C I R E D 19 th International Conference on Electricity Distribution Vienna, May Transition Joints Behaviour. Paper 457 INTRODUCTION

Similar documents
TIME DOMAIN SPECTROSCOPY (TDS) AS A DIAGNOSTIC TOOL FOR MV XLPE UNDERGROUND LINES

ECONOMICAL 36 kv CABLE SYSTEM FOR THE BELGIAN NETWORK

INSULATION CONDITION OF DRY-CURED XLPE CABLES MEASURED OVER A PERIOD OF 13 YEARS

Condition Monitoring Program of HV Cable Systems

ANALYSIS OF FAILURE IN POWER CABLES FOR PREVENTING POWER OUTAGE IN ALEXANDRIA ELECTRICITY DISTRIBUTION COMPANY IN EGYPT

Underground Cable Diagnostic Testing Utilizing Partial Discharge Technique

M4000 Diagnostic Test System For Power Apparatus Condition Assessment

AMERICAN NATIONAL STANDARD

220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX

High Temperature Operation of Extruded Distribution Cable Systems. White Paper

Diagnostic & Testing Services

Revision of Qualification Procedures for High Voltage and Extra High Voltage AC Extruded Underground Cable Systems

Medium Voltage 12/20 (24)kV NF C cable system. Xavier Brosse Luanda May 2009

How to Implement PoE in Your Harsh Industrial Environment

INTEGRATED CIRCUITS DATA SHEET. TDA4510 PAL decoder. Product specification File under Integrated Circuits, IC02

CHAPTER 1. Introduction

2004 SC B1 PROGRESS REPORT (INSULATED CABLES)

640 kv XLPE HVDC cable system

HAL Series. Versatile range of production line testers.

System solutions: Partial discharge measurement and monitoring systems.

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES

Monitor QA Management i model

REFURBISHMENT OF SECONDARY SYSTEMS IN HIGH VOLTAGE SUBSTATIONS LESSONS LEARNED IN VENEZUELA

Long Term Analysis of Cables Problems in Egyptian Distribution Network

Fieldbus Testing with Online Physical Layer Diagnostics

CHAPTER 3. HV and EHV Cable System Aging and Testing Issues

Highly Accelerated Stress Screening of the Atlas Liquid Argon Calorimeter Front End Boards

Using Ultrasound and Infrared Technologies for Metal-Clad Switchgear Inspections

Aging test: integrated vs. non-integrated splices shield continuity systems.

Designing Intelligence into Commutation Encoders

2 Work Package and Work Unit descriptions. 2.8 WP8: RF Systems (R. Ruber, Uppsala)

FORENSIC CASEBOOK. By Bob Huddleston, Eastman Chemical Co. One of the most common. reasons for marriage failure

Extreme Experience Research Report

DUCATI SISTEMI S. P. A. DUCA47-96 USER MANUAL

18 GHz, 2.2 kw KLYSTRON GENERATOR GKP 24KP 18GHz WR62 3x400V

Commissioning the TAMUTRAP RFQ cooler/buncher. E. Bennett, R. Burch, B. Fenker, M. Mehlman, D. Melconian, and P.D. Shidling

HARMONIZATION OF SYNOPTIC BLOCK DIAGRAMS ON THE CONTROL PANELS OF MV SWITCHGEAR AND CONTROLGEAR

TRF STEP-DOWN TRANSFORMER USER MANUAL

ILC-LNF TECHNICAL NOTE

Industriefunkuhren. Technical Manual. IRIG-B Generator-Module for analogue / digital Signals of Type: IRIG-B / IEEE C / AFNOR NF S87-500

Comparative Analysis of Organic Thin Film Transistor Structures for Flexible E-Paper and AMOLED Displays

MPI Cable Selection Guide

Agilent N9355/6 Power Limiters 0.01 to 18, 26.5 and 50 GHz

USER MANUAL. Compact dimensions 6 DIN modules, with 4 LED s display with 7 segments, for an excellent reading of the measurements

G4500. Portable Power Quality Analyser. Energy Efficiency through power quality

Measurement Accuracy of the ZVK Vector Network Analyzer

American National Standard for Lamp Ballasts High Frequency Fluorescent Lamp Ballasts

LMH0344 3Gbps HD/SD SDI Adaptive Cable Equalizer

Tutorial on Technical and Performance Benefits of AD719x Family

Lecture 17 Microwave Tubes: Part I

Catalogue Ignitors and power switches for HID

R&S RT-Zxx High-Voltage and Current Probes Specifications

Beam Loss Detection for MPS at FRIB

Alcatel-Lucent 5620 Service Aware Manager. Unified management of IP/MPLS and Carrier Ethernet networks and the services they deliver

LED Driver Linear / area dimming

Motion detector theluxa P300 KNX Motion detector theluxa P300 KNX

Arduino Nixie Clock Classic Rev4 and Rev5 All In One Modular Rev2

Front End Electronics

HDMI Demystified. Industry View. Xiaozheng Lu, AudioQuest. What Is HDMI? Video Signal Resolution And Data Rate

Guidelines for Specification of LED Lighting Products 2010

BAS70 series; 1PS7xSB70 series

OpticalProducts. Illuminating Your Network. Testing the World s Networks

013-RD

Cable solutions for all environments. Scapa Cable Solutions

10 SERIES. Light dependent relays A

DEVELOPMENT OF A 270 kv XLPE CABLE SYSTEM FOR HVDC APPLICATION

Digital Logic Design: An Overview & Number Systems

Arduino Nixie Clock Modular Rev3

Lecture 18 Design For Test (DFT)

ANSI DESIGN TEST REPORT Report No. EU1250-HR-00 Type PVI Intermediate Class Surge Arrester

User manual. Long Range Wireless HDMI/SDI HD Video Transmission Suite

A MISSILE INSTRUMENTATION ENCODER

10 Mb/s Single Twisted Pair Ethernet Preliminary Cable Properties Steffen Graber Pepperl+Fuchs

Low Loss RG 402 Equivalent

LED Driver Linear / area fixed output

Arduino Nixie Clock Classic Rev4 and Rev5 All In One

Test Device Containment Module (TCM) Optimal conditions for reliable results

FMEA of Cable Failures within a Fire PSA

. The vertical pull-in range is approximately 10 Hz at fv = 60 Hz.

Mitigation of Cascading Outages and Prevention of Blackouts:System-Wide Corrective Control

Text with EEA relevance. Official Journal L 036, 05/02/2009 P

Methods of Inspection to Determine the Presence of Potential Arc Flash Incidents

Time-Lag Relays. User s Handbook (General Model)

SCHEDA TECNICA. Amarro per cavi 13,5mm Amarro per cavi 16,5mm. MS217F00 Amarro per cavi 13,5mm MS218F00 Amarro per cavi 16,5mm

IOT OPERATIONAL EXPERIENCE ON ALICE AND EMMA AT DARESBURY LABORATORY

GA A26497 SOLID-STATE HIGH-VOLTAGE CROWBAR UTILIZING SERIES-CONNECTED THYRISTORS

R&S RT-Zxx High-Bandwidth Probes Specifications

EMI/EMC diagnostic and debugging

MICROMASTER Encoder Module

WP36BHD T-1 (3mm) Blinking LED Lamp

Datasheet. LED Transformers. LED Transformer 120W 24V V. LED Transformers

Bringing an all-in-one solution to IoT prototype developers

Power over Ethernet Transformers 60 W series

What to look for when choosing an oscilloscope

Pulsed Klystrons for Next Generation Neutron Sources Edward L. Eisen - CPI, Inc. Palo Alto, CA, USA

GP-500 SERIES - Low Voltage

Uncooled amorphous silicon ¼ VGA IRFPA with 25 µm pixel-pitch for High End applications

klm Mark Scheme Science A 4405 / Physics 4403 General Certificate of Secondary Education Unit Physics P Examination January Series

Design for Testability

Industriefunkuhren. Technical Manual. OEM Sync-Module FE1000 (IRIG-B) ENGLISH

Transcription:

DIAGNOSI FOR ABLE SYSEM ASSE MANAGEMEN AND PREVENIVE MAINENANE A EDF hierry ESPILI Fabrice ZORZI Roger AMBRUN EDF R&D France EDF R&D France EDF EGD - France thierry.espilit@edf.fr fabrice.zorzi@edf.fr roger.tambrun@edf.fr INRODUION French MV underground network had been early and massively developed with innovative and reliable synthetic cable which represent 85 % of the MV underground network. However Paper Insulated Lead overed (PIL) cables, mainly installed 40 years ago, are still operated, particularly in French major cities. As it could need a significant amount of investment replacement of those cables is anticipated by EDF asset management to define the adequate renewal strategy. For that, accurate condition assessments based on diagnostic tools are needed. Even if most of PIL cables are still in good condition, presence of such cable lead to fault rate increase, specifically during hot summer. his is mainly due to transition joint with water penetration, so efforts on diagnostic methods were first focused on those bad joints. Managed in a second stage cable assessment is becoming soon the central activity. he off line diagnostic method developed and applied by EDF R&D for preventive joint replacement operations is first described. hen program in order to reach more accurate diagnostic criteria and to reduce resources involved in diagnostic are presented. OFFLINE DIAGNOSI MEHOD FOR RANSIION JOIN WIH WAER INGRESS Background Following increasing of fault rate observed during summer 2003 heat wave, works were engaged by EDF R&D to explain degradation mechanisms involved and define preventive method in order to limit failure occurrence. Expertises hold on about 150 failed transition joints shown that water ingress in joint insulation paper was observed in most of the cases. an delta measurements were rapidly applied in order to characterise temperature behaviour of bad joints because this well known method is used for many years in order to appreciate insulation performance. More over, previous works performed at EDF R&D and by other research teams shown that tan delta measurement performed at very low frequency (or in a range of low frequency like dielectric spectroscopy) [1], [2] were able to detect moisture or interface phenomena. hus such phenomena could be observed due to presence of water in the paper/oil impregnation complex. est carried on several joint samples removed from networks showed both : Dramatic decrease of insulation dielectric characteristics versus temperature increase and good correlation with water content in insulation papers after joint expertise, Ability of 0.1 Hz tan delta measurement performed at ambient temperature to differentiate the bad joint behaviour at higher temperature. hree type of behaviour were identified as shown in fig. 1: ype 1 : Slight increase of tan delta versus temperature and water content in paper < 1%, ype 2 : Moderated increase of tan delta versus temperature and water content in paper between 1 and 2 %, ype 3 : Dramatic increase of tan delta versus temperature and water content in paper > 2%. an delta 0,5 0,4 0,3 0,2 0,1 ransition Joints Behaviour 0,0 20 30 40 50 60 ( ) ype 1 Reference values Figure 1 ype 3 ype 2 On site Detection of joint with water penetration close to breakdown with tan delta measurement needs definition of reference values for : he healthy real cable section he same section with a bad joint. IRED2007 Session 1 Paper No 457 Page 1 / 5

Healthy section reference lassical model (fig.1) to define tan delta was used : with We simply assume that Figure 2 Where R represent dielectric loss and conductivity phenomena. Presence of transition joint implies presence of synthetic and paper cables in the same section. In order to manage the difference of tan delta value for this 2 type of cable we use the model to represent cables association : R1 R Figure 3 Where R1, 1 are describing the first type of cable (paper one) and R2, 2 the second type (synthetic). tg 1 δ R1R 2 ( 1 2) ω R1 + R2 + I 1 Rω 1 R ω 1 R2 U I 2 U hen tan delta value for the total cable section can be approached by : plp + sls considering that capacitance per unit of length is the same for an synthetic cable and a paper cable. Lp and Ls are respectively the total length of paper and synthetic cable, p and s are respectively the tan delta value for healthy paper and synthetic cable. Obviously this relation give an approximation of the value expected for an healthy section. However this approximation is compatible with the level of information generally available for the components of the cable section in on site conditions. Measurement performed on mixed cable sections (different paper and synthetic lengths associated from 150 to 1300 m), re-created in laboratory in order to reproduce real configuration, allow us to appreciate the approximation accuracy (able 1). If capacitance of cables is taken in account, the difference between calculated value and measured value is about 10%. his difference rise up to 50 % if same value of capacitance is taken for the two type of cable. ested section Paper length (m) Synt length (m) an delta at 12 kv able 1 an delta precise calc. Dif. an delta simp. calc. Dif. PIL 144 0 3,4 3,40 0% 3,00 12% Synt 0 43 0,29 0,29 0% 0,20 31% N 1 Synt 0 500 0,23 0,23 0% 0,20 13% N 2 Mix 144 500 1,42 1,26 11% 0,83 42% N 1 Mix 144 1000 0,9 0,84 6% 0,55 39% N 2 Mixt 285 500 1,94 1,77 9% 1,22 37% N 3 Mixt N 4 285 300 2,2 2,17 1% 1,56 29% We will see later that this difference is acceptable because values are dramatically higher when there is a bad joint on the section. + 22 δ 1 1 tg 1 + 2 IRED2007 Session 1 Paper No 457 Page 2 / 5

Bad joint reference Presence of a weak joint on an healthy section can be described by the simplified model presented above. When paper and synthetic cable lengths are associated with a joint, relation become : jlj + L m L + Lj and plp + sls where : m : tan delta measured with presence of a joint with water ingress on the cable section, j : tan delta value of the joint, Lj : length of the joint (about 1 m). : calculated tan delta value of the healthy cable section with the length and reference tan delta values for each type of cable. onsidering that the length of the joint can be neglected in front of cable length the following simplified relation can be used : j + plp + sls m then tan delta value for the joint can be approached by : j m ( ) plp sls In order to reach the tan delta value for a critical joint, measurements had been performed with joint removed from network associated to different lengths of cable. Joints used were failed ones or healthy joints coupled to failed ones. he measurement were performed on healthy phases after verification they were not damaged by the breakdown. 19 phases were tested in 47 configurations. Joints with the higher measured tan delta values were selected to determine the reference value for a critical joint (able 2). reated angente delta Variation section 6 KV 12 KV 18 KV 24 KV (%/kv) 43 m Synt. 489.6 601.9 727.6 4.1 +Joint N 54 143 m Pilc + 119.8 136.9 158.3 2.7 Joint N 54 285 m Pilc + Joint N 54 52.3 63.2 75.7 3.7 43 m. Synt. + N 55 Ph 3 143 m Pilc + N 55 Ph 3 285 m Pilc + N 55 Ph 3 N 48 N 55 Ph 1 N 56 685.4 847.1 1004.8 3.9 133.2 163.1 192.2 3.7 72.7 87.8 102.7 3.4 206.4 247.6 283.2 322.0 3.1 512.8 630.2 742.6 3.7 1012.3 able 2 Joint N 54 (able 3) was selected as the critical joint (close to breakdown) reference for the calculation of tan delta value regarding cable length associated. hen the critical threshold was fixed at 12000 10-3 : Section 285 m Pilc + Joint N 54 able length (m) an delta cable an delta Mes. j*lj (10-3 m) 285 3,3 52 13965 able 3 In order to appreciate the variation of tan delta versus applied voltage representative of presence of a critical joint, a criteria had also been defined. Although tan delta increase versus voltage for healthy paper cables, increase with a critical joint is much more important. his criteria / U (%/kv)is calculated with the IRED2007 Session 1 Paper No 457 Page 3 / 5

following relation : (18kV ) (6kV ) 100 % / U (6kV ) 12 he alert level is reached when this value is over 3%/kV. On site application Use of reference values haracteristics of the measured cable section are needed to determine paper and synthetic cable lengths. hen the healthy tan delta value waited S H and the critical threshold S are calculated for comparison purpose. able 4 give a synthetic presentation on measurements results use for recommendation. g δ < Sc/2 Sc/2 <g δ < Sc g δ > Sc δ/ U%<3% Healthy Follow evolution ritical δ/ U%>3% Follow evolution able 4 Follow evolution Very critical he diagnostic method used on site combine tan delta and partial discharges measurements. he last one is useful to discriminate large scale cable alterations. In such cases joint replacement is not a mater and replacement of cable section has to be considered. Usual PD rules adapted to the French PIL cables network specificity are used for measurement interpretation and recommendation. Limitations lear and accurate recommendations are given for cable sections shorter than 1 km which is the range of application advised. his is not a real restriction because most of French urban networks are without derivation. For this type of network, 90% of cable sections are shorter than 500 m. Nevertheless, influence of bad joint on tan delta is more difficult to put in evidence for longer sections (S H and S are too close). Attenuation of pd pulses with long paper cable sections is also taken in consideration. Another limitation is due to the fact that tan delta gives an evaluation of the whole cable section and doesn t allow altered joint location. Unfortunately PD measurement cannot be used for that. Most of the joint tested don't generate critical partial discharges features. On site results Investigations were performed in 2004 and 2005 in order to confirm range of application and criteria but the first pilot deployment of the method was managed during spring 2006 in Nantes and Marseille. onfrontation to operators requests for 26 selected cable sections was very positive on a technical point of view : 16 of them were found in good condition whereas replacement were initially considered, for 10 of them, high level of risk due to presence of joint with water penetration was identified. Since the beginning of the investigations, about 50 cable sections have been tested. Relevance of recommendations was proven in all the cases for which verification was possible. Different verification method applied : test after replacement with return to normal values, breakdown after voltage excursion for identified critical section, laboratory measurements and expertise on removed joints, summer failure on an identified critical joint not removed An example of verification is given able 5: Section Identification N 7089 Lycée echnique N 0892 Soubzmain Length (m) 137 % PIL 9% hreshold 88 an delta before replacement 6 KV 277 62 323 12 KV 346 72 396 18 KV 83 an delta after replacement 6 KV 12 5 13 12 KV 13 5 13 18 KV 13 5 14 Lab measurements of removed joint Length (m) 43 % PIL 0% hreshold 279 6 KV 1369 234 12 KV 1630 274 18 KV 2194 317 able 5 Economical aspects Even if the integration of the method in a network replacement procedure has not yet been defined, deployment will be continued for local applications with measurement system equipment of dedicated team. Economical interest for diagnostic method integration in a replacement procedure was calculated by comparing excavation costs avoided and diagnostic costs. Pay off depends on the reliability and accuracy of network IRED2007 Session 1 Paper No 457 Page 4 / 5

information available for operators to determine intervention. REFERENES ONLUSION AND PERSPEIVES he diagnostic method developed for detection of cable sections with failure risk due to presence of joints with water penetration has to be considered validated. onfrontation in real replacement operations gives confidence on method ability to : Avoid non pertinent excavations, Delay non critical intervention, Identify section with failure risk, lassify the different selected sections versus joint risk and cable condition, Guarantee efficiency of replacement intervention. [1] W.S. Zaengle. Author, 2001, "Dielectric spectroscopy in time and frequency domain for HV power equipment", ISH 2001Keynote Speech Session-9. [2] R. Neimanis,. K. Saha, R. Eriksson, 2000, "Determination of Moisture ontent in Mass Impregnated able Insulation using Low Frequency Dielectric Spectroscopy, IEEE Power Engineering Society Summer Meeting, Seattle, USA. Method is available for large deployment with objectives selected for asset management strategy optimisation. Data collection of performed measurements will contribute to improve accuracy of recommendation. However off line diagnostic method is resources consuming. So on line methods based on partial discharges measurements will be experimented in order to define range of applicability and knowledge rules. For that, installation of several on line devices are planed during the beginning of this year. As electrical networks are ageing and capital intensive, reaching materials remaining life time of components is a mater of concern for EDF like other utilities in the world. A large scale program of cable sample removal has been engaged by EDF R&D. Expertise, physico-chemical analysis, electrical tests and accelerated ageing are planed. his program aim to define the actual assessment of paper cable and to approach residual life time versus operating conditions and materials environment. Long section of cable will also be removed in order to perform partial discharges measurement to reach more accurate criteria for PIL condition assessment. IRED2007 Session 1 Paper No 457 Page 5 / 5