HARMONIZATION OF SYNOPTIC BLOCK DIAGRAMS ON THE CONTROL PANELS OF MV SWITCHGEAR AND CONTROLGEAR

Similar documents
Identification - electrical services

Draft for Public Comment

3WS(Cape Town/Secretariat)1

ECONOMICAL 36 kv CABLE SYSTEM FOR THE BELGIAN NETWORK

Specification. NGTS Issue 1 October 1993

LED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series

Engineering Instruction

FORENSIC CASEBOOK. By Bob Huddleston, Eastman Chemical Co. One of the most common. reasons for marriage failure

Medium Voltage 12/20 (24)kV NF C cable system. Xavier Brosse Luanda May 2009

REFURBISHMENT OF SECONDARY SYSTEMS IN HIGH VOLTAGE SUBSTATIONS LESSONS LEARNED IN VENEZUELA

INTERNATIONAL STANDARD

AES-402 Automatic Digital Audio Switcher/DA/Digital to Analog Converter

220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 FIRE PREVENTION FOR CABLES, CABLE TRAYS AND CONDUITS

Instructions for Use P.154-UP (9/4) P.155-UP (9/8) P.150-UP-12 (9/12) P.150-UP-16 (9/16)

A. Almeida.do Vale M. J. Dias Gongalves Zita A. Vale Member,IEEE

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITHOUT METALLIC SCREEN

LED Driver Linear / area fixed output

Photovoltaic Module Installation Manual (IEC)

Automatic Test System AT-S + with STAR + Technology Features

Photovoltaic Module Installation Manual (IEC)

ELECTRICAL SAFETY INSPECTION REPORT

Installation Guide VL-MV10. Model No.

LED Driver Compact fixed output

CITOCUT Plasma inverter cutting range

sequenza 1000/1250 al manuale di istruzioni instruction manual 1^ edizione, ottobre st edition october 1996

PHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series

SHARP Plasma inverter cutting range

SINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS

Instructions for Use P.160-AP-8 (13/8) P.160-CP-8 (13/8) P.160-CP-12 (13/12) P.160-CP-16 (13/16)

LED Driver Compact fixed output

PicoScope 3000 Series Automotive User guide

Peak Atlas IT. RJ45 Network Cable Analyser Model UTP05. Designed and manufactured with pride in the UK. User Guide

PRESTOJET Plasma inverter cutting range

(Notices) NOTICES FROM EUROPEAN UNION INSTITUTIONS AND BODIES COMMISSION

LED Driver Compact dimming

PicoScope 4000 Automotive PC Oscilloscopes

I r A Protection against direct contact Finger and back-of-hand proof to VDE 0106 part 100

multi-function meters

Model 1421 Distribution Amplifier

PicoScope 2000 Series PC Oscilloscopes

KRF EMC Filters Installation, Operation and Maintenance Manual

PTS RABKA TRADE AND PRODUCTION COMPANY

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS

AES-404 Digital Audio Switcher/DA/Digital to Analog Converter

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

28 & 32 & 40 & 55 & 65 & 84-INCH TFT-LCD 4K MONITOR

T5, T8, TC-L. PC T5 PRO lp W V 50/60/0 Hz, HO. Electronic ballasts Linear lamps T5, T8 and compact lamps TC-L

Description Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100

Description Set value in neutral conductor is synchronous with set value Ir of main pole. CSA 100. conductor. I r A 50-63

ELECTRICAL SAFETY INSPECTION REPORT

OPERATION MANUAL JENDPM008 THERMOCOUPLE PANEL THERMOMETER. TIP TEMPerature Products 340 W Broad Street Burlington, NJ 08016

llen-bradley 194R-HM4-NFPA3

LED control gear Compact fixed output

Protective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A

HYL-035D0850G103. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

Power Injector 1520 Series

LF101XF Six Function DCC Function Only Decoder Art. No February 2007

APPLICATION NOTE. Practical Tips for Using Metalic Time Domain Reflectometers (The EZ Way) What is a Time Domain Reflectometer?

Remote Voltage Detector - JET (RVD) Medium and High Voltage kV AC

KNX Dimmer RGBW - User Manual

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

CNK JR. SERIES CABLE-NOOK JR. TABLETOP INTERCONNECT BOXES USER'S GUIDE

AMERICAN NATIONAL STANDARD

User Guide UD51. Second encoder small option module for Unidrive. Part Number: Issue Number: 5.

CNK221 CABLE-NOOK JR. INTERCONNECT BOX USER S GUIDE

Trusted 40 Channel 120 Vac Digital Input FTA

LED Driver Compact fixed output

Telemetry Receiver Installation Guide

Trusted 40 Channel 120 Vac Digital Input FTA

MIKRO POWER FACTOR CORRECTION COMPONENTS

SWA Cable BS6724 Steel Wire Armoured LSZH Eland Product Group A9L

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 872 LIGHT EMITTING DIODE TRAFFIC SIGNAL LAMP UNITS JULY 19, 2002

Tube Rotator. User Guide. Version 1.2

INSTRUCTION AND MAINTENANCE VIDEO MOTORE PROJECTION SCREEN

Monochrome Video Monitors

CITOCUT Plasma inverter cutting range

INSTALLATION MANUAL. ST-CVTSD520-WSD-W Smoke Detector Covert Camera. v1.2 8/11/11 1

PEGAS 160 T PULSE HF PEGAS 200 T PULSE HF

Operating Instructions 07/2007 Edition. SINAMICS G130/G150 Line harmonics filter. sinamics

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

SMPTE STANDARD Gb/s Signal/Data Serial Interface. Proposed SMPTE Standard for Television SMPTE 424M Date: < > TP Rev 0

Emergency lighting units EM powerled

INSTALLATION MANUAL. ST-CVTMD420-WPIR-W Covert Motion Detection Color Camera. v1.3 8/11/11 1

Arc Detector for Remote Detection of Dangerous Arcs on the DC Side of PV Plants

Contactor Monitoring Relay CMD Cost-Effective Solution for Safe Machines

DIRECTORATE-GENERAL III INDUSTRY Legislation and standardization and telematics networks Standardization

Sample Test Project. District / Zonal Skill Competitions. Skill- Electrical Installation. Category: Construction and Building Technology


Operating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130

Micro-DCI 53ML5100 Manual Loader

-V- New. Connecting cables for valves, socket type B, industry standard Type codes Connecting cable with PUR cable sheath NEBV B2 W 3 F P K 0.

English. User Manual sub8 Subwoofer SUBWOOFER. Supporting your digital lifestyle

Safety Codes Council Conference Banff C Panel Discussion

DA IN 1-OUT LINE DRIVER WITH EQUALIZATION + AUDIO USER S GUIDE

Trends and Challenges of HV Cable Systems

Operating instructions

Dynatel Advanced Cable Locator 2250

User Manual CC DC 24 V 5A. Universal Control Unit UC-1-E. General Information SET. Universal Control Unit UC-1 Of Central Lubrication PAUSE CONTACT

Transcription:

HARMONIZATION OF SYNOPTIC BLOCK DIAGRAMS ON THE CONTROL PANELS OF MV SWITCHGEAR AND CONTROLGEAR Yvan L. Tits ELECTRABEL 8, Boulevard du Régent, B-1000 Brussels (Belgium) Tel: +32 2 518 62 66 - Fax: +32 2 518 68 77 - E-mail: yvan.tits@electrabel.be SUMMARY The aim of this article is to make utilities aware of the need for harmonization at a time when more and more manufacturers are bringing MV switchgear and controlgear onto the market and when increasing attention is being centred on the importance of the manmachine interface. It will identify the various stages in the development of this subject, present selected options and give examples of the results obtained for MV switchgear and controlgear from various manufacturers. INTRODUCTION Recent years have seen a growing trend on MV distribution networks, and especially in distribution substations, to replace open materiel with MV metal or insulating enclosed equipment. This has led to fewer injuries to workmen, often due to direct contact with active parts, possibly as a result of the lack of automatic locking not technically realisable. The risk of operating errors has not been totally eliminated due to the fact that it is generally due to a human error, and to the lack of convergence of the various synoptic block diagrams designed by the manufacturers. Position indicators combined with synoptic block diagrams replace a direct visual inspection. Consequences of potential operating errors can thus only occur in adjacent stations (essentially by unwanted connections). This paper studies the main causes of accidents and incidents, the solutions offered by the here above mentioned evolution and the choices that need to be made concerning the man-machine interface in order to maximise positive effects of this evolution. MAIN CAUSES OF ACCIDENTS Current situation Most of the accidents or incidents that occur in distribution substations whether they result in the accelerated ageing of the equipment, damage to the equipment or, more seriously, personal injury can generally be attributed to three principal causes : 1. direct contacts with actives parts; 2. failure to check the availability (i.e. not live) of the equipment by means of a reliable system before carrying out the work; and, most frequently : 3. operator s inadvertence and lack of concentration. A fourth cause could appear by use of unreliable or unsuitable equipment. This can be avoided by adapting technical specifications to network characteristics and checking the strict conformity of proposed devices. The consequences of any unlikely equipment defects can be further minimised by requiring that the protected equipment be resistant to internal arc faults and ensuring the compatibility between installation and housing. Conclusion Since, as we have seen, the causes of accidents or incidents are mainly due to human error, the safest way of reducing the frequency with which they occur is to counter these three main causes and their consequences by harmonising the man-machine interface, harmonization witch facilitates the operator s circumspection. SUGGESTED SOLUTIONS 1. Protection from direct contact The first cause may be avoided to a large extent by using metal or insulating enclosed equipment, as is generally the case for new installations today. Adequate locking measures now make it impossible for the operator to reach a live area either voluntarily or accidentally or to work in the vicinity of live parts without a protective screen.

2. Reliable checks on availability Once we have adopted the concept of protected equipment, the second cause of accidents can be dealt with by equipping the operator with a reliable means of checking whether or not a part is live. The position of the device carrying out the test must be clearly marked so as to avoid any errors of interpretation (see also definition of the typical synoptic block diagram ). This condition is met if the manufacturer is required to fit in a VDS -type interface (Voltage Detecting System), in accordance with one of the options of IEC standard 61243-5, clearly specifying the voltage range in which the system should operate and compatible with the corresponding detection equipment (e.g. 10.0-16.0 kv to cover all voltages between these two values). The operator s detection equipment must be checked regularly and must comply with this same standard following the same option (high or low impedance). This also makes it possible to comply with the safety rules set out in standard EN 50110-1, and therefore to run a reliable check on the absence of voltage before earthing. This also avoids reducing the service life of the earthing switch which can close 1, 2 or 5 times on making current, depending on the class of equipment. 3. Harmonization of the man-machine interface With open equipment, the inadvertence of the field operator could led to physical consequences on the author of the error, within the substation self. With enclosed equipment, the field operator is well protected and so, inside the substation, any mistakes only result in accelerated equipment ageing (e.g. caused by closing on a short-circuit). Consequences of an incorrect operation on field operators working in a neighbouring substation or on the section of the network between two substations still exist. If the field operator is working on installations where interfaces can strongly differ from others, depending on the manufacturer, and if he doesn t frequently operate any inadvertence can result in an operation error. The diversity of installations on the network has become unavoidable by the liberalisation of market. This situation leads inevitably to an increasing number of different presentation on the local command boards. Finding a solution : in view of the major discrepancies noted between the synoptic block diagrams on the control panels of equipment from different manufacturers, we have attempted to clarify and harmonise the situation. We worked closely with the various parties concerned (technical experts, safety officers and field operators) and enlisted the help of an ergonomics consultant in order to determine the optimal type of diagram. After a series of meetings in our training centres examining the various types of equipment used on the Belgian network, coupled with visits to substations including a large numbers of cells, the working group was made fully aware of the difficulties encountered by field operators having to interpret a multitude of synoptic block diagrams presentations. These meetings identified the plus points of existing diagrams. The result was a typical structure for a synoptic block diagram which all field operators could agree upon and allowing for a common and univocal interpretation of all MV distribution network equipment. This approach does not question the quality of synoptic block diagram taken individually, but well the diversity among them. DEFINITION OF THE TYPICAL SYNOPTIC BLOCK DIAGRAM Preconditions The principles have to be adaptable to most of the existing equipment, the aim being to not have to wait for a new generation of technology and to avoid increasing the cost of equipment. The main principles must be easily translated into technical requirements that manufacturers offering equipment on the Belgian market should be made to comply with. A deadline should be set for conformity with these requirements. The other Belgian distributors have been involved in this process from the outset, thus ensuring the harmonization of supplies to the Belgian market which in turn simplifies the task of manufacturers. Block diagrams - technical requirements Area of application: the general rules apply to metal or insulating enclosed switchgear and controlgear which do not allow for a clear and unobstructed view of the equipment and a direct and unambiguous indication of its position (open, closed, earthed, test, etc.). However, the points regarding control mechanisms 11 to 14 are applicable to all enclosed equipment. Block diagram : the representation of the block diagram must be simple and logical so that there can only be one possible, clear and immediate interpretation. The text on the diagram must be kept to a strict minimum (see point 9: cable direction, type and diameter). 1. The block diagram shall be affixed to the front panel of the cells, on a part that cannot be removed without special tools.

2. The main busbar must be represented by an unbroken horizontal line on top of the diagram affixed to the front panel. 3. On each cell a vertical line (busbar branch) branches off the main busbar line. These lines should be marked with the position indicators of the switchgears. Depending on the physical location of the switchgear and controlgear inside the envelop, it is not always possible to pass a single vertical line through the position indicators concerned. The diagram must nevertheless be drawn in the simplest and clearest manner. 4. The position indicators of the switchgear and controlgear must be representative of their physical position. They should either show an unbroken line (device closed) or a broken line (device open) on the diagram. 5. The lines of the block diagram must be starkly contrasted against the background colour. The difference in reflective power (as a percentage of the incident light radiation) between the lines on the diagram and the background colour must be at least 65%. (For information, this difference is achieved with white or aluminium tones against black, dark blue, crimson, slate grey, dark brown, etc.). 6. The colour used for the lines on the diagram and for the position indicators must not be used for anything else. Similar shades cannot be used on the surface of the diagram (the cells cannot be separated by lines of the same shade of colour). Red, green and yellow may not be used for the single-wire diagram. 7. Lines must be no thinner than 3 mm. The widths of all lines representing power circuits are identical. 8. Any lines that have no meaning for the diagram and all unnecessary text on the surface of the diagram must be eliminated towards easy reading. 9. The voltage detection interfaces should be represented on the diagram by the symbol for a capacitieve outlet. This symbol should also be placed adjacent to the actual interface in case the latter is not in the immediate vicinity (preferably level with the location of the detector). 10. For cable cell, the symbol used to represent the terminal box is a shaded, inverted triangle in the same colour as the line of the MV power circuit. In this case, a free space, bearing no inscription, must be in the immediate vicinity of (and preferably below) the symbol for the connecting cable terminal box. This empty space (in the diagram background colour) should be at least 40 mm high and 150 mm wide. It will contain the information regarding cable direction, type and diameter. 11. It shall be positioned on a part that cannot be removed without special tools. 12. The controls must be conspicuous thanks to the colour of their background area (green and yellow striped for earthing devices, red for switches, disconnectors and circuit-breakers) which we will call control areas. These control areas must be located as close as possible to the position indicators for the devices controlled. If the relationship between the control and the position indicator is not clear from the diagram, a dotted line shall run from the control area to the position indicator concerned. Note that the choice of colours is taking into account their meaning in international standards. 13. These control areas also contain a box displaying the symbol of the device controlled (in accordance with IEC standard 617) in black against a white background or vice versa. These boxes are not framed (to avoid a lack of clarity resulting from too many lines). 14. These control areas must be positioned on the diagram in such a way that it is impossible to mistake the controls and indications they contain with those of neighbouring cells. To this end, for the equipment that is not part of cubical switchgear or controlgear (within the meaning of the Belgian standard NBN EN 298), the cells may be separated if necessary by a wide unbroken line in a different colour from the colours used on the diagram. 15. Motorised controls are shown on a control area (identical to that for manual controls) which also features the motorisation symbol (in line with IEC 617) and identifying the device controlled. The device information is repeated at the device position indicator on the diagram to avoid any possible confusion. The motorisation symbol must also be indicated on the diagram. A block diagram taking into account all the above mentioned rules is shown below. Manufacturers have been invited to submit their suggested diagrams to Electrabel in order to avoid any misinterpretation of the specifications.

OO OO OO OO OO OO CEL A I 0 M I 0 M Rouge Red Vert/Jaune Green/Yellow CEL A FIGURE 1 - Example of synoptic block diagram CONCLUSION We feel that observing these rules may improve the safety of all those who will wish to take them into account, and may amount to some harmonization of enclosed switchgear and controlgear presentation on an European level. This would in turn reduce equipment costs. The Belgian market is a very open one, and the leading international manufacturers have already taken steps in order to adapt their equipment and bring it into line with our specifications. EXAMPLES Here are a few examples of new or adapted installations resulting from close co-operation between Electrabel and the various manufacturers active on the Belgian market:

FIGURE 2 - Application of synoptic block diagram

FIGURE 3 - Application of synoptic block diagram REFERENCES [1] CEI 60073 : CEI, Basic and safety principles for man - machine interface, marking and identification.. Coding principles for indication devices and actuators (1996). [2] CEI 60417-1 et -2 : CEI, Graphical symbols for use on equipment - Part 1 : Overview and application, - Part 2 : Symbol originals. (1998) [3] CEI 60617-1 à 13 : CEI, Graphical symbols for diagrams - Parties 1 à 13. (1985 à 1997) [4] CEI 60298 : CEI, A.C. metal-enclosed switchgear and controlgear for rated voltages above 1 kv and up to and including 52 kv (1990).