PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0553 Identification for Communications Systems

Similar documents
UNM IT/Telecommunications Guide Specification Labeling 11/07/

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION

1.0 GENERAL. 1.2 SUMMARY.1 Section Includes:

SECTION FIBER OPTIC STATION CABLES

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus

DESIGN!!GUIDELINES!!!!!

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE)

Request for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards.

Request for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION TELECOMMUNICATIONS SYSTEM INFRASTRUCTURE

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

Information Technology Services DESIGN AND INSTALLATION STANDARDS

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

Telecommunication Infrastructure Project September 20, 2002

WJHW, Inc. 6 April 2016 Texas Tech University Issue for CD Set Sports Performance Complex Lubbock, Texas

APPENDIX A Verify All Part Numbers (Partial List of Approved Products)

STRUCTURED CABLE SYSTEM (SCS)

City of Winter Springs, FL

SECTION COMMUNICATIONS HORIZONTAL CABLING

Statement of Work. Falcon Stadium Locker Room Audio-Visual & Telecommunications Package. 3 May 2018

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

Project No. # Page 1

A. All communications equipment rooms shall be installed in a neat and workmanlike manner.

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT

Technical Specifications Florida Gulf Coast University

Mfgr. Berk Tek ea , Berk Tek ea , Berk Tek ea. Berk Tek ea ,350.

CABLING STANDARDS FOR

Project No. # Page 1

SECTION COMMUNICATIONS HORIZONTAL CABLING

Northwestern University Information Technology Building Infrastructure Requirements for Communication Facilities ( January 2010)

Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING

MTS FiON. for Multiple Dwelling Units (MDUs) Brownfield

Michigan State University Construction Standards EXTERIOR FIBER OPTIC CABLE SYSTEM PAGE

SPECIAL SPECIFICATION 8540 Telecommunication Cable

CASS COUNTY, MICHIGAN CASSOPOLIS, MI REQUEST FOR PROPOSAL SPECIFICATIONS

PURCHASING DEPARTMENT. Project # Addendum # # of pages Original Issue Date Request Doc # April 15, see text below

Follow The Leader In Shielded Technology

C. Link offers a standard 1-year warranty on all parts and labor. Manufacturer's warranty is available for larger projects.

REQUEST FOR PROPOSALS UK Audiovisual System to Renovate/Expand the Law Building ADDENDUM #2 1/16/2019

Section Communications Optical Fiber Backbone Cabling

B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines.

SPECIAL SPECIFICATION 6559 Telecommunication Cable

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017

SITE All work shall be performed at Center Park Substation (1895 Kernan Blvd, Jacksonville, Fl ). DATE: 04/03/2018

ADDENDUM NO. 2 This addendum consists of 8 pages. Kenai Peninsula Borough Purchasing & Contracting

Connected Solutions. April $ Post, 19 Rack ELERK1FR BK

CASS COUNTY, MICHIGAN CASSOPOLIS, MI REQUEST FOR PROPOSAL SPECIFICATIONS

A. The requirements of Section govern the work specified in this section.

SPECIAL SPECIFICATION 6686 BSIF CCTV Central Equipment

The University of Texas at Austin September 30, 2011

CRESTRON SITE PACK, LAST REVISION: 25/01/2017

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

REQUEST FOR PROPOSALS UK Audiovisual System to Renovate/Expand the Law Building ADDENDUM #3 1/17/2019

Colorado River Union High School District 1004 Hancock Rd Bullhead City, AZ (928)

SECTION TESTING OF COPPER CABLES

STANDARDS SECTION (16651) COMMUNICATIONS DISTRIBUTION SYSTEM (Rev. Jun 2011)

Target Interface / Construction Compliance Inspection Checklist

SPECIAL SPECIFICATION 2344 TMC Support Equipment

SECTION COMMUNICATIONS HORIZONTAL CABLING

Telecommunciations Infrastructure Project September 20, A. Broadband radio frequency active and passive components

1/9/2016 TECHNOLOGY DESIGN GUIDELINES SCCPSS. Savannah-Chatham County Public School System

March 4 th, Addendum No. 1. Brooklyn College Systems Integrator Broadcast Television Equipment Project No: BY019/

VGA CAT-5 1:8 Distribution S VGA CAT-5 Distribution R

Request for Proposal (RFP)

The MTS FiON Network. for Multiple Dwelling Units (MDUs) Greenfield/Brownfield Renovations

SPECIAL SPECIFICATION :1 Video (De) Mux with Data Channel

DESIGN STANDARD FOR AUDIOVISUAL SYSTEMS

B. Shop Drawings: Show layout and types of-projection screens.. Include the following:

Brown University. Communications Standard Parts List

2002, Cisco Systems, Inc. All rights reserved.

RCIT Cable Certification Testing Revised 10/2017

ADDENDUM NUMBER 02 TO THE BID DOCUMENTS. BID DOCUMENT: RFP #G PE Building Audio Visual System San Jose City College

Msquare Innotech Solutions Pvt. Ltd. Complete integration of business solution. About Us: Mission:

Section COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cable Management and Ladder Rack

A108. OBSOLETE SERVICE OFFERINGS - TELEPHONE ANSWERING SERVICE FACILITIES

Spec Sheet. InterReach Fusion Wideband 2.5 GHz WiMAX. In-Building Wireless Networking System. Product Highlights

VGA CAT-5 1:8 Distribution S VGA CAT-5 Distribution R. EXT-VGA-CAT5-148S EXT-VGA-CAT5-148R User Manual

SPECIAL SPECIFICATION 8494 CCTV Central Equipment

DATA/TELECOMMUNICATIONS REQUEST FOR PRICING

DESIGN STANDARD FOR AUDIOVISUAL SYSTEMS

Liberty Mutual Structured Cabling Specification Bid and Build Structured Cabling Technical Specification for:

CR-R880-BL: Indoor/Outdoor Proximity Reader with 10cm (4in) read range

NETWORK INFRASTRUCTURE STANDARDS. Prepared by UIT Network Services

Invitation to Bid SCOREBOARD - WHH

BUSD Ramona Middle School Gymnasium Project AV Project

SECTION COMMUNICATIONS CABLING. (Sub-Sub-Bid Required, Part of Sub-Bid Section ELECTRICAL)

btnet new products Modular and preloaded patch panels btnet

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification

Rogers Communication Center Cable Documentation and Identification Policy

Panduit Recommended Best Case Practice Split Fibre

1.0 REVISION NOTES INTRODUCTION AND PURPOSE Introduction Purpose CONTACT INFORMATION 3

Mediacom Upgrade/Splicing Procedures (based on original document from Corporate dated 4/16/98)

Lyndhurst Secondary Technology Package Addendum # Bid Date: Wednesday, August 30, 1:00PM. Items issued in this addendum:

Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab*

Product information 19" 1U HD Patch Panel 48xRJ45/s, Cat. 6A, gray, fully populated

Request for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS

Transcription:

1 General 1.1 Scope of work 1.1.1 The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the completion of the installation. 1.1.2 Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing the following operations recognized as necessary for the installation, termination, and labeling of all telecommunications infrastructure as described on the Drawings and/or required by these specifications. 1.2 Intent of the drawings and specifications 1.2.1 These Specifications, together with the Drawings accompanying them, are intended to depict the installation requirements necessary to support this Project. 1.2.2 Contractor shall furnish materials shown and/or called for on the Drawings but not mentioned in the Specifications, or vice versa, that are necessary for the installation and support of the described work, whether or not specifically called for in both. 1.2.3 Contractor shall provide incidental equipment and materials required for the completion of systems included in this contract whether or not specified or shown on the Drawings. 1.3 Communication 1.3.1 It is Purdue s expectation that the A/E of Record will work jointly with Purdue s Telecommunication representatives to address specific technical issues and Owner requirements. 1.3.2 All questions, deviations, comments concerning guideline(s) interpretation, content, and/or use must be submitted in writing to the Project Manager for approval. 1.3.3 No deviations from these guidelines shall be incorporated into the project without written approval from the Project Manager and Purdue Telecommunications representative. 2 Products 2.1 Copper, Fiber, and Coax Riser Cable Labels in TRs 2.1.1 Panduit #T050X000VPC-BK, 0.5 2.2 Copper, Fiber, and Coax Horizontal Cable Labels in TRs and behind faceplates 2.2.1 Panduit #S100X150VAC, 1.0 wide x 1.5 length, white, print-on vinyl label or Owner 2.3 Telephone 110-Block Labels in TRs 2.3.1 Panduit #T038X000VPC-BK, 0.38 2.4 Faceplate Labels at the PIC Location 2.4.1 Panduit #T038X000VPC-BK, 0.38 2.5 Patch Panel Labels in TRs 2.5.1 Panduit #C061X030FJC, 0.61 wide x 0.30 height, one-port identifier, white, adhesive, polyolefin label or Owner 3 Execution 3.1 All horizontal cable labeling 3.1.1 Cables shall be labeled with selflaminating marking tape, Panduit LS8 labeler or Owner approved equal labeling system. 3.1.1.1 Size of letters and numbers shall be no less than 5/16 high by 1/8 wide. 3.1.2 Horizontal voice and data cables at the BDF/IDF end cables shall be labeled with the information indicating termination of the opposite end of the cables. 3.1.2.1 This shall include room location and jack designation. 3.1.2.2 Place label on a visible part of cable within 12 of termination point for ease of identification after 3.1.2.3 All faceplate labeling shall be labeled left to right, top to bottom. A specific voice line shall always be labeled last in the series, unless a TV jack is present in which case the voice jack shall precede the TV jack. Examples: At the BDF/IDF end the 4-pair data cables for the 1st location in room 1137 would be labeled: 1137-A and 1137-B. At the BDF/IDF end the 4-pair voice cable for the 1st location in room 1137 would be labeled: 1137-1 3.1.3 Horizontal voice and data cables at the rooms cables shall be labeled 1-3 from termination Page 1 of 5

with the following: BDF/IDF TR room # - room # - Jack 3.1.3.1 Labels shall be visible by removing outlet cover plate. 3.1.3.2 For rooms with multiple outlet locations, identification would begin with the first receptacle to the left of the main entrance to the room and continuing clockwise around the room. Examples: 1106-1137-A, 1106-1137- B, 1106-1137-1. 3.1.4 Horizontal fiber cables at the BDF/IDF end shall be labeled with the information indicating termination of the opposite end of the cables. 3.1.4.1 Label shall include room location, fiber type ( S for singlemode, M for multimode), and jack designation. 3.1.4.2 Place label on a visible part of cable within 12 of termination point for ease of identification after Example: At the BDF/IDF end the 2- strand fiber cable for the first location in room 1137 would be labeled: 1137FOS-A with the FO indicating fiber optic cable and the S indicating single-mode fiber type. Note: Fiber is labeled in pairs. (Blue and Orange strands would be treated as jack A ) 3.1.5 Horizontal fiber cables at the rooms shall be labeled 4 from termination with the following: BDF/IDF Telecom room # - room # FO(S or M)- Jack Example: 1106-1137FOS-A, 1106-1137FOS-B. 3.1.6 The label shall be visible by removing outlet cover plate. 3.1.7 For rooms with multiple outlet locations, identification would begin with the first receptacle to the left of the main entrance to the room and continuing clockwise around the room. Note: Fiber is labeled in pairs. (Blue and Orange strands would be treated as jack A ) 3.2 CATV cables 3.2.1 CATV cables at the BDF/IDF shall be labeled at each end with the information indicating termination of the opposite end of the cables. 3.2.1.1 This shall include Cable system, room number, and cable number at opposite end. 3.2.1.2 Place label on a visible part of cable 12 from end of cable for ease of identification after Example: MRDH has a BDF TR (room B009A) and IDF TR (room 285S). In this case room 285S distributes cable to room 236SE. At the IDF end the horizontal cable from the room would be labeled: TV236SE-1. 3.2.2 CATV cables at the rooms shall be labeled 4 from termination with the following: BDF/IDF TR room # - TVroom # - Jack Example: 285S-TV236SE-1. This shall be visible by removing outlet cover plate. For rooms with multiple outlet locations, identification would begin with the first receptacle to the left of the main entrance to the room and continuing clockwise around the room. 3.3 Room numbers used for PIC labeling shall only contain preceding zeros when an alpha character precedes the zeros. Example: The PIC in room G002 would be labeled as G002-A/B/1 Example: The PIC in room 002 would be labeled as 2-A/B/1 3.4 Copper Riser Cable Labeling 3.4.1 All riser cables shall be labeled with self-laminating marking tape, Panduit LS8 labeler, Brady TLS2200 labeler, or Owner approved equal labeling system. 3.4.2 At the BDF and IDF, the copper riser cables shall be labeled at each end with the information indicating termination of the opposite end of the cables. This shall include building acronym and cable number and room location. 3.4.2.1 Place label on a visible part of cable close to wiring block for ease of identification after Example: LYLE has a BDF TR, room B036, and an IDF TR, room 1006. Page 2 of 5

At the IDF end the 1st cable would be labeled: LYLE01-B036 At the BDF end the 1st cable would be labeled: LYLE01-1006 Note: Multiple riser cables between the BDF and IDFs are to be labeled as the same cable. e.g. Riser cables FS01 consists of (2) 100-pair cables (FS01, 1-100; FS01, 101-200). The cable label along with the pair count shall be labeled at each end of the wiring blocks. 3.5 Fiber Riser Cable Labeling 3.5.1 All fiber optic riser cables shall be labeled at each end with the information indicating: Building Cable number FO indicating a fiber and opposite end of cable. o S shall be used after the FO to indicate the use of single-mode fiber. o M shall be used after the FO to indicate the use of multi-mode fiber. 3.5.2 Fiber type shall be labeled on the front of the fiber enclosure: SMF for single mode fiber; MMF for multimode fiber. 3.5.3 Verify cable number with a Purdue IT Infrastructure Services Representative before labeling. Example: In BDF room B098A, PHYS (Physics): PHYS01-FOM226 = the first 12-strand, multimode fiber riser cable to IDF room 226. Example: In BDF room B098A, PHYS (Physics): PHYS01-FOS226 = the first 12-strand, single-mode fiber riser cable to IDF room 226. 3.6 Copper Riser 110-Block Labeling 3.6.1 At the BDF and IDF, voice riser cables are terminated on their respective 110 blocks. Label only 1st and last pairs on each row of 110 blocks. Place cable number of riser cable on wiring block label in center of label. 3.7 Coax Riser Labeling (CATV) 3.7.1 At the BDF and IDF, CATV riser cables shall be labeled at each end with the information indicating termination of the opposite end of the cables. Example: At the IDF end in PHYS the 1st riser cable from the BDF would be labeled: TV01-B098A. At the BDF end the same cable would be labeled: TV01-226 3.8 Horizontal 110-Block Labeling (Critical Circuits) 3.8.1 At the IDF, voice horizontal cables are terminated on their respective S110 blocks, with pairs on the blocks labeled in ascending room number order. 3.8.2 All horizontal cables from same room should be terminated in sequential order on S110 blocks. Single 4-pair cables will be labeled with a room location and a jack designation. e.g. 1113-1 = a single voice jack in room 1113. 3.8.3 Size of letters and numbers on labels for 110 wiring blocks shall be no less than 3/8 high. 3.8.4 Horizontal Patch Panel Labeling (Data) 3.8.5 At the IDF, data horizontal cables are terminated on their respective patch panels, with jacks on the panels labeled in ascending room number order. 3.8.6 All horizontal cables from same room should be terminated in sequential order at the patch panels. 3.8.7 Size of letters and numbers on labels for patch panels shall be no less than 3/32 high by 1/16 wide. Example: Single 4-pair cables will be labeled with a room location and a jack designation. e.g. 1137-A = a single data jack in room 1137. 3.9 Faceplate Labeling: 3.9.1 At the rooms, the jacks will be labeled on the faceplates using the plastic insert to cover a printed identification tag with room number and proper jack designation as follows: 3.9.2 Jack designation: Data and VOIP = A through ZZ Traditional Voice and Critical Circuits = 1 through 999. Examples: 1195-A = 1st data jack in 1195-B = 2nd data jack in 1195-AA = 27th data jack in 1195-AB = 28th data jack in. Example: 1195-1 = 1st voice jack in Page 3 of 5

3.9.3 Size of letters and numbers on labels for faceplates shall be no less than 3/8 high. 3.9.4 At the rooms, the fiber jacks will be labeled on the faceplates using the plastic insert to cover a printed identification tag with room number and proper jack designation as follows: 3.9.5 Jack designation: Fiber = A through ZZ. Example: 1195FOM-A = 1st multimode fiber jack in 1195FOM-B = 2nd multimode fiber jack in 1195FOM-AA = 27th multimode fiber jack in 1195FOM-AB = 28th multimode fiber jack in. 3.9.6 At the rooms, the coax jacks will be labeled on the faceplates using the plastic insert to cover a printed identification tag with room number and proper jack designation as follows: Jack designation: TVrm#-1 Example: TV236SE-1, 1st coax jack in room 236SE 3.10 Wall Mounted Fiber Box Labeling: 3.10.1 All wall mounted fiber termination boxes shall be labeled with cable information on the inside of the fiber termination box door using manufacturer s label. 3.11 Equipment Frame Fiber Enclosure Labeling: 3.11.1 All equipment frame fiber enclosures shall be labeled with cable information on the labeling panel below the enclosure using manufacturer s label. 3.11.2 All frame labeling shall be coordinated with Purdue IT Infrastructure Services Representative prior to label placement 3.12 Wireless Access Point PICs: 3.12.1 At the BDF/IDF end, the PICs installed for wireless access points (AP) data horizontal cables shall be labeled with the information indicating termination of the opposite end of the cables. This shall include room location and jack designation. 3.13.1.1 Place label on a visible part of cable within 12 of termination point for ease of identification after Example: At the BDF/IDF end the 4- pair data cable for the WAP in room 1137 would be labeled: 1137AP-A and 1137AP-B 3.13.1.2 Size of letters and numbers shall be no less than 5/16 high by 1/8 wide. 3.12.2 At the rooms, the horizontal cables shall be labeled 4 from termination with the following: BDF/IDF TR room # - room #AP - Jack Note: The WAP PICs shall be labeled in each room starting from A/B. These PICs do not fall within the alphanumeric order of the normal PICs within the same room. 3.13 Special Labeling Installations 3.13.1 Contractor is responsible for contacting a Purdue IT Infrastructure Services Representative so that Purdue may provide instruction for labeling of elevator phones, fire alarms, ETS phones, Fiber Optic PICs, and other special circuits. Failure to contact a Purdue IT Infrastructure Services Representative to clarify labeling requirements may result in re-labeling at the cost of the contractor. Submission of a RFI is required to document that contact with a Purdue IT Infrastructure Services Representative was made. 3.13.2 Departmental cables where data is distribute within the same room and not from the BDF or IDF shall be labeled as follows: 3.13.2.1 At the remote equipment cabinet or enclosure, data horizontal cables are terminated on their respective patch panels, with jacks on the panels labeled in alphabetic order. 3.13.2.2 At the outlets, identification would begin with the first receptacle to the left of the main entrance to the room and continuing clockwise around the room. Example: Single 4-pair cable will be labeled with a jack designation. DPT- A = a single data jack within the room. DPT-B = next jack within the room. Place label on visible part of the cable within 4 of the 3.13.3 Departmental cables shall be labeled differently than cables distributed from the telecom room so they can easily be identified. Contact a Purdue IT Infrastructure Services Representative for special labeling and patch panel termination Page 4 of 5

instructions at least 48 hours prior to the start of labeling. 3.13.4 Above Ceiling PICs for applications other than wireless access points which are located above 6 AFF shall be labeled as room #AC - Jack and room # - Jack Example: At the BDF/IDF end the 4- pair data cable for the above ceiling data PIC in room 1137 would be labeled: 1137AC-A and 1137AC-B Note: The above ceiling PICs shall be labeled in each room starting from A/B. These PICs do not fall within the alphanumeric order of the normal PICs within the same room. 3.14 PIC Re-labeling 3.14.1 Contractor is responsible for relabeling all existing PICs that are moved or changed. This includes but is not limited to any PICs with rooms in which the room number has changed as part of the construction project. This also includes all termination hardware (110 blocks, patch panels, cables, and faceplates). 3.14.2 All PIC relabeling shall follow the guidelines within this section. 3.14.3 Existing identification shall be recorded and submitted with as-built documentation. 3.14.4 Old labels on the cabling, faceplate, and/or patch panel shall be completely removed and replaced with new labels when a PIC requires relabeling. Page 5 of 5