Continuous Currents. When inspectors see a photovoltaic (PV) power system. through Curious Cables. by John Wiles

Similar documents
Cambria County Association for the Blind and Handicapped 175 Industrial Park Road Ebensburg, PA Prepared for: Prepared by:

Power and Control T YPE BY RAVI GANATR November/December IAEI NEWS

Photovoltaic Module Installation Manual (IEC)

IndyGo Facility Upgrades Project 35671EE

Photovoltaic Module Installation Manual (IEC)

System 500. Non-fire-rated, mineral insulated copper sheathed wiring cable

Selecting Cables for Power over Ethernet

SECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.

Safety Codes Council Conference Banff C Panel Discussion

Sunny Boy 700U SOLARTECHNOLOGY. Installation Guide. Photovoltaic, Grid-Tied String Inverter

CHAPTER 14 WIRING SIGNALS AND LIGHTING FIELD GUIDE Wiring Requirements WIRING

How to Implement PoE in Your Harsh Industrial Environment

Target Interface / Construction Compliance Inspection Checklist

Report on Comments June 2013 NFPA 70

IEEE-SA SCC-18 Report by Representatives to NFPA NEC CMP-6 January 6-8, 2010 on Actions Taken on Proposals by CMP-6 for NEC 2011 ROC Prepared by

INSTALLATION INSTRUCTIONS RGB / RGBW 24V LED TAPE

Sunny Boy 1100U SOLARTECHNOLOGY. Installation Guide. Photovoltaic, Grid-Tied String Inverter

ICS Digital Menu. Installation Guide Version 1.1

INSTALLATION AND OPERATION M

PRELIMINARY Sunny Boy 240-US

File E Project December 11, 2013 REPORT DRIVERS FOR LIGHT-EMITTING DIODES ARRAYS MODULES AND CONTROLLERS

SECTION INTERCOMMUNICATIONS AND PROGRAM SYSTEMS

Fiberglass - Technical Data

SITE All work shall be performed at Center Park Substation (1895 Kernan Blvd, Jacksonville, Fl ). DATE: 04/03/2018

Next Generation PoE Standards and Codes Update. Frank Straka Panduit Corporation

Cellular Signal Booster



SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS

MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

SECTION COMMUNICATIONS HORIZONTAL CABLING

5-in-1 Cable Tester User Manual Model

Ultra Quiet Series Electric Air Handler

Instruction Manual MODEL RSP SANITARY ELECTRONIC PRESSURE TRANSMITTER

FORENSIC CASEBOOK. By Bob Huddleston, Eastman Chemical Co. One of the most common. reasons for marriage failure

Installation Manual SaVi Note Underwater LED Light

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

Errata NFPA 70. Proposed 2014 Edition

INSTALLATION INSTRUCTIONS MODEL VSBX-236 LED 3 X 8 INDOOR SCOREBOARD

SATRI AMPLIFIER AMP-51R. Owner s Manual

SECTION 5900 TRAFFIC SIGNALS CITY OF LEE S SUMMIT, MISSOURI DESIGN CRITERIA

SECTION 7 -- CROSS-CONNECT SYSTEMS

INSTALLATION INSTRUCTIONS FOR. MODEL 2230LED

The Chan-L-Wire Pro Series Lighting Distribution

INSTALLATION INSTRUCTIONS FOR

Identification - electrical services

FLUID VIEW 12V LED TAPE LIGHT

STRUCTURED CABLE SYSTEM (SCS)

WLB SERIES HID Lighting for Hose Down Applications

Multi-Channel Passive Transceiver Hubs Installation Sheet

INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 FIRE PREVENTION FOR CABLES, CABLE TRAYS AND CONDUITS

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITHOUT METALLIC SCREEN

MODELS USIX-024 AND USIX-120 INSTRUCTION SHEET FOR FEDERAL SIGNAL UNISTAT STATUS INDICATOR MODEL USIX

SPECIAL SPECIFICATION 6559 Telecommunication Cable

Effective earthing of screened cables

RoHS. Atma-Sphere Music Preamplifier. model P-2 OWNER'S MANUAL. Please study this document carefully before using equipment

ACTIVE IF SPLITTER/COMBINER UHP-IFS

Installation. SAPTF33xx-1xx in the Network. Standard Configuration

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

DS1 Cross-Aisle Panel

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

DISTRIBUTION AMPLIFIER

1995 Metric CSJ SPECIAL SPECIFICATION ITEM 6031 SINGLE MODE FIBER OPTIC VIDEO TRANSMISSION EQUIPMENT

SINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS

READ THESE INSTRUCTIONS COMPLETELY AND CAREFULLY

HelioSentry Installation & User s Guide (Also Contains Instructions for the SolarSentry )

Site Installation Model MP-8433

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School

TR6102HD HDTV/DVD/COMPONENT VIDEO TO RGBHV TRANSCODER USER S GUIDE

SPECIAL SPECIFICATION 1291 Fiber Optic Video Data Transmission Equipment

ELECTRICAL INCIDENT REPORT BUSHFIRE NEAR 22 NUKKLGUP LOOP YALLINGUP WESTERN AUSTRALIA 5 JANUARY Report prepared by: EnergySafety WA EIS

3 Cold Shrink Products

Site Installation Model MP-8424

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 872 LIGHT EMITTING DIODE TRAFFIC SIGNAL LAMP UNITS JULY 19, 2002

What is SnoCam? SnoCam Installation Guide. SolarVu

TECHNICAL SUPPORT , or FD151CV-LP Installation and Operation Manual 15.1 Low Profile LCD

english SGC inverter series hf transformer input voltage up to 800 V touch screen built-in data loggers

Power Injector 1520 Series

RGB 5050 PixelControl LED Super Flat Rope Part Numbers: PSFR-RGB-W-20

Building + Mounting Learn Rooftop Basics

24 Volt RGB/RGA Super Flat LED Rope Part Numbers: SFR-RGB-W, SFR-RGB-B, SFR-RGA-W, SFR-RGA-B

Monochrome Video Monitors

Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab*

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

GenSPEED Category 5e Cables 3

BROCHURE MC LUMINARY CABLES

PVI 3000/PVI 4000 PVI 5000/PVI 5300

AE-341 SERIES PROCESS INDICATORS 2 TO 6 DIGITS 0-20 MA, 4-20 MA, 0-5V, OR 0-10V SCALED INPUT

File E Project December 11, 2013 REPORT DRIVERS FOR LIGHT-EMITTING DIODES ARRAYS MODULES AND CONTROLLERS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SPECIAL SPECIFICATION 6911 Fiber Optic Video Data Transmission Equipment

TB806AUX Class E A / Cat.6A UTP Keystone Jack (Auto press-fit)

Modular pulse operated latching relay 16 A

Operating Manual. Automated Gear. Apollo Design Technology, Inc Fourier Drive Fort Wayne, IN USA

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Warning and Safety Information. FCC Information

SPECIAL SPECIFICATION 8540 Telecommunication Cable

APPLIANCES /// MTA, CST-100 II AND SL-156 CONNECTORS. CONNECTORS/ APPLIANCES MTA, CST-100 II and SL-156 Connectors

Transcription:

PV Wiring: Continuous Currents through Curious Cables by John Wiles When inspectors see a photovoltaic (PV) power system for the first time, they will usually be faced with a type of wiring method not normally seen in residential or commercial electrical systems. That wiring method is the use of single-conductor exposed cables to connect the individual PV modules together in the PV array and is permitted by NEC 690.31. Exposed, single-conductor wiring is usually seen only in older neighborhoods as aerial feeders between buildings and in obsolete (but still with us) knob-and-tube wiring systems. A Little History PV modules, for the most part, are currently manufactured (and listed) with attached leads with connectors attached [see photo 1/inset 1]. The leads are 3 4 feet long and have polarized connectors, one for the positive output and one for the negative output. Historically, this exposed wiring method was allowed into the Code in 1984 because PV modules at that time had single, widely spaced output terminals diagonally opposed at opposite corners on the back of the modules [see photo 2/inset 2]. It was deemed too difficult (and wasteful) to use one of the conventional wiring methods to make connections to these single terminals when many of the connections were routed to another single terminal on an adjacent module only a few inches away. Subsequent to the early days, where exposed terminals and insulating caps were used, junction boxes were added at each end of the module, one for the positive and one for the negative contact [see photo 3/inset 3]. In the 1990s, both positive and negative contacts were placed in a conduit-ready junction box at one end of the modules[see photo 4/inset 4]. These types of modules with conduit-ready junction boxes are still available on special order from a few manufacturers for use where local codes require the use of conduit, particularly in commercial installations. 20 IAEI NEWS July.August 2007 www.iaei.org

Photo 1. Modern PV module with leads and connectors Inset 1. Sealed terminal box and MultiContact connectors Workmanship Is Important The length of the leads attached to PV modules is sufficiently long to allow the modules to be mounted side by side in either portrait or landscape orientation. In either orientation, but particularly in the portrait configuration, the excess length of the leads should be gathered and secured to the module frames or mounting racks to provide some degree of mechanical protection from wind, rain, snow and ice. In no case should the single conductor leads touch the roof or be allowed to move in the wind. This could cause the cable insulation to be abraded or place strain on the module terminal boxes where the cables attach. Conductor Types The conductors permanently attached to the PV module are part of the listed module assembly and, presumably, Underwriters Laboratories (UL) has verified that the cables meet the necessary safety requirements. In most cases, the cables will be marked USE-2 or USE-2/ RHW-2, and some also will be marked Sunlight Resistant indicating better ultra-violet capability than the basic USE-2, which is tested for UV resistance but not marked as such. PV modules are connected in series (called strings) and, after making anywhere from 4 to 24 series connections, the positive and negative conductors at the ends of the string are some distance apart. In order to bring these two points to a common location, single conductor wiring is again used. Although USE, SE, and UF cables are allowed by Section 690.31, the installer typically uses a USE-2 or USE-2/RHW-2 cable to get both the negative and positive negative conductors to a common junction point in the PV array. At this point, the exposed conductors are transitioned, using a junction box to one of the common wiring methods found in chapter 3. Don t be misled by extraneous markings like MSHA and DLO as shown on the cable in the lead-in picture. This sunlight-resistant RHW-2 cable is not allowed by Section 690.31 for exposed, fieldinstalled, PV module interconnections. Since the environment is hot and wet on exposed roofs, usually THHN/THWN-2 or RHW-2 conductors are installed in conduit. EMT is commonly used and, where allowed by local codes, RNC may be used. In some cases, LNFC has been used and when properly attached to the supporting structure may be acceptable. A discussion of the routing of this output circuit may be found in the Perspectives on PV in the May/June 2007 IAEI News. In NEC-2008, cable types USE, UF, and SE are being removed from Section 690.31 due to temperature limitations and availability in the needed sizes (10, 12, and 14 AWG) for the module interconnections. A new PV conductor will appear in NEC-2008 in Section 690.31. It is mentioned in the comment for Section 690.35 in the 2005 NEC Handbook. This is a single-conductor cable designated PV Wire, Photovoltaic Wire, PV Cable, or Photovoltaic Cable. This cable will have an insulation that is thicker than the insulation on USE-2 (conduit fill will have to be calculated), it will be marked Sunlight Resistant, and it will have the necessary flame retardant and smoke properties that will allow it to be used inside buildings in conduit. This cable will be one of the wiring methods required when the PV array is operated in an ungrounded manner in PV systems that use the new transformerless inverters. See Section 690.35 for the current requirements for such systems. www.iaei.org July.August 2007 IAEI NEWS 21

any field-installed cables should be 1.56 times the module short-circuit current (Isc) after the conditions of use are applied. In most cases, the factory-attached cables have sufficient ampacity. However, in very hot climates, the ampacity calculations should be checked. The ampacity of these conductors in free air should be evaluated using Table 310.17. Inset 2. Exposed terminal minus the insulating cover Equipment Grounding Conductors Equipment grounding conductors connected to the PV module frames should be sized at 1.25 times the module short-circuit current (Isc). On large PV arrays, where fuses are used to protect these conductors, Table 250.122 can be used. This will result in a smaller, but adequate, equipment-grounding conductor than will be calculated using the 1.25 Isc value. INSPECTION AREAS REQUIRING ADDITIONAL ATTENTION Inspectors have seen the following problems in noncode-compliant installations. Common Sense and Durability The exposed, single-conductor cables should only be used for module interconnections. They should not be run across the roof away from the PV array, but should be transitioned at or under the PV array to another wiring method found in chapter 3 that is appropriate for the conditions of use. Photo 2. Early (1980s) PV module with exposed, widely spaced terminals A Typical System The three-wire diagram for a typical residential PV system is shown in figure 1. The modules are connected in series with the 12 AWG leads with polarized connectors that are permanently attached at the factory. A 12 AWG USE-2/RHW-2 conductor is used to get the negative end of the string back to a junction/pull box where it and the positive lead are transitioned to 10 AWG THHN/ THWN-2 conductors in a ¾-inch EMT conduit. Conductor Ampacity The module short-circuit currents may range from 1 amp to about 17 amps (in unusual cases). The larger 300+ watt PV modules have short-circuit currents approaching 12 amps. The ampacity of the attached and Cables Like It Hot The modules may operate up to 80 C and wiring touching or near the backs of these hot modules should have 90 C-rated insulation. The outdoor environment is a wet environment so -2 conductors should be used that have a 90 C, wet rated insulation both in and out of conduit. Conduits in sunlight on roofs are going to be hot. See fine print note 2 for Section 310.10 in NEC-2005, and also see proposals in this area for the 2008 NEC. An added 17 C to the average high temperature will be the minimum addition to the ambient temperature in NEC- 2008. In areas where average high ambient temperatures of 40 C (104 F) are experienced, then conduits are going to be operating at least at 57 C. Appropriate temperature deratings may dictate the use of larger conductors than have been used previously to accommodate the reduced ampacity at the higher temperatures. Grounding Critical Module grounding deserves at least a book by itself. With PV modules serving as power sources that will be 22 IAEI NEWS July.August 2007 www.iaei.org

Photo 3. Older (1990s) PV module with two junction boxes generating hazardous voltages for the next 40 50 years, individual module grounding is a critical issue. This is particularly important since the module frames are difficult-to-ground aluminum and should remain solidly grounded for the life of the module. A ground fault in a module could energize an ungrounded frame at dangerous voltages if the module were still connected to the rest of the PV array while the module is being removed or otherwise serviced. The old, old Code requirement of Inset 3. Junction box single polarity connecting the ground first and disconnecting it last must certainly apply to PV modules. Module Protective Fuse The backs of all listed PV modules are marked with a value of a Maximum Series Fuse or similar wording. The overcurrent device, where required and used, protects the internal module conductors from damage from overcurrents that could be forced through the module from external sources. While many residential PV systems do not require overcurrent protection in the dc circuits, the larger commercial systems usually do require dc overcurrent protection. This will be the subject of another Perspectives on PV. The Code requires that any overcurrent device installed in the output of a module be rated for 1.56 Isc. There are a few modules being made (for unknown reasons) that have a maximum series fuse value of less than 1.56 Isc. This poses a Code quandary. Section 690.8 says use a fuse rated at 1.56 Isc, but Section 110.3 says to follow the product labels. Any inspector seeing such a module should report the problem to UL through the AHJ channel on the UL web site. Photo 4. Special order PV module with conduit-ready junction box Inset 4. Junction box, both polarities Summary PV module wiring can indeed pose questions. However, the basic requirements can be found in Article 690 and www.iaei.org July.August 2007 IAEI NEWS 23

Figure 1. Residential PV system, 3-wire schematic as soon as those curious currents travel away from the PV array, they are contained in wiring systems familiar to all inspectors. Don t forget, it is a hot and wet environment. For Additional Information If this article has raised questions, do not hesitate to contact the author by phone or e-mail. E-mail: jwiles@ nmsu.edu Phone: 505-646-6105 A color copy of the latest version (1.6) of the 150- page, Photovoltaic Power Systems and the 2005 National Electrical Code: Suggested Practices, published by Sandia National Laboratories and written by the author, may be downloaded from this web site: http://www. nmsu.edu/~tdi/photovoltaics/codes-stds/pvnecsug- Pract.html The Southwest Technology Development Institute web site maintains a PV Systems Inspector/Installer Checklist and all copies of the previous Perspectives on PV articles for easy downloading. Copies of Code Corner written by the author and published in Home Power Magazine over the last 10 years are also available on this web site: http://www.nmsu.edu/~tdi/photovoltaics/codes-stds/codes-stds.html The author makes 6 8 hour presentations on PV Systems and the NEC to groups of 40 or more inspectors, electricians, electrical contractors, and PV professionals for a very nominal cost on an as-requested basis. A schedule of future presentations can be found on the SWTDI web site. John Wiles works at the Institute for Energy and the Environment (IEE) (formerly the Southwest Technology Development Institute) at New Mexico State University. SWTDI has a contract with the US Department of Energy to provide engineering support to the PV industry and to provide that industry, electrical contractors, electricians, and electrical inspectors with a focal point for Code issues related to PV systems. He serves as the secretary of the PV Industry Forum that submitted 42 proposals for Article 690 in the 2008 NEC. He provides draft comments to NFPA for Article 690 in the NEC Handbook. As an old solar pioneer, he lived for 16 years in a stand-alone PV-power home in suburbia with his wife, two dogs, and a cat permitted and inspected, of course. He is installing a new PV system on his home that is utility-interactive with a full-house battery back up system using a New Mexico Homeowner s Electrical Permit. This work was supported by the United States Department of Energy under Contract DE-FC 36-05-G015149 24 IAEI NEWS July.August 2007 www.iaei.org