INTRODUCTION TERMINAL LAYOUTS FX2N-4AD-TC SPECIAL FUNCTION BLOCK USER S GUIDE

Similar documents
FX-4AD-TC SPECIAL FUNCTION BLOCK USER'S GUIDE

INTRODUCTION TERMINAL LAYOUTS FX2N-4AD SPECIAL FUNCTION BLOCK USER S GUIDE

FX-2DA SPECIAL FUNCTION BLOCK USER'S GUIDE

FX0N-3A SPECIAL FUNCTION BLOCK

LX3V-4AD User manual Website: Technical Support: Skype: Phone: QQ Group: Technical forum:

USER S MANUAL. FX2N-8AD Analog input block

FX2N-2DA SPECIAL FUNCTION BLOCK

ANALOG I/O MODULES AD268 / DA264 / TC218 USER S MANUAL

FX2N-2AD SPECIAL FUNCTION BLOCK

FX2N-232IF RS232C INTERFACE BLOCK

WECON LX3V-2TC2DA BD Board

C200H-AD002/DA002 Analog I/O Units Operation Guide

WECON LX3V-2PT2DA BD Board

PACSystems* RX3i Thermocouple Input Module, 12 Channels, IC695ALG412-CB

MicroLogix 1200 Thermocouple/mV Input Module

PACSystems* RX3i. Isolated Thermocouple Input Module, 6 Channels, IC695ALG306-EB Isolated Thermocouple Input Module, 12 Channels, IC695ALG312-EB

E6CP-A. An Absolute Encoder at About the Same Price as an Incremental Encoder. Ideal for robot limit signals. Low-cost Encoder with Diameter of 50 mm

R1MS-GH3 BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL THERMOCOUPLE & DC INPUT MODULE MODEL. (8 points; isolated)

AI-1204Z-PCI. Features. 10MSPS, 12-bit Analog Input Board for PCI AI-1204Z-PCI 1. Ver.1.04

Operating Instructions

SAFETY PRECAUTIONS. (Read these precautions before using this product.)

WECON LX3V-2PT-BD Module

AI-1664LAX-USB. Features. 100KSPS 16-bit Analog Input Unit for USB AI-1664LAX-USB 1. Ver.1.01

LX3V-2PT-BD User manual

AD12-16U(PCI)EV. Features. High-Speed Analog Input Board for PCI AD12-16U(PCI)EV 1. Ver.1.01

Industriefunkuhren. Technical Manual. IRIG-B Generator-Module for analogue / digital Signals of Type: IRIG-B / IEEE C / AFNOR NF S87-500

AD16-16U(PCI)EV. Features. High-Speed & Resolution Analog Input Board for PCI AD16-16U(PCI)EV 1. Ver.1.02

MELSEC-L Digital-Analog Converter Module User's Manual -L60DA4 -L60DAVL8 -L60DAIL8

Trusted 40 Channel 120 Vac Digital Input FTA

AD16-64(LPCI)LA. Non-isolated high precision analog input board for Low Profile PCI AD16-64(LPCI)LA 1. Ver.1.01

WECON LX3V-2TC-BD Module

Multifunction Digital Timer

32 Channel CPCI Board User Manual

PicoScope 3000 Series Automotive User guide

INSTALLATION AND OPERATION INSTRUCTIONS EVOLUTION VIDEO DISTRIBUTION SYSTEM

MELSEC iq-f FX5 User's Manual (Analog Control - Intelligent function module)

Model Number Structure

Guide for installers. METTLER TOLEDO MultiRange System solution analog Ex1. Hazardous area. Safe area

Trusted 40 Channel 120 Vac Digital Input FTA

Triple RTD. On-board Digital Signal Processor. Linearization RTDs 20 Hz averaged outputs 16-bit precision comparator function.

REMOTE I/O R30 SERIES. PC CONFIGURATOR SOFTWARE Model: R30CFG Ver Users Manual

PicoScope 4000 Automotive PC Oscilloscopes

User Guide. HDMI Fiber Optic Extender. DVI-7350a

Operating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130

A/D and D/A convertor 0(4) 24 ma DC, 16 bits

AI-1616L-LPE. Features. High-precision Analog input board (Low Profile size) for PCI Express AI-1616L-LPE 1. Ver.1.02 Ver.1.01

Data Acquisition Networks. Installing and Configuring the DM01 Hardware

Trusted 40 Channel Analogue Input FTA

Guide for installers. METTLER TOLEDO MultiRange System solution Point Ex.

Accessories. Servo Motors. Servo Motors B-47. Accessories

Installation Manual SaVi Note Underwater LED Light

INSTALLATION AND OPERATION M

K-BUS Dimmer Module User manual-ver. 1

Vorne Industries. 87/719 Analog Input Module User's Manual Industrial Drive Itasca, IL (630) Telefax (630)

NTB-500A. Medium Speed Network Terminal Box. Supports dynamic measurement at medium-speed synchronous sampling!

Preventing Fieldbus Physical Layer Problems

Ordering Information. Absolute 60-mm-dia. Rotary Encoder E6F-A. High Accuracy and Durability for Automatic Equipment.

Installation Guide VL-MV10. Model No.

Driver circuit for MPPC

LED control gear Compact dimming. Uconverter LCAI 2x38 W 0500 K013 one4all ECO series. Ordering data

User Manual. Model 1372A and 1374A HDMI Switchers. 1T-SX-632 Model 1372A 2X1 Switcher. v1.3 2x1 SWITCHER. v1.3 INPUT ENHANCE POWER

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

Thermocouple and RTD Modules for Compact FieldPoint

User Guide UD51. Second encoder small option module for Unidrive. Part Number: Issue Number: 5.

DISTRIBUTION AMPLIFIER

Colour Explosion Proof Video Camera USER MANUAL VID-C

DS 400 P. Intelligent Electronic Pressure Switch in Hygienic Stainless Steel Ball Housing. on hygienic process connections

RF Semiconductor Test AXRF RF Port Upgrade Kits

Standard RS232 RS ma

Analogue output module DAO 081

XW3D. Simple Wiring of Sensor Actuators. Connector Terminal Boxes. Specifications. Materials and Finish. Connection Combinations

Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module

V/L V/H H/L H/H. Satellite - Input. Programmable Cascadable switch. with 32 User Bands with Terrestrial input & 1 Legacy port

Instruction Manual. Universal Flow Controller Model 261 / 261-EC-01

SIMATIC. ET 200S distributed I/O 2AO U HS analog electronic module (6ES7135-4FB52-0AB0) Preface. Properties 1. Parameters 2.

MICROMASTER Encoder Module

Contact-Type Digital Displacement Sensor. HG-S Series. User's Manual WUME-HGS panasonic.net/id/pidsx/global

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

CC-Link IE Field Network Analog-Digital Converter Module User's Manual -NZ2GF2BN-60AD4 -NZ2EX2B-60AD4

HYL-035D0850G103. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

Kramer Electronics, Ltd.

LXM23DU10M3X motion servo drive - Lexium 23 - single phase V - 1 kw - I/O

SOFTLINK 300. Modules Specifications. Reference Manual

AF-300 E11 Adjustable Frequency Drive

ODW-621. RS-232 Point-to-point applications

G5-series AC Servo Drives with Built-in EtherCAT Communications Linear Motor Type

User Manual CC DC 24 V 5A. Universal Control Unit UC-1-E. General Information SET. Universal Control Unit UC-1 Of Central Lubrication PAUSE CONTACT

ORDERING Page 6 BASLER RELAY STANDARDS, DIMENSIONS, ACCESSORIES Request bulletin SDA

SIMATIC. ET 200S distributed I/O IM151-1 BASIC interface module (6ES7151-1CA00-0AB0) Preface. Properties 1. Parameters 2. Error and system messages 3

Rack mounted telephone- and leased line modem for industrial applications

Kramer Electronics, Ltd. USER MANUAL. Model: VP-200Dxl. XGA Differential Amplifier / DA

GT1030-LBD(W) / GT1030-LBD(W)2 GT1020-LBD(W) / GT1020-LBD(W)2 / GT1020-LBL(W)

Kramer Electronics, Ltd. USER MANUAL. Model: FC Analog Video to SDI Converter

Signet 2250 Hydrostatic Level Sensor

K3NX Process Meter OPERATION MANUAL

PicoScope 2000 Series PC Oscilloscopes

Kramer Electronics, Ltd. USER MANUAL. Model: 900xl. Power Amplifier

MCR3 POWER EQUIPMENT. Microprocessor Controlled Constant Current Regulator. Compliance with Standards. Uses. Features

E8Y. Micropressure Sensor with Easy-to-Read Digital Display. Differential Pressure Sensor. Ordering Information. Sensors

MELSEC iq-r Inter-Module Synchronization Function Reference Manual

Transcription:

FX2N-4AD-TC SPECIAL FUNCTION BLOCK USER S GUIDE JY992D65501A This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX2N-4AD-TC special function block and should be read and understood before attempting to install or use the unit. Further information can be found in the FX PROGRAMMING MANUAL and FX2N SERIES HARDWARE MANUAL. 1 INTRODUCTION The FX2N-4AD-TC analog block amplifies the signal from four thermocouple sensors (type K or J) and converts the data into 12 bit reading s stored in the FX2N base unit. Both Centigrade ( C) and Fahrenheit ( F) can be read. Reading resolution is 0.4 C/0.72 F of type K and 0.3 C/0.54 F of type J. All data transfers and parameter settings are adjusted through software control of the FX2N-4AD-TC ; by use of the TO/ applied instructions in the FX2N PC. The FX2N-4AD-TC occupies 8 points of I/O on the FX2N expansion bus. The 8 points can be allocated from either inputs or outputs. The FX2N-4AD-TC draws 40mA from the 5V rail of the FX2N base unit or powered extension unit. Thermocouples with the following specifications can be used: Type K (JIS 1602-1981) Type J (JIS 1602-1981) 1.1 EXTERNAL DIMENSIONS Weight: Approx. 0.3 kg (0.66 lbs) Dimensions: mm (inches) Accessories: Self adhesive labels for special function block number identification. 2 Thermocouple 1 SLD shielded 3KW L+ L- Thermocouple 1 shielded 24VDC±10% 50mA 4 24+ 24- Class 3 Grounding PC (100 Wor less) Extension cable 3 L+ L- 2 SLD 3KW DC/DC Temperature compensation circuit FX2N-4AD-TC Analog Input Block TERMINAL LAYOUTS +15V AG -15V *1: The compensating cables that can be used for connecting with the thermocouple are the following. Type K: KX-G, KX-GS, KX-H, KX-HS,WX-G,WX-H,VX-G Type J: JX-G, JX-H For every 10Ω of line resistance, the compensating cable will indicate a temperature 0.12 C higher than actual. Check the line resistance before using. Long compensating cables are more prone to noise interference, therefore a short (less than 100m) compensating cable is recommended. Unused channels should have a wire link connected between their + and - terminals to prevent an error being detected on that channel. *2: If there is excessive electrical noise, connect the SLD terminal to the ground terminal on the unit. *3: Connect the ground terminals of the FX2N-4AD-TC unit and the base unit. Use class 3 grounding on the base unit. *4: The 24V DC built-in supply of the programmable controller may be used as the power supply.

3 3.1 Environmental specification INSTALLATION NOTES AND USAGE Environmental specifications (excluding following) Dielectric withstand voltage Same as those for the FX2N base unit 500VAC, 1min (between all terminals and ground) 3.2 Power supply specification Analog circuits Digital circuits 24V DC ±10%, 60mA 5V DC, 40mA (internal power supply from base unit 3.3 Performance specification Analog Inputs Centigrade ( C) Fahrenheit ( F) Both C and F are available by reading the appropriate buffer memory (BFM). Input signal Thermocouple: type K or J (either can be used for each channel), 4 channels, JIS 1602-1981 Rated temprature Type K -100 C to +1,200 C Type K -148 F to +2,192 F range Type J -100 C to +600 C Type J -148 F to +1,112 F Digital output Resolution Overall accuracy Calibration point Conversion speed 12 bit conversion stored in 16 bit 2 s complement form Type K -1,000 to 12,000 Type K -1,480 to 21,920 Type J -1,000 to 6,000 Type J -1,480 to 11,120 Type K 0.4 C Type K 0.72 F Type J 0.3 C Type J 0.54 F ± (0.5% full scall +1 C) Freezing point of pure water 0 C / 32 F (240ms ± 2%) 4 channels (unused channels are not converted) Note : Earth-tipped thermocouples are not suitable for use with this unit. Analog Inputs continued... Conversion Characteristics (Type K) +12,000 (Type K) +21,920 (Type J) +6,000 (Type J) +11,120 Readings given at calibration reference point 0 C/32 F (0/320) respectively. (subject to the overall accuracy) -100 C -1,000-148 F +600 C +1,200 C (Type J) (Type K) -1,480 +1,112 F +2,192 F (Type J) (Type K) Miscellaneous Isolation Number of occupied I/O points Photo-coupler isolation between analog and digital circuits. DC/DC isolation of power from FX2N base unit. No isolation between analog channels. 8 points taken from the FX2N expansion bus (can be either inputs or outputs) 3.4 Buffer memory assignment *#0 BFM CONTENTS Thermocouuple type K or J selection mode. At shipment: H0000 *#1-#4 to Averaged temperature reading to be averaged (1 to 256) Default = 8 #5-#8 to Averaged temprature in 0.1 C units #9-#12 to Present temprature in 0.1 C units #13-#16 to Averaged temprature in 0.1 F units #17-#20 to Present temprature in 0.1 F units #21-#27 Reserved *#28 Digital range error latch #29 Error status #30 Identification code K2030 #31 Reserved The FX2N-4AD-TC communicates with the programmable controller through use of buffer memories. BFMs #21 to #27 and #31 are reserved. All non reserved BFMs can be read by the programmable controller using the command. BFMs (buffer memories) marked with an * can be written to, from the programmable controller using the TO command.

(1) Buffer Memory BFM #0: Thermocouple type K or J selection mode BFM #0 is used to select K or J type thermocouples for each channel. Each digit of a 4 digit hexadecimal number corresponds to one channel, the least significant digit being channel 1. [ Example ] H 3310 CH2 CH3 0 = K type 1 = J type 3 = Not used A/D conversion time is 240ms per channel. When 3" (not used) is set for a channel, A/D conversion is not executed for that channel and so the total conversion time is decreased. In the above example, the conversion time is as follows: 240ms (conversion time per channel) 2channels (number of channels being used) = 480ms (total conversion time) (2) Buffer Memory BFMs #1 to #4: Number of temperature readings to be averaged When the number of temperature readings to be averaged is specified for BFMs #1 to #4, the averaged data is stored in BFMs #5 to #8 ( C) and #13 to #16 ( F). Only the range 1 to 256 is valid for the number of temperature readings to be averaged. If a value outside of this range is input, the default value of 8 is used. (3) Buffer Memory BFMs #9 to #12 and #17 to #20: Present temperature These BFMs store the present value of the input data. This value is stored in units of 0.1 C or 0.1 F, but the resolution is only 0.4 C or 0.72 F for type K and 0.3 C or 0.54 F for type J. 3.5 Status Information (1) Buffer Memory BFM #28: Digital range error latch BFM #29 b10(digital range error) is used to judge whether the measured temperature is within the unit s range or not. BFM #28 latches the error status of each channel and can be used to check for thermocouple disconnection. b15 or b8 b7 b6 b5 b4 b3 b2 b1 b0 Not used High Low High Low High Low High Low CH3 CH2 Low : Latches ON when temperature measurement data goes below the lowest temperature measurement limit. High : Turns ON when temperature measurement data goes above the highest temperature measurement limit, or when a thermocouple is disconnected. When an error occurs the temperature data before the error is latched. If the measured value returns to within valid limits the temperature data returns to normal operation. (Note: The error remains latched in (BFM #28)) An error can be cleared by writing K0 to BFM #28 using the TO instruction or turning off the power. (2) Buffer Memory BFM #29: Error status Bit devices of BFM #29 ON OFF b0 : Error When either b2 or b3 is ON A/D conversion is stopped for the error channel No error b1 : Not used b2 : Power source 24VDC power supply failure power supply normal b3 : Hardware error A/D or other hardware failure Hardware Normal b4 to b9 : Not used b10 : Digital range error b11 : Averaging number error Digital output/analog input value is outside the specified range. Selected number of averaged results is outside the available range -see BFM #1 to #4 Digital output value is normal. Averaging is normal. (between 1 to 256) b12 to b15 : Not used (3) Identification Code Buffer Memory BFM #30 The identification code or ID number for a Special Block is read from buffer memory BFM #30 using the command. This number for the FX2N-4AD-TC unit is K2030. The programmable controller can use this facility in its program to identify the special block before commencing data transfer to and from the special block. 3.6 Installation location This unit measures temperature according to the temperature difference between the temperature measurement part (themocouple) and the terminal block. If this unit is installed in a place where the temperature of the terminal block varies rapidly, a measuring error may occur. For this reason, the unit should be installed in a place free from excessive temperature variation. 3.7 Using crimp terminations Use crimp terminations of the type indicated on the left. Secure the termination using a tightening torque of between 5 and 8 kg cm. Wire only to the module terminals discussed in this manual. Leave all others vacant.

4 SYSTEM BLOCK DIAGRAM FX2N series Command information write and data status read DC24V Power Source POWER LED 5V Power Supply Buffer TO Memory RAM CPU System ROM DC/DC FX2N-4AD-TC Analog Block Photocoupler Converted data Control signals ±15V Gain and offset values are stored in EEPROM 5V 24V LED A/D A/D LED Cyclic switching Analog Input Noncontact analog switch CH2 CH3 5 EXAMPLE PROGRAM In the program shown below, the FX2N-4AD-TC occupies the position of special block number 2 ( that is the third closest block to the programmable controller). A type K thermocouple is used on and a type J on CH2. CH3 and are not used. The averaging count is four. The averaged values in degrees C of input channels and CH2 are stored respectively in data registers D0 and D1. M8002 Initial Pulse M8002 Initial Pulse FNC79 TO FNC10 CMP K2 K0 H3310 K1 K2 K30 D2 K1 Specify the type of thermocouple. H3310 Block No.2 BFM#0 and CH3: not used CH2: type J(1) : type K(0) Block No.2 BFM #30 (D2) Identification code K2030 D2 M0 When (K2030) = (D2), M1 = ON. i.e. When identification code is K2030, M1 = ON. This initial step checks that the special function block placed at position 2 is actually an FX2N-4AD-TC, i.e. its unit identification number is 2030 (BFM #30). This step is optional, but it provides a software check that the system has been configured correctly. M8000 RUN monitor M10 Block No.2 BFM #29 (K4M10) Transfer the error status to (M25 to M10). When error is found, M10 = ON Represents b0 BFM #29 M3 Error found This step provides optional monitoring of the FX2N-4AD-TC Error Buffer Memory (#29). If there is an Error on the FX2N-4AD-TC, bit b0 of BFM #29 will be set on. This can be read by this program step, and output as a bit device in the FX2N programmable controller (M3 in this example). Additional Error devices can be output in a similar manner, e.g. b10 BFM #29 Digital range error. (see below) M8000 M10 M3 Represents b0 BFM #29 M20 M4 Represents b10 BFM #29 M1 FNC79 TO P K2 K1 K4 K2 (K4) (BFM #1), (K4) (BFM #2) Number of samples is changed to four on both and CH2. K2 K5 D0 K2 (BFM #5) (D0), (BFM #6) (D1) Transfer the averaged temperature value in C to the data registers. This step is the actual reading of the FX2N-4AD-TC input channels. It is essentially the only program step which is needed. The TO instruction in this example, sets the input channels, and CH2, to take the average reading of four samples. The instruction reads the average temperatures (BFM #5 and #6) for input channels and CH2 of the FX2N-4AD-TC. If direct temperature readings are required BFM #9 and #10 should be read instead, e.g. special FX2N-4AD-TC result No. of block No.2 BFM number destination words read

6 DIAGNOSTICS 6.1 _Preliminary checks I. Check whether the input/output wiring and/or extension cables are properly connected on FX2N-4AD-TC analog special function block II. Check that the FX2N system configuration rules have not been broken, i.e. the number of special function blocks does not exceed 8 and the total system I/O is equal or less than 256, I/O. III. Ensure that the correct operating range has been selected for the application. IV. Check that there is no power overload on either the 5V or 24V power sources, remember the loading on the FX2N base unit or a powered extension unit varies according to the number of extension blocks or special function blocks connected. V. Put the FX2N base unit into RUN. 6.2 Error checking If the FX2N-4AD-TC special function blcok does not seem to operate normally, check the following items. Check the status of the POWER LED. Lit : The extension cable is properly connected. Otherwise : Check the connection of the extension cable. Check the external wiring. Check the status fo the 24V LED (top right corner of the FX2N-4AD-TC). Lit : FX2N-4AD-TC is ON, 24VDC power source is ON. Otherwise : Possible 24VDC power failure, if ON possible FX2N-4AD-TC failure. Check the status fo the A/D LED (top right corner of the FX2N-4AD-TC). Lit : A/D conversion is proceeding normally. Otherwise : Check buffer memory #29 (error status). If any bits (b0, b2, b3) are ON, then this is why the A/D LED is OFF. 6.3 Checking special function block numbers Other special units of blocks that use /TO commands, such as analog input blocks, analog output blocks and high-speed counter blocks, can be directly connected to the base unit of the FX2N programmable controller or to the right side of other extension blocks or units. Each special block is consecutively numbered from 0 to 7 beginning from the one closest to the base unit. A maximum of eight special blocks can be connected. 7 EMC CONSIDERATIONS Electromagnetic compatibility or EMC must be considered before using the FX2N-4AD-TC. Mitsubishi recommend that the thermocouple sensors used, should be fitted with a form of seild or screening as protection against EMC noise. If some form of cable protection is used, the Shield must be terminated at the SLD terminals as shown in chapter 2. Because of the delicate nature of all analog signals, failure to take good EMC precautions could lead to EMC noise induced errors ; up to ±10% of actual values. This is an absolute worst case figure, users who do take good precautions can expect operation within normal tolerances. EMC considerations should include selection of good quality cables, good routing of those cables away from potential noise sources. Additionally it is recommended that signal averaging is used as this will reduce the effects of random noise spikes.

Guidelines for the safety of the user and protection of the FX2N-4AD-TC special function block This manual has been written to be used by trained and competent personnel. This is defined by the European directives for machinery, low voltage and EMC. If in doubt at any stage during the installation of the FX2N-24AD-TC always consult a professional electrical engineer who is qualified and trained to the local and national standards. If in doubt about the operation or use of the FX2N-4AD-TC please consult the nearest Mitsubishi Electric distributor. Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment. All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples. Manual number : JY992D65501 Manual revision : A Date : JUNE 1997 HEAD OFFICE:MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100 TELEX:J24532 CABLE MELCO TOKYO HIMEJI WORKS:840, CHIYODA CHO, HIMEJI, JAPAN JY992D65501A Effective JUN. 1997 s are subject to change without notice

FX2N-4AD-TC SPECIAL FUNCTION BLOCK USER S GUIDE JY992D65501A This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX2N-4AD-TC special function block and should be read and understood before attempting to install or use the unit. Further information can be found in the FX PROGRAMMING MANUAL and FX2N SERIES HARDWARE MANUAL. 3 INSTALLATION NOTES AND USAGE 3.1 Environmental specification Environmental specifications (excluding following) Same as those for the FX2N base unit Dielectric withstand voltage 500VAC, 1min (between all terminals and ground) 3.2 Power supply specification Analog circuits 24V DC ±10%, 60mA Digital circuits 5V DC, 40mA (internal power supply from base unit (1) Buffer Memory BFM #0: Thermocouple type K or J selection mode BFM #0 is used to select K or J type thermocouples for each channel. Each digit of a 4 digit hexadecimal number corresponds to one channel, the least significant digit being channel 1. [ Example ] H 3310 CH2 CH3 0 = K type 1 = J type 3 = Not used A/D conversion time is 240ms per channel. When 3" (not used) is set for a channel, A/D conversion is not executed for that channel and so the total conversion time is decreased. In the above example, the conversion time is as follows: 240ms (conversion time per channel) 2channels (number of channels being used) = 480ms (total conversion time) (2) Buffer Memory BFMs #1 to #4: Number of temperature readings to be averaged When the number of temperature readings to be averaged is specified for BFMs #1 to #4, the averaged data is stored in BFMs #5 to #8 ( C) and #13 to #16 ( F). Only the range 1 to 256 is valid for the number of temperature readings to be averaged. If a value outside of this range is input, the default value of 8 is used. (3) Buffer Memory BFMs #9 to #12 and #17 to #20: Present temperature These BFMs store the present value of the input data. This value is stored in units of 0.1 C or 0.1 F, but the resolution is only 0.4 C or 0.72 F for type K and 0.3 C or 0.54 F for type J. 1 INTRODUCTION The FX2N-4AD-TC analog block amplifies the signal from four thermocouple sensors (type K or J) and converts the data into 12 bit reading s stored in the FX2N base unit. Both Centigrade ( C) and Fahrenheit ( F) can be read. Reading resolution is 0.4 C/0.72 F of type K and 0.3 C/0.54 F of type J. All data transfers and parameter settings are adjusted through software control of the FX2N-4AD-TC ; by use of the TO/ applied instructions in the FX2N PC. The FX2N-4AD-TC occupies 8 points of I/O on the FX2N expansion bus. The 8 points can be allocated from either inputs or outputs. The FX2N-4AD-TC draws 40mA from the 5V rail of the FX2N base unit or powered extension unit. Thermocouples with the following specifications can be used: Type K (JIS 1602-1981) Type J (JIS 1602-1981) 3.3 Performance specification Analog Inputs Centigrade ( C) Fahrenheit ( F) Both C and F are available by reading the appropriate buffer memory (BFM). Input signal Thermocouple: type K or J (either can be used for each channel), 4 channels, JIS 1602-1981 Rated temprature Type K -100 C to +1,200 C Type K -148 F to +2,192 F range Type J -100 C to +600 C Type J -148 F to +1,112 F Digital output Resolution Overall accuracy Calibration point Conversion speed 12 bit conversion stored in 16 bit 2 s complement form Type K -1,000 to 12,000 Type K -1,480 to 21,920 Type J -1,000 to 6,000 Type J -1,480 to 11,120 Type K 0.4 C Type K 0.72 F Type J 0.3 C Type J 0.54 F ± (0.5% full scall +1 C) Freezing point of pure water 0 C / 32 F (240ms ± 2%) 4 channels (unused channels are not converted) Note : Earth-tipped thermocouples are not suitable for use with this unit. 3.5 Status Information (1) Buffer Memory BFM #28: Digital range error latch BFM #29 b10(digital range error) is used to judge whether the measured temperature is within the unit s range or not. BFM #28 latches the error status of each channel and can be used to check for thermocouple disconnection. b15 or b8 b7 b6 b5 b4 b3 b2 b1 b0 High Low High Low High Low High Low Not used CH3 CH2 Low : Latches ON when temperature measurement data goes below the lowest temperature measurement limit. High : Turns ON when temperature measurement data goes above the highest temperature measurement limit, or when a thermocouple is disconnected. When an error occurs the temperature data before the error is latched. If the measured value returns to within valid limits the temperature data returns to normal operation. (Note: The error remains latched in (BFM #28)) An error can be cleared by writing K0 to BFM #28 using the TO instruction or turning off the power. 1.1 EXTERNAL DIMENSIONS Weight: Approx. 0.3 kg (0.66 lbs) Dimensions: mm (inches) Accessories: Self adhesive labels for special function block number identification. Analog Inputs continued... Conversion Characteristics Readings given at calibration reference point 0 C/32 F (0/320) respectively. (subject to the overall accuracy) Miscellaneous Isolation Number of occupied I/O points (Type K) +12,000 (Type J) +6,000-100 C -1,000 (Type K) +21,920 (Type J) +11,120-148 F +600 C +1,200 C (Type J) (Type K) -1,480 Photo-coupler isolation between analog and digital circuits. DC/DC isolation of power from FX2N base unit. No isolation between analog channels. 8 points taken from the FX2N expansion bus (can be either inputs or outputs) +1,112 F +2,192 F (Type J) (Type K) (2) Buffer Memory BFM #29: Error status Bit devices of BFM #29 ON OFF b0 : Error When either b2 or b3 is ON A/D conversion is stopped for the error channel No error b1 : Not used b2 : Power source 24VDC power supply failure power supply normal b3 : Hardware error A/D or other hardware failure Hardware Normal b4 to b9 : Not used b10 : Digital range error b11 : Averaging number error Digital output/analog input value is outside the specified range. Selected number of averaged results is outside the available range -see BFM #1 to #4 Digital output value is normal. Averaging is normal. (between 1 to 256) b12 to b15 : Not used (3) Identification Code Buffer Memory BFM #30 The identification code or ID number for a Special Block is read from buffer memory BFM #30 using the command. This number for the FX2N-4AD-TC unit is K2030. The programmable controller can use this facility in its program to identify the special block before commencing data transfer to and from the special block. 2 Thermocouple 1 SLD shielded 3KW L+ L- Thermocouple 1 shielded 24VDC±10% 50mA 4 24+ 24- Class 3 Grounding PC (100 Wor less) Extension cable 3 L+ L- 2 SLD 3KW DC/DC Temperature compensation circuit FX2N-4AD-TC Analog Input Block TERMINAL LAYOUTS +15V AG -15V *1: The compensating cables that can be used for connecting with the thermocouple are the following. Type K: KX-G, KX-GS, KX-H, KX-HS,WX-G,WX-H,VX-G Type J: JX-G, JX-H For every 10Ω of line resistance, the compensating cable will indicate a temperature 0.12 C higher than actual. Check the line resistance before using. Long compensating cables are more prone to noise interference, therefore a short (less than 100m) compensating cable is recommended. Unused channels should have a wire link connected between their + and - terminals to prevent an error being detected on that channel. *2: If there is excessive electrical noise, connect the SLD terminal to the ground terminal on the unit. *3: Connect the ground terminals of the FX2N-4AD-TC unit and the base unit. Use class 3 grounding on the base unit. *4: The 24V DC built-in supply of the programmable controller may be used as the power supply. 3.4 Buffer memory assignment *#0 BFM CONTENTS Thermocouuple type K or J selection mode. At shipment: H0000 *#1-#4 to Averaged temperature reading to be averaged (1 to 256) Default = 8 #5-#8 to Averaged temprature in 0.1 C units #9-#12 to Present temprature in 0.1 C units #13-#16 to Averaged temprature in 0.1 F units #17-#20 to Present temprature in 0.1 F units #21-#27 Reserved *#28 Digital range error latch #29 Error status #30 Identification code K2030 #31 Reserved The FX2N-4AD-TC communicates with the programmable controller through use of buffer memories. BFMs #21 to #27 and #31 are reserved. All non reserved BFMs can be read by the programmable controller using the command. BFMs (buffer memories) marked with an * can be written to, from the programmable controller using the TO command. 3.6 Installation location This unit measures temperature according to the temperature difference between the temperature measurement part (themocouple) and the terminal block. If this unit is installed in a place where the temperature of the terminal block varies rapidly, a measuring error may occur. For this reason, the unit should be installed in a place free from excessive temperature variation. 3.7 Using crimp terminations Use crimp terminations of the type indicated on the left. Secure the termination using a tightening torque of between 5 and 8 kg cm. Wire only to the module terminals discussed in this manual. Leave all others vacant.

4 SYSTEM BLOCK DIAGRAM 6 6.1 _Preliminary checks DIAGNOSTICS FX2N series Command information write and data status read DC24V Power Source POWER LED 5V Power Supply Buffer TO Memory RAM CPU System ROM DC/DC FX2N-4AD-TC Analog Block Photocoupler Converted data Control signals ±15V Gain and offset values are stored in EEPROM 5V 24V LED A/D A/D LED Cyclic switching Analog Input Noncontact analog switch CH2 CH3 I. Check whether the input/output wiring and/or extension cables are properly connected on FX2N-4AD-TC analog special function block II. Check that the FX2N system configuration rules have not been broken, i.e. the number of special function blocks does not exceed 8 and the total system I/O is equal or less than 256, I/O. III. Ensure that the correct operating range has been selected for the application. IV. Check that there is no power overload on either the 5V or 24V power sources, remember the loading on the FX2N base unit or a powered extension unit varies according to the number of extension blocks or special function blocks connected. V. Put the FX2N base unit into RUN. 5 In the program shown below, the FX2N-4AD-TC occupies the position of special block number 2 ( that is the third closest block to the programmable controller). A type K thermocouple is used on and a type J on CH2. CH3 and are not used. The averaging count is four. The averaged values in degrees C of input channels and CH2 are stored respectively in data registers D0 and D1. M8002 Initial Pulse M8002 Initial Pulse FNC79 TO FNC10 CMP K2 K0 H3310 K1 K2 K30 D2 K1 EXAMPLE PROGRAM Specify the type of thermocouple. H3310 Block No.2 BFM#0 and CH3: not used CH2: type J(1) : type K(0) Block No.2 BFM #30 (D2) Identification code K2030 D2 M0 When (K2030) = (D2), M1 = ON. i.e. When identification code is K2030, M1 = ON. This initial step checks that the special function block placed at position 2 is actually an FX2N-4AD-TC, i.e. its unit identification number is 2030 (BFM #30). This step is optional, but it provides a software check that the system has been configured correctly. 6.2 Error checking If the FX2N-4AD-TC special function blcok does not seem to operate normally, check the following items. Check the status of the POWER LED. Lit : The extension cable is properly connected. Otherwise : Check the connection of the extension cable. Check the external wiring. Check the status fo the 24V LED (top right corner of the FX2N-4AD-TC). Lit : FX2N-4AD-TC is ON, 24VDC power source is ON. Otherwise : Possible 24VDC power failure, if ON possible FX2N-4AD-TC failure. Check the status fo the A/D LED (top right corner of the FX2N-4AD-TC). Lit : A/D conversion is proceeding normally. Otherwise : Check buffer memory #29 (error status). If any bits (b0, b2, b3) are ON, then this is why the A/D LED is OFF. M8000 RUN monitor M10 Block No.2 BFM #29 (K4M10) Transfer the error status to (M25 to M10). When error is found, M10 = ON Represents b0 BFM #29 M3 Error found This step provides optional monitoring of the FX2N-4AD-TC Error Buffer Memory (#29). If there is an Error on the FX2N-4AD-TC, bit b0 of BFM #29 will be set on. This can be read by this program step, and output as a bit device in the FX2N programmable controller (M3 in this example). Additional Error devices can be output in a similar manner, e.g. b10 BFM #29 Digital range error. (see below) 6.3 Checking special function block numbers Other special units of blocks that use /TO commands, such as analog input blocks, analog output blocks and high-speed counter blocks, can be directly connected to the base unit of the FX2N programmable controller or to the right side of other extension blocks or units. Each special block is consecutively numbered from 0 to 7 beginning from the one closest to the base unit. A maximum of eight special blocks can be connected. Guidelines for the safety of the user and protection of the FX2N-4AD-TC special function block This manual has been written to be used by trained and competent personnel. This is defined by the European directives for machinery, low voltage and EMC. If in doubt at any stage during the installation of the FX2N-24AD-TC always consult a professional electrical engineer who is qualified and trained to the local and national standards. If in doubt about the operation or use of the FX2N-4AD-TC please consult the nearest Mitsubishi Electric distributor. M8000 M10 M20 M3 M4 Represents b0 BFM #29 Represents b10 BFM #29 Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment. All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples. M1 FNC79 TO P K2 K1 K4 K2 (K4) (BFM #1), (K4) (BFM #2) Number of samples is changed to four on both and CH2. K2 K5 D0 K2 (BFM #5) (D0), (BFM #6) (D1) Transfer the averaged temperature value in C to the data registers. This step is the actual reading of the FX2N-4AD-TC input channels. It is essentially the only program step which is needed. The TO instruction in this example, sets the input channels, and CH2, to take the average reading of four samples. The instruction reads the average temperatures (BFM #5 and #6) for input channels and CH2 of the FX2N-4AD-TC. If direct temperature readings are required BFM #9 and #10 should be read instead, e.g. special FX2N-4AD-TC result No. of block No.2 BFM number destination words read 7 EMC CONSIDERATIONS Electromagnetic compatibility or EMC must be considered before using the FX2N-4AD-TC. Mitsubishi recommend that the thermocouple sensors used, should be fitted with a form of seild or screening as protection against EMC noise. If some form of cable protection is used, the Shield must be terminated at the SLD terminals as shown in chapter 2. Because of the delicate nature of all analog signals, failure to take good EMC precautions could lead to EMC noise induced errors ; up to ±10% of actual values. This is an absolute worst case figure, users who do take good precautions can expect operation within normal tolerances. EMC considerations should include selection of good quality cables, good routing of those cables away from potential noise sources. Additionally it is recommended that signal averaging is used as this will reduce the effects of random noise spikes. Manual number : JY992D65501 Manual revision : A Date : JUNE 1997 HEAD OFFICE:MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100 TELEX:J24532 CABLE MELCO TOKYO HIMEJI WORKS:840, CHIYODA CHO, HIMEJI, JAPAN JY992D65501A Effective JUN. 1997 s are subject to change without notice