EG4015. Digital Generator Governor Controller User Manual

Similar documents
EA63-7D. Generator Automatic Voltage Regulator Operation Manual. Self Excited Automatic Voltage Regulator

Self Excited Automatic Voltage Regulator For Generator Compatible with Marathon SE350* Operation Manual

EA350. Generator Automatic Voltage Regulator Operation Manual

ADVR-053. Universal Hybrid Analog-Digital Voltage Regulator Operation Manual

EVC300i. Generator Automatic Voltage Regulator Operation Manual

EVC600i. Generator Automatic Voltage Regulator Operation Manual

Universal Hybrid Analog-Digital Voltage Regulator Operation Manual

1.5mm amplitude at 10 to 55Hz frequency in each X, Y, Z direction for 2 hours 500m/s² (approx. 50G) in each X, Y, Z direction for 3 times

ADVR-08. Universal Hybrid Analog-Digital Voltage Regulator Operation Manual

Assembly. Front view. LEDs. Parametrization interface. Power Bus

ORDERING Page 6 BASLER RELAY STANDARDS, DIMENSIONS, ACCESSORIES Request bulletin SDA

Contactless encoder RI360P0-QR24M0-INCRX2-H1181

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

AF-300 E11 Adjustable Frequency Drive

2 WIRE - LOOP POWERED TRANSMITTER FOR PT100 AND NI100 PROBES

High performance circuit breakers

INSTALLATION MANUAL FT-FOTR-1VDE-ST-S

Reproduce Amplifier Revision-D

Contactless Encoder Analog RI360P0-QR24M0-ELIU5X2-H1151

Contactless Encoder IO-Link Ri360P0-QR24M0-IOLX2-H1141

HYL-035D0850G103. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

TOSHIBA Industrial Magnetron E3328

INSTALLATION MANUAL FT-FOTR-8VD-ST-S. 8-Channel Digital Duplex Baseband Video Transmitter and Receiver With Reverse Data Transmission for PTZ Cameras

INSTRUCTION & OPERATION MANUAL. MODEL MMW-05 (5kW) MUROMACHI MICROWAVE FIXATION SYSTEM

VLC-3 USER'S MANUAL. Light Program Controller. M rev. 04 K rev. 00 & ( ( 5, 352*5$0 1 : $ 2 ' 6(77,1*6 )81&7,216

SQM40/41 Actuators for air and gas dampers

Contactless Encoder Incremental: ppr RI360P0-QR24M0- INCRX2-H1181

ORDERING Page 6 STANDARDS, DIMENSIONS and ACCESSORIES Request bulletin SDA

MS2540 Current Loop Receiver with RS485 Communication

RGB-3400-X RGB SEQUENCER / 3-CHANNEL UNIVERSAL LED DIMMER

P Output Ratings. Dimensions and Weights. Prime Rating

P Output Ratings. Dimensions and Weights. Prime Rating

P88-3. Output Ratings. Dimensions and Weights. Prime Rating

P Output Ratings. Dimensions and Weights. Prime Rating

P Output Ratings. Dimensions and Weights. Prime Rating

P Output Ratings. Dimensions and Weights. Prime Rating

P550-3L. Output Ratings. Dimensions and Weights. Prime Rating

P65-5. Output Ratings. Dimensions and Weights. Prime Rating

82384R. SPM-A Synchronizer. Installation, Operation, and Calibration Manual. Manual 82384R

Bill of Materials: Super Simple Water Level Control PART NO

Manual. Analog (U/I) Sendix M3661 / M3681. Sendix M3661R. Sendix M5861. Absolute multiturn encoder. Order code: 8.M36X1.XXXX.XX12

SyG 02 and SyG 02-SB

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

P400-3L. Output Ratings. Dimensions and Weights. Prime Rating

Inductive linear position sensor LI300P0-Q25LM0-LIU5X3-H1151

P Output Ratings. Dimensions and Weights. Prime Rating

Flat-Bed Module Recorders

LXM23DU10M3X motion servo drive - Lexium 23 - single phase V - 1 kw - I/O

Standard signal metering in wall-mounting case

Soft starter, 66 A, V AC, Us= 24 V DC, with control unit, Frame size N. Function Soft starter for three-phase loads, with control unit

AK-PVE4 Operating Instructions. Measuring of norm signals in wall-type units. Performance:

ADJUSTABLE SPEED DRIVES. nc1 Drive

Ratings at 0.8 power factor. Please refer to the output ratings technical data section for specific generator set outputs per voltage.

P1000P1/P1100E1 50Hz

P Output Ratings. Dimensions and Weights. Prime Rating

P800P1/P900E1. Output Ratings. Dimensions and Weights. Prime Rating

P Output Ratings. Dimensions and Weights. Prime Rating

Transfer Switch. OTECA (Spec A) OTECB (Spec A) OTECC (Spec A) OTECD (Spec A) Amperes. English Original Instructions (Issue 5)

UDC100 Universal Digital Controller. Specification. Overview. Features. Features, continued /99 Page 1 of 4

POINTS POSITION INDICATOR PPI4

P1350P1/P1500E1 50Hz

Product Manual (Revision U, 10/2007) Original Instructions. SPM-A Synchronizer. Installation and Operation Manual

MODEL PA II-R (1995-MSRP $549.00)

Figure 1: Device components

02/11/2015

Series CT7N Bimetallic Overload Relays

MICROMASTER Encoder Module

DCP100 Digital Control Programmer Specifications

Magnecraft General Purpose Relays 750R Series DPDT and 3DPT, 10 A

16 Stage Bi-Directional LED Sequencer

Instruction Manual. Universal Flow Controller Model 261 / 261-EC-01

MTI-2100 FOTONIC SENSOR. High resolution, non-contact. measurement of vibration. and displacement

Contactless encoder Ri360P0-QR24M0-HESG25X3-H1181

BOSTON GEAR CONTROLLERS. ACE 10 Series 1/4 through 3 HP Adjustable Frequency AC Motor Controllers MEX (55) QRO (442)

Junior Max (JR Max ) Controller

Model Number Structure

Telemetry Receiver Installation Guide

User Guide. Single-Link DVI Active Cable Extender. DVI-7171c

LED DRIVERS. LQC4D-V1 4 channels. User Manual FEATURES

LVDT. Inductive Position Transducer - Hydraulic Series. SM-HYD Hydraulic Series. Key-Features:

SURFACE MOUNT HIGH REPEATABILITY, BROADBAND TO-5 RELAYS DPDT

Electrical connection

34MD Series. Motor/Driver Combination. User s Guide E. Landon Drive Anaheim, CA

www. ElectricalPartManuals. com l Basler Electric VOLTAGE REGULATOR FEATURES: CLASS 300 EQUIPMENT AVC63 4 FEATURES AND APPLICATIONS

DLP600M 6+1 Relay Module for Heating and Cooling Plants

Installation. SAPTF33xx-1xx in the Network. Standard Configuration

Operating instructions Electronic preset counter Type series 717

Electronic Panel Meters DIGEM Preference Program Process control, automation & laboratory uses Class 0.01 to 1 Current, Voltage, Frequency,

COHERENCE ONE PREAMPLIFIER

Manual #: UMA1074 Rev. 2 October, Hall Research Technologies, Inc 1163 Warner Ave. Tustin, CA 92780

Indoor Linear 80W Driver SI-C215280N2KR

Operation Manual TX20 1/8 DIN Microcomputer Based ph/orp Controller with relays

Contactors. Agency approvals. UL 508 Guide No. NLDX2, File # E CE/Semko Certified EN :1991 IEC DP 30 C 3P - 1 /B

3.5. Control Relays and Timers. Contents. 9575H Series 3000 Type AA, AC and DC. General Purpose Relays Type AA

PHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series

Modular Lube Lubrication Systems System Controls

DATA SHEET. Synchronisers, FAS-113DG ANSI code 25

Electrical connection

Agency approvals UL 508 Guide No. NLDX2, File # E CE/Semko Certified EN :1991 IEC DP 30 C 3P - 1 /B

Photoelectric Sensors E3F2

Transcription:

EG4015 Digital Generator Governor Controller User Manual Digital Governor for use in Gas and Diesel Generators with smoke and idle controls. Senses generator frequency, no magnetic pickup unit (MPU) is required. Applicable to all types of generator engines and also supports External, Internal, and PT Pump mounted actuators. SP POWERWORLD LTD Willows, Waterside, Ryhall, Stamford, Lincs, PE9 4EY, UK Tel: +44 1780 756872 - Email: info@sp-powerworld.com www.sp-powerworld.com

SECTION 1 : SUMMARY The EG4015 uses the generator frequency to control engine speed. It works without a magnetic pickup (MPU), a digital circuit detects the reference frequency from the generators output. Digital governors are not influenced by frequency drift caused by temperature. For example over a temperature range from -40 to +80 C the frequency drift is only +/- 0.1 Hz. EG4015 uses advanced PID algorithms, together with GAIN and DIF pots to simplify adjustments and governor response. The EG4015 can be used in all types of engine actuators that work with less than 15Amps and Cummins PT PUMP. LED indicators allow users to easily determine operational and fault conditions making it easy to install and calibrate. SECTION 2 : SPECIFICATION Sensing Input (S1, S2) Protection Functions Voltage 1 600 Vac Loss Sensing Protection Frequency 5 100 Hz Actuator Short Circuit Protection activate to stop the output Overspeed Protection activate to stop the output Operating Voltage (DC+, DC-) Max. 57 Hz @ 50 Hz system Voltage 10 32 Vdc Max. 67 Hz @ 60 Hz system Reverse Voltage Protection VR Adjustment Max. -50 Vdc SPEED 50 Hz : 45 to 55 Hz 60 Hz : 55 to 65 Hz Actuator Output (ACT+, ACT-) DIP PID Differential adjustment Current Continuous 15A GAIN PID Actuator output gain adjustment Steady State Speed Band DIP Switch +/- 0.25 % (with stable load) SW1 Actuator type OFF : External or Internal mount ON : PT PUMP mount IDLE Speed Frequency SW2 Ramp time OFF : 10 seconds ramp time 25 Hz @ 50 Hz mode ON : Immediate 30 Hz @ 60 Hz mode SW3 frequency selection OFF : 60 Hz ON : 50 Hz Temperature Drift Frequency Range 0.1 Hz @ -40 to +80 C Environment Operating Temperature -40 to +80 C External Frequency Control (VR1, VR2, VR3) Storage Temperature -40 to +85 C Frequency adjustment range Relative Humidity Max. 95% +/- 2 Hz 5K ohms 1watt potentiometer Vibration 5 Gs @ 60 Hz EMI Suppression Dimensions Internal electromagnetic interference filtering 162.0 (L) x 112.0 (W) x 43.0 (H) mm and common mode ferrite beads Weight Static Power Dissipation 330 g +/- 2% Min. 120 ma @ 12 Vdc Min. 60 ma @ 24 Vdc 2 EG4015

SECTION 3 : APPEARANCE / DIMENSIONS / INSTALLATION DRAWING 112.0 88.0 Accessory package Four ea. M5L30 bolts 5.2 138.0 162.0 18.3 43.0 29.5 Unit : mm Figure 1 Outline Drawing SECTION 4 : ALARMS AND WIRING DIAGRAM ATTENTION 1. Installation personnel must receive training. Defective installations may cause damage and injury to personnel. 2. Always install an independent shutdown device. If by chance power is lost the generator can stop and avoiding damage to equipment and personnel. 3. Install a second engine shutdown device is suggested, such as an emergency fuel switches or air intake damper in order to immediate stop the engine if there is a system failure. 4. Always use a 20A slow-blow fuse between the battery and the governor. 5. Use #AWG10 (2.58 mm 2 ) or a higher between the battery and the actuator. 6. SENSING wire to (S1, S2) must be # AWG18 (1.02 mm 2 ) with an insulation voltage rating of 600V or higher. EG4015 3

GAIN adjustment DIF. adjustment Generator frequency DIP OFF ON SW1 External or Internal PT PUMP mount mount actuator actuator SW2 10 seconds ramp time Immediate start SW3 60 Hz 50 Hz 1 2 3 Flashing : Standby, not operating Steady:Sensing Input Active Steady:Open detected Steady : Actuator current (short circuit) over Steady:Engine overspeed S1, S2 terminals L1, L2 (phase-to-phase) always connect to input side of the breaker. 20A Fuse Power SW L-L Generator SW-A Engine Start Switch Open:Disabled Closed:To force actuator output when no residual generator voltage is present on startup. + 12/24 VDC Actuator SW-B Engine Idle Switch Closed:Engine @ Idle speed 25 Hz @ 50 Hz mode 30 Hz @ 60 Hz mode Load Shield Ground Use wires with shield (Mylar foil insulation with copper grounding wire) grounded on one side only. External Frequency Control 5K ohms 1 watt potentiometer:+/- 2 Hz Leave the terminal open when no external pot is used. 4 EG4015

SECTION 5 : INSTALLATION 5.1 Inspections before starting engine 5.1.1 Check that all wiring is correct. Before starting the engine, turn on the power source to the unit (Power SW) and close the engine start switch (SW-A). The actuator will be forced to its maximum on position confirming that the wiring between the battery and the actuator are working normally. This also confirms the actuator is working smoothly without getting stuck. Repeat several times to check the operation. 5.1.2 Set GAIN, DIF potentiometers (pots) to a central position. 5.1.3 If the external frequency control potentiometer is used, it should be adjusted to its central position. Keep these terminals open when not in use. 5.1.4 DIP SW 1, 2, 3 should be set to the desired modes of the system. 5.1.5 Idle setting. With SW-B closed the engine will enter idle speed (25 Hz or 30 Hz). When SW-B is opened the engine will go directly to the rated speed (50 Hz or 60 Hz). Select according to generator requirement. 5.1.6 Use an analog frequency meter while making adjustments to make it easier to measure changes in generator frequency. 5.1.7 We recommend installing a fuel switch that can immediately shutdown the engine when the system is not operating normally. 5.2 Starting the engine 5.3 Idle (IDLE) operation Engine is started and SW-B is closed : the engine will enter Idle speed (25 Hz or 30 Hz). When the engine Idle Speed countdown is completed SW-B will open and the engine will reach the rated frequency (50 Hz or 60 Hz). Engine is started and SW-B is opened : engine will go directly to the rated operating frequency. 5.4 Engine Speed Ramp Time 5.4.1 DIP SW2 OFF - the ramp up time from Idle frequency to rated frequency is 10 seconds. 5.4.2 DIP SW2 ON - the generator will immediately go to rated frequency. 5.5 Unstable engine speed If the engine speed is unstable when running adjust the GAIN pot counter-clockwise (CCW) until the engine stabilizes. 5.6 Generator frequency adjustment When the engine speed is stable, then adjust the SPEED potentiometer on the governor or the external 5K frequency pot to your rated frequency (50 or 60 Hz). 5.7 Restart the generator Shutdown the generator and restart to confirm that the governor is controlling engine speed and starts smoothly. If it is stable during this period then go to < SECTION 6. Optimal Engine Response Adjustment Procedure > below but if not stable repeat Step 5.1. 5.2.1 After turning on the unit power (Power SW) start the engine. 5.2.2 When the starter motor begins to turn terminals S1, S2 will detect the starting frequency and the actuator will be forced to its maximum engine start output (pulled to all the way on). After the engine is started (frequency > 18 Hz), the controller will automatically adjust the actuator according to frequency. 5.2.3 If the residual voltage of the generator is too low ( < 1 Vac @ 5 Hz) terminals S1, S2 cannot detect the starting frequency and the actuator will have no output, thus preventing the engine from starting. In this situation connect the engine start switch (SW-A) directly to the starter motor. Alternatively, when the engine is starting close the engine start switch (SW-A). The actuator will open to full output when the engine is cranking helping the engine to start smoothly. EG4015 5

SECTION 6 : Optimal Engine Response Adjustment Procedure 6.1 After Step 5. Installation is completed and engine start operation is smooth, carry out the following adjustments with generator in a no-load condition. 6.2 Slowly adjust the GAIN potentiometer clockwise (CW) until frequency swings rapidly, then slowly adjust in a counter-clockwise direction (CCW) until the frequency is stable. Wait for the frequency to stabilize, then adjust a further turn counter-clockwise (CCW). CCW 1/2 Grid CW CCW GAIN GAIN GAIN 6.3 Slowly adjust the DIF pot (CCW) until the frequency goes from stable to oscillating, then slowly adjust (CW). The oscillations will gradually stabilize. Wait for the frequency to stabilize then turn (CW) approximately one more time. CW 1 Grid CCW CW DIF DIF DIF 6.4 Push (or tap) the arm of the actuator with your hand or add a load to the generator and observe how the frequency recovers. If normal it should return quickly to stability. If further adjustments are required then repeat Steps 6.2 and 6.3 to readjust. 6.5 Optimal response curve and the DIF potentiometer adjustment. DIF setting insufficient - oscillations continue long after a load has added DIF setting for optimal response curve DIF setting too high. Frequency recovers too slow after a load has been added 6.6 Optimal response curve and the GAIN adjustment GAIN setting too low. Frequency recovers slowly after a load is added GAIN setting for optimal response curve GAIN setting too high. Oscillations continue far too long after a load is added 6 EG4015

SECTION 7 : TROUBLESHOOTING PROBLEM CORRECTIVE ACTION 7.1 Engine Overspeed 1. Engine overspeed caused by inappropriate setting of GAIN & DIF potentiometers. Adjust settings according to procedure in Step. 5. 2. Check whether or the wiring for the voltage detection inputs (S1, S2) is normal, and whether or not the residual voltage produced is > 1 Vac. 3. Check whether actuator is stuck in lowest position, causing overspeed. 4. If all of the checks above are normal then change the EG4015 controller. 7.2 Actuator cannot open completely to maximum output 7.3 Actuator does not operate 7.4 Over Current (short circuit) protection lamp illuminated 1. Check if the battery voltage is below 10 Vdc. 2. Check if the actuator has overheated. 3. Check whether the actuator specs. match the driving power supply voltage. 4. Check that the linkage between the actuator and the fuel valve is not impeded. 5. For actuator installation refer to Electronic Governor Controller Concept http://www.kutai.com.tw/en/electronic-governor.html 1. Check the power switch and the fuse. 2. Using an ohm meter measure ACT+, ACT- terminals will measure the internal resistance of the actuator (pay attention to measurement polarity). If the actuator is damaged it is possible that the measured resistance level will not meet the specifications of the actuator. Change the actuator to meet system requirements. 3. Confirm that the actuator has been installed in accordance with Step 5.1.1 1. Check whether or not the actuator is short-circuited. 2. Check whether the actuator has a parallel diode. Ensure that the ACT+ is connected to the N (Cathode) pole of the diode, and ACT- is connected to the P (Anode) pole. 7.5 Engine will not start 1. Check whether or not the actuator is a maximum during starting. If it cannot be opened to the maximum then reference Step 7.2 above. 2. Check whether there is sufficient fuel and the fuel switch is open. 3. It is possible that air could be trapped in the fuel line. 4. Check the fuel time for leaks. Try manually operating the engine. 7.6 Engine speed oscillates irregularly 7.7 Engine speed continually swings after a load is added 7.8 Frequency oscillates in a small range 7.9 Radio Frequency Interference (RFI) causing irregular engine speed oscillations 1. Measure voltage between B+ and B- on the EG4015. If voltage is insufficient ( < 10 Vdc) it could possibly cause irregular operation. Change the battery. 2. RFI caused by improper shielding. Fix shield grounding wire. 1. Gain adjustment is not good. Re-adjust Gain setting according to Step SECTION 6. Optimal Engine Response Adjustment Procedure. 1. Check the linkage between the actuator and the fuel valve, either too tight or if there is a gap (too loose). Correct any problems with the linkage. 1. Install EG4015 in a grounded metal case in order to shield from RFI. Appearance and specifications of products are subject to change for improvement without prior notice. EG4015 7