www. ElectricalPartManuals. com l Basler Electric P. 0. BOX 269 HIGHLAND, ILLINOIS 62249, U.S.A. PHONE FAX

Similar documents
ORDERING Page 6 BASLER RELAY STANDARDS, DIMENSIONS, ACCESSORIES Request bulletin SDA

ORDERING Page 6 STANDARDS, DIMENSIONS and ACCESSORIES Request bulletin SDA

www. ElectricalPartManuals. com l Basler Electric VOLTAGE REGULATOR FEATURES: CLASS 300 EQUIPMENT AVC63 4 FEATURES AND APPLICATIONS

BE3-GPR GENERATOR PROTECTIVE RELAY

CLASS 300 EQUIPMENT BE3-25A AUTO-SYNCHRONIZER (Single Phase)

BE1-81O/U Frequency Protection. Washington State University Hands-On Relay School.

Intertie Protection M 3520

Type MG-6 Auxiliary Relay Class 1E

02/11/2015

PRINCIPLES AND APPLICATIONS

Bulletin 190 IEC Modular Starter System

MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz

3.5. Control Relays and Timers. Contents. 9575H Series 3000 Type AA, AC and DC. General Purpose Relays Type AA

UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load Cell

Generator protection relay

GP-500 SERIES - Low Voltage

EA63-7D. Generator Automatic Voltage Regulator Operation Manual. Self Excited Automatic Voltage Regulator

Transfer Switch. OTECA (Spec A) OTECB (Spec A) OTECC (Spec A) OTECD (Spec A) Amperes. English Original Instructions (Issue 5)

PBC series. RoHS. Ready. IEC-Type Contactors & Accessories 9-80 Amp AC-3, Amp AC-1 AC Coils. P&B PBC Series IEC Type Contactors & Accessories

Multifunction Digital Timer

Series CT7N Bimetallic Overload Relays

LED control gear Compact dimming. Uconverter LCAI 2x38 W 0500 K013 one4all ECO series. Ordering data

Kuhnke Technical Data. Contact Details

MILLITARY SPECIFICATION SHEET

CAMTO LTD. Arc detecting system DC/AC

Weekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N

1 Power Protection and Conditioning

Solid-State Digital Timer

Magnetic and Hydraulic-Magnetic Circuit Breaker

Standard RS232 RS ma

Weekly Time Switch. Rated time Time setting range Time division 24 hrs x 7 days 00:00 to 23:59 1min

HS-509 VIBRATION TRIP MODULE

High performance circuit breakers

Magnecraft Power Relays

DPS-250AB-18 E. 電氣規格 (Electrical Specification) REV. Description Date DESCRIPTION : MODEL NO. : Date Drawn Desing(EE) Design(ME) DOCUMENT NO. : REV.

TeSys contactors. Model d. Type of contactor LC1- LC1- LC1- LC1- LC1-D115 & D09 D18 D25 D38 D40 D50 D95 LC1-D150 DT20 & DT25 DT32 & DT40

POWR-GARD Ground-Fault Protection PGR-3100 SERIES Ground-Fault Indication System. PGR-3100 Manual. Ground-Fault Indication System.

LED Driver Compact fixed output

MATE3 Owner s Manual Addendum

LED Driver Linear / area fixed output

Assembly. Front view. LEDs. Parametrization interface. Power Bus

Magnecraft General Purpose Relays 750R Series DPDT and 3DPT, 10 A

LED Driver Compact fixed output

LED Driver Compact fixed output

Figure 1: Standard 906 Sensor and Pulser Disc. Figure 2: Standard 906 Sensor and Pulser Wrap

SEL-251 SEL SEL DISTRIBUTION RELAY

CURRENT INJECTION RELAY TESTER CR-100. ( Code P60212 (770081) ) INSTRUCTIONS MANUAL ( M / 05A ) (c) CIRCUTOR S.A.

Datasheet - SRB301LC 24VAC/DC

Ordering details. Approval. Classification

HYL-035D0850G103. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

PHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

GR circuit breaker - hydraulic magnetic, Datasheet

LED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series

Systems Pow-R Breakers Renewal Parts and Accessories

TeSys circuit-breakers

ALLEN BRADLEY TIMING RELAY

Time-Lag Relays. User s Handbook (General Model)

multi-function meters

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

Sentinel I24 Digital Input and Output Configuration

LED Driver Compact dimming

Self Excited Automatic Voltage Regulator For Generator Compatible with Marathon SE350* Operation Manual

AF-300 E11 Adjustable Frequency Drive

Panel cutout required: 1.772" x 3.622" (45mm x 92mm) 1.76" (45mm) 2.45" (62mm) 3.20" (81mm) 3.60" (91mm) 0.59" (15mm) Special Features

Vorne Industries. 87/719 Analog Input Module User's Manual Industrial Drive Itasca, IL (630) Telefax (630)

3AH3 Vacuum Circuit-Breakers

Datasheet - SRB-E-201ST

MRU3-2 - Voltage relay with evaluation of symmetrical components

Power Circuit of a UL508A Panel. Typical UL489 Application

LAUREL ELECTRONICS, INC.

Model Number Structure

EG4015. Digital Generator Governor Controller User Manual

HD4/R. MV SF6 circuit-breakers for secondary distribution

SPECIFICATION ESD FSP500-80MPD. Released Date:2015/07/27-14:41:38

LAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description

LoopBack Relay. SGLB363 Series. With Built-in AC Bypass Capacitors / DC LoopBack Relay

USER S GUIDE. 1 Description PROGRAMMABLE 3-RELAY LOGIC MODULE

Process Transmitter RMA 422

T L Audio. User Manual C1 VALVE COMPRESSOR. Tony Larking Professional Sales Limited, Letchworth, England.

Contactors and Contactor Assemblies

LED control gear Compact fixed output

Provides an activation of Relay 1 triggered by Input 1. The function also provides an option for reverse-logic on the activation of Input 1.

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Type Contact form Model Ag (Au clad) Standard DPDT G6A-274P-ST-US Low-sensitivity DPDT G6A-274P-ST40-US

Junior Max (JR Max ) Controller

EA350. Generator Automatic Voltage Regulator Operation Manual

Type Contact form Model

Description Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100

2-output DALI controller

Description Set value in neutral conductor is synchronous with set value Ir of main pole. CSA 100. conductor. I r A 50-63

INSTALLATION MANUAL FT-FOTR-8VD-ST-S. 8-Channel Digital Duplex Baseband Video Transmitter and Receiver With Reverse Data Transmission for PTZ Cameras

1900/25 Vibration Monitor

Model IQ4-PC User Manual Revision Date:

Passive UTP Transceiver Hub with Integral Camera Power Installation Guide

Emergency lighting units EM powerled

Type: DILM12 10(24VDC) Article No.:

ALM-6813/6812 INSTALLATION AND PROGRAMMING MANUAL

Instruction Manual. Series 3000 Model R-165A. Audio/Video IF/RF Relay Panel. CATV Switching and Control

Description. Specifications and Ordering Information 1900/27 Vibration Monitor

Transcription:

- L M limn The BE1- Ground Fault Overvoltage Relay provides sensitive protection for ungrounded and high resistance grounded systems. ADVANTAGES Provides 1 00% stator ground fault protection. 100/120 Vac or 200/240 Vac nominal sensing input. Four sensitivity ranges for overvoltage are available: 1-20 and 1 0-50 Vac for a 100/120 Vac input and 2-40 and 20-100 Vac for a 200/240 Vac input. Four sensitivity ranges for undervoltage are available: 0.1-2.5 Vac and 0.5-12 Vac for a 100/120 Vac input and 0.2-5 Vac and 1-24 Vac for a 200/240 Vac input. nstantaneous, definite, and inverse time characteristics. 40 db harmonic filtering. Low sensing input burden. Power supply status contact. Qualified to the requirements of -ANS/EEE C37.90.1-1989 and EC 255 for surge withstand capability; - EC 255-5 for impulse. UL Recognized under Standard 508, UL File #E97033. NSTRUCTON MANUAl ADDTONAL NFORMATON Request publication 9-1714-00-990 STANDARDS, DMENSONS & ACCESSORES Request bulletin SDA l Basler Electric P. 0. BOX 269 HGHLAND, LLNOS 62249, U.S.A. PHONE 618 654 2341 FAX 618 654 2351 BE1- GROUND FAULT OVERVOLTAGE RELAY r APPLCATON Page2 SPECFCATONS Page 3 EXTERNAL CONNECTONS Page 6 ORDERNG Page 7 UBG-6 10-95

BE1- GROUND FAULT OVERVOLTAGE -- PURPOSE The available fault current for single-phase-to-ground faults is very limited for ungrounded systems and systems which are grounded through a high resistance. This current limiting reduces the possibility of extensive equipment damage, and eliminates the need for a neutral breaker by reducing the fault current below the level required to sustain an arc. But it remains important to detect and isolate singlephase-to-ground faults in order to prevent their evolution into more dangerous faults such as phaseto-phase-to-ground and three-phase-to-ground faults. Sensitive voltage relays can be used to detect ground faults where the fault current is very small. The BE1- is especially suited to the task. HGH RESSTANCE GROUNDNG A common method of grounding an ac generator is to connect a distribution transformer between the neutral of the generator and the station ground. The distribution transformer's primary voltage rating is equal to, or greater than, the generator's rated line-to-neutral voltage. ts secondary is rated at 200/240 Vac or 100/120 Vac. A resistor is connected across the secondary winding of the transformer. When reflected through the transformer it is effectively a high resistance. R = p R s X N2 where R P is the effective primary resistance R5 is the actual value of the secondary resistor N is the turns ratio of the distribution transformer The available single-phase-to-ground fault current at the generator terminals is greatly reduced by the high effective resistance of the distribution transformer and secondary resistor. The distribution transformer provides isolation for the protection scheme and reduces the voltage to a convenient level. The BE 1- ground fault overvoltage relay is connected across the secondary resistor to detect the increase in voltage across the distribution transformer caused by a ground fault in the generator stator windings. A ground fault at the generator terminals will result in rated line-to-neutral voltage across the transformer primary, while ground faults near the neutral will result in lower voltages. The overvoltage relay set- 2 APPLCATON point must be higher than any neutral voltage resulting from normal unbalances in order to avoid nuisance trips. This will allow a certain percentage of the stator windings near the neutral to go unprotected by the overvoltage relay. The overvoltage relay function typically protects 90 to 95% of the generator stator windings. The BE1- ground fault overvoltage relay monitors the fundamental frequency (50 or 60 Hz) voltage which accompanies a ground fault, and is insensitive to the third harmonic voltage present during normal operation. One hundred percent protection of the generator stator windings is obtainable with the optional overlapping undervoltage element. The undervoltage element is tuned to measure the third harmonic voltage which is present in the generator neutral under normal operating conditions. The undervoltage element detects the reduction of the normal third harmonic voltage which accompanies a ground fault near the neutral point of the generator. An undervoltage inhibit feature is included with the third harmonic undervoltage element. This feature supervises the undervoltage element of the ground fault relay to prevent misoperation during startup and shutdown by monitoring the generator terminal voltage. UNGROUNDED SYSTEMS The BE1- ground fault overvoltage relay is used to detect ground faults on ungrounded three-phasethree-wire systems. The relay is connected as shown in Figure 1. A set of voltage transformers are wired with a grounded wye primary and a broken delta secondary. The BE1- is connected across the broken delta. t is often necessary to connect a resistor across the broken delta to avoid ferroresonance. SOURCE FGURE 1. UNGROUNDED 3-PHASE, 3-WRE SYSTEM

The grounded wye/broken delta voltage transformers act as a zero sequence filter by summing the three phase voltages. Under normal conditions this sum is zero. When a ground fault occurs, the BE1- ground fault overvoltage relay will detect the presence of the secondary zero sequence voltage (3V0}. FUNCTONAL DESCRPTON The specifications on these pages define the features and options that can be combined to exactly satisfy an application requirement. The block diagram (Figure 2) illustrates how the various standard features, as well as the options, function together. NPUTS Nominal sensing input ratings, defined by the style number, are 100/120 or 200/240 Vac with a maximum burden of 2 VA single-phase at nominal 50/60 Hz. The maximum continuous voltage rating is 360 Vac for 100/120 Vac nominal, and 480 Vac for 200/240 Vac nominal. Overvoltage Sensing n a typical application, the BE1- Ground Fault Overvoltage Relay monitors the voltage across a resistor in the generator's grounding circuit. The voltage across the resistor is supplied to the sensing transformer in the relay. The derived secondary voltage is applied to an active EXTERNAL POWER -1----1 SOURCE APPLCATON (continued) SPECFCATONS FRONT PANEL -- BE1- GROUND FAULT OVERVOLTAGE The BE1- ground fault overvoltage relay greatly reduces the risk of equipment damage by detecting and isolating the first ground to occur on an ungrounded system. filter to obtain the fundamental component of the input voltage. f this voltage exceeds the OVERVOLTAGE PCKUP (controlled at the front panel}, an LED illuminates, and an internal signal is developed which may be employed three different ways, depending upon the timing option selected. 1. The overvoltage output relay is energized instantaneously. 2. A definite time delay is initiated whose period is determined by the front panel TME DAL over a range or 0.1 to 99.9 seconds. At the expiration of the time delay, the overvoltage output contacts close. 3. An inverse time delay is initiated whose period is determined by two factors: a. Magnitude of the overvoltage condition (±2% or 100 mv or whichever is greater for the 120 Vac pickup range or ±2% or 200 mv for the 240 Vac pickup range}, and b. Selection of a particular response curve by the front panel Tl ME DELAY over the range of 01 to 99 (±5% or 25 msec, whichever is greater) (Reference Figure 4.) DEFNTE OR NVERSE TME DELAY UNDER VOLTAGE FGURE 2. FUNCTONAL BLOCK DAGRAM 3

BE1- GROUND FAULT OVERVOLTAGE -- Undervoltage Sensing Option An optional undervoltage measuring element is sensitive to the third harmonic (150 Hz or 180 Hz) voltage present at the generator neutral, and insensitive to the fundamental frequency (50 or 60 Hz). The undervoltage element determines within 5 cycles whether the third harmonic voltage is above or below the UNDERVOLTAGE PCKUP setting on the front panel. f below, the UNDERVOLTAGE LED will illuminate, and an internal signal is developed which may be employed three different ways, depending upon the timing option selected. 1. The undervoltage output relay is energized instantaneously. 2. A definite time delay is initiated whose period is determined by the front panel TME DAL over a range or 0.1 to 99.9 seconds. At the expiration of the time delay, the undervoltage output contacts close. 3. An inverse time delay is initiated whose period is determined by two factors: a. Magnitude of the undervoltage condition (±2% or 100 mv or whichever is greater for the 120 Vac pickup range or ±2% or 200 mv for the 240 Vac pickup range), and b. Selection of a particular response curve by the front panel TME DAL over the range of 01 to 99 (±5% or 25 msec, whichever is greater) (Reference Figure 3.) --- so --- :===:::::. 40 -- 10 _ 07 05 _ 03 02 12 11 10 9 8 7 6 5 4 3 2 1 100/120 Vac NPUT 24 22 20 18 16 14 12 10 8 6 4 2 200/240 Vac NPUT VOLTAGE DFFERENCE FROM PCKUP FGURE 3. UNDERVOLTAGE NVERSE TME CHARACTERSTC CURVES 4 40.0 30.0 20.0 10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0 2.0 1.0 0.9 0.8 0.7 0.6 0.5 04 0.3 0.2 0.1 SPECFCATONS (continued) Undervoltage nhibit When the undervoltage sensing option is selected, an undervoltage inhibit circuit is included which monitors the generator terminal voltage. When the terminal voltage is less than the UNDERVOLTAGE NHBT setting on the front panel, the undervoltage sensing option is inhibited to prevent relay operation during start-up or shutdown of the generating unit. The UNDERVOLTAGE NHBT range is continuously adjustable from 40 to 120 Vac for the nominal 100/120 Vac units, and 80 to 240 Vac for the 200/240 Vac units. PCKUP ACCURACY Relay pickup will not vary from its setting more than as follows for variations in input power or operating temperature within the specified limits. For 120 Vac sensing range: ±2.0% or 100 millivolts, whichever is greater. For 240 Vac sensing range: ±2.0% or 200 millivolts, whichever is greater. DROPOUT RATO Overvoltage and undervoltage elements reset within 2.0% of their actual pickup level within seven cycles. 400 300 200 10.0 9.0 8.0 70 6.0 5.0 4.0 3.0 2.0 1.0 0.9 0.8 0.7 0.6 05 0.4 03 02 0.1 10Q/120VaciNPUT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 200/240 Vac NPUT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 VOLTAGE DFFERENCE FROM PCKUP FGURE 4. OVERVOLTAGE NVERSE TME CHARACTERSTC CURVES 15 16 30 32 " < 0 w " 99 so 60 50 40 30 20 10 07 05 03 02 01

TMNG ACCURACY Definite time is adjustable from 00.1 to 99.9 seconds, in steps of 0.1 seconds. Accuracy is within ± % of least significant digit ±25.0 milliseconds. nverse time is adjustable from 01 to 99 in increments of 01. The setting defines a curve as illustrated in Figures 3 and 4. nverse timing is accurate within ±5% or 25.0 milliseconds, whichever is greater, for any combination of time dial and pickup setting. POWER SUPPLY One of five power supply types may be selected to provide internal operating power. They are described in Table 1. TA BLE 1. POWER SUPPLY OPTONS Type K J L Y* z Nominal 48 Vdc 125 Vdc 24 Vdc 48 Vdc 250 Vdc Voltage 120 Vac 125 Vdc 230 Vac Burden?.OW 7.5W 7.5W?.OW 12.0W 15.0 VA 7.5W 33.5 VA *The type Y power supply is field selectable for use with either 48 or 125 Vdc. Selection must be accomplished at the time of installation and prior to the application of power. POWER SUPPLY STATUS OUTPUT The power supply output relay is energized and its NC output contact is opened when power is applied to the relay. Normal internal relay operating voltage maintains the power supply status output relay in a continuously energized state with its output contact open. f the power supply output voltage falls below the requirements of proper operation, the power supply output relay is deenergized, closing the NC output contact. OUTPUTS Output contacts are rated as follows: Resistive 120/240 Vac - make 30 A for 0.2 seconds, carry 7 A continuously, break 7 A. 250 Vdc - make and carry 30 A for 0.2 seconds, carry 7 A continuously, break 0.1 A. 500 Vdc - make and carry 15 A for 0.2 seconds, carry 7 A continuously, break 0.1 A. SPECFCATONS ccontinued) nductive ---BE1- GROUND FAULTOVERVOLTAGE 120/240 Vac, 125 Vdc, 250 Vdc - break 0.1 A (L/R = 0.04). Push-to-Energize Output Pushbuttons Accessible with a thin non-conducting rod through the front panel, push-to-energize pushbuttons are available to energize each output relay for testing the external control/protective system wiring. TARGET Magnetically latched, manually reset, target indicators are optionally available to indicate that an output has tripped. Either internally operated or current operated targets may be specified. Current operated targets require 0.2 A in the output trip circuit to actuate, and trip circuit current must not exceed 30 A for 0.2 seconds, 7 A for 2 minutes, and 3 A continuous. Current operated targets may be selected only when normally open (NO) output contacts have been specified. SURGE WTHSTAND CAPABLTY Qualified to ANS/EEE C37. 90-1978, C37.90a-1974, Surge Withstand Capability Test and EC 255, mpulse Test and Dielectric Test. MECHANCAL Operating Temperature -40 C (-40 F) to +70 C (+158 F) Storage Temperature -65 C (-85 F) to +100 C (+212 F) Case Size: S 1. Weight 13.6 pounds maximum. Shock n standard tests, the relay has withstood 15g in each of three mutually perpendicular axes without structural damage or degradation of performance. Vibration n standard tests, the relay has withstood 2g in each of three mutually perpendicular axes swept over the range of 10 to 500 Hz for a total of six sweeps, 15 minutes for each sweep, without structural damage or degradation of performance. 5

-.--. BE1- GROUND FAULT OVERVOLTAGE -- A B C 528 + CONTROL BUS - CONTROL BUS n PS 12 13 BE1- A B C CONNECTONS ).. \ r' 39 :&,...L.. / ' \ 1 f OWER} ' /,.. Q 4 ) ", r' & ; r 5 1 20 & & T 59 T N 59 N 8 9 18 19 LEGEND: GROUND FAULT OVERVOLTAGE RELAY 52 POWER CRCUT BREAKER V""' TC OV UV PS.& FUSE GROUND FAULT OVERVOL TAGE OVERLAPPNG GROUND FAULT (UNDERVOL T AGE AND OVERVOL T AGE) FGURE 5. TYPCAL CONNECTONS 6 PT BE1- TRP COL OVER VOLT AGE CONTACTS OPT ONAL UNDER VOLT AGE CONTACTS POWER SUPPLY STATUS N.O. CONTACTS SHOWN. ALSO AVALABLE WTH N.C. CONTACTS. TARGET AVALABLE WTH N.O. CONTACTS ONLY. DASHED LNES APPLY ONLY TO D.C. POWERED MODELS. 20 OPT ONAL AUXLARY OVERVOL TAGE RELAY AVALABLE WTH N.O. OR N.C. CONTACTS. OPTONAL AUXLARY UNDERVOLTAGE RELAY AVALABLE WTH N.O. OR N.C. CONTACTS. A B C R UNGROUNDED SYSTEM 6 BE1-7

MODEL NUMBER BE1- Ground Fault Overvoltage Relay. STYLE NUMBER The style number appears on the front panel, drawout cradle, and inside the case assembly. This style number is an alphanumeric combination of characters identifying the features included in a particular unit. The sample style number below illustrates the manner in which the various features are designated. The Style Number dentification Chart (page 8) defines each of the options and characteristics available for this device. SAMPLE STYLE NUMBER: ASF F6J D1 S3F The style number above describes a BE1- Ground Fault Overvoltage Relay having the following features. Sensing nput Type Sensing nput Range (5) SENSNG NPUT TYPE SENSNG NPUT RANGE HOW TO ORDER: (A) Single-phase 120 Vac, 60 Hz (nominal) with 1-20 range OUTPUT TMNG POWER SUPPLY Designate the model number followed by the complete Style Number. BE1-! Style No. 0 0 0-0 0 0-0 0 0 0 0 Complete the Style Number by selecting one feature from each column of the Style Number dentification Chart and entering its designation letter or number into the appropriate square. (Two squares are used to indicate time delay characteristics.) All squares must be completed. ORDERNG Output Timing Power Supply Target Option 1 Option 2 Option 3 Option 4 ---BE1- GROUND FAULT OVERVOLTAGE (F) Two NO output relays: one for the overvoltage function and one for the undervoltage function (F6) nverse for the overvoltage function; definite time for the undervoltage function (J) 125 Vdc or 100/120 Vac (D) Two (one for each function), current operated (1) Undervoltage element (S) Push-to-energize outputs (3) Two NO auxiliary output relays (one per function) (F) Semi-flush mounting NOTE: The description of a complete relay must include both the model number and the style number. TARGET OPTON SAMPLE STYLE NUMBER LLUSTRATED 1 OPTON 2 OPTON 3 OPTON STANDARD ACCESSORES: The following accessories are available for the BE1- Ground Fault Overvoltage Relay. Test Plug To allow testing of the relay without removing system wiring, order two test plugs, Basler Electric part number 10095. Extender Board The extender board permits troubleshooting of the printed circuit boards outside of the relay cradle. Order Basler Electric part number 9 1655 00 100. 7 4

BE1- SENSNG NPUT TYPE A) Single-phase voltage SENSNG NPUT RANGE 1) 100 Vac, 50 Hz, nominal 1-20 2) 100 Vac, 50 Hz, nominal 10-50 3) 200 Vac, 50 Hz, nominal 2-40 4) 200 Vac, 50 Hz, nominal 20-100 5) 120 Vac, 60Hz, nominal 1-20 6) 120 Vac, 60 Hz, nominal 10-50 7) 240 Vac, 60 Hz, nominal 2-40 8) 240 Vac, 60 Hz, nominal 2Q-1 00 STYLE NUMBER DENTFCATON CHART OUTPUT E) One NO relayover F) Two NO relaysb. one over, LZ.i one under G) One NC relayover H) Two NC relays one over, L LZ.ione under NOTES: When target is D, output must be E or F. Requires option 1-1 or option 1-2. 3) All relays are supplied in S1 case. TMNG A 1) Over-instantaneous D1) Over-inverse E1) Over-definite (0.1-99.9 sec.) F1) Over-instantaneous under-definite Li\(0.1-99.9 sec.) F2) Over-instantaneous under-inverse F3) Over-definite 6 (0.1-99.9 sec.) LZ.\ under-instantaneous F4) Over-definite f), (0.1-99.9 sec.) LZ.i under-inverse F5) Over-inverse ffi under-instantaneous F6) Over-inverse L- under-definite LZ.i(0.1-99.9 sec.) F7) Over-definite ffi under-definite BE1- POWER SUPPLY J) 125 Vdc and 100/120 Vac K) 48 Vdc L) 24 Vdc Y) Selectable 48/125 Vac Z) 250 Vdc and 230 Vac TARGET ffi N) None C) nternally Operated D) Current Operated Sensing input range must be 1, 2, 5, or 6. Output must be p or "H". Sensing input range must be 3, 4, 7, or 8. Output must be p or "H'. OPTON 1 0) None 1) Undervoltage element - f), high range 0.5 to 12Vac 1.0 to 24Vac 2) Undervoltage element low range- 0.1 to 2.5Vac 0.2 to 5.0Vac OPTON2 N) None S) Push-toenergize outputs Basler Electric 0) None OPTON 3 1) One NO auxiliary output - over 2) One NC auxiliary output - over 3) Two NO auxiliary outputs-one over, one under 4) Two NC auxiliary outputs-one over, ffione under OPTON4 F) Serli-flush mounting r) Projection mounting ROUTE 143, BOX 269, HGHLAND, LLNOS U.S.A. 62249 P.A.E. Les Pins, 67319 Wasselonne Cedex FRANCE PHONE 618-654-2341 FAX 618-654-2351 PHONE (33-3-88) 87-1010 FAX (33-3-88) 87-0808 051-004 http://www.basler.com, info@basler.com Printed in U.S.A.