IGNITION TRANSFORMER FOR BURNERS TAR SERIES FEATURES TAR10 Bulletin E5004 rev06 13/11/03 115 / 230 V 50 / 60 Hz 2 / 1 A 220 VA Intermittence every 3 minutes: 20% 1.3 kg 38 cm Type of H.T. cable siliconic (external diameter 7 mm) (max 2 m) Working temperature: 0 70 C Transformer function : Mounting position: any F5004I01 Transformer TAR10 substitutes all models previoulsy sold. FEATURES TAR11 115 / 230 V 50 / 60 Hz 2 / 1 A 220 VA Intermittence: 100 % (fixed) 2 kg 38 cm Type of H.T. cable siliconic (external diameter 7 mm) (max 2 m) Working temperature: 0 70 C Transformer function: only ignition Mounting position: any Gas burners. Gas oil burners. Fuel oil burners. APPLICATIONS DESCRIPTION TAR series ignition transformers may be used with different flame detection systems and on any kind of spark electrode of whatever form. It is possible assemble the transformer inside optional box ESA TRAFO. Headquarters Esa S.r.l. Via E. Fermi 40 I24035 Curno (BG) Italy Tel. +39.035.461906 Fax +39.035.461501 esa@esacombustion.it www.esacombustion.it International Sales Pyronics International S.A./N.V. Zoning Ind., 4ème rue B6040 Jumet Belgium Tel +32.71.256970 Fax +32.71.256979 marketing@pyronics.be
Bulletin E5004 rev06 13/11/03 INSTALLATION The equipment can be mounted in any positions, avoiding placing it in proximity of heat or direct irradiation sources, and in such condition as to be exposed with products of the combustion, liquid, solvents or corrosive gas. The equipment must be installed by skilled staff, in compliance with the regulations in force at the time and in the place of installation. This device is intended for permanent connection to the electric installation and should never be fitted with a reverible mains plug. Check correct connections after installation and verify that supply voltage and frequency are correct. In the connection between ignition transformer and probe, employ only silicon cables for high voltage use serious VS or GVR, avoiding to place them in metallic conduit or plastic conduit, even if these last doesn't create remarkable problems, ideally the cable must be left free in air. Main point is not dispose more high voltage cables coming from different ignition transformers in the same conduit. Respect the maximum lengths of high voltage cables (max 2 m), even if the suggested length is 1 m. Detection probes and connectors (if any) must be isolated and out of reach. The casing must be adequately protected; only skilled personnel should be allowed to touch or work on it. Suitable warnings should be placed next to the probes, if necessary. Always connect the protection groung to the correct terminals and to any metallic frames using conductors of suitable section. Before carrying out any operation on ignition transformer, ensure that supply voltage are disconnected. 2/9
Bulletin E5004 rev06 13/11/03 DIMENSIONS TAR10 D5004I06 DIMENSIONS TAR11 D5004I05 3/9
ELECTRICAL WIRING (ESA ESTRO) detection signal IGNITION AND DETECTION Terminal board: ESA ESTRO terminal board, please look at bulletin E7013. I II III IV V VI VII VIII IX X XI XII ESA ESTRO TAR 11 IGNITION ONLY Terminal board: ESA ESTRO I II III IV V VI VII VIII IX X XI XII ESA ESTRO terminal board, please look at bulletin E7013. 4/9
Bulletin E5004 rev06 13/11/03 ELECTRICAL WIRING (ESA GENIO) IGNITION AND DETECTION Terminal board: ESA GENIO G N T U detection signal ESA GENIO terminal board, please look at bulletin E7020. IGNITION ONLY TAR 11 Terminal board: ESA GENIO G N T ESA GENIO terminal board, please look at bulletin E7020. 5/9
ESA BOSSII and ESA QUAD terminal boards, please look at bulletins E7011 and E7012. ELECTRICAL WIRING (ESA BOSSII and ESA QUAD) detection signal L A N B G 1 + 2 3 G 4 V 5 N 6 T 7 N 8 F 9 G 10 IGNITION AND DETECTION (only with ESA devices) Terminal boards: ESA BOSSII ESA QUAD sold out ESA BOSSII and ESA QUAD terminal boards, please look at bulletins E7011 and E7012. L A N B G 1 + 2 3 G 4 V 5 N 6 T 7 N 8 F 9 G 10 Terminal boards: ESA BOSSII ESA QUAD sold out IGNITION ONLY 6/9
FEATURES TAR2 TRANSFORMER 110/220 V 50 Hz 1 x 9000 V 2.2/1.1 A 240 VA Intermittence every 3 minutes: 33% 2 kg 55 cm Suitable for double electrodes systems D5004E04 FEATURES TAR4 115/230 V 50 Hz 1 x 5000 V 0.9/0.45 A 13 ma 105 VA Intermittence every 3 minutes: 15% 1 kg 25 cm Suitable for single and double electrodes systems F5004E03 FEATURES TAR5 110/220 V 50 Hz 1.3/0.65 A 16 ma 145 VA Intermittence: 100% 2 kg 55 cm Suitable for double electrodes systems D5004E04 7/9
FEATURES ELECTRONIC TAR6 TRANSFORMER 110/220 V 50/60 Hz 1 x 15000 V 0.4/0.2 A 25 ma 45 VA Intermittence every 2 minutes: 50% 370 g 56 cm Max. length WAND outer tubing: 70 mm Suitable for single and double electrodes systems D5004E01 FEATURES TAR7 115/230 V 50/60 Hz 1 A 220 VA Intermittence every 4 minutes: 25% 1.9 kg 38 cm Suitable for single and double electrodes systems D5004E05 FEATURES TAR8 115/230 V 50/60 Hz 1 A 220 VA Intermittence every 3 minutes: 20% 1.3 kg 38 cm Suitable for double electrodes systems D5004E06 8/9
ELECTRICAL WIRING Catalog No. Use Primary phase Primary neutral Wires colour Secondary outlet Detection signal Earthing TAR2 TAR4 TAR5 TAR6 TAR7 TAR8 TAR10 TAR11 & (*) & & (*) only with ESAPYRONICS instruments NOTE: Based on the company s policy aimed at a continuous improvement on product quality, ESAPYRONICS reserves the right to bring changes to the technical characteristics of this device without previous notice. Our catalog updated to the latest version is available on our web site www.esacombustion.it and it is possible to download modified documents WARNING: When operating, this combustion system can be dangerous and cause harm to persons or damage to equipment. Every burner must be provided with a protection device that monitors the combustion. The installation, adjustment and maintenance operations should only be performed by trained and qualified personnel. 9/9