AL, 35 KV, 20x12 AWG CN wires cable by means of two constant force springs (shown in Figure 2 and 3). This shield connection procedure is in compliance with the installation instructions of the 3M Cold Shrink QS4 Integrated Splice Series shown in Figure 5. * Two half-lapped layers of Scotch Electrical Shielding Tape 24 was applied to the cable semi-con, the CN wires were then laid on top and the ends were wrapped with aluminum tape to hold them in place. Figure 4: Crimped connector connecting the CN wires. The connector used is a 10006 2/0 CU Insulation Semi-Con Press down edge tightly Neutral wires 3M Aluminum Foil Tape Strip 1115B Scotch Electrical Shielding Tape 24 Figure 5: 3M Cold Shrink QS4 Integrated Splice Series 6

Test procedure Approximately 200A were circulated through the CN wires of the test loop, which ran on a three-hours on and three-hours off current cycle. At the beginning of each of the two current cycles during an eight-hour workday, a salt/water solution with a concentration of 300 µs/cm was sprayed over the connections (vinyl taped constant force springs, non-vinyl taped constant force springs, and crimp connector). ON OFF Study methodology The reason for vinyl taped connections versus non-vinyl taped connections was to understand the performance difference that taping the constant force spring introduces. The omission of the tape or the use of incorrect taping technique (e.g., tape not properly stretched, or tape applied on the shielding sleeve as opposed to over the constant force springs, or only one layer of tape applied as opposed to two) are frequent mistakes in the field. The reason for running 200A RMS through the loop was to age the connections faster as opposed to testing with lower ampacities necessitating more cycles. The application of the salt/water solution was intended to simulate field corrosion conditions and to faster age/degrade the connections. Results The test results show (see Chart 2) that the crimped CN connection is stable over time, while the taped and non-taped constant force spring connections to the shielding sleeve have the tendency to degrade faster as measured through temperature increases over the duration of the cycles. The graph below shows results for 1013 cycles completed from 07/20/2017 to 04/03/2018 with an additional 194 cycles for a total of 1207 cycles to 05/22/2018 with the test setup and procedure described above. Chart 2 JCN Shield Load Cycling 120 200 100 80 150 Temperature ( C) 60 100 Current (A) 40 50 20 0 0 0 200 400 600 800 1,000 1,200 Cycles Crimp Connector Vinyl Taped Constant Force Spring Non-vinyl Taped Constant Force Spring Current 7

Results (cont d) 1.0 As can be seen in Chart 2, the crimp connector is stable and running at a temperature below 47.2 C (the range of temperature measurements is 41.03 C-47.16 C) for 1,207 cycles, well below the taped and non-vinyl taped connections, over the same number of cycles. 2.0 The vinyl taped connections reached an average of 80.61 C and the non-vinyl taped connections reached an average exceeding 100 C after 1,013 cycles. 3.0 Both the vinyl taped, and non-vinyl taped connections have the tendency to degrade faster compared to the crimp connector, but the vinyl taped connections behave somewhat better (slower rate of degradation) compared to the non-vinyl taped connections. This can be explained by the fact that the applied vinyl tape adds pressure to the constant force springs and makes it more difficult for either the salt/ water spray solution to reach the constant force spring/shielding sock connection, or for the spring connections to loosen during the heat cycling, or both. 4.0 8 The reason for completing the additional 194 cycles after the first 1,013 cycles was to understand if the same trend is confirmed (increase in temperature of the constant force spring connections versus the stable crimp connections) if we tighten up the constant force springs after loosening up during the 1,013 cycles testing. As can be seen on Chart 2, both the vinyl taped, and non-vinyl taped constant force spring connections exhibit a similar temperature increase trend from cycle 1,014 to 1,207. The temperature of the non-vinyl taped constant force spring connection at the end of cycle 1,207 was 51.16 C (33.06 C at the beginning of cycle 1014) and the temperature for the vinyl taped connection at the end of cycle 1,207 was 41.38 C (25.57 C at the beginning of cycle 1,014).

Table 1 gives a summary of the temperature measurements: Cycle number End of 1,013 Cycle 1014/End of cycle 1,207 Avg. temperature range (from MIN. to MAX. readings) over 1,207 cycles Avg. taped connections temperature Avg. un-taped connections temperature Avg. crimped connector temperature 80.61 C 100.74 C 40.29 C 25.57/41.38 C 33.06/51.16 C 40.29/43.2 C 27.81-90.11C 28.87-104.86C 40.29-47.16 C Table 1: Temperature measurements for accelerated aging test on CN wires with shielding sleeve and constant force springs. 5.0 Since no visible signs of corrosion were observed during visual examination after cycle 1,013, it is difficult to understand the impact of the salt/water spray applied at the beginning of each current on cycle and its impact on connection degradation of the constant force spring connections. It is possible that the salt/water produced some contact degradation, but not to the degree that the corrosion becomes visible. Note: the installation of the shielding sock, constant force springs and the vinyl tape has been performed by qualified lab personnel in compliance with the 3M Cold Shrink QS4 Integrated Splice installation instructions. The scope of the test (aside from the vinyl verus non-vinyl taped connections) was not to evaluate a combination of installation inconsistences (e.g., constant force springs not tightened properly; missing one or more constant force springs; some constant force springs taped, some not; vinyl tape present between shielding sleeve and springs preventing a good connection, etc.), but to try to understand the speed of degradation in a somewhat corrosive environment. 9

Discussion From splice body to material to installation, the end user should carefully consider all advantages and disadvantages of integrated versus non-integrated splices 1 and the specific operating conditions of the electric system it is part of. The design of the grounding system (e.g., type, cross-bonding, potential circulating currents, etc.) can also have an impact on the longevity of the shielding system of the splice and cable. 10

Conclusion The end-user should evaluate and understand not only the differences in installation steps between an integrated and non-integrated splice but should also try to determine which environmental factors may impact the long-term performance of the cable/splice assembly. This type of aging test demonstrates that crimped CN connections typically used with non-integrated splices are more stable compared to the constant force spring/shielding sleeve connections used with integrated splices under the described test conditions. For more information about 3M electrical products and solutions contact us at: 3Menergysolutions@mmm.com. 11

3M Science. Applied to Life.TM Electrical Markets Division Customized Solutions Building Customer Value Technical Expertise Customer Experience Reliable Products and Total Cost of Ownership References 1 2 White paper How do you take your splice? Integrated or not?, May 2015 Test report Cold shrink integrated splice kits, metallic shield restoration sock continuous current evaluation TRQSIII-IJ_MS-CC, February 2009 Important Notice The technical information, guidance, and other statements contained in this document or otherwise provided by 3M are based upon records, tests, or experience that 3M believes to be reliable, but the accuracy, completeness, and representative nature of such information is not guaranteed. Such information is intended for people with knowledge and technical skills sufficient to assess and apply their own informed judgment to the information. No license under any 3M or third party intellectual property rights is granted or implied with this information. 3M Electrical Markets 3M Canada P.O. Box 5757 London, ON N6A 4T1 1-800-364-3577 3M.ca/Electrical 3M, 3M Science. Applied to Life. and Scotch are trademarks of 3M. Used under license in Canada. 2018, 3M. All rights reserved. 1807-12376 E BA-18-26903