Trusted 40 Channel 120 Vac Digital Input FTA

Similar documents
Trusted 40 Channel 120 Vac Digital Input FTA

Trusted 40 Channel Analogue Input FTA

Trusted TMR I/O SmartSlot Slot Cables

Backlight Replacement

llen-bradley 194R-HM4-NFPA3

Operating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130

Model 1421 Distribution Amplifier

GuardPLC Certified Function Blocks -- Basic Suite

Power Injector 1520 Series

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS

Instructions. P MHz 1X/10X Passive Probe

Industrial Monitor Update Kit

SINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS

Operating Instructions 07/2007 Edition. SINAMICS G130/G150 Line harmonics filter. sinamics

MODELS USIX-024 AND USIX-120 INSTRUCTION SHEET FOR FEDERAL SIGNAL UNISTAT STATUS INDICATOR MODEL USIX

Model Number Structure

Document Part Number: Copyright 2010, Corelis Inc.

MICROMASTER Encoder Module

DA IN 1-OUT LINE DRIVER WITH EQUALIZATION + AUDIO USER S GUIDE

Installation Guide VL-MV10. Model No.

User Guide. HDMI Fiber Optic Extender. DVI-7350a

PAM-1840 Preamplifier Operation Manual

DA1931CT/ TP to Video + Audio Receiver

USER MANUAL. 22" Class Slim HD Widescreen Monitor L215DS

User Guide UD51. Second encoder small option module for Unidrive. Part Number: Issue Number: 5.

CNK221/241/261/321/341/361 Cable-Nook Jr. User s Guide

Analog Input Module HART Ex n Inputs, 8 Channels Series 9461/15

Model Camera System (CCTV) User Manual

Kramer Electronics, Ltd. USER MANUAL VM-20HD. Dual 1:10 HD/SD SDI Distribution Amplifier

DISTRIBUTION AMPLIFIER


SC / /205 Passive Audio Adapters User s Guide

3G/HD/SD-SDI to HDMI Converter

9" B/W MONITOR CEM-09/09A-2 12" B/W MONITOR CEM-12/12A-2 OPERATION MANUAL

VGA to DVI Extender over Fiber SET

Analog Input Module HART Ex i / I.S. Inputs, 8 Channels Type 9461/

Children cannot always recognize potential hazards properly. This 5.1 system is not designed for operation in a heavy industry environment.

Colour Explosion Proof Video Camera USER MANUAL VID-C

USER MANUAL. 27 Full HD Widescreen LED Monitor L27ADS

Spectra Batten (Order code: LEDJ95)

4, 8, 16 Port VGA/ Audio Extender / Splitter With Local Output with SPDIF Model #: VGA-C5SP-8

Electro Magnetic Compatibility (EMC) Warning. Important notes for users in the U.K. FCC declaration. Caution. Fuse

TP HDMI OVER ANYWIRE TRANSMITTER

INSTALLATION MANUAL FT-FOTR-1VDE-ST-S

Description. Specifications and Ordering Information 1900/27 Vibration Monitor

VGA / Audio Extender Single CAT5 / CAT6 with RGB Delay Control & EQ

TRANSCENSION 6-CHANNEL DMX DIMMER PACK (order code: BOTE40) USER MANUAL

Installation and Operation Manual

MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz

P XGA TFT Monitor. User s Manual

Kramer Electronics, Ltd. USER MANUAL. Model: VM Video Component Distributor

Spectroscopy Module. Vescent Photonics, Inc E. 41 st Ave Denver, CO Phone: (303) Fax: (303)

USER MANUAL Full HD Widescreen LED Monitor L236VA

Kramer Electronics, Ltd.

AEQ TH-03 Digital Hybrid of 1 (TH-03.1) or 2 lines (TH-03.2) with Frequency Extender

KHT 1000C HV-Probe Calibrator. Instruction Manual

SQM40/41 Actuators for air and gas dampers

TVAC20000 User manual

FOM-9010, FOM-9011 and FOM-9012

Operation Manual VMS 3.0 Video System

TIL311 HEXADECIMAL DISPLAY WITH LOGIC

SignalOn Series. L-Band Power Inserter Module INSTALLATION & OPERATION MANUAL. 1.2 GHz. D3.

VGA / Audio Extender Single CAT5 / CAT6 with RGB Delay Control & EQ

DALI TOUCHPANEL BASIC TW. Operating and control unit

32 Channel CPCI Board User Manual

HD1-DX HDMI Extender

USER MANUAL Full HD Widescreen LED Monitor L215IPS

User s Manual. Document # , Rev 1.2, 6/12/2006

USER MANUAL. 27 Full HD Widescreen LED Monitor L270E

INSTALLATION MANUAL FT-FOTR-8VD-ST-S. 8-Channel Digital Duplex Baseband Video Transmitter and Receiver With Reverse Data Transmission for PTZ Cameras

5 Port DVI Splitter VIDEO WALLS VIDEO PROCESSORS VIDEO MATRIX SWITCHES EXTENDERS SPLITTERS WIRELESS CABLES & ACCESSORIES

Model Extend HDMI audio and video connections up to 300 feet. Add up to 8 additional receivers with a dedicated network switch

LINE DRIVERS MANUAL PART NUMBER: DA3000TM0 1-IN, 1-OUT COMPOSITE VIDEO + AUDIO LINE DRIVER TABLE MOUNT USER S GUIDE

ANALOG I/O MODULES AD268 / DA264 / TC218 USER S MANUAL

RT USB RETRACTABLE CABLE

DA1909 COMPUTER VIDEO LINE DRIVER WITH EQUALIZATION USER S GUIDE

Cisco Aironet 1520 Series Outdoor Mesh Access Point Power Injector Installation Instructions

SWR Programmable Audio Switcher U S E R S M A N U A L

ACCESSORIES MANUAL PART NUMBER: TNP500. Universal Tilt N Plug Interconnect Box USER'S GUIDE

DS / /113. Pair (TP) User s Guide

User Guide. DVI + HDCP Fiber Optic Extender DVI-7330

Installation Guide. Cellular Plug-in for Inverters with SetApp. Version 1.1

ACCESSORIES MANUAL PART NUMBER: PRODUCT REVISION: 1 TNP100. Tilt N Plug Interconnect Box USER'S GUIDE

RT AUDIO RETRACTABLE CABLE

SG4424 HDTV Slave Sync Generator User Guide

RT USB RETRACTABLE CABLE

LINE DRIVERS MANUAL PART NUMBER: DA2000TM 1-IN, 1-OUT TABLE MOUNT COMPUTER VIDEO + AUDIO LINE DRIVER USER S GUIDE

FX-4AD-TC SPECIAL FUNCTION BLOCK USER'S GUIDE

Serial Flash Programmer. S550-SFWv3 FA Mode. Operation Manual. Sunny Giken Inc.

LXM23DU10M3X motion servo drive - Lexium 23 - single phase V - 1 kw - I/O

User Guide. HDMI Active Cable Extender. DVI-7370c

USER S MANUAL CCTV LED MONITOR MODEL: ADE-117N1 ADE-119N1 ADE-118W1 ADE-121W1 ADE-124W Atherton Electronics Corp. All rights reserved.

USER MANUAL Full HD Widescreen LED Monitor L215ADS

Gamma instabus. Technical product information

TR6102HD HDTV/DVD/COMPONENT VIDEO TO RGBHV TRANSCODER USER S GUIDE

Stratos Duo RGB. User Manual. Order code: EQLED371

(1) (2) (3) Bedienungs- und Montageanleitung. Safety instructions. Structure of the device

MS2540 Current Loop Receiver with RS485 Communication

PNP300 / PNP300UN / PNP350

PNP300 & PNP350 POP N PLUG SLIM INTERCONNECT BOX USER S GUIDE

Transcription:

ICSTT-RM290F-EN-P (PD-T8824) Trusted Product Overview The Trusted 40 Channel 120 Vac Digital Input Field Termination Assembly (FTA) T8824 is designed to act as the main interface between a field device generating a digital signal and the Trusted TMR 120 Vac Digital Input Module T8424. Features: 40 input channels per FTA. Industry standard field device connections (2-wire). Standard DIN rail compatibility. Simple installation and connection. 120 Vac operation. Fused field power supply per channel. Rockwell Automation Publication ICSTT-RM290F-EN-P Issue 7

Trusted ICSTT-RM290F-EN-P Page intentionally left blank Rockwell Automation Publication ICSTT-RM290F-EN-P Issue 7

PREFACE PREFACE In no event will Rockwell Automation be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples given in this manual are included solely for illustrative purposes. Because of the many variables and requirements related to any particular installation, Rockwell Automation does not assume responsibility or reliability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, with respect to use of information, circuits, equipment, or software described in this manual. Allen Bradley, LISTEN. THINK. SOLVE., Rockwell Automation, TechConnect, and Trusted are trademarks of Rockwell Automation, Inc. All trademarks are acknowledged. DISCLAIMER It is not intended that the information in this publication covers every possible detail about the construction, operation, or maintenance of a control system installation. You should also refer to your own local (or supplied) system safety manual, installation and operator/maintenance manuals. REVISION AND UPDATING POLICY This document is based on information available at the time of its publication. The document contents are subject to change from time to time. The latest versions of the manuals are available at the Rockwell Automation Literature Library under "Product Information" information "Critical Process Control & Safety Systems". TRUSTED RELEASE This technical manual was updated for Trusted Release 4.0. LATEST PRODUCT INFORMATION For the latest information about this product review the Product Notifications and Technical Notes issued by technical support. Product Notifications and product support are available at the Rockwell Automation Support Centre at http://rockwellautomation.custhelp.com At the Search Knowledgebase tab select the option "By Product" then scroll down and select the Trusted product. Some of the Answer ID s in the Knowledge Base require a TechConnect Support Contract. For more information about TechConnect Support Contract Access Level and Features, click on the following link: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/50871 This will get you to the login page where you must enter your login details. Rockwell Automation Publication ICSTT-RM290F-EN-P Issue 7 i

PREFACE IMPORTANT A login is required to access the link. If you do not have an account then you can create one using the "Sign Up" link at the top right of the web page. DOCUMENTATION FEEDBACK Your comments help us to write better user documentation. If you discover an error, or have a suggestion on how to make this publication better, send your comment to our technical support group at http://rockwellautomation.custhelp.com ii Issue 7 Rockwell Automation Publication ICSTT-RM290F-EN-P

PREFACE SCOPE This manual specifies the maintenance requirements and describes the procedures to assist troubleshooting and maintenance of a Trusted system. WHO SHOULD USE THIS MANUAL This manual is for plant maintenance personnel who are experienced in the operation and maintenance of electronic equipment and are trained to work with safety systems. SYMBOLS In this manual we will use these notices to tell you about safety considerations. SHOCK HAZARD: Identifies an electrical shock hazard. If a warning label is fitted, it can be on or inside the equipment. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which can cause injury or death, property damage or economic loss. ATTENTION: Identifies information about practices or circumstances that can cause injury or death. CAUTION: Identifies information about practices or circumstances that can cause property damage or economic loss. BURN HAZARD: Identifies where a surface can reach dangerous temperatures. If a warning label is fitted, it can be on or inside the equipment. This symbol identifies items which must be thought about and put in place when designing and assembling a Trusted controller for use in a Safety Instrumented Function (SIF). It appears extensively in the Trusted Safety Manual. IMPORTANT NOTE TIP Identifies information that is critical for successful application and understanding of the product. Provides key information about the product or service. Tips give helpful information about using or setting up the equipment. Rockwell Automation Publication ICSTT-RM290F-EN-P Issue 7 iii

PREFACE WARNINGS AND CAUTIONS WARNING: EXPLOSION RISK Do not connect or disconnect equipment while the circuit is live or unless the area is known to be free of ignitable concentrations or equivalent AVERTISSEMENT - RISQUE D EXPLOSION Ne pas connecter ou déconnecter l équipement alors qu il est sous tension, sauf si l environnement est exempt de concentrations inflammables ou équivalente MAINTENANCE Maintenance must be carried out only by qualified personnel. Failure to follow these instructions may result in personal injury. CAUTION: RADIO FREQUENCY INTERFERENCE Most electronic equipment is influenced by Radio Frequency Interference. Caution should be exercised with regard to the use of portable communications equipment around such equipment. Signs should be posted in the vicinity of the equipment cautioning against the use of portable communications equipment. CAUTION: The module PCBs contains static sensitive components. Static handling precautions must be observed. DO NOT touch exposed connector pins or attempt to dismantle a module. iv Issue 7 Rockwell Automation Publication ICSTT-RM290F-EN-P

PREFACE ISSUE RECORD Issue Date Comments 5 Jun 16 Rebranded and updated to incorporate IEEE standards with correction of typographical errors and also standardise the Relative Humidity Range and Operating Temperature statements in the Specification Section. 6 Aug 17 Figure 2 Single Channel Schematic and Voltage details in Specifications table updated. Clarified distinction between operating range and measurement range. 7 Jan 19 Spec table and diagrams updated Updated to display Rockwell Automation publication numbers. Added trademarks statement. Rockwell Automation Publication ICSTT-RM290F-EN-P Issue 7 v

PREFACE Page intentionally left blank vi Issue 7 Rockwell Automation Publication ICSTT-RM290F-EN-P

Table of Contents Table of Contents 1. Description... 3 2. Installation... 5 3. Associated Cable Selection... 7 4. Cable Capacitance... 9 5. Assembly Pinout Connections... 11 5.1. AC Supply TB1 Connections... 11 5.2. Field TB2 TB5 Connections... 11 5.3. Field TB6 TB9 Connections... 12 5.4. Field TB10 TB13 Connections... 13 5.5. Field TB14 TB17 Connections... 13 5.6. Field TB18 TB21 Connections... 14 5.7. SK1 Connections... 14 5.8. SK2 Connections... 15 5.9. SK3 Connections... 15 5.10. SK4 Connections... 16 5.11. SK5 Connections... 16 6. Specifications... 19 Rockwell Automation Publication ICSTT-RM290F-EN-P Issue 7 1

Table of Contents Page intentionally left blank 2 Issue 7 Rockwell Automation Publication ICSTT-RM290F-EN-P

1. Description 1. Description Figure 1 T8824 Photo The T8824 provides termination for a maximum of 40 input channels from various types of field devices which generate a digital input. Figure 2 below shows the configuration of a single channel. Figure 2 Single Channel Schematic The supply for the field is derived from a 120 Vac feed which is connected to AC Input terminal block TB1. The supply is then fed to each channel. Rockwell Automation Publication ICSTT-RM290F-EN-P Issue 7 3

1. Description The supply voltage to the field is fed via the 50 ma fuse. This effectively limits the current in the field loop. The incoming signal (digital) from the field device is fed to the digital input module via a resistive divider. This divides the voltage down to levels suitable for an analogue measurement. Revision E T8824 FTAs use two power resistors in series, as shown in the circuit diagram in Figure 2. Earlier revisions used 4x4 resistor arrays. The resistor arrays on the top half are 68 K and the bottom resistor arrays are 1 K. Line monitoring is limited to voltage detection on the module. Refer to Trusted TMR 120 Vac Digital Input Module 40 Channel, publication ICSTT-RM450 (PD-T8424) for details. The cable linking the 40 channels on the input module to the FTA is terminated at five 10- way connectors (SK1 to SK5). The input signals from the field (40-off) are connected by 2- wire arrangements terminated on 5-off 16-way terminal blocks. 4 Issue 7 Rockwell Automation Publication ICSTT-RM290F-EN-P

2. Installation 2. Installation T8824 is designed to be mounted on either of the TS32 or TS35 DIN rails in the horizontal or vertical positions as required. Figure 3 T8824 General Arrangement Rockwell Automation Publication ICSTT-RM290F-EN-P Issue 7 5

2. Installation Page intentionally left blank 6 Issue 7 Rockwell Automation Publication ICSTT-RM290F-EN-P

3. Associated Cable Selection 3. Associated Cable Selection Refer to the product descriptions detailed below: ICSTT-RM311 (PD-TC200) Trusted I/O Companion Slot Cables Rockwell Automation Publication ICSTT-RM290F-EN-P Issue 7 7

3. Associated Cable Selection Page intentionally left blank 8 Issue 7 Rockwell Automation Publication ICSTT-RM290F-EN-P

4. Cable Capacitance 4. Cable Capacitance With long field cables the capacitive coupling of the cable can cause a significant voltage to be seen at the T8424 input when the field switch is open. This causes the T8424 to report that the field switch is still on when it is turned off. Revision E T8824 FTAs have lower loop resistance, which reduces the capacitive noise and increases the available loop length. The table below shows some estimated maximum lengths for different cables and mains supplies. Practical distances will be less than this due to other noise and for switching safety margins. Revision E Earlier revisions 15 pf/m, 110 V, 50 Hz 2940 m 890 m 30 pf/m, 110 V, 50 Hz 1470 m 470 m 15 pf/m, 110 V, 60 Hz 2450 m 790 m 30 pf/m, 110 V, 60 Hz 1220 m 390 m 15 pf/m, 120 V, 50 Hz 2620 m 850 m 30 pf/m, 120 V, 50 Hz 1310 m 420 m 15 pf/m, 120 V, 60 Hz 2190 m 700 m 30 pf/m, 120 V, 60 Hz 1090 m 350 m Table 1 Theoretical maximum cable lengths Rockwell Automation Publication ICSTT-RM290F-EN-P Issue 7 9

4. Cable Capacitance Page intentionally left blank 10 Issue 7 Rockwell Automation Publication ICSTT-RM290F-EN-P

5. Assembly Pinout Connections 5. Assembly Pinout Connections 5.1. AC Supply TB1 Connections Pin Service 1 120 Vac Live 2 120 Vac Live 3 120 Vac Neutral 4 120 Vac Neutral Table 2 AC Supply TB1 Connections 1 TB1 L L N N 4 5.2. Field TB2 TB5 Connections Figure 4 AC Supply TB1 Connections Pin Loop Power terminal Signal terminal TB2 TB3 1 Channel 1 Channel 1 2 Channel 2 Channel 2 1 Channel 3 Channel 3 2 Channel 4 Channel 4 TB4 1 Channel 5 Channel 5 Rockwell Automation Publication ICSTT-RM290F-EN-P Issue 7 11

5. Assembly Pinout Connections Pin Loop Power terminal Signal terminal 2 Channel 6 Channel 6 TB5 1 Channel 7 Channel 7 2 Channel 8 Channel 8 Table 3 Field TB2 TB5 Connections 5.3. Field TB6 TB9 Connections Figure 5 Field TB2 TB5 Connections Pin Loop Power terminal Signal terminal TB6 TB7 TB8 TB9 1 Channel 9 Channel 9 2 Channel 10 Channel 10 1 Channel 11 Channel 11 2 Channel 12 Channel 12 1 Channel 13 Channel 13 2 Channel 14 Channel 14 1 Channel 15 Channel 15 2 Channel 16 Channel 16 Table 4 Field TB6 TB9 Connections 12 Issue 7 Rockwell Automation Publication ICSTT-RM290F-EN-P

5. Assembly Pinout Connections 5.4. Field TB10 TB13 Connections Pin Loop Power terminal Signal terminal TB10 TB11 TB12 TB13 1 Channel 17 Channel 17 2 Channel 18 Channel 18 1 Channel 19 Channel 19 2 Channel 20 Channel 20 1 Channel 21 Channel 21 2 Channel 22 Channel 22 1 Channel 23 Channel 23 2 Channel 24 Channel 24 5.5. Field TB14 TB17 Connections Table 5 Field TB10 TB13 Connections Pin Loop Power terminal Signal terminal TB14 TB15 TB16 TB17 1 Channel 25 Channel 25 2 Channel 26 Channel 26 1 Channel 27 Channel 27 2 Channel 28 Channel 28 1 Channel 29 Channel 29 2 Channel 30 Channel 30 1 Channel 31 Channel 31 2 Channel 32 Channel 32 Table 6 Field TB14 TB17 Connections Rockwell Automation Publication ICSTT-RM290F-EN-P Issue 7 13

5. Assembly Pinout Connections 5.6. Field TB18 TB21 Connections Pin Loop Power terminal Signal terminal TB18 TB19 TB20 TB21 1 Channel 33 Channel 33 2 Channel 34 Channel 34 3 Channel 35 Channel 35 4 Channel 36 Channel 36 5 Channel 37 Channel 37 6 Channel 38 Channel 38 7 Channel 39 Channel 39 8 Channel 40 Channel 40 Table 7 Field TB18 TB21 Connections 5.7. SK1 Connections Pin Service 1 0 V 2 Channel 1 3 Channel 2 4 Channel 3 5 Channel 4 6 Channel 5 7 Channel 6 8 Channel 7 9 Channel 8 10 Not used Table 8 SK1 Connections 14 Issue 7 Rockwell Automation Publication ICSTT-RM290F-EN-P

5. Assembly Pinout Connections 5.8. SK2 Connections Pin Service 1 0 V 2 Channel 9 3 Channel 10 4 Channel 11 5 Channel 12 6 Channel 13 7 Channel 14 8 Channel 15 9 Channel 16 10 Not used Table 9 SK2 Connections 5.9. SK3 Connections Pin Service 1 0 V 2 Channel 17 3 Channel 18 4 Channel 19 5 Channel 20 6 Channel 21 7 Channel 22 8 Channel 23 Rockwell Automation Publication ICSTT-RM290F-EN-P Issue 7 15

5. Assembly Pinout Connections Pin Service 9 Channel 24 10 Not used Table 10 SK3 Connections 5.10. SK4 Connections Pin Service 1 0 V 2 Channel 25 3 Channel 26 4 Channel 27 5 Channel 28 6 Channel 29 7 Channel 30 8 Channel 31 9 Channel 32 10 Not used Table 11 SK4 Connections 5.11. SK5 Connections Pin Service 1 0 V 2 Channel 33 3 Channel 34 4 Channel 35 5 Channel 36 16 Issue 7 Rockwell Automation Publication ICSTT-RM290F-EN-P

5. Assembly Pinout Connections Pin Service 6 Channel 37 7 Channel 38 8 Channel 39 9 Channel 40 10 Not used Table 12 SK5 Connections Rockwell Automation Publication ICSTT-RM290F-EN-P Issue 7 17

5. Assembly Pinout Connections Page intentionally left blank 18 Issue 7 Rockwell Automation Publication ICSTT-RM290F-EN-P

6. Specifications 6. Specifications Field Supply Voltage Power Dissipation Isolation Maximum Current (Field Supply) Fusing Operating Temperature Storage Temperature Relative Humidity Operating and Storage Environmental Specifications 90-150 Vac 0.65 W / Channel (120 Vac); 26 W max 1 W / channel (150 Vac); 40 W max N/A. Isolation provided in T8424 Module only. 5.4 ma per channel (120 Vac) 6.7 ma per channel (150 Vac) 50 ma fuse for each channel field voltage supply. 0 C to +60 C (+32 F to +140 F) -25 C to +70 C (-13 F to +158 F) 10 % 95 %, non-condensing Refer to Document ICSTT-TD003 Dimensions Height Width Depth 111 mm (4.4 in) 335 mm (13.2 in) 51 mm (2 in) Weight 900 g (2 lb) Rockwell Automation Publication ICSTT-RM290F-EN-P Issue 7 19