3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500

Similar documents
3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN

3M Cold Shrink Splice Kit QS-III 5514A

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-2-4/0

3M Cold Shrink QS4 Integrated Splice Kit QS4-35TS

3M Cold Shrink Splice Kit QS-III 5416A

3M Cold Shrink Splice Kit QS-III 5515A

3M Cold Shrink QS4 Integrated Splice Kit QS4-15SP-2-4/0

3M Cold Shrink QS-III Splice Kit 5467A(S)-WF

Cold Shrink Three-Conductor Splice Kit QS-III for use on Armor and Non-Armor Cables Instructions IEEE Std kv Class 250 kv BIL

3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT

F CAUTION. Jacketed Concentric Neutral (JCN) Cable. Concentric Neutral (CN) Cable. IEEE Std. No. 48 Class 1 Termination 15 kv Class 110 kv BIL

Cold Shrink Silicone Rubber Termination QT-II

3M Cold Shrink Foldback Splice Jacket Kit

3M Cold Shrink Rubber Splicing Kit 5552

3M Motor Lead Inline Splice 5331, 5332, 5333 & 5334

Instructions. Cable with Armor F CAUTION. October Rev A

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

Quick Term II Silicone Rubber Termination Kits for Shielded Cables Instruction Sheet

Quick Term II. Cold Shrink Silicone Rubber Termination (With High-K Stress Relief) Instruction Sheet. Quick Term II. Silicone Rubber Termination Kits

Industrial Loadbreak Elbow

3M Scotchcast Flexible Power Cable Splice Kits 82-F Series

3M Sensored Termination (15 kv) QX-T15I-vi1-E

HSK Mine and Portable Cable Splice

3M Scotchcast Mine and Portable Cable Splice and Jacket Repair Kit M-40

3 Foam Sealed Closure 2" (50 mm) with Compound Compression

3M Better Buried Compound Compression Closure System

TFT-150R-G. Tape Shield Cable (page 2) Suggested Installation Equipment (not supplied with kit) Wire Shield Cable (page 7)

3M Better Buried Closures

3M Scotchcast Reenterable Signal and Control Cable Splicing Kits 78-R Series

Cold Shrink Straight Joint

Quick Term III. 3M Cold Shrink 3 Core Indoor Termination. 3.3 kv mm 2

3 SLiC Aerial Closure with Rubber End Seal

3M Better Buried Closure (with 3M Scotchlok Shield Bond Connector 4462-FN and 3M High Gel Re-enterable Encapsulant 8882)

3M Fiber Optic Splice Closure 2178-XSB/XSB-FR & 2178-XLB/XLB-FR 3M Cable Addition Kit 2181-XB/XB-FR

3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR

Scotch Heavy Duty Vinyl Electrical Tape 22

Solutions for Electronic Specialty Markets (ESM)

3M Distribution Box (DDB)

3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR 3M Cable Addition Kit 2181-XL and 2181-XL/FR

3M SLiC 530/533/733-2 Port 0.61 Cable Entry Bracket 3M SLiC 530/533/733-2 Port-MSM 0.61 Cable Entry Bracket

SLiC Fiber Aerial Closure System

3M Fiber Optic Splice Tray 2527 with 3M PLC Optical Splitter

Communication Markets Division 3M Scotchlok Connectors and Tools. Proven. Solutions for. Today s Applications

3M Super 23 Electrical Tape

27mm ECAM Double Cable Entry Port

3M Coupling Tray FDTC-10S-COUPLINGTRAY

Built tough for long-term connections

Built tough for long-term connections

Scotchlok Connectors and Tools

18mm ECAM Cable Entry Port

3M Locator Plate N

2179-CD Series Fiber Optic Splice Closure. Installation Instructions

INSTALLATION INSTRUCTION PEM1423ENG ENGLISH

COOPER POWER SERIES. 600 A 15/25 kv class DT625 T-body installation and cable preparation instructions. Deadbreak Apparatus Connectors MN650017EN

K & B Flame Retardant Building Riser Closures

Cabinet Tools and Accessories Ordering Guide

Aging test: integrated vs. non-integrated splices shield continuity systems.

INSTALLATION INSTRUCTION PEM1368ENG ENGLISH

3M No Polish Jacketed SC/APC Connector

PEM1124ENG ENGLISH. STK TERMINATION KIT FOR PLASTIC CABLE WITHOUT ARMOURING 1 kv STKR TERMINATION KIT FOR PLASTIC CABLE WITH ARMOURING 1 kv

3M Merchandising Catalog. Unrivaled. Product Presence to. Meet Your Merchandising Needs

2178-L/S Series Fiber Optic Splice Case with Gasket

3 Cold Shrink Products

3M 8900 Single-mode SC Crimplok Connector

2178 Fiber Optic Splice Case and 2181 Cable Addition Kit

SLiC Fiber Aerial Closure 533 and 733

PEM1126ENG ENGLISH STPKR. TERMINATION KIT FOR PAPER CABLE WITH LEAD SHEATH 1 kv INSTALLATION INSTRUCTION

3M No Polish Jacketed SC/APC Connector

STRAIGHT TWO WAY JOINT3/C, PAPER INSULATED, SHIELDED, LEAD COVERED CABLE. Revised: October 10, 2008 Revised By: SGL Approved By: RHS SPLICES

VITALink Taped Splice Straight Through Crimp

3M Slim Lock Closures

Coaxial Cable Feedline Choke Kit - 50 Ω

4320 SS-25 Self-Strip Terminating Block

LEGEND POWER SYSTEMS

Instruction Guide February 2017

3M Cross-Connect Cabinets 4220SVB, 4220SVC and 4220SVE 3M Junction Box (JBOX)

Instructions for Use of Overlap Seam Repair Kit:

3M Mini D Ribbon (MDR) Cable Assembly

Rotor Blade Protection Kit 8999K11

Dynatel Advanced Cable Locator 2250

2016 Cable Splicing Courses

3M Fiber Optic Wall Mount Enclosure 8430 Series

MOTOR LEAD TO DOWN HOLE CABLE SPLICE PROCEDURE

Communication Markets Division. 3M Fiber Closures. Smart design makes your job easier.

3M Fiber Closures BPEO

3M MetPak 2-FB Header

FOSC-600 C and D I N S T A L L A T I O N I N S T R U C T I O N

3M We are Projectors! When the show must go on, 3M makes it easy:

FOSC 450 C6 and D6 Closures

High Density Block BRCP. HD BRCP- 128/192/256 pair. Installation Instructions

Low Voltage Splices, 1000 V or less

3M Cross-Connect Cabinets 4220SVB, 4220SVC and 4220SVE Skirt and Stabilizers

3M Fiber Optic Closure System LL

Sections 1. Application Equipment 2. Cable Preparation 3. Assembly 4. Termination Procedure 5. Inspection 6. Repair 7.

3M Pak 10 Socket 1 mm Straight and Right Angle, Surface Mount PK10 Series

3M New Construction Cross-Connect Cabinets. The. Commitment. Your Copper Requires

UNSIGNED HARDCOPY NOT CONTROLLED

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES

Electrical Markets 3M ScotchCode Wire Marking and Identification System. Quality. Marking. For Most Projects

PYROTENAX TERMINATION KITS COMMERCIAL WIRING. For Pyrotenax copper sheathed mineral insulated (MI) wiring cable

Transcription:

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500 for Jacketed Concentric Neutral (JCN) and Flat Strap Neutral Cable Instructions IEEE Std. 404 15 kv Class 150 kv BIL CAUTION Working around energized systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all electrical systems before installing product. Kit Selection Table Kit Number Cable Insulation O.D. Range Conductor Size Range QS4-15JCN-4/0-500 0.84" 1.38" (21,3 35,1 mm) 4/0 AWG 500 kcmil* (95-240 mm 2 ) * Splices (including size transitions) can be made to smaller or larger conductors (but larger conductors may require special neutral handling), provided both cables are within the Insulation O.D. Range and the connector meets the dimensional requirements shown below. Connector Dimensional Requirements Minimum Inches (mm) Maximum Inches (mm) Outside Diameter 0.69" (17,5 mm) 1.49" (38 mm) Length Aluminum (Al/Cu) Compression Length Copper Compression and 3M Shearbolt Connector QCI 4/0-600 5.00" (127 mm) 5.75" (146 mm) January 2013 3 78-8141-5583-0-A

1.0 Kit Contents a. 3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound Tubes P55/R (non-silicone grease) (2 ea.) d. Scotch Rubber Mastic Tape 2228 Rolls, 2" x 36" (2 ea.) e. Scotch Mastic Strips 2230, 6" length (9 ea.) f. Cold Shrink Adapter Tube (1 ea.*) g. 3M Cable Cleaning Pads CC-3 (1 ea.) h. Cut-back Template (1 ea.) i. Instruction Booklet (1 ea.) *Cold shrink adapter tube may not be included in all kits. Note: Do not use knives to open plastic bags. Note: Connector not shown, but if included, it is indicated on the packaging label. 2 78-8141-5583-0-A

2.0 Prepare Cables 2.1 Check to be sure the cable fits within the kit ranges as shown on the cover page. 2.2 Prepare cables according to standard procedures. Refer to template provided or illustration below for proper dimensions (Figure 1). 4" (102 mm) 11 3/4" (298 mm) 7 1/4" (184 mm) Cable Jacket Neutral Wires Semi-con Insulation Figure 1 2.3 Clean or cover cable jacket 30" (760 mm) from jacket edge on side where splice body will be parked. 2.4 Select a Scotch Mastic Strip 2230 from the kit and remove white release liners. Using light tension, apply a single wrap of mastic at the edge of the cable jacket and partially over the neutral wires. (Figure 2). Neutral Wires Scotch Mastic Strip 2230 Cable Jacket Semi-con Figure 2 78-8141-5583-0-A 3

2.5 Carefully bend the cut neutral wires up and away from the cable semi-con. Fold neutral wires over cable jacket, taking care to keep wire profile low by following the concentric turn in the cable. Secure the ends of the neutral wires with one wrap of vinyl tape. Fold one Scotch Mastic Strip 2230 in half lengthwise and apply one wrap only at cable jacket edge under the neutral wires (Figure 3). Knead mastic around neutral wires. Fold mastic strip in half lengthwise Bend neutral wires over cable jacket Semi-Con Insulation Scotch Mastic Strip 2230 Scotch Mastic Strip 2230 Neutral Wires Figure 3 2.6 Apply an additional single wrap of Scotch Mastic Strip 2230 at the edge of the cable jacket and partially over the neutral wires. Overwrap mastic with vinyl tape, taking care not to extend tape along neutral wires (Figure 4). 1 Wrap of Vinyl Tape Cable Jacket Scotch Mastic Strips 2230 Overwrap with vinyl tape Figure 4 4 78-8141-5583-0-A

2.7 Slide integrated splice body onto clean cable jacket, loose core end first (Figure 5). Loose core end Integrated splice body Cleaned cable jacket 3.0 Install Connector Figure 5 Note: If using a crimp-type connector, go to step (3.3). 3.1 If using a 3M Shearbolt Connector QCI 4/0-600, refer to the instructions included with the connector for insulation cut-back dimension. Insulation removal length shall not exceed 3" (76 mm) from conductor end (Figure 6). Refer to connector instructions for dimensions Figure 6 3.2 Install 3M Shearbolt Connector QCI 4/0-600 according to the instructions included with the connector (Figure 7). Shearbolt Connector Go to section 4.0 Install Splice. Figure 7 78-8141-5583-0-A 5

3.3 If using a crimp type connector, remove cable insulation for 1/2 connector length plus an allowance* for increases in connector length due to crimping. Insulation removal length shall not exceed 2 7/8" (73 mm) from conductor end. Do not install connector now (Figure 8). *Note: This assumes that the installer has determined the increased length of an aluminum connector crimped with a specific tool and die. Aluminum (Al/Cu) Crimp Connector Growth Chart Conductor Size Typical growth allowance (per end) 4/0 AWG-500 kcmil 1/4" (6 mm) Note: 1) Copper connectors do not require a length change allowance. 2) Maximum aluminum connector crimped length allowed is 5.75" (146 mm). One-half connector length + growth allowance* Figure 8 3.4 For 4/0 AWG through 350 kcmil copper connectors, or connectors with an O.D. between 0.69-0.84" (17,5-21,3 mm): Park cold shrink adapter tube on cable insulation (Figure 9). Cold shrink adapter tube Figure 9 6 78-8141-5583-0-A

3.5 Install connector. See table (on cover) for proper connector dimensions. (For standard 3M Connectors, refer to table at the end of this instruction for crimping information). Remove any excess oxidation inhibitor from connector ends if aluminum connector is used (Figure 10). Connector 4.0 Install Splice Figure 10 4.1 Apply a tape marker to semi-con insulation shield on cable which does not contain splice. Measure 9" (229 mm) from center of connector (Figure 11). 9" (229 mm) Figure 11 Tape Marker Semi-con 4.2 If using cold shrink adapter tube: Position adapter tube over the connector. Shrink adapter near center of connector by pulling and unwinding the loose core end in a counter-clockwise direction (Figure 12). Cold shrink adapter tube Figure 12 78-8141-5583-0-A 7

4.3 Clean cables using standard practice: a. Do not allow solvent or abrasive to contact the cable semi-conductive insulation shield. b. Do not reduce cable insulation diameter below 0.84" (21,3 mm) specified for the splice. c. The insulation surface must be round, smooth and free of cuts/voids. Sanding may be necessary, finish sanding should be done with a 120 grit or higher electrical grade abrasive. d. Make certain that the cable insulation is smooth, clean and dry before continuing. 4.4 Apply 3M Red Compound P55/R on cable insulations, making certain to fill in edge of cable semi-con. Do not use silicone grease (Figure 13). Fill semi-con step Fill semi-con step Apply Red Compound Apply Red Compound Figure 13 Note: This core installs differently than other cold shrink products. 4.5 Position the splice body over connector area, aligning end of the splice body (not the core) at the center of the tape marker. Slowly start to remove the splice core by pulling and unwinding the loose core end counterclockwise, allowing only ¼" (6 mm) of the splice to shrink onto the tape marker. Carefully slide the splice body off the tape marker by pulling and twisting until the entire tape marker is exposed. Continue removing the core to complete the splice body installation (Figure 14). Note: The splice body ends must overlap onto the semi-con of each cable by at least 1/2" (13 mm). Note: Do not push the splice body toward the tape marker as this may cause the end to roll under. If the end does roll under, DO NOT use sharp-edged tools to pull it out as this could cut and damage the splice. Unwind Counter-clockwise Figure 14 Align splice body with tape marker 8 78-8141-5583-0-A

5.0 Connect Shielding 5.1 Remove the vinyl tape holding the shield sleeve on the rejacketing tube, and spread the shield sleeve out toward the cable jacket. Note: The 3M Cold Shrink Integrated Splice Body includes a pre-installed ground braid for external grounding on either side of the splice body. If not using the ground braid, it may be tied into the ground system with the shield sleeve using constant force springs as shown below. 5.2 Hand-tighten the shield sleeve outward and secure it (along with the ground braid if not grounding externally) to the neutral wires on either side of the splice using two constant force springs on each end between the vinyl tape at the jacket edge and the vinyl tape as shown (Figure 15). Note: If using a ground strap for external grounding, leave room for a third constant force spring over the shield sock at the jacket end. Refer to step (6.5). 5.3 If shield sleeve extends beyond neutral wires, it may be interwoven with the constant force springs. Trim excess ground braid if needed. Cinch (tighten) the spring after wrapping the final winding (Figure 15). Rejacketing Tube Cable Jacket Vinyl Tape Ground Braid Constant Force Springs Figure 15 5.4 Wrap two half-lapped layers of vinyl tape over the constant force springs (Figure 16). Vinyl Tape Figure 16 78-8141-5583-0-A 9

6.0 External Grounding (Optional) Note: Use these instructions if circuit grounding is required at this location. Note: If using a ground strap for external grounding, go to step (6.5). 6.1 If using a ground wire: Connect a ground wire to the pre-installed ground braid on the integrated splice using an appropriate connector. Keep connector profile as low as possible. For C-tap or H-tap connectors, position flat against the cable. Crimp connector following the connector manufacturer s recommendations (Figure 17). Connector Ground Wire Ground Braid Figure 17 6.2 Cut one mastic sealing strip into two equal pieces. Place one piece on the cable jacket centered under the ground wire near the jacket end. Roll two mastic strips into small rolls. Place one roll on either side of the ground wire. (Figure 18). Ground Wire Half Mastic Strip Rolled Mastic Ground Wire Rolled Mastic Cable Jacket Half Mastic Strip Figure 18 10 78-8141-5583-0-A

6.3 Place the other half mastic strip over the previously applied mastic and ground wire. Press the mastic around the ground wire and to the cable jacket (Figure 19). Ground Wire Second Half Mastic Strip Figure 19 6.4 Wrap two half-lapped layers of vinyl tape over the ground connector (Figure 20). Ground Wire Mastic Seal for Ground Wire Go to section 7.0 Install Jacket. Figure 20 Vinyl Tape 6.5 If using a ground strap (ground strap and constant force spring not included): Wrap the ground strap around the shield sleeve with the tails toward the cable jacket (Figure 21). Shield Sleeve Ground Strap Figure 21 78-8141-5583-0-A 11

6.6 Secure ground strap to the shield sleeve using a constant force spring (Figure 22). Constant Force Spring Figure 22 6.7 Overwrap the spring with two layers of stretched vinyl tape (Figure 23). Vinyl Tape Figure 23 6.8 Place one mastic sealing strip on the cable jacket under the solder blocks of the ground strap (Figure 24). Solder Block Mastic Strip Figure 24 12 78-8141-5583-0-A

6.9 Place another mastic strip over the solder blocks. Press the mastic strips around the solder blocks and onto the cable jacket. If tails overlap at the solder blocks, place a piece of mastic between them (Figure 25). Second Mastic Strip 7.0 Install Jacket Note: Jacketing is not optional. Figure 25 7.1 Wrap a roll of slightly stretched Scotch Rubber Mastic Tape 2228, 2" x 36" around cable jacket at edge of cut neutrals (tacky side toward cable) (Figure 26). Stretch and tear off last 1 2" (25 50 mm) of mastic (Figure 27). If grounding was applied, apply tape over mastic strips. 2" rubber mastic 2" rubber mastic Figure 26 Stretch and tear off last 1 2" (25 50 mm) of rubber mastic Figure 27 78-8141-5583-0-A 13

7.2 Remove the clear plastic wrap. Install the rejacketing tube by twisting the tube (not the yellow liner) from side to side to start the movement. Then slide and unroll the tube over the constant force springs and rubber mastic. (Figure 28). Repeat on other side. Twist to break seal, then slide tube Liner Figure 28 7.3 Cut off yellow liners and discard. Figure 29 7.4 Connect optional grounding. Note: In applications where the splice is regularly exposed to high levels of ultra-violet radiation (i.e. direct sunlight), wrap two half-lapped layers of Scotch Super 33+ Vinyl Electrical Tape or Scotch Vinyl Electrical Tape Super 88 over the re-jacketing tube. 14 78-8141-5583-0-A

Crimping Tool - Die Sets (number of crimps/end) 3M Connector Number Conductor Size (AWG or kcmil) Burndy MD6 MY29 Y34A Y35, Y39, Y45*, Y46* Thomas & Betts Corp. Y1000** TBM 5 TBM 8 TBM 12 TBM 15 Square D Co. Anderson Div. VC6-3** VC6-FT** VC8C** 10008 (Cu) 4/0 BG(3) 4/0(1) A28R(2) U28RT(2) --- Purple(2) Purple(2) --- 54H(2) (2) --- 20008 (Al/Cu) 4/0 W660(4) 4/0(2) A28AR(2) U28ART(2) (1) --- White(4) --- 66(4) (2) --- 11008 (Cu) 4/0 BG(4) 4/0(2) A28R(3) U28RT(3) --- Purple(3) Purple(3) --- 54H(3) (3) --- CI-4/0 (Al/Cu) 4/0 W-249(3) --- --- U28ART(2) --- --- Blue(4) --- 76(2) (2) --- 10009 (Cu) 250 W166(3) 250(1) A29R(2) U29RT(2) --- Yellow(2) Yellow(2) --- 62(2) (2) --- 20009 (Al/Cu) 250 W249(3) --- A29AR(2) U29ART(2) (1) --- --- 71H(2) 71H(2) (3) --- 11009 (Cu) 250 W166(4) 250(2) A29R(3) U29RT(3) --- Yellow(3) Yellow(3) --- 62(3) (3) --- CI-250 (Al/Cu) 250 --- --- --- U31ART(2) --- --- --- 87H(2) 87H(2) (2) --- 10010 (Cu) 300 --- --- A30R(3) U30RT(2) --- --- White(2) --- 66(2) (2) --- 20010 (Al/Cu) 300 --- --- A30AR(2) U30ART(2) (1) --- --- 76H(3) 76(1) (2) --- 11010 (Cu) 300 --- --- A30R(3) U30RT(3) --- --- White(3) --- 66(3) (3) --- CI-300 (Al/Cu) 300 --- --- --- U31ART(2) --- --- --- 87H(2) 87H(2) (2) --- 10011 (Cu) 350 --- --- A31R(2) U31RT(2) --- --- Red(3) --- 71H(3) (2) --- 20011 (Al/Cu) 350 --- --- --- U31ART(2) (1) --- --- 87H(3) 87H(3) (2) --- 11011 (Cu) 350 --- --- A31R(3) U31RT(3) --- --- Red(4) --- 71H(4) (3) --- CI-350 (Al/Cu) 350 --- --- --- U31ART(2) --- --- --- 87H(2) 87H(2) (3) --- 20012 (Al/Cu) 400 --- --- --- U32ART(4) (1) --- --- 94H(4) 94H(4) (2) (2) 10014 (Cu) 500 --- --- A34R(2) U34RT(2) --- --- Brown(3) --- 87H(3) (2) --- 20014 (Al/Cu) 500 --- --- --- U34ART(4) (1) --- --- 106H(3) 106H(3) (2) (2) 11014 (Cu) 500 --- --- A34R(4) U34RT(3) --- --- Brown(4) --- 87H(4) (3) --- CI-500 (Al/Cu) 500 --- --- --- U34ART(3) --- --- --- --- 106H(3) (3) --- *Y45 and Y46 accept all Y35 dies ("U Series"). For Y45, use PT6515 adapter. For Y46, use PUADP adapter. **Anderson VC6-3, VC6-FT, VC8C and Burndy Y1000 require no die set. 78-8141-5583-0-A 15

3M, Super33+ and Scotch are trademarks of 3M Company. All other trademarks are property of their respective owners. Important Notice All statements, technical information, and recommendations related to 3M's products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed. Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability associated with such use. Any statements related to the product which are not contained in 3M's current publications, or any contrary statements contained on your purchase order shall have no force or effect unless expressly agreed upon, in writing, by an authorized officer of 3M. Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture at the time of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M's option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be liable for any indirect, special, incidental or consequential loss or damage arising from this 3M product, regardless of the legal theory asserted. 3 Electrical Markets Division 6801 River Place Blvd. Austin, TX 78726-9000 800.245.3573 Fax 800.245.0329 www.3m.com/electrical Please Recycle. Printed in USA. 3M 2013. All Rights Reserved. 78-8141-5583-0-A