I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Similar documents
Description Set value in neutral conductor is synchronous with set value Ir of main pole. CSA 100. conductor. I r A 50-63

I r A Protection against direct contact Finger and back-of-hand proof to VDE 0106 part 100

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Description Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Protective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A

I r A I i = I n x. Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Protective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A

Type: NZMN1 A100 Article No.: Sales text Circuit breaker3p systems/cable prot. Ordering information Number of poles

Climatic proofing Damp heat, constant, to IEC Damp heat, cyclic, to IEC

Soft starter, 66 A, V AC, Us= 24 V DC, with control unit, Frame size N. Function Soft starter for three-phase loads, with control unit

Minicontactorrelay,2NO/2NC,DCoperated

Type: DILM25 10(24V50HZ) Article No.:

Type: DILM12 10(24VDC) Article No.:

AS09..S 3-pole Contactors - Spring Terminals

Product Information. Circuit Breaker BZM1(16 to 125 A) Circuit Breaker BZM2 (125 to 250A) Circuit Breaker BZM3 (250 to 400A)

GV3P80 TeSys GV3P thermal-magn motor circuit breaker 70-80A EverLink

Series CT7N Bimetallic Overload Relays

TeSys contactors. Model d. Type of contactor LC1- LC1- LC1- LC1- LC1-D115 & D09 D18 D25 D38 D40 D50 D95 LC1-D150 DT20 & DT25 DT32 & DT40

Datasheet - SRB-E-201ST

Datasheet - SRB301LC 24VAC/DC

Bulletin 190 IEC Modular Starter System

Contactor 4 kw / 400 V with 3 Main Contacts and max. 4 Auxiliary Contacts Series 8510/122

Ordering details. Approval. Classification

TeSys circuit-breakers

LC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC

with handle LIMOGES Cedex 1. DESCRIPTION - USE 3. DIMENSIONS Symbol: Technology: Use:. For controlling a load remotely via a switch 2.

GV2ME. Product data sheet Characteristics. TeSys GV2-Circuit breaker-thermal-magnetic A - screw clamp terminals. Main.

GV2ME. Product data sheet Characteristics. TeSys GV2-Circuit breaker-thermal-magnetic A -screw clamp terminals. Main.

LC1D12P7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A V AC coil

Circuit breakers BZM. Circuit breakers BZM

GV2ME083 TeSys GV2 - Circuit breaker - thermal-magnetic A - spring terminals

CT7N CT7 CT7K 4 6 CT TJ 4 6 CT7K TKK 6 10 CT TK 6 9 CT7K TKL

PBC series. RoHS. Ready. IEC-Type Contactors & Accessories 9-80 Amp AC-3, Amp AC-1 AC Coils. P&B PBC Series IEC Type Contactors & Accessories

A V 50Hz / V 60Hz

LC1D09FE7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A V AC coil

LC1D32P7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A V AC 50/60 Hz coil

GV2ME. Main. Device short name. Device application

LC1D12B7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A - 24 V AC coil

LC1D50AF7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 50 A V AC 50/60 Hz coil

DMX and 4000 air circuit breakers from 800 to 4000 A

GV2P05. Main. Device short name. Device application

02/11/2015

LC3D115M7 TeSys D - star delta starter - 3 x 3P (3 NO) A V AC coil

Modular pulse operated latching relay 16 A

LC1D80F7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 80 A V AC 50/60 Hz coil

GV2ME086 TeSys GV2 - Circuit breaker - thermal-magnetic A - lugs-ring terminals

LC1D65AF7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC 50/60 Hz coil

LED Driver Compact fixed output

LC1D25G7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A V AC coil

LC1D09B7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A - 24 V AC coil

LC1D150G7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 150 A V AC coil

High performance circuit breakers

GV2ME. Main. Device short name. Device application

LED control gear Compact fixed output

Analog Input Module HART Ex i / I.S. Inputs, 8 Channels Type 9461/

LC1D09F7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A V AC coil

LED Driver Compact fixed output

Analog Input Module HART Ex n Inputs, 8 Channels Series 9461/15

LC3D180AV7 TeSys D - star delta starter - 3 x 3P (3 NO) - 18 A V AC coil

PHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series

LED Driver Linear / area fixed output

Circuit-Breakers for Motor Protection Series 8523/8

LED Driver Compact dimming

llen-bradley 194R-HM4-NFPA3

LC1D09M7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A V AC coil

Magnetic and Hydraulic-Magnetic Circuit Breaker

LXM23DU10M3X motion servo drive - Lexium 23 - single phase V - 1 kw - I/O

LC1D150B7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 150 A - 24 V AC 50/60 Hz coil

LC1D50AFE7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 50 A V AC 50/60 Hz coil

Power Circuit of a UL508A Panel. Typical UL489 Application

LC3D80B7 TeSys D - star delta starter - 3 x 3P (3 NO) - 80 A - 24 V AC coil

Generator protection relay

KRF EMC Filters Installation, Operation and Maintenance Manual

LED MODULES READYLINE DL

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control

Grid feeding monitoring according to VDE-AR-N 4105 and BDEW CM-UFD.M31

4/2 Introduction. 4/4 5SV RCCBs. 4/10 5SM3 RCCBs. 4/13 SIQUENCE 5SM3/5SU1 universal current-sensitive RCCBs, type B and type B+

GR circuit breaker - hydraulic magnetic, Datasheet

Features XT SC 012 B B A

Features XT SC 012 B B A

Amphenol. Amphenol-Tuchel Electronics GmbH. C 112 Series M12 - Connectors

16 A and 25 A power contactors with or without handle

Weekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

AF-300 E11 Adjustable Frequency Drive

8 Installation Equipment

GR circuit breaker - hydraulic magnetic, Datasheet

DATA SHEET. The Advantys model STBDAI5260 Digital Input Module provides 2 isolated discrete input points that operate on a 115 VAC power source.

SINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS

Operating Instructions 07/2007 Edition. SINAMICS G130/G150 Line harmonics filter. sinamics

Interface Relays and Optocouplers Product group picture

OT 100/ /700 P5

Manual Motor Starter Specifcations

ORDERING Page 6 BASLER RELAY STANDARDS, DIMENSIONS, ACCESSORIES Request bulletin SDA

GV3P401 TeSys GV3 termo magnetski-prekidač-30 40A- EverLink BTR/izravni konektori

PRINCIPLES AND APPLICATIONS

Process transmitter RMA422

LED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series

Transcription:

Circuit-breaker,3p,160A Partno. NZMN2-M160 CatalogNo. 265724 Similar to illustration Deliveryprogram Product range Circuit-breaker Protective function Motor protection Standard/Approval IEC Installation type Fixed Release system Thermomagnetic release Construction size NZM2 Description Tripping class 10 A IEC/EN 60947-4-1, IEC/EN 60947-2 Number of poles 3 pole Standard equipment Screw connection Switchingcapacity 400/415 V 50 Hz I cu ka 50 Rated current = rated uninterrupted current I n = I u A 160 Settingrange Overload trip I r A 125-160 The circuit-breaker fulfills all requirements for AC-3 switching category. Short-circuit releases Non-delayed I i = I n x 8-14 MotorratingAC-350/60Hz 380 V 400 V P kw 75 MotorratingAC-350/60Hz 400 V P kw 75 RatedoperationalcurrentAC-350/60Hz 400 V I e A 134 Technicaldata General Standards IEC/EN 60947 Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100 Climatic proofing Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 Ambient temperature Ambient temperature, storage C - -40 - + 70 Operation C -25 - +70 Mechanical shock resistance (10 ms half-sinusoidal shock) according to IEC 60068-2-27 g 20 (half-sinusoidal shock 20 ms) 09/07/2017 265724 - HPL-ED2017 V36.0 EN 1 / 10

Safe isolation to EN 61140 Between auxiliary contacts and main contacts V AC 500 between the auxiliary contacts V AC 300 Weight kg 2.345 Mounting position Vertical and 90 in all directions With XFI earth-fault release: - NZM1, N1, NZM2, N2: vertical and 90 in all directions with plug-in unit - NZM1, N1, NZM2, N2: vertical, 90 right/left with withdrawable unit: - NZM3, N3: vertical, 90 right/left - NZM4, N4: vertical with remote operator: - NZM2, N(S)2, NZM3, N(S)3, NZM4, N(S)4: vertical and 90 in all directions Direction of incoming supply as required Degree of protection Device In the operating controls area: IP20 (basic degree of protection) Enclosures With insulating surround: IP40 With door coupling rotary handle: IP66 Terminations Tunnel terminal: IP10 Phase isolator and strip terminal: IP00 Other technical data (sheet catalogue) Temperature dependency, Derating Circuit-breakers Rated current = rated uninterrupted current I n = I u A 160 Rated surge voltage invariability U imp Main contacts V 8000 Auxiliary contacts V 6000 Rated operational voltage U e V AC 690 Details apply for 3 pole system protection circuit-breaker with thermomagnetic release NZMN(H)1(2)(3)-A to 500 A. For rated operating voltage switching via 3 contacts: DC correction factor for instantaneous release response value: NZM1: 1.25, NZM2: 1.35, NZM3: 1.45 Set value for I i at DC = set value I i AC/correction factor DC Switchingofonepole viatwoseriescontacts Switchingofone poleviathreeseries contacts Overvoltage category/pollution degree III/3 Rated insulation voltage U i V 1000 Use in unearthed supply systems V Switchingcapacity 690 Rated short-circuit making capacity I cm 240 V I cm ka 187 400/415 V I cm ka 105 440 V 50/60 Hz I cm ka 74 525 V 50/60 Hz I cm ka 53 690 V 50/60 H Ic ka 40 Rated short-circuit breaking capacity I cn I cn Icu to IEC/EN 60947 test cycle O-t-CO Icu ka 09/07/2017 265724 - HPL-ED2017 V36.0 EN 2 / 10

240 V 50/60 Hz I cu ka 85 400/415 V 50/60 Hz I cu ka 50 440 V 50/60 Hz I cu ka 35 525 V 50/60 Hz I cu ka 25 690 V 50/60 Hz I cu ka 20 Ics to IEC/EN 60947 test cycle O-t-CO-t-CO Ics ka 240 V 50/60 Hz I cs ka 85 400/415 V 50/60 Hz I cs ka 50 440 V 50/60 Hz I cs ka 35 525 V 50/60 Hz I cs ka 25 690 V 50/60 Hz I cs ka 5 Rated short-time withstand current t = 0.3 s I cw ka 1.9 t = 1 s I cw ka 1.9 Utilization category to IEC/EN 60947-2 A Rated making and breaking capacity Rated operational current I e A AC-1 AC--3 380 V 400 V I e A 160 415 V I e A 160 690 V I e A 160 380 V 400 V I e A 134 415 V I e A 134 Lifespan, mechanical(of which max. 50 % trip by shunt/undervoltage release) Operations 20000 Lifespan, electrical AC-1 AC--3 400 V 50/60 Hz Operations 10000 415 V 50/60 Hz Operations 10000 690 V 50/60 Hz Operations 7500 400 V 50/60 Hz Operations 6500 415 V 50/60 Hz Operations 6500 690 V 50/60 Hz Operations 5000 Max. operating frequency Ops/h 120 Total downtime in a short-circuit ms < 10 Terminalcapacity Standard equipment Screw connection Optional accessories Box terminal Tunnel terminal connection on rear Round copper conductor Box terminal Solid 2 mm 1 x (10-16) 2 x (6-16) Stranded 2 mm 1 x (25-185) 2 x (25-70) Tunnel terminal Solid mm 2 1 x 16 Stranded mm 2 Stranded 2 mm 1 x (25-185) Bolt terminal and rear-side connection Direct on the switch Solid 2 mm 1 x (10-16) Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit-breaker. 09/07/2017 265724 - HPL-ED2017 V36.0 EN 3 / 10

2 x (6-16) Stranded 2 mm 1 x (25-185) 2 x (25-70) Al conductors, Cu cable Solid mm 2 1 x 16 Stranded mm 2 Stranded 2 mm 1 x (25-185) Cu strip (number of segments x width x segment thickness) Box terminal Bolt terminal and rear-side connection min. mm 2 x 9 x 0.8 max. mm 10 x 16 x 0.8 (2x) 8 x 15.5 x 0,8 Flat copper strip, with holes min. mm 2 x 16 x 0.8 Flat copper strip, with holes max. mm 10 x 24 x 0.8 Copper busbar (width x thickness) mm Bolt terminal and rear-side connection Screw connection M8 Direct on the switch Control cables min. mm 16 x 5 max. mm 24 x 8 2 mm 1 x (0.75-2.5) 2 x (0.75-1.5) DesignverificationasperIEC/EN61439 Technical data for design verification Rated operational current for specified heat dissipation I n A 160 Equipment heat dissipation, current-dependent P vid W 38.4 Operating ambient temperature min. C -25 Operating ambient temperature max. C 70 IEC/EN 61439 design verification 10.2 Strength of materials and parts 10.2.2 Corrosion resistance Meets the product standard's requirements. 10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements. 10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements. 10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects Meets the product standard's requirements. 10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements. 10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated. 10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated. 10.2.7 Inscriptions Meets the product standard's requirements. 10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated. 10.4 Clearances and creepage distances Meets the product standard's requirements. 10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated. 10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated. 10.7 Internal electrical circuits and connections Is the panel builder's responsibility. 10.8 Connections for external conductors Is the panel builder's responsibility. 10.9 Insulation properties 10.9.2 Power-frequency electric strength Is the panel builder's responsibility. 10.9.3 Impulse withstand voltage Is the panel builder's responsibility. 10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility. 10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. 10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be observed. 09/07/2017 265724 - HPL-ED2017 V36.0 EN 4 / 10

10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be observed. 10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. TechnicaldataETIM6.0 Low-voltage industrial components (EG000017) / Motor protection circuit-breaker (EC000074) Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kv) / Motor protection circuit-breaker (ecl@ss8.1-27-37-04-01 [AGZ529013]) Overload release current setting A 125-160 Adjustment range undelayed short-circuit release A 1280-2240 Thermal protection Yes Phase failure sensitive No Switch off technique Thermomagnetic Rated operating voltage V 690-690 Rated permanent current Iu A 160 Rated operation power at AC-3, 230 V kw 45 Rated operation power at AC-3, 400 V kw 90 Type of electrical connection of main circuit Screw connection Type of control element Rocker lever Device construction Built-in device fixed built-in technique With integrated auxiliary switch No With integrated under voltage release No Number of poles 3 Rated short-circuit breaking capacity lcu at 400 V, AC ka 50 Degree of protection (IP) IP20 Height mm 184 Width mm 105 Depth mm 149 09/07/2017 265724 - HPL-ED2017 V36.0 EN 5 / 10

Characteristics 09/07/2017 265724 - HPL-ED2017 V36.0 EN 6 / 10

Durchlassstrom 09/07/2017 265724 - HPL-ED2017 V36.0 EN 7 / 10

Durchlassenergie 09/07/2017 265724 - HPL-ED2017 V36.0 EN 8 / 10

Dimensions Blow out area, minimum clearance to adjacent parts Minimum clearance to adjacent parts 09/07/2017 265724 - HPL-ED2017 V36.0 EN 9 / 10

Additionalproductinformation(links) IL01206006Z(AWA1230-1916)Circuit-Breaker,basicunit IL01206006Z (AWA1230-1916) Circuit-Breaker, basic unit Temperature dependency, Derating ftp://ftp.moeller.net/documentation/awa_instructions/il01206006z2015_11.pdf http://ecat.moeller.net/flip-cat/?edition=hplen&startpage=17.172 09/07/2017 Eaton Industries GmbH http://www.eaton.eu 09/2017 by Eaton Industries GmbH 265724 - HPL-ED2017 V36.0 EN 10 / 10