HVDC cable accessories

Similar documents
640 kv XLPE HVDC cable system

640 kv extruded HVDC cable system

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITHOUT METALLIC SCREEN

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Revision of Qualification Procedures for High Voltage and Extra High Voltage AC Extruded Underground Cable Systems

Protective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Description Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100

Description Set value in neutral conductor is synchronous with set value Ir of main pole. CSA 100. conductor. I r A 50-63

ECONOMICAL 36 kv CABLE SYSTEM FOR THE BELGIAN NETWORK

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

I r A Protection against direct contact Finger and back-of-hand proof to VDE 0106 part 100

TERMINATIONS AND JOINTS FOR XLPE-INSULATED kv MEDIUM VOLTAGE CABLES

Soft starter, 66 A, V AC, Us= 24 V DC, with control unit, Frame size N. Function Soft starter for three-phase loads, with control unit

HIGH VOLTAGE CABLE ACCESSORIES - Application, Design, Installation, Testing - Ivan Jovanovic G&W Electric Company

CLP s first 400kV XLPE cable application

KRF EMC Filters Installation, Operation and Maintenance Manual

Photovoltaic Module Installation Manual (IEC)

Medium Voltage 12/20 (24)kV NF C cable system. Xavier Brosse Luanda May 2009

LED MODULES READYLINE DL

Trends and Challenges of HV Cable Systems

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES

Filters for Power Lines (Low Leakage Current)

Photovoltaic Module Installation Manual (IEC)

Panel-mounting thermostats, type series EM

Bharat Heavy Electricals Limited HIGH PRESSURE BOILER PLANT, TIRUCHIRAPPALLI CONTROLS AND INSTRUMENTATION/FB

INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 FIRE PREVENTION FOR CABLES, CABLE TRAYS AND CONDUITS

Identification - electrical services

CONTACT-DUO-PROFILE. Contact-Duo-Profile overview

TeSys contactors. Model d. Type of contactor LC1- LC1- LC1- LC1- LC1-D115 & D09 D18 D25 D38 D40 D50 D95 LC1-D150 DT20 & DT25 DT32 & DT40

Joint paper: Feasibility and technical aspects of partial undergrounding of extra high voltage power transmission lines

I r A I i = I n x. Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX

7 Lighting Technology

Indoor Linear 80W Driver SI-C215280N2KR

Emerging Subsea Networks

AS09..S 3-pole Contactors - Spring Terminals

INTERNATIONAL TELECOMMUNICATION UNION DIGITAL SECTIONS AND DIGITAL LINE SYSTEMS DEFINITION OF TERMS RELEVANT TO OPTICAL FIBRE SUBMARINE CABLE SYSTEMS

Magnetic and Hydraulic-Magnetic Circuit Breaker

Pendant Light Fitting IEC Series 6470/2

Revision 2.0 Parts List Minor

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 PURPOSE 2.0 SCOPE 3.0 CODES, STANDARDS AND REFERENCES

An introduction to Kabeldon cable accessories kv

Revision 3.0 Parts List Salvador 1~, 3~

sequenza 1000/1250 al manuale di istruzioni instruction manual 1^ edizione, ottobre st edition october 1996

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

02/11/2015

Panel-Mounted Thermostat

LC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC

Revision 2.0 Parts List Minette 1~, 3~

with handle LIMOGES Cedex 1. DESCRIPTION - USE 3. DIMENSIONS Symbol: Technology: Use:. For controlling a load remotely via a switch 2.

JUMO extherm-at Type , Explosion-proof surface-mounted thermostat for zones 1, 2, 21, and 22

For Sales & Information, Call Toll Free: (888)

GV3P80 TeSys GV3P thermal-magn motor circuit breaker 70-80A EverLink

Amphenol. Amphenol-Tuchel Electronics GmbH. C 112 Series M12 - Connectors

ABB IEC International Pin and Sleeve

High Voltage Cables kv. Handling and Operating Instructions

EX-PROTECTED PORTABLE POWER SUPPLY UNITS

LED Driver Compact fixed output

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS

LC1D09FE7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A V AC coil

LIGHTING: ENCLOSED AND GASKETED AREA FLUORESCENT. Applications. Illustrated Feature. Certifications and Compliances

Modular pulse operated latching relay 16 A

Connecting cables for valves, round plug connectors Product range overview

Slot-type Photomicrosensor with connector or pre-wired models (Non-modulated) *1. configuration. Dark-ON/Light-ON

Guide for installers. METTLER TOLEDO MultiRange System solution analog Ex1. Hazardous area. Safe area

PHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series

Gamma instabus. Technical product information

Operating instructions

Ordering details. Approval. Classification

Climatic proofing Damp heat, constant, to IEC Damp heat, cyclic, to IEC

Mechanical flow switch for On/Off control

LED Driver Compact fixed output

ImproX (TRT) Twin Remote Terminal INSTALLATION MANUAL

Cable solutions for all environments. Scapa Cable Solutions

LED Driver Linear / area fixed output

Protective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A

USER MANUAL. WARNING Read the instructions before using the machine. EN (Original Instruction) / 1704

ES-Mega MegaBeans. Access Control System. User Manual. People in Motion

INSTRUCTION AND MAINTENANCE VIDEO MOTORE PROJECTION SCREEN

Illustrated Feature. Options

LED control gear Compact fixed output

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

EXPlora. Introduction

B1-00. SPECIAL REPORT FOR SC B1 (Insulated Cables) Walter Zenger. Special Reporter

Flygt Submersible Motor Cables

Cables for robot applications

with additional normally-open signalling contact l With integrated AS interface Safety at Work.

Safe, Accurate, and Repeatable

IndyGo Facility Upgrades Project 35671EE

Hinges with built-in safety multiple switch SUPER CFSW. Hinges and connections. IP67 RoHS PA

E2V Technologies CX2668A, CX2668AX Air-Cooled, Hollow Anode, Two-Gap Metal/Ceramic Thyratrons

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 872 LIGHT EMITTING DIODE TRAFFIC SIGNAL LAMP UNITS JULY 19, 2002

Type: NZMN1 A100 Article No.: Sales text Circuit breaker3p systems/cable prot. Ordering information Number of poles

LED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series

PRINCIPLES AND APPLICATIONS

Effective earthing of screened cables

3 Cleaning. 4 Technical data

DOME OPTIC SPLICE CLOSURE

SWA Cable BS6724 Steel Wire Armoured LSZH Eland Product Group A9L

Transcription:

^=r SVENSKA KRAFTNÄT SWEDISH NATIONAL GRID UNIT, BUSINESS AREA OUR REFERENCE TR14-02-5E DATE 2018-09-21 CONSULTATIÖNS NT, NB TECHNICAL GUIDELINE EDITION 1 APPROVED TD HVDC cable accessories This technical guideline describes the principal design and construction requirements Svenska kraftnät applies to HV accessories to be used in HVDC cable systems for submarine and underground installations. The guideline shall be used when purchasing and designing extruded HVDC cable systems. SvK4005E. v4.0, 2016-04-27

2 (13) Edition Change notes Date 1 First edition of this technical guideline 2018-09-21

3 (13) Content 1 References... 4 2 Definitions and abbreviations... 6 3 General... 6 3.1 Manufacturer s prequalification... 6 3.2 Lifetime... 6 3.3 Materials... 6 3.4 Performance... 6 4 Joints... 6 4.1 Factory joint... 7 4.2 Field joint... 7 5 Termination... 8 6 Link box... 11 7 Surge arresters... 12 8 Earthing blade... 13 9 Discharge resistor... 13 10 Testing... 13 11 Documentation... 13

4 (13) 1 References The cable design of cable accessories shall comply with requirements in the following references. TR14-02-2E TR14-02-3E TR14-03-1E TR01-12E TR01-13 TR 01-16 IEC TS 60815-4 IEC 62155 IEC 61462 IEC 60099-9 SS 421 01 67 SS-EN 60228 IEC 62067 IEC 60287 HVDC extruded cable HVDC mass-impregnated cable Earthing of HVAC and HVDC Cable Systems Self-Contained Surge Arresters 12-420 kv Stamnätsstationer jordning Skyltar i ställverk Selection and dimensioning of high-voltage insulators intended for use in polluted conditions Part 4: Insulators for d.c. systems Hollow pressurized and unpressurized ceramic and glass insulators for use in electrical equipment with rated voltages greater than 1 000 V Composite hollow insulators - Pressurized and unpressurized insulators for use in electrical equipment with rated voltage greater than 1 000 V - Definitions, test methods, acceptance criteria and design recommendations Surge arresters Part 9: Metal-oxide surge arresters without gaps for HVDC converter stations Dimensionering av utomhusställverk Vind- och islaster Conductors of insulated cables. Power cables with extruded insulation and their accessories for rated voltages above 150 kv (Um = 170 kv) up to 500 kv (Um = 550 kv) Test methods and requirements Electric cables - Calculation of the current rating

5 (13) IEC 60853 Cigré TB No 623 Cigré Recommendation Cigré TB No 496 Cigré TB No 490 Cigré TB No 194 Calculation of the cyclic and emergency current rating of cables Recommendations for mechanical testing of submarine cables ÉLECTRA No 189 Recommendations for tests of power transmission DC cables for a rated voltage up to 800 kv. Recommendations for Testing DC Extruded Cable Systems for Power Transmission at a Rated Voltage up to 500 kv Recommendations for testing of long AC submarine cables with extruded insulation for system voltage above 30 (36) to 500 (550) kv Construction, laying and installation techniques for extruded and self contained fluid filled cable systems

6 (13) 2 Definitions and abbreviations Definitions and abbreviations used in this technical guideline, as well as in all other TR14 documents, can be found in a separate document in the TR14 series, TR14-01-2E. 3 General 3.1 Manufacturer s prequalification Manufacturers shall have expertise in and substantial experience of designing, manufacturing and installing underground and submarine HVDC cables for the specified voltage level (or higher) and specified cable technology (extruded or MI). The manufacturer shall be able to present two reference projects as a basis for a prequalification. 3.2 Lifetime The design of cable accessories with respect to used materials, manufacturing techniques as well as electrical, thermal and mechanical stresses shall have the theoretical lifetime of at least 50 years. 3.3 Materials The materials used for delivery accessories must be of the same type and designation as for the qualification tests and type tests. The materials shall not be changed during the project. 3.4 Performance The cable accessories must fulfil the same electrical, mechanical and thermal performance requirements as the HVDC cable, including static and transient stresses and overloading. Requirements for HVDC cables are described in TR14-02-2E and TR14-02-3E. 4 Joints Sections of cables incorporating conductor joints must have the same mechanical robustness and handling characteristics as the cable. The cable conductors may not be joined by exothermic welding.

7 (13) The number of any type of joints in the final installed HVDC link must be minimised. 4.1 Factory joint A factory joint is defined as a joint made in the factory before armouring of the cable. The factory joints must be flexible and meet the same electrical performance requirements as for the cable. Sections of cables incorporating factory joints must have the same mechanical robustness and handling characteristics as the cable. This ability is to be proven in tests by the same mechanical and electrical performance and requirements as is valid for the cable. Sections of cable incorporating factory joints must have the same corrosion properties as the cable itself. Sections of cable incorporating factory joints must have the same water tightness properties as the cable itself, except that the joint itself does not need specific means for longitudinal water blocking. 4.2 Field joint Submarine cable A field joint is defined as a joint performed on an already wire-armoured cable and which is performed in the planned operation of jointing the consecutive cable loading lengths. Field joints may also be used for repairs, and are then referred to as repair joints. Field joints for extruded cables may be rigid. Rigid submarine joints may use parts from the pre-fabricated underground joints. Underground cable Field joints for extruded underground cables must be prefabricated. The earthed joints shall have screen separation. The remaining joints shall be used without screen separation. The design with screen separation must allow for sheath testing of cable sections after installation. Transition joint Transition joints are joints that connect cables with significant differences in design. For example, jointing an armoured submarine cable with underground cable is considered as a transition joint.

8 (13) Transition joint between submarine and underground cables requires a hang-off of the armour wires. 5 Termination The termination in this context is considered to consist of: the cable termination, support stands, foundation and all other necessary equipment including link box, earthing conductors and temporary grounding point, in order to have a complete operational installation. The design of the cable termination shall comply with the following conditions. Air temperature -40 +35 C Design wind velocity 34 m/s Ice layer thickness 20 mm Solar radiation 1000 W/m 2 The cable termination outer insulators must have a design and material appropriate and qualified for HVDC conditions (composite or porcelain). The colour must be uniform and coordinated with other insulators in the same yard. The insulators shall be maintenance free and shall not require regular cleaning. The design of porcelain insulators shall comply with IEC 62155. The design of composite insulators shall comply with IEC 61462. The profile of the insulators shall comply with IEC 60815-4 Section 10. The minimum Unified Specific Creepage Distance (USCD) for porcelain and composite insulators shall be according to Figure 1 and Table 1 below:

9 (13) Figure 1: USCD of insulators for HVDC cable terminations in different pollution areas in Sweden.

10 (13) Table 1: USCD of insulators for HVDC cable terminations in different pollution areas in Sweden. If a manufacturer presents positive service experience of similar cable termination in similar environment, lower creepage distance than proposed by technical guidelines could be considered. The termination shall be insulated from the support stand and shall be connected to earth by a separate earth conductor. All earthing connections including connections from the cable sheath and armouring shall have an electrical and mechanical design that meets any operation condition and failure conditions with respect to ohmic heating. Dimensioning of the earthing conductor shall be according to TR01-13. The top bolt of the terminations shall be equipped with a grounding ball-stud. It shall be mechanically robust to allow for connection of a grounding clamp with a grounding cable and allow for grounding using an insulated grounding stick from ground level. The grounding ball-stud shall be designed to withstand short circuit current of the link. The grounding ball-stud shall not disturb electric field distribution of corona rings. Corona rings shall be made of aluminium and shall not be covered/painted with any additional material. The cable termination is identified by the following data, which also shall be stated on the permanent rating plate: Rated continuous voltage pole-ground, U 0 (kv) Rated DC current, I 0 (A) Name of manufacturer Type designation and identification of the complete cable termination Year of manufacture

11 (13) Serial number The rating plate shall be made of corrosion resistant material; preferably stainless steel. The rating plate shall be attached at suitable location on the side of the metallic base of the termination insulation body. The cable terminations shall be marked with the signs according to TR 01-16. 6 Link box Link boxes shall be used for earthing purposes at earthed underground cable joint bays, transition joint bays and cable termination stands. The other joint bays shall have no link boxes. The link boxes shall allow for connecting the screens to local earth wires (insulated or not) from the permanent earthing system. The design of link boxes shall allow for screen separation in order to allow for sheath testing of cable sections. This shall allow for separation between the screens of the jointed cables, and separation between cable screens and the installed earth plane. It shall be possible to reassemble the initial earthing configuration in the link box after screen separation is no longer required. Earthed underground cable joint bays and transition joint bays shall be equipped with a buried link box. There shall be one link box for both cable poles in symmetrical monopole scheme. The link boxes for cable terminations shall be fitted on the termination steel stand. There shall be one link box for each cable termination. The underground link box shall have Intrusion Protection class of IP68. A stainless steel box with the bolted lid is required. The design of the underground link box shall allow reusing the gasket after opening the link box. The link box for installation on cable termination stand shall have Intrusion Protection class of IP54. The construction of the link-box shall prevent water condensation inside. A stainless steel box with the lockable lid on hinges is required. All incoming link cables into a link box shall be marked with nametags allowing identifying to which joint screens they are connected. The terminals in the link box shall be logically arranged and consistent in all link boxes (e.g. first link-cable is from positive joint west side, second link-cable from positive joint east side, etc.).

12 (13) A sign shall be attached on the outside of the underground link box lid. The sign shall be according to the example below and shall contain the following: Electric hazard sign Text Varning! Risk för farlig potential. Potentialjorda linkbox med närliggande delar av ledande material och omgivande mark innan arbetet påbörjas Svenska kraftnät s logo Svenska kraftnät s Littra designation of the cable link Joint pit designation The markings and signs shall have yellow background and black text. The markings shall be made from weather-proof material and shall have the life-length as the cable system. Figure 2: Example of a link-box sign. 7 Surge arresters Every cable termination shall be protected from Switching (SI) and Lightning (LI) impulses with surge arresters. In some cases, if it is found applicable, Svk may relieve from LI protection requirement. Surge arrester design shall follow TR01-12 in applicable parts and IEC 60099-9.

13 (13) The surge arrester Protection Level (PL) shall be calculated based on the cable system Withstand Voltage (WV). The relation between the cable system withstand voltage and surge arrester protection level for SI and LI shall be according to the following equations: SIWV = 1,15 SIPL LIWV = 1,15 LIPL 8 Earthing blade At each cable termination an earthing blade shall be installed enabling safe earthing before opening of the cable circuit. 9 Discharge resistor The cable manufacturer shall state if the cables at floating HVDC potential at SIPL can be discharged instantaneously by direct grounding or a discharge resistor is needed/preferred. In case discharge resistor is needed/preferred the cable manufacturer shall state the safe discharge duration. 10 Testing Testing of HVDC cable systems and accessories is covered in Svenska kraftnät technical guideline TR14-04-1E. 11 Documentation The design of accessories, calculations, life-time estimations, testing etc. shall be documented according to document list described in TR08-05. Documentation shall comply with requirements in TR08-01 and TR08-02.