Synchronization Check Relay ARGUS 7

Similar documents
Tebis application software

Technical Manual Pico Timer - Programmer EM

application software

application software

Operating instructions Electronic preset counter Type series 717

EDL8 Race Dash Manual Engine Management Systems

EC456 Power System Protection Lab #1 Overcurrent Protection Relay

Tebis application software

Innovative Air Systems ABN When Calling For Support Quote:.doc

WELDING CONTROL UNIT: TE 450 USER MANUAL

Installing the FOREST SHUTTLE S / L

WaveMaker III Gartech Enterprises Inc. 12/17/2012

2-output DALI controller

ASNT_PRBS20B_1 18Gbps PRBS7/15 Generator Featuring Jitter Insertion, Selectable Sync, and Output Amplitude Control

013-RD

INDEP. QUARTZ MIN. - 1/2 MIN. AFNOR / IRIG B DHF / RADIO

USER GUIDE TO THE ARENA OPERATION

OWL micro+ WIRELESS ELECTRICITY MONITOR

Smart-Encoder : Optical Incremental

DATA SHEET. Synchronisers, FAS-113DG ANSI code 25

Understanding VFD. Variable Frequency Drive. nfi. nfi

BE3-GPR GENERATOR PROTECTIVE RELAY

VISUALIZED DIGITAL TIMER

EZ Encoder : Optical Incremental (P Series)

Model 5405 Dual Analog Sync Generator Data Pack

Transmitter Interface Program

The DataView PowerPad III Control Panel

PC/HDTV to PC/HDTV converter (CP-251F)

This guide gives a brief description of the ims4 functions, how to use this GUI and concludes with a number of examples.

2000 W, 2450 MHz Microwave Generator GMP 20K SM 56M230 FST 3 IR

GSC2mini - Pneumatic/Hydraulic Timer Based Valve-Gate Sequence Controller lnstruction Manual

800 Displaying Series Flowmeter

ET BLU MIX RX-Condo-3

GSCmini - Pneumatic Timer Based Valve-Gate Sequence Controller lnstruction Manual

imso-104 Manual Revised August 5, 2011

Operations Manual RD-BR1. Radian Research, Inc. CT Burden & Ratio Analysis Module

ED3. Digital Encoder Display Page 1 of 13. Description. Mechanical Drawing. Features

GSC2mini - Pneumatic/Hydraulic Timer Based. lnstruction Manual

RYKO Italia s.r.l. V. Casale Morano Po (Al) t f

Tebis TX100 Configurator

Features of the 745T-20C: Applications of the 745T-20C: Model 745T-20C 20 Channel Digital Delay Generator

Understanding VFD Allen Bradley Power Flex 4M Variable Frequency Drive. nfi

Contents: 1 LANsmart Pro Main Unit 4 Remote Unit: ID1, ID2, ID3, ID4

VISSIM Tutorial. Starting VISSIM and Opening a File CE 474 8/31/06

Ultra SERIES App Instructions

Automatic Transfer Switch Control PLC Operator s Manual

UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load Cell

PIPV200 QUAD System. User Manual

Artistic Licence. moody & moody cv. User Guide. Download the user guide by scanning the following QR code: moody & moody cv User Guide.

Revision 1.2d

GFT Channel Digital Delay Generator

Serie TV Manager for Enigma2 Systems

HSE-200 CONTROLLER / EDITOR

Professional 4-channel Thermocouple Thermometer plus Infrared Thermometer

Casambi App User Guide

Model 4455 ASI Serial Digital Protection Switch Data Pack

imso-104 Manual Revised July 19, 2012

TC-1 Timeclock. Operating and Programming Instructions Thursday, 25 March Lighting Controls for the World we live in

Radio Thermostat Clock

TASKI Service Tool Edition: V5.10/2014

Tri-level Control HF Sensor

FOREST SHUTTLE S / L / M RECEIVER

A B C D. Call-way AB

SERVICE MANUAL COOKING. Built-in ovens. S.E.T. (Simple Electronic Timer) Electronic Programmer. Publication Corso Lino Zanussi,30

LED control gear Compact dimming. Uconverter LCAI 2x38 W 0500 K013 one4all ECO series. Ordering data

MICROMASTER Encoder Module

C Module Description

Part No. ENC-LAB01 Users Manual Introduction EncoderLAB

BER MEASUREMENT IN THE NOISY CHANNEL

NETBELL SETTING INSTRUCTION

16 Stage Bi-Directional LED Sequencer

Film-Tech. The information contained in this Adobe Acrobat pdf file is provided at your own risk and good judgment.

VLC-3 USER'S MANUAL. Light Program Controller. M rev. 04 K rev. 00 & ( ( 5, 352*5$0 1 : $ 2 ' 6(77,1*6 )81&7,216

AN-822 APPLICATION NOTE

Using an IDT Redlake X4 High-Speed Camera with MiDAS DA

Single Axis Position Controller

MAutoPitch. Presets button. Left arrow button. Right arrow button. Randomize button. Save button. Panic button. Settings button

R5 RIC Quickstart R5 RIC. R5 RIC Quickstart. Saab TransponderTech AB. Appendices. Project designation. Document title. Page 1 (25)

C Module Description

UTH-170 Installation and Manual

User Manual CC DC 24 V 5A. Universal Control Unit UC-1-E. General Information SET. Universal Control Unit UC-1 Of Central Lubrication PAUSE CONTACT

REMOTE DISPLAY WIRELESS DECODER MK II

Model IQ4-PC User Manual Revision Date:

CET DOUBLE COUNTER WITH TWO THRESHOLDS LBM62CD. Type: TECHNICAL FEATURES

Master Clock MPU-I. Operating manual. Edition MPUi_m_e4.doc

Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module

Digital differential Pressure switch Model DPS Instruction manual

Defrost Control Installation and Programming of Version 3.1 Cards

Model DT-311J. And DT-311J-230V(AC) DIGITAL STROBOSCOPE INSTRUCTION MANUAL

K9123, K9134, K9135 Remote Programming Instructions and Specifications

CAMTO LTD. Arc detecting system DC/AC

TABLE OF CONTENTS. 2 SGM Light Technology 23/08/1999 Ver. 2.00

Standard RS232 RS ma

OPERATION AND MAINTENANCE

Operating Instructions (ed. 5.97) Electronic Preset Counter Type Series 904

Controllers, series CON Indicators, series IND. Controllers and indicators

C8000. sync interface. External sync auto format sensing : AES, Word Clock, Video Reference

STX Stairs lighting controller.

Viewing Serial Data on the Keysight Oscilloscopes

Pre-processing of revolution speed data in ArtemiS SUITE 1

Transcription:

Synchronization Check Relay ARGUS 7 Page 1 of 8

Table of Contents Secondary injection tests:... 3 Phase Angle Test:... 3 CS PHASE ANGLE:... 3 SS PHASE ANGLE:... 3 SLIP FREQUENCY TEST:... 4 CS SLIP FREQUENCY:... 4 SS SLIP FREQUENCY:... 6 SYSTEM SPLIT ANGLE:... 6 TIMING TEST:... 6 CS SLIP TIMER:... 6 CS CONTACT RESET TIME:... 6 SS SLIP TIMER:... 7 SS CLOSE PULSE TIMER:... 7 SPLIT TIMER:... 7 VOLTAGE ELEMENT TESTS:... 7 VOLTAGE DETECTOR TEST:... 7 UNDER VOLTAGE TEST:... 8 DIFFERENTIAL VOLTAGE TEST:... 8 VOLTAGE MEASUREMENT TEST:... 8 O/P RELAYS OPERATION:... 8 STATUS I/P OPERATION:... 8 Page 2 of 8

Secondary injection tests: 1. Connect Red phase of FREJA as your Line voltage. 2. Connect Uref of FREJA as your BUS voltage. 3. Insert your test plug and make connections as per drawing. 4. Go to the HMI of the relay press DOWN arrow and scroll through the menu to change different settings of parameters. 5. To change settings of any parameter, press RIGHT arrow and you will enter in a specific setting menu. 6. Now press enter and you can change its value. 7. Now use up, down and right arrow to change any value to a specific value. Phase Angle Test: CS PHASE ANGLE: 1. Make the settings under menu CHECK SYNCH MENU. 2. Set the angle as per format. 3. Keep System Split disable. 4. Now to configure O/P contact on CS (Check Synchronization), go to HMI of the relay and press DOWN arrow 6 times unless you reach O/P relay configuration. Now configure any contact on Check Synchro and connect your buzzer on this contact. 5. Now inject in such a way that frequency of Uref and R is kept at 60 Hz and voltage at rated i.e. 63.5 and angle of LINE i.e. our red phase is increased from zero to a value greater than setting. 6. Now decrease the angle of LINE voltage and note the pick up value of O/P contact. Now increase the value of angle such that contact D/O. Note this value as well. 7. Now keep the LINE angle at zero and change BUS angle i.e. Uref from zero to a value greater than set value and now decrease to note the P/U value and again increase to note the D/O value. SS PHASE ANGLE: 1. Go to CHECK SYNCH MENU and make SYSTEM SPLIT enable and make the angle 90 degree e.g. 2. Now to make the setting of SYSTEM SPLIT go to menu SYSTEM SYNC and set your values here. 3. Now again to configure O/P contact go to HMI of the relay and press DOWN arrow until you reach O/P RELAY CONFIG press right arrow to enter and on any relay e.g. on REL4 press ENTER and now select this output on SYSTEM SYNC. 4. Now increase first LINE angle and make it greater than 90 degree or whatever the angle setting for SS such that SYSTEM SPLIT LED appears on the relay. 5. Now decrease the angle so that our contact picks up. Note this value. 6. For SYSTEM SPLIT PHASE ANGLE no D/O value exists. Page 3 of 8

SLIP FREQUENCY TEST: CS SLIP FREQUENCY: 1. Go to CHECK SYNCH menu and make the SYSTEM SPLIT detector OFF. 2. Now set the value of frequency as per your format. 3. Make the O/P contact on CS. And connect a buzzer with this contact. 4. Go to FREJA WIN software. And click on SYNC. Page 4 of 8

5. Click on PROCEED. 6. Now click on U & f MAX MIN window. Here do the following settings as shown in the picture. Page 5 of 8

7. Now make the frequency value of AU out of the set value. Now decrease this value slowly until your O/P contact picks up. 8. Now decrease the value of frequency until O/P contact D/O. 9. For now we will keep line frequency constant and change the BUS frequency. 10. So connect BUS voltage connection to the red phase of freja and connect LINE voltage connection on Uref. 11. Now again increase frequency beyond set value and start decreasing it to note the P/U value and now increase it again to note the D/O value. SS SLIP FREQUENCY: 1. Go to CHECK SYNCH menu and make the SYSTEM SPLIT detector ON and make its value 90 degree. 2. Now go to SYSTEM SPLIT menu and set its value as per format. 3. Now on same page of FREJA WIN do the same procedure to measure P/U and D/O value. SYSTEM SPLIT ANGLE: 1. Go to CHECK SYNCH menu and make the SYSTEM SPLIT detector ON and make its value as per your format. 2. Now go to FREJA instrument and keep BUS angle at zero and increase LINE angle above set value unless RED LED of SYSTEM SPLIT appears. This is our P/U value for SS ANGLE. TIMING TEST: CS SLIP TIMER: 1. Go to CHECK SYNCH menu. Make SYSTEM SPLIT OFF, make its angle e.g. 15 degree and set CS timer as per your format. 2. On freja instrument 1 st page keep the angle b/w your LINE and BUS i.e. the Uref and RED phase of freja more than 15 degree i.e. make it out of CHECK SYNC angle setting. 3. On 2 nd page of freja make angle b/w the two voltages equal to zero. 4. On 3 rd page of FREJA, run 1 st page for 2 sec and make 2 nd page time more than the set value for CS SLIP TIMER. 5. O/P relay should be configured on CS and it should be connected in the BI of FREJA. 6. Now start the FREJA and note the time. CS CONTACT RESET TIME: 1. On freja instrument 1 st page keep the angle b/w your LINE and BUS i.e. the Uref and RED phase of freja more than 15 degree i.e. make it out of CHECK SYNC angle setting. 2. On 2 nd page of freja make angle b/w the two voltages equal to zero. 3. On 3 rd page of FREJA, run 1 st page for 2 sec and make 2 nd page time more than the set value for CS SLIP TIMER. 4. Now connect the START contact of TM200 timer with the CS O/P contact and short the START and STOP contact of TM200. Make start contact from OFF to ON and STOP contact ON to OFF. 5. Press the start button of FREJA and measure the time on TM200. Page 6 of 8

SS SLIP TIMER: 1. Go to CHECK SYNCH menu and make SYSTEM SPLIT ON and make its setting lets say 90 degree. 2. Now go to SYSTEM SYNCH menu and set its timer. 3. On freja instrument 1 st page keep the angle b/w your LINE and BUS i.e. the Uref and RED phase of freja more than 90 degree i.e. make it in SYSTEM SPLIT condition. 4. On 2 nd page of freja make angle b/w the two voltages equal to zero. 5. On 3 rd page of FREJA, run 1 st page for 2 sec and make 2 nd page time more than the set value for SS SLIP TIMER. 6. O/P relay should be configured on SS and it should be connected in the BI of FREJA. 7. Now start the FREJA and note the time. SS CLOSE PULSE TIMER: 1. Go to SYSTEM SYNCH menu and set the SS CLOSE PULSE TIMER. 2. On freja instrument 1 st page keep the angle b/w your LINE and BUS i.e. the Uref and RED phase of freja more than 90 degree i.e. make it in SYSTEM SPLIT condition. 3. On 2 nd page of freja make angle b/w the two voltages equal to zero. 4. On 3 rd page of FREJA, run 1 st page for 2 sec and make 2 nd page time more than the set value for SS SLIP TIMER. 5. Now connect the START contact of TM200 timer with the SS O/P contact and short the START and STOP contact of TM200. Make start contact from OFF to ON and STOP contact ON to OFF. 6. Press the start button of FREJA and measure the time on TM200. SPLIT TIMER: 1. Go to CHECK SYNCHRO menu and set the SPLIT TIMER setting. 2. On freja instrument 1 st page keep the angle b/w your LINE and BUS i.e. the Uref and RED phase of freja more than 90 degree i.e. make it in SYSTEM SPLIT condition. 3. On 2 nd page of freja make angle b/w the two voltages equal to zero. 4. On 3 rd page of FREJA, run 1 st page for 2 sec and make 2 nd page time more than the set value for SS SLIP TIMER. 5. Now connect the START contact of TM200 timer with the SYSTEM SPLIT O/P contact and short the START and STOP contact of TM200. Make start contact from OFF to ON and STOP contact ON to OFF. 6. Press the start button of FREJA and measure the time on TM200. VOLTAGE ELEMENT TESTS: VOLTAGE DETECTOR TEST: 1. Go to HMI of the relay. Press DOWN arrow unless you reach VOLTAGE SETTING menu. 2. In this menu press DOWN arrow unless you reach LIVE LINE & DEAD LINE setting. 3. Make these settings as per your format. 4. Configure O/P contact to LIVE LINE. 5. Now keep BUS voltage at 63.5 V and increase LINE voltage from zero to a level when your O/P contact picks up. Now decrease it unless your O/P contact drops off. Do the same procedure for LIVE BUS & DEAD BUS. Page 7 of 8

UNDER VOLTAGE TEST: 1. Go to HMI of the relay. Press DOWN arrow unless you reach VOLTAGE SETTING menu. 2. In this menu press DOWN arrow unless you reach LINE UNDER VOLTAGE setting. Now set this value as per your format. 3. Configure O/P contact for LINE UNDER VOLTAGE. 4. Now keep BUS voltage at 63.5 V and increase the LINE voltage from zero unless your contact drops off. Now decrease your voltage unless this contact picks up. 5. Do the same for BUS UNDER VOLTAGE. DIFFERENTIAL VOLTAGE TEST: 1. Go to HMI of the relay. Press DOWN arrow unless you reach VOLTAGE SETTING menu. 2. In this menu press DOWN arrow unless you reach DIFFERENTIAL VOLTAGE setting. Now set this value as per your format. 3. Configure O/P contact for DIFFERENTIAL VOLTAGE OP. 4. First keep the BUS voltage constant at 63.5 V and decrease LINE voltage from 63.5 V and note the pick up and drop off value of the contact. 5. Then keep LINE voltage constant at 63.5 V and decrease BUS voltage from 63.5 V and note P/U and D/O value of the contact. VOLTAGE MEASUREMENT TEST: 1. Go to HMI of the relay. Press down arrow and you will see SETTINGS MODE press RIGHT arrow and you can see INSTRUMENTS MODE. Press DOWN arrow and you will see BUS VOLTAGE and LINE voltage. This is the primary voltage. Press DOWN arrow again and you will again see BUS VOLTAGE and LINE VOLTAGE. This is the secondary value. 2. Now you inject from FREJA as per your format and note the values from HMI. O/P RELAYS OPERATION: 1. Go to HMI of the relay. Press down arrow until you will see O/P RELAY configuration menu. 2. Here configure each O/P relay on LINE/ BUS UNDER VOLTAGE. Since without injection this O/P is high so contact will pick up. And you can check the continuity of the contact. STATUS I/P OPERATION: 1. Go to HMI of the relay. Press down arrow and you will see SETTINGS MODE press RIGHT arrow and you can see INSTRUMENTS MODE. Press DOWN arrow and you will see STATUS INPUTS. 2. Now ask SHANKER to connect +ve supply with the positive of I/P contact and negative with ve of the I/P contact. 3. Now look at HMI of the relay corresponding I/P will become 1. Page 8 of 8