Revision of Qualification Procedures for High Voltage and Extra High Voltage AC Extruded Underground Cable Systems

Similar documents
ECONOMICAL 36 kv CABLE SYSTEM FOR THE BELGIAN NETWORK

Medium Voltage 12/20 (24)kV NF C cable system. Xavier Brosse Luanda May 2009

CLP s first 400kV XLPE cable application

640 kv XLPE HVDC cable system

CHAPTER 3. HV and EHV Cable System Aging and Testing Issues

640 kv extruded HVDC cable system

220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX

DEVELOPMENT OF A 270 kv XLPE CABLE SYSTEM FOR HVDC APPLICATION

TERMINATIONS AND JOINTS FOR XLPE-INSULATED kv MEDIUM VOLTAGE CABLES

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES

High Temperature Operation of Extruded Distribution Cable Systems. White Paper

HIGH VOLTAGE CABLE ACCESSORIES - Application, Design, Installation, Testing - Ivan Jovanovic G&W Electric Company

HVDC cable accessories

Joint paper: Feasibility and technical aspects of partial undergrounding of extra high voltage power transmission lines

Trends and Challenges of HV Cable Systems

High Voltage Cables kv. Handling and Operating Instructions

Cable installation guidelines

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITHOUT METALLIC SCREEN

EE028: Practical High Voltage Cable Jointing and Termination

B1-00. SPECIAL REPORT FOR SC B1 (Insulated Cables) Walter Zenger. Special Reporter

Cable solutions for all environments. Scapa Cable Solutions

2004 SC B1 PROGRESS REPORT (INSULATED CABLES)

XS_-EU. M8 and M12 Sensor Connectors. Ordering Information

Flygt Submersible Motor Cables

Condition Monitoring Program of HV Cable Systems

3M Super 23 Electrical Tape

ANALYSIS OF FAILURE IN POWER CABLES FOR PREVENTING POWER OUTAGE IN ALEXANDRIA ELECTRICITY DISTRIBUTION COMPANY IN EGYPT

INSULATION CONDITION OF DRY-CURED XLPE CABLES MEASURED OVER A PERIOD OF 13 YEARS

TA0311 TECHNICAL ARTICLE High Temperature Electronics 1 Introduction 2 Why the need for high-temperature semiconductors?

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 PURPOSE 2.0 SCOPE 3.0 CODES, STANDARDS AND REFERENCES

SWA Cable BS6724 Steel Wire Armoured LSZH Eland Product Group A9L

This document is a preview generated by EVS

Diagnostic & Testing Services

Flame-retardant cable for

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

POLICY & APPLICATION GUIDE FOR 11kV POLYMERIC CABLES

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

Low Loss RG 402 Equivalent

System solutions: Partial discharge measurement and monitoring systems.

Description Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100

PEM1124ENG ENGLISH. STK TERMINATION KIT FOR PLASTIC CABLE WITHOUT ARMOURING 1 kv STKR TERMINATION KIT FOR PLASTIC CABLE WITH ARMOURING 1 kv

3M Sensored Termination (15 kv) QX-T15I-vi1-E

ENGINEERING COMMITTEE Interface Practices Subcommittee. ANSI/SCTE (Formerly IPS SP 001)

D-COAX, Inc. D-COAX d086 Series Cable Pair. High Frequency, Skew Matched, Phase Stable Cable Pair (65 GHz)

LED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series

LED MODULES READYLINE DL

Protective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A

3 Cold Shrink Products

SECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.

PEM1126ENG ENGLISH STPKR. TERMINATION KIT FOR PAPER CABLE WITH LEAD SHEATH 1 kv INSTALLATION INSTRUCTION

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

LEGEND POWER SYSTEMS

SUMITOMO PRODUCT SPECIFICATION. FutureFLEX. TCxxMSOS-2 HIGH PERFORMANCE OSP TUBE CABLE SERIES WITH GALVANIZED STEEL INTERLOCKED ARMORING

Aging test: integrated vs. non-integrated splices shield continuity systems.

HOG 86. The incremental HeavyDuty encoder for highest demands

PRODUCT CATALOGUE 2016

Australian/New Zealand Standard

3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT

SUMITOMO PRODUCT SPECIFICATION. FutureFLEX. TCxxMSOS DIELECTRIC HIGH PERFORMANCE OSP TUBE CABLE SERIES

Bharat Heavy Electricals Limited HIGH PRESSURE BOILER PLANT, TIRUCHIRAPPALLI CONTROLS AND INSTRUMENTATION/FB

Cables for robot applications

Product Classification. Dimensions. Environmental Specifications. General Specifications. Material Specifications. Mechanical Specifications

FP_B.1_BorougePte Ltd _Medium voltage XLPE cable for long and reliable service life

C I R E D 19 th International Conference on Electricity Distribution Vienna, May Transition Joints Behaviour. Paper 457 INTRODUCTION

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Underground Cable Diagnostic Testing Utilizing Partial Discharge Technique

Emerging Subsea Networks

HYL-035D0850G103. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 FIRE PREVENTION FOR CABLES, CABLE TRAYS AND CONDUITS

Micro duct Cable with HDPE Sheath for Installation by Blowing

Gamma instabus. Technical product information

Description Set value in neutral conductor is synchronous with set value Ir of main pole. CSA 100. conductor. I r A 50-63

Scotch Heavy Duty Vinyl Electrical Tape 22

Single output models feature wide-range output adjustability to meet a wide variety of standard and user-specific output voltage requirements.

NC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM

ETSI ES V1.1.1 ( )

Optical Fibre Cable Technical Specification. Duct Cable GYFTY-24,48,72,144,216B1.3

ENGINEERING COMMITTEE

PRODUCT INFORMATION NYY-J, NYY-O

UNDERGROUND CONSTRUCTION MANUAL MATERIAL DATA

GSCC004 Rev. 1 23/02/2018

Catalogue Ignitors and power switches for HID

Amphenol. Amphenol-Tuchel Electronics GmbH. C 112 Series M12 - Connectors

Identification - electrical services

Operating instructions

D-COAX, Inc. D-COAX Male-Female 1501 Series Cables and Cable Pairs. High Frequency, Skew Matched, Phase Stable Cable Pair (40 GHz)

INTERNATIONAL STANDARD NORME INTERNATIONALE

HID control gear Electronic. PCIS, PCS outdoor FOX B011 PCI outdoor. Ordering data. Circuit power1. tc/ta for 60,000 h For luminaires with 1 lamp

Connecting cables NEBS, for sensors

SERIES BNC 50, COAXIAL MINIATURE CONNECTORS

TN0885 Technical note

SPECIAL SPECIFICATION 6559 Telecommunication Cable

Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

Road cables. The foundation for a reliable traffic infrastructure.

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

ENGINEERING COMMITTEE Interface Practices Subcommittee SCTE Test Method for Cable Weld Integrity

Undergrounding HV and EHV Window of Opportunity Opens

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

Generator protection relay

8D with High Frequency Coaxial Contact

Transcription:

Revision of Qualification Procedures for High Voltage and Extra High Voltage AC Extruded Underground Cable Systems Tutorial vor the ICC Educational Session on November 11 2009 in Scottsdale, AZ by Wim Boone 2/5/2010 1

Table of contents Introduction Long duration test EHV (150-500kV) Extension of prequalification test (EQ) Long duration test HV (30-150kV) Functional Analysis Conclusions 2/5/2010 2

Introduction Innovative changes are necessary to improve the product, to remain competitive There is little incentive for the manufacturer to make improvements, if the expensive long term testing has to be repeated CIGRE WG B1-06 was asked to provide recommendations to qualify a modification to a cable system, without making the full set of tests, which are currently specified in standards WG B1-06 has published Technical Brochure 303 in 2006 2/5/2010 3

Terms of reference WG B1-06 AC extruded cables 30-500 kv - Review and complete qualification procedures (type tests, PQ tests) - Prepare innovative solutions, without jeopardizing the system reliability - Evaluate whether present long term tests can be replaced by shorter ones - Examine if a modification to a cables system can be qualified without making the full set of tests - The conclusions have been offered to IEC for further standardisation 2/5/2010 4

Reference standards IEC 62067, October 2001,Power cables with extruded insulation and their accessories for rated voltages above 150 kv (Um=170kV) up to 500 kv (Um=550kV)-Test methods and requirements IEC 60840, April 2004,Power cables with extruded insulation and their accessories for rated voltages above 30 kv (Um=36kV) up to 150 kv (Um=170 kv)-test methods and requirements

PQ tests Focus on PQ tests, because of costs and time PQ test recommended by CIGRE and incorporated in IEC 62067 Only those manufacturers whose products have passed the PQ tests have been allowed to participate in subsequent EHV cable projects 2/5/2010 6

Experience with HV cable syst. In general experience is good A new generation HV XLPE cables slim design is developed with similar technology and higher operating stresses, as high as EHV XLPE cables The experience with slim design HV cables is still limited 2/5/2010 7

Experience with EHV cable syst. For more details (see tutorial on service experience) XLPE cable is at present preferred transmission type cable (availability, leakage) Experience with EHV XLPE cable is still limited, although application of EHV XLPE cable is fast growing (see next table) 2/5/2010 8

Application of EHV extruded cable systems. Country Rated Voltage /kv Denmark (Copenhagen:South Denmark (Copenhagen:North Conductor size/mm² Route lengths/ km 400 1600 Cu 22 1997 400 1600 Cu 12 1999 Germany (Berlin/ BEWAG 400 1600 Cu 6.3 1998 Germany(Berlin/ BEWAG 400 1600 Cu 5.5 2000 Japan (Tokyo) 500 2500 Cu 39.8 2000 UAE (Abu Dhabi) 400 800 Cu 1.3 2000 Spain (Madrid) 400 2500 Cu 12.8 2004 Denmark (Jutland) 400 1200 Al 14.5 2004 United kingdom (London) 400 2500 Cu 20 2005 The Netherlands (R dam) 400 1600 Cu 2.25 2005 Commissionning year Austria (Wienstrom) 380 1200 Cu 5.2 2005 2/5/2010 9

Long duration test EHV cable systems Long duration test=pq test was introduced to compensate for lack of experience with EHV XLPE cables The PQ tests checks the performance under realistic conditions: - Design concept - Long term performance (heat cycling +overvoltage) - Installation aspects 2/5/2010 10

Long duration test PQ test shows in particular critical position of the joints; impulse test at the end of the test Although manufacturers are learning from problems in early PQ tests results, PQ test is considered to be necessary 2/5/2010 11

Main items of PQ test to be considered for revision Range of approval in relation with calculated nominal stresses The duration of heating cycle voltage test PD tests Procedure in case of component failure during test Final control at the end of the test 2/5/2010 12

Range of approval New PQ test has to be performed in case of higher system voltage with higher insulation screen stress than in the qualified system 2/5/2010 13

Heating cycle test The duration of the voltage application (1.7 Uo) is an important factor because of accessory failures At present the duration is 180 heat cycles (8/16) up to 95 gr.c max.(with large conductor and installed in the soil 1 cycle takes more than 1 day) The duration of the voltage application should remain 1 year=8760h 2/5/2010

PD tests Reduction of insulation thickness may result in considerable higher stress at defects, voids, fissures, increasing risk of PD activity Consequently the size of defects has to be reduced accordingly PD tests are therefore a necessary tool as an early warning for degradation and subsequent failure 2/5/2010 15

System component failure Repair/replacement of a failed accessory during test is allowed Repair of cable failure is not allowed, unless failure has been caused by external incident or the cable has already been prequalified 2/5/2010 16

Final control test After the test has been completed an impulse test has to be performed on the whole test loop The whole test loop has to do with the desirability to check the insulating properties at the interfaces in the accessories and the cable. An impulse test on the cable only, as was done in the past, is not sufficient 2/5/2010 17

Changes in a prequalified system What changes are substantial in such a way that the PQ test has to be repeated? Functional Analysis Method correlates the function performed by a certain item to the test required to check that function. 2/5/2010 18

Changes in a prequalified syst.(2) Some small changes do not require the repetition of a full PQ Some major changes require the repetition of the full PQ test Some changes require the performance of a simplified long term-test, called Extension of Prequalification test (EQ) 2/5/2010 19

Situations of changes in a prequalified system The exchange of components (cable or accessories), already prequalified in systems from different manufactures or from different plants from the same manufacturer The modification to cable components The modification to accessory components within the same family 2/5/2010 20

Evaluation of changes in a prequalified system. Cable and/or accessory Already qualified on another cable system within the same or higher insulation screen stress Already qualified on another cable system with a lower insulation screen stress (calculated) or not qualified cable non electrical Type Test (TT) + Extension of qualification test (EQ) Joint EQ TT + PQ Metal enclosed Termination Outdoor Termination EQ EQ electrical and non electrical TT + Prequalification Test (PQ) TT + PQ TT+PQ 2/5/2010 21

Tests because of modifications to a cable in a prequalified EHV cable system Component Modification Proposed test Conductor Copper to Aluminium Larger cross-section TT and PQ TT Insulation Change of base resin Change in cross linking package (peroxide/antioxidant) Nature of polymer (XLPE, LDPE, HDPE, EPR) Higher conductor stress, no increase of insulation screen stress Increase of insulation screen stress New extrusion line or transfer of extrusion line with earlier experience in-house New extrusion line, or transfer of extrusion line without earlier experience TT TT TT and PQ TT TT and PQ TT TT and PQ 2/5/2010 22

Tests because of modifications to an accessory within the same family in a prequalified EHV cable system Component Type of modification Proposed test Joint Higher calculated electrical stress design and construction Compound of main insulation body Changing nature of polymer, (EPR, Silicone.) Material of semi-con electrodes Fixation of cable ends on either side of the joint EQ PQ EQ EQ EQ

Principles of the Extension of PQ test (EQ) 60 thermal cycles witout voltage 20 cycles with 2Uo+PD+hot impulse test The 60 daily cycles + 20 cycles are intended to allow relaxation of mechanical stresses trapped in the cable during manufacture, resulting in retraction of the XLPE insulation The retraction of the cable insulation within an accessory can initiate PD activity 2/5/2010 24

.. Retraction of XLPE insulation and PE oversheath Retraction (mm) 35.0 30.0 25.0 20.0 15.0 10.0 5.0 0.0-5.0 Evolution of the retraction 0 10 20 30 40 50 60 70 80 Number of heat cycles Retraction of oversheath Retraction of insulation In addition the heat cycles are producing a radial expansion and retraction of the cable insulation and of the accessory components that can also influence the interfacial pressure in accessories. 2/5/2010 25

Recommendations to IEC 62067 New cable systems: - Maintain 1 year PQ test - Allow in case of an accessory failure the continuation and completion of the PQ test for the undisturbed component - Perform PD tests during PQ test - Perform impulse test at the end of the test on the complete test loop - Maintain unchanged present range of TT and PQ approval 2/5/2010 26

Recommendations to IEC 62067 Exchange of a prequalified component: - Introduce a simplified long term test of 60+20 cycles in case of exchange of prequalified components with other components or in case of less significant modifications of cable or accessory 2/5/2010 27

Long duration test HV cable systems Traditionally EHV cables are operating at higher stresses than HV cables Due to good experience with EHV cables, HV cables are being produced with reduced insulation thickness (slim design) Higher stresses at main insulation and at interfaces between cables and accessories 2/5/2010 28

Increase of Electric stress with system voltage 100 Impulse stresses Working stress (kv/mm) 10 AC stresses 1 10 100 1000 Voltage level (kv) 2/5/2010 29

Arguments pro Long term test High electric stresses increase failure risk Shrinkage is only stabilized after 80 cycles New accessory designs are coming Failures in high stress cables 2/5/2010 30

Arguments against long term test Many manufacturers have good experience so far Reluctance of some utilities, to test entire syst. if they buy their HV cables and accessories separately Longterm test is costly 2/5/2010 31

Range of PQ test For prefabricated joints, mainly impulse stresses at the cable interface are critical For taped or field-molded joints also AC and impulse stresses at the conductor are critical Therefore the PQ test is recommended for cable systems with conductor stresses higher than 8kV/mm and insulation screen stresses above 4 kv/mm 2/5/2010 32

Recommendations to IEC 60840 Intoduce the following PQ test: Voltage, 1.7 Uo 180 heating cycles, to max. 95 degr C Cooling to ambient PD tests Impulse test on the complete loop Examination of the test loop 2/5/2010 33

Exchanges and modifications The procedure and the sequence of EQ tests are the same as for the EHV cable systems 2/5/2010 34

Functional Analysis International standards are necessary for both manufacturers and customers An advantage of International standards is the world wide acceptance of the test evidence A disadvantage of international standards is the limited incentive of manufacturers to make incremental improvements, as this requires a complete repetition of the type testing 2/5/2010 35

Functional Analysis (2) According to IEC 62067 the PQ test need to be repeated in case of substantial changes There is no agreed method to decide what is substantial

Functional Analysis (3) In the Functional Analysis method a process is developed, where the significance of a change can be evaluated and the need for further testing agreed: - PQ test - EQ test - Type test - Other test 2/5/2010 37

Functional Analysis Method Consider the functions performed by each part of a cable or accessory construction and indicate how each function is tested Consider a number of possible changes that can be made and indicate what additional testing might be required 2/5/2010 38

Functional Analysis Tables Table for cable components Table for Joint components Table for Termination components 2/5/2010 39

Functional Analysis Table Structure of the table with 5 columns: Component Function Specification/threat Test to ckeck the functionality Comments 2/5/2010 40

Cable components Conductor Inner semiconducting screen Insulation Outer semiconducting screen Longitudinal water tight layer Metal screen Oversheath 2/5/2010 41

Functions/properties Electrical conductivity (conductor, screen) Dielectric properties (insulation, oversheath) Mechanical properties Thermal-mechanical properties Chemical properties Interfaces with other components Watertightness Overall properties 2/5/2010 42

Threat for function of conductor Overheating Mechanical deformation due to bending or pulling during installation Corrosion High interface resistance with connectors Thermal-mechanical expansion Water penetration 2/5/2010 43

Functional Analysis Functional Analysis of a High Voltage Cable and cable components (Example) Cable component Function or Property Specification/ Threat Test to check the functionality Comments A B C D E Conductor Electrical Conduct. a.no overheating with nominal current a.resistance measurement a For large conductors AC resistance test should be performed as type test -b. Limit b. If temperature rise -b. Calculation of temperature is considered thermal short with thermal dangerous, a short circuit temperature short circuit circuit test is current proposed as a development test. 2/5/2010 44

Tests not in IEC Short circuit test Examination of XLPE cable insulation in hot oil Examination of protrusions and decontaminants Moisture content in semicon layers Grain size measurement on lead sheath Fatigue test of lead sheath Side wall pressure test on cable Mechanical impact on oversheath Compatibility test of additives and filling material with cable and accessory material 2/5/2010 45

Conclusions EHV Cable systems: - Maintain PQ test of 1 year - Continuation of PQ test in case of accessory failure - Impulse test on complete loop - Introduce EQ test mainly in case of changes of or in accessories: 80 heat cycles, of which 20 will be with 2Uo 2/5/2010 46

Conclusions (2) HV cable systems: - Introduce PQ test of 0.5 year for high stress cables (8/4 kv/mm) - Continue test in case of accessory failure during test - Impulse test on complete loop - EQ test for changes/modifications at components, the same as for EHV 2/5/2010 47

Conclusions (3) Funtional analysis - FA method is recommended to assess the significance of changes and the selection of related tests - Lists are made available with appropriate tests in case of changes - Not only standardized tests but also development tests are being used 2/5/2010 48

End of presentation Thank you for your attention 2/5/2010 49