Class E A / Cat.6A Screened Coupler Patented Qualified Class E A / Cat.6A (500MHz) of ANSI/TIA-568-C.2 IEC 60603-7-51 AMD 2,Class E A CENELEC EN 50173-1
Specification Specification: Qualified Screened Category 6A of ANSI/TIA-568-C.2 IEC 60603-7-51 AMD 2,Class E A CENELEC EN 50173-1 Electrical: Current Rating: 1.5 Amps Insulation Resistance: 500 Mohms Minimum Contact Resistance: 20 mohms Maximum DC Resistance: 0.1 ohms Maximum Mechanical: Plug insertion life: 750 Cycles minimun Plug & Jack contact force: 100 Grams minimun Plug retention force: 30 lbs minimun Temperature: -40 to 150 F (-40 to 68 C) Using FCC-Approved Plug Available for snapping into 24 ports patch panel Standard RJ45 female to female adapter for easy cable connection. L30mm x W16.8mm x H16.1mm It provides extension solution Easily snap in and out from wall outlets and patch panels Packing: 1pc/printed bag 500pcs/carton Physicals: Housing: High Impact flame retardant plastic Shielded: 0.25t copper alloy with nickel plated Bracket: 0.3t SUS 301 PCB: FR4, 1.0mm thickness Jack wire: Phosphor bronze gold over nickel plated 250.0 370.0 490.0
Test parameters Requirement according to Fluke DTX ISO11801 PL2 Class E A ISO11801 Class E A ISO11801 Chan Class E A Low IL ISO11801 PL3 Class E A Fluke DTX-1800 Class E A / Cat.6A measuring Configuration setup Configuration 1 : 2 Connectors made of Cat.6A S/FTP Patch cable, two couplers and additional patch cables. Margin to the limit: Coupler Length NEXT RL Copuler [m] [db] [db] [No] Pass/Fail 2 Connectors 12.5 3.7 8.2 S1 / S2 Pass 3.4 8.1 S1 / S2 Pass 2 Connectors 56.4 5.7 5.1 S1 / S2 Pass 5.6 5.1 S1 / S2 Pass Configuration 2 : 3 Connectors made of 15m Cat.6A S/FTP solid cable, 5m patch cable, coupler and additional patch cables. Margin to the limit: Coupler Length NEXT RL Copuler [m] [db] [db] [No] Pass/Fail 3 Connectors _2m+5m at main side 7+15+2 3.4 7.4 S1 / S2 Pass 3.3 7.4 S1 / S2 Pass 3 Connectors _2m+5m at remote side 2+15+7 3.7 8.6 S1 / S2 Pass 3.6 8.6 S1 / S2 Pass
Test parameters Requirement according to Fluke DTX ISO11801 PL2 Class E A ISO11801 Class E A ISO11801 Chan Class E A Low IL ISO11801 PL3 Class E A Fluke DTX-1800 Class E A / Cat.6A measuring Configuration setup Configuration 3 : 2 Connectors made of Cat.6A S/FTP Patch cable, two couplers and additional patch cables. Margin to the limit: Coupler Length [m] NEXT [db] RL [db] Copuler [No] Pass/Fail 2 Connectors PL_5m at 8.8 1.2 5.6 S1 / S2 1.0 5.7 S1 / S2 Pass Pass 2 Connectors PL_5m at 52.8 2.2 2.8 S1 / S2 Pass 2.1 2.9 S1 / S2 Pass Configuration 4 : 3 Connections made of 15m Cat.6A S/FTP solid cable, 5m patch cable, coupler and additional patch cables. Margin to the limit: Coupler Length [m] NEXT [db] RL [db] Copuler [No] Pass/Fail 3 Connectors PL_5m at main side 5+15 1.2 4.9 S1 / S2 0.6 5.0 S1 / S2 Pass Pass 3 Connectors PL_5m at remote side 15+5 1.4 6.3 S1 / S2 Pass 1.3 6.3 S1 / S2 Pass
Patent Designed Highlight: Taiwan Patent No.: M430058 U.S. Patent (Pending) I Concept of compensation: The terminal holder structure for Telebox TA196BSS coupler has an intermediate bracket arranged on the middle part of the top wall of the circuit board thereof to hold the center inserts, so that the two sides contact distance is sufficient for crosstalk compensation, avoiding crosstalk interference and improving communication quality. II Implementation of compensation: When used in a 10G Ethernet network in the frequency range 1MHz to 500MHz, a different geometric position of metal can change the coupling phenomenon of surrounding metals, thereby indirectly affecting alteration of asymmetric phase retardation and increasing or decreasing of crosstalk vector in device crosstalk interference. III Result of outperformance: In other words, the arrangement of the intermediate bracket on the circuit board can compensate for crosstalk loop space, effectively reducing crosstalk interference in the TA196BSS coupler.
What s difference between Class E A and Cat.6A? Standard Configuration Cat.6A or Class E A (500MHz) AMD 2 CENELEC EN50173-1 EIA/TIA 568-C.2 Class E A Class E A Class E A Class E A Cat.6A Cat.6A <<Comparison Chart I>> For the regional US American cabling standard EIA/TIA 568-C.2, see <<Comparison Chart I>>, it describes channels and permanent links as Cat. 6A. For the international cabling standard and the European cabling standard EN 50173-1, both standards configurations like channels and permanent links are called Class E A. When you compare EIA/TIA with ISO/IEC or EN, they are not only naming differently, but also transmission performance requirements show significant variations, see below comparison charts. v.s. EIA/TIA568-C.2 NEXT Limits Minimum NEXT db -20-30 Transmission performance differences between ISO/IEC and EIA/TIA Frequency MHz 1.0 16.0 65.0 53.2 EIA/TIA 568-C.2 65.0 53.2 100.0 39.9 39.9-40 200.0 250.0 34.8 33.1 34.8 33.1-50 100 200 300 400 500 Frequency MHz EIA/TIA 568-C.2 350.0 500.0 30.6 27.9 30.3 26.1 Minimum NEXT db -20-30 -40 v.s. EIA/TIA568-C.2 NEXT Limits -50 100 200 300 400 500 Frequency MHz Transmission performance differences between ISO/IEC and EIA/TIA EIA/TIA 568-C.2 Frequency MHz 1.0 16.0 100.0 200.0 250.0 350.0 450.0 500.0 65.0 54.6 41.8 36.9 35.3 32.6 30.2 27.8 EIA/TIA 568-C.2 65.0 54.6 41.8 36.9 35.3 31.8 26.7
Relative Products KP24XX FG01XX FG0501
Telebox Industries Corp. 4F, No. 306 Tatung Road, Sec. 1, Hsichih-Taipei 22146, Taiwan Tel:+886-2-26429337 Fax:+886-2-26425779 url: www.telebox.com email: sales@telebox.com