FX-4AD-TC SPECIAL FUNCTION BLOCK USER'S GUIDE

Similar documents
INTRODUCTION TERMINAL LAYOUTS FX2N-4AD-TC SPECIAL FUNCTION BLOCK USER S GUIDE

INTRODUCTION TERMINAL LAYOUTS FX2N-4AD SPECIAL FUNCTION BLOCK USER S GUIDE

FX-2DA SPECIAL FUNCTION BLOCK USER'S GUIDE

FX0N-3A SPECIAL FUNCTION BLOCK

LX3V-4AD User manual Website: Technical Support: Skype: Phone: QQ Group: Technical forum:

USER S MANUAL. FX2N-8AD Analog input block

ANALOG I/O MODULES AD268 / DA264 / TC218 USER S MANUAL

FX2N-232IF RS232C INTERFACE BLOCK

FX2N-2DA SPECIAL FUNCTION BLOCK

FX2N-2AD SPECIAL FUNCTION BLOCK

WECON LX3V-2TC2DA BD Board

WECON LX3V-2PT2DA BD Board

R1MS-GH3 BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL THERMOCOUPLE & DC INPUT MODULE MODEL. (8 points; isolated)

C200H-AD002/DA002 Analog I/O Units Operation Guide

MicroLogix 1200 Thermocouple/mV Input Module

PACSystems* RX3i Thermocouple Input Module, 12 Channels, IC695ALG412-CB

PACSystems* RX3i. Isolated Thermocouple Input Module, 6 Channels, IC695ALG306-EB Isolated Thermocouple Input Module, 12 Channels, IC695ALG312-EB

AD16-16U(PCI)EV. Features. High-Speed & Resolution Analog Input Board for PCI AD16-16U(PCI)EV 1. Ver.1.02

SAFETY PRECAUTIONS. (Read these precautions before using this product.)

AI-1204Z-PCI. Features. 10MSPS, 12-bit Analog Input Board for PCI AI-1204Z-PCI 1. Ver.1.04

E6CP-A. An Absolute Encoder at About the Same Price as an Incremental Encoder. Ideal for robot limit signals. Low-cost Encoder with Diameter of 50 mm

Industriefunkuhren. Technical Manual. IRIG-B Generator-Module for analogue / digital Signals of Type: IRIG-B / IEEE C / AFNOR NF S87-500

AD12-16U(PCI)EV. Features. High-Speed Analog Input Board for PCI AD12-16U(PCI)EV 1. Ver.1.01

LX3V-2PT-BD User manual

AD16-64(LPCI)LA. Non-isolated high precision analog input board for Low Profile PCI AD16-64(LPCI)LA 1. Ver.1.01

AI-1664LAX-USB. Features. 100KSPS 16-bit Analog Input Unit for USB AI-1664LAX-USB 1. Ver.1.01

Operating Instructions

MELSEC-L Digital-Analog Converter Module User's Manual -L60DA4 -L60DAVL8 -L60DAIL8

WECON LX3V-2PT-BD Module

AI-1616L-LPE. Features. High-precision Analog input board (Low Profile size) for PCI Express AI-1616L-LPE 1. Ver.1.02 Ver.1.01

Contact-Type Digital Displacement Sensor. HG-S Series. User's Manual WUME-HGS panasonic.net/id/pidsx/global

WECON LX3V-2TC-BD Module

Data Acquisition Networks. Installing and Configuring the DM01 Hardware

Accessories. Servo Motors. Servo Motors B-47. Accessories

MELSEC iq-f FX5 User's Manual (Analog Control - Intelligent function module)

REMOTE I/O R30 SERIES. PC CONFIGURATOR SOFTWARE Model: R30CFG Ver Users Manual

Guide for installers. METTLER TOLEDO MultiRange System solution analog Ex1. Hazardous area. Safe area

Trusted 40 Channel 120 Vac Digital Input FTA

Preventing Fieldbus Physical Layer Problems

Model Number Structure

Installation Guide VL-MV10. Model No.

Triple RTD. On-board Digital Signal Processor. Linearization RTDs 20 Hz averaged outputs 16-bit precision comparator function.

Trusted 40 Channel Analogue Input FTA

On-screen display signal strength meter Version 1.02

PicoScope 3000 Series Automotive User guide

NTB-500A. Medium Speed Network Terminal Box. Supports dynamic measurement at medium-speed synchronous sampling!

Vorne Industries. 87/719 Analog Input Module User's Manual Industrial Drive Itasca, IL (630) Telefax (630)

INSTALLATION AND OPERATION INSTRUCTIONS EVOLUTION VIDEO DISTRIBUTION SYSTEM

32 Channel CPCI Board User Manual

PicoScope 4000 Automotive PC Oscilloscopes

Trusted 40 Channel 120 Vac Digital Input FTA

BL67 electronic module 2 analog inputs for thermoelements BL67-2AI-TC

CC-Link IE Field Network Analog-Digital Converter Module User's Manual -NZ2GF2BN-60AD4 -NZ2EX2B-60AD4

Kramer Electronics, Ltd. USER MANUAL. Model: VP-200Dxl. XGA Differential Amplifier / DA

Analogue output module DAO 081

Instruction Manual. Universal Flow Controller Model 261 / 261-EC-01

Guide for installers. METTLER TOLEDO MultiRange System solution Point Ex.

Ordering Information. Absolute 60-mm-dia. Rotary Encoder E6F-A. High Accuracy and Durability for Automatic Equipment.

General Wiring and Installation Guidelines. Typical Mounting Installations Electrical Connections General Guidelines Common Questions & Answers

Kramer Electronics, Ltd.

Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module

Kramer Electronics, Ltd. USER MANUAL. Model: VP-100. VGA/XGA to RGBHV Converter

DS 400 P. Intelligent Electronic Pressure Switch in Hygienic Stainless Steel Ball Housing. on hygienic process connections

DLM471S-5.1 MULTICHANNEL AUDIO LEVEL MASTER OPERATION MANUAL IB B. (Mounted in RMS400 Rack Mount & Power Supply) (One of 4 Typical Cards)

LED control gear Compact dimming. Uconverter LCAI 2x38 W 0500 K013 one4all ECO series. Ordering data

User Manual. Model 1372A and 1374A HDMI Switchers. 1T-SX-632 Model 1372A 2X1 Switcher. v1.3 2x1 SWITCHER. v1.3 INPUT ENHANCE POWER

STBART0200K standard analog input kit STB - 2 I - 15 bits + sign

EZCOM-1. PLC - to - AMS MESSAGE DISPLAY INTERFACE INSTALLATION AND OPERATING INSTRUCTIONS. Rev March, 2001

Kramer Electronics, Ltd. USER MANUAL. Model: VM Video Component Distributor

PROGRAMMABLE DC SOURCE VIEW RECORDERS Programmable DC Source FEATURES

Driver circuit for MPPC

Kramer Electronics, Ltd. USER MANUAL. Model: FC Analog Video to SDI Converter

General Specifications

Multifunction Digital Timer

A/D and D/A convertor 0(4) 24 ma DC, 16 bits

SUBCARRIER TRANSFER FILTER INSTRUCTION BOOK IB622702

MINI MCR-SL-F-UI-NC. Frequency transducers. Data sheet. 1 Description

SOFTLINK 300. Modules Specifications. Reference Manual

Kramer Electronics, Ltd. USER MANUAL. Model: PT-102VN. 1:2 Video DA

1. Overview. SSI-1016G interfaces with 24, 25 and 26 bit Temposonics SSI sensor. Block diagram. as PNP open collector output

Process Transmitter RMA 422

K-BUS Dimmer Module User manual-ver. 1

User Guide. HDMI Fiber Optic Extender. DVI-7350a

Installation Manual SaVi Note Underwater LED Light

MELSEC iq-r Channel Isolated Digital-Analog Converter Module User's Manual (Application) -R60DA8-G -R60DA16-G -RY40PT5B-AS

Operation Manual TX20 1/8 DIN Microcomputer Based ph/orp Controller with relays

DS 200 P DS 200 P. Electronic Pressure Switch with Flush Process Connection

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

Thermocouple and RTD Modules for Compact FieldPoint

ZN-PD-SA. Air Particle Sensor. Continuously monitor dust fallout and particles which detract from product quality. Ordering Information.

Z-D-IN. RS485 Modbus Module 5 Digital Inputs

Model /29S RF Splitter

DISTRIBUTION AMPLIFIER

Kramer Electronics, Ltd. USER MANUAL. Model: 900xl. Power Amplifier

User Guide UD51. Second encoder small option module for Unidrive. Part Number: Issue Number: 5.

SCALE & WEIGHT DISPLAYS

OPERATION MANUAL JENDPM008 THERMOCOUPLE PANEL THERMOMETER. TIP TEMPerature Products 340 W Broad Street Burlington, NJ 08016

Panel-mounting thermostats, type series EM

ACTIVE IF SPLITTER/COMBINER UHP-IFS

AES-402 Automatic Digital Audio Switcher/DA/Digital to Analog Converter

Transcription:

FX-4AD-TC SPECIAL FUNCTION BLOCK USER'S GUIDE JY992D55901A This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX-4AD-TC special function block and should be read and understood before attempting to install or use the unit. Further information can be found in the FX PROGRAMMING MANUAL and FX SERIES HARDWARE MANUAL. 1 INTRODUCTION The FX-4AD-TC analog block amplifies the signal from four thermocouple sensors (type K or J) and converts the data into 12 bit reading's stored in the FX base unit. Both Centigrade ( C) and Fahrenheit ( F) can be read. Reading resolution is 0.4 C/0.72 F of type K and 0.3 C/0.54 F of type J. All data transfers and parameter settings are adjusted through software control of the FX-4AD-TC ; by use of the TO/FROM applied instructions in the FX PC. Note : FX programmable controllers versions 2.0 or later (those with serial number 13 or larger) are required as these units have the TO/FROM applied instructions in their instruction set. All FX2C Models may be used. The FX-4AD-TC occupies 8 points of I/O on the FX expansion bus. The 8 points can be allocated from either inputs or outputs. The FX-4AD-TC draws 40mA from the 5V rail of the FX base unit or powered extension unit. Thermocouples with the following specifications can be used: Type K (JIS 1602-1981) Type J (JIS 1602-1981)

1.1 External dimensions Weight : Approx. 0.5kg (1.1 lbs) Dimensions: mm (inches) Accessories : Self adhesive labels for special function block number identification. Terminal screws M3.5 (0.14) 24V LED A-D LED Mounting holes 5.5mm (0.27) dia. Any connection to these terminals may damage the FX-4AD-TC. 125(4.92) 140(5.51) DIN rail mounting slot 35mm (1.38) Extension cable and connector 63 (2.48) 73 (2.87) 10 (0.39) 95 (3.74) 2 TERMINAL LAYOUTS Thermocouple SLD CH4 L4+ L4-24VDC ±10% 60mA *3 *4 Class 3 grounding (100 Ω or less) *1 Shielded cable PC *2 SLD *1 Thermocouple CH1 Shielded cable L1+ L1-24VDC+ 24VDC- 3k Ω 3k Ω CH4 CH1 Temperature compensation circuit DC/DC converter FX-4AD-TC Analog Input Block Extension cable *AG : Analog Ground +15V AG -15V *1 : The compensating cables that can be used for connecting with the thermocouple are the following. Type K: KX-G, KX-GS, KX-H, KX-HS, WX-G, WX-H, VX-G Type J : JX-G, JX-H For every 10 Ω of line resistance, the compensating cable will indicate a temperature 0.12 C higher than actual. Check the line resistance before using. Long compensating cables are more prone to noise interference, therefore a short (less than 100m) compensating cable is recommended. Unused channels should have a wire link connected between their + and - terminals to prevent an error being detected on that channel. *2 : If there is excessive electrical noise, connect the SLD terminal to the ground terminal on the unit. *3 : Connect the ground terminals of the FX-4AD-TC unit and the base unit. Use class 3 grounding on the base unit. *4 : The 24V DC built-in supply of the programmable controller may be used as the power supply.

3 INSTALLATION NOTES AND USAGE 3.1 General specification Item General specifications Specification Same as those for the FX base unit 3.2 Power supply specification Item Analog circuits Digital circuits Specification 24V DC ± 10%, 60mA 5V DC, 40mA (internal power supply from base unit) 3.3 Performance specifications Analog inputs Item Input signal Rated temperature range Digital output Resolution Overall accuracy / Calibration point Conversion speed Centigrade ( C) Fahrenheit ( F) Both C and F are available by reading the appropriate buffer memory (BFM). Thermocouple:type K or J(either can be used for each channel),4 channels, JIS 1602-1981 Type K Type J -100 C to +1,200 C -100 C to +600 C Type K Type J -148 F to +2,192 F -148 F to +1,112 F 12 bit conversion stored in 16 bit 2's complement form Type K Type J Type K Type J -1,000 to +12,000-1,000 to +6,000 0.4 C 0.3 C Type K Type J Type K Type J -1,480 to +21,920-1,480 to +11,120 0.72 F 0.54 F ± (0.5% full scale +1 C) / Freezing point of pure water 0 C / 32 F (240ms ± 2%) 4 channels (unused channels are not converted) Note : Earth-tipped thermocouples are not suitable for use with this unit.

Analog inputs continued... Conversion Characteristics (Type K) +12,000 (Type J) +6,000 (Type K) +21,920 (Type J) +11,120 Readings given at calibration reference point 0 C / 32 F (0 / 320) respectively. (subject to the overall accuracy) -100 C -1,000 +600 C (Type J) +1,200 C (Type K) -148 F -1,480 +320 +32 F +1,112 F (Type J) +2,192 F (Type K) Miscellaneous Item Isolation Number of occupied I/O points Specification Photo-coupler isolation between analog and digital circuits. DC/DC converter isolation of power from FX base unit. No isolation between analog channels. 8 points taken from the FX expansion bus (can be either inputs or outputs) 3.4 Buffer memory assignment BFM CONTENTS *# 0 Thermocouple type K or J selection mode, At shipment : H0000 *# # # CH1 to CH4 Averaged temperature reading to be averaged 1-# 4 (1 to 256) Default = 8 5-# 8 CH1 to CH4 Averaged temperature in 0.1 C units 9-# 12 CH1 to CH4 Present temperature in 0.1 C units # 13-# 16 CH1 to CH4 Averaged temperature in 0.1 F units # 17-# 20 CH1 to CH4 Present temperature in 0.1 F units # 21-# 27 Reserved *# 28 # 29 # 30 # 31 Digital range error latch Error status Indentification code K2030 Reserved The FX-4AD-TC communicates with the programmable controller through use of buffer memories. BFMs #21 to #27 and #31 are reserved. All non reserved BFMs can be read by the programmable controller using the FROM command. BFMs (buffer memories) marked with an "*" can be written to, from the programmable controller using the TO command.

3.5 Status Information (1) Buffer Memory BFM #0: Thermocouple type K or J selection mode BFM #0 is used to select K or J type thermocouples for each channel. Each digit of a 4 digit hexadecimal number corresponds to one channel, the least significant digit being channel 1. [ Example ] H 3 3 1 0 CH1 CH2 CH3 CH4 0= K type 1= J type 3= Not used A/D conversion time is 240ms per channel. When "3"(not used) is set for a channel, A/D conversion is not executed for that channel and so the total conversion time is decreased. In the above example, the conversion time is as follows: 240ms (conversion time per channel) 2channels (number of channels being used)=480ms(total conversion time) (2) Buffer Memory BFMs #1 to #4: Number of temperature readings to be averaged When the number of temperature readings to be averaged is specified for BFMs #1 to #4, the averaged data is stored in BFMs #5 to #8( C) and #13 to #16( F). Only the range 1 to 256 is valid for the number of temperature readings to be averaged. If a value outside of this range is input, the default value of 8 is used. (3) Buffer Memory BFMs #9 to #12 and #17 to #20: Present temperature These BFMs store the present value of the input data. This value is stored in units of 0.1 C or 0.1 F, but the resolution is only 0.4 C or 0.72 F for type K and 0.3 C or 0.54 F for type J. (4) Buffer Memory BFMs #28: Digital range error latch BFM#29 b10(digital range error) is used to judge whether the measured temperature is within the unit's range or not. BFM#28 latches the error status of each channel and can be used to check for thermocouple disconnection. b15 or b8 b7 b6 High Low CH4 b5 b4 High Low CH3 b3 b2 High Low CH2 b1 b0 High Low CH1 Not used Low : Turns ON when temperature measurement data goes below the lowest temperature measurement limit. High : Turns ON when temperature measurement data goes above the highest temperature measurement limit, or when a thermocouple is disconnected. An error can be cleared by writing K0 to BFM#28 using the TO instruction. In case of disconnection, temperature data before disconnection is latched.

(5) Buffer Memory BFMs #29: Error status Bit devices of BFM #29 b0:error b1:not used b2:power source b3:hardware error b4 to b9:not used Digital range b10: error Averaging b11: number error b12 to b15:not used ON When either b2 or b3 is ON A/D conversion is stopped for all channels DC 24V power supply failure A/D converter or other hardware failure Digital output/analog input value is outside the specified range. Selected number of averaged results is outside the available range -see BFM #1 to #4 OFF No error Power supply normal Hardware normal Digital output value is normal. Averaging is normal. (between 1 and 256) (6) Identification Code Buffer Memory BFM #30 The identification code or ID number for a Special Block is read from buffer memory BFM #30 using the FROM command. This number for the FX-4AD-TC unit is K2030. The programmable controller can use this facility in its program to identify the special block before commencing data transfer to and from the special block. 3.6 Installation location This unit measures temperature according to the temperature difference between the temperature measurement part (thermocouple) and the terminal block. If this unit is installed in a place where the temperature of the terminal block varies rapidly, a measuring error may occur. For this reason, the unit should be installed in a place free from excessive temperature variation. 3.7 Using crimp terminations less than 6.8mm (0.27) less than 6.8mm (0.27) Use M3.5 (0.14) Use crimp terminations of the type indicated on the left. Secure the termination using a tightening torque of between 5 and 8 kg cm. Wire only to the module terminals discussed in this manual. Leave all others vacant.

4 SYSTEM BLOCK DIAGRAM FX series Command information write and data status read DC 24V Power Source POWER LED 5V Power Supply TO FROM Buffer Memory RAM CPU System ROM Converted data Gain and offset values are stored in EEPROM Photocoupler A D converter Analog Input Control signals Noncontact ±15V A-D analog LED switch DC/DC 5V Cyclic switching converter 24V LED FX-4AD-TC Analog Block CH1 CH2 CH3 CH4

5 EXAMPLE PROGRAM In the program shown below, the FX-4AD-TC occupies the position of special block number 2 (that is the third closest block to the programmable controller). A type K thermocouple is used on CH1 and a type J on CH2. CH3 and CH4 are not used. The averaging count is four. The averaged values in degrees C of input channels CH1 and CH2 are stored respectively in data registers D0 and D1. M8002 Initial pulse M8002 Initial pulse FNC 79 TO FNC 78 FROM P K2 K0 H3310 K1 K2 K30 D2 K1 Specify the type of thermocouple. CH4 and CH3:not used(3) CH2:type J(1) CH1:type K(0) H3310 Block No.2 BFM#0 Block No.2 BFM #30 (D2) Identification code FNC 10 CMP K2030 D2 M0 When (K2030) = (D2), M1 = ON. i.e. When identification code is K2030, M1 = ON. This initial step checks that the special function block placed at position 2 is actually an FX-4AD-TC, i.e. its unit identification number is 2030 (BFM #30). This step is optional, but it provides a software check that the system has been configured correctly. M8000 RUN monitor FNC 78 FROM P K2 K29 K4M10 K1 Block No.2 BFM #29 (K4M10) Transfer the error status to (M25 to M10). When error is found, M10 = ON. M10 Error found M3 Represents b0 BFM #29 This step provides optional monitoring of the FX-4AD-TC Error Buffer Memory (#29). If there is an Error on the FX-4AD-TC, bit b0 of BFM #29 will be set on. This can be read by this program step, and output as a bit device in the FX programmable controller (M3 in this example). Additional Error devices can be output in a similar manner, e.g. b10 BFM #29 Digital range error. (see below) M8000 FNC 78 FROM P K2 K29 K4M10 K1 M10 M3 Represents b0 BFM #29 M20 M4 Represents b10 BFM #29 M1 FNC 79 TO P K2 K1 K4 K2 (K4) (BFM #1), (K4) (BFM #2) Number of samples is changed to four on both CH1 and CH2. FNC 78 FROM K2 K5 D0 K2 (BFM #5) (D0), (BFM #6) (D1) Transfer the averaged temperature value in C to the data registers. This step is the actual reading of the FX-4AD-TC input channels. It is essentially the only program step which is needed. The "TO" instruction in this example, sets the input channels, CH1 and CH2, to take the average reading of four samples. The "FROM" instruction reads the average temperatures (BMF #5 and #6) for input channels CH1 and CH2 of the FX-4AD-TC. If direct temperature readings are required BFM #9 and #10 should be read instead, e.g. FNC 78 FROM P special block No.2 K2 K29 K4M10 K1 FX-4AD-TC BFM number result destination No. of words read

6 DIAGNOSTICS 6.1 Preliminary checks I. Check whether the input/output wiring and/or extension cables are properly connected on FX-4AD- TC analog special function block. II. Check that the FX system configuration rules have not been broken, i.e. the number of special function blocks does not exceed 8 and the total system I/O is equal or less than 256, I/O. III. Ensure that the correct operating range has been selected for the application. IV. Check that there is no power overload on either the 5V or 24V power sources, remember the loading on the FX base unit or a powered extension unit varies according to the number of extension blocks or special function blocks connected. V. Put the FX base unit into RUN. 6.2 Error checking If the FX-4AD-TC special function block does not seem to operate normally, check the following items. Check the status of the POWER LED. Lit : The extension cable is properly connected. Otherwise : Check the connection of the extension cable. Check the external wiring. Check the status of the "24V" LED (top right corner of the FX-4AD-TC). Lit : FX-4AD-TC is ON, 24V DC power source is ON. Otherwise : Possible 24V DC power failure, if ON possible FX-4AD-TC failure. Check the status of the "A-D" LED (top right corner of the FX-4AD-TC). Lit : A-D conversion is proceeding normally. Otherwise : Check buffer memory #29 (error status). If any bits (b2 or b3) are ON, then this is why the A-D LED is OFF.

6.3 Checking special function block numbers Other special units or blocks that use FROM/TO commands, such as analog input blocks, analog output blocks and high-speed counter blocks, can be directly connected to the base unit of the FX programmable controller or to the right side of other extension blocks or units. Each special block is consecutively numbered from 0 to 7 beginning with the one closest to the base unit. A maximum of eight special blocks can be connected. FX-48MR-ES X000 ~ X027 Y000 ~ Y027 FX-4AD Special block 0 FX-8EX X030 ~ X037 FX-2DA Special block 1 FX-32ER X040 ~ X057 Y030 ~ Y047 FX-4AD-TC Special block 2

7 EMC CONSIDERATIONS Electromagnetic compatibility or EMC must be considered before using the FX-4AD-TC. Mitsubishi recommend that the thermocouple sensors used, should be fitted with a form of shield or screening as protection against EMC noise. If some form of cable protection is used, the "Shield" must be terminated at the SLD terminals as shown in chapter 2. Because of the delicate nature of all analog signals, failure to take good EMC precautions could lead to EMC noise induced errors ; up to ±10% of actual values. This is an absolute worst case figure, users who do take good precautions can expect operation within normal tolerances. EMC considerations should include selection of good quality cables, good routing of those cables away from potential noise sources. Additionally it is recommended that signal averaging is used as this will reduce the effects of random noise "spikes".

Guidelines for the safety of the user and protection of the FX-4AD-TC special function block This manual has been written to be used by trained and competent personnel. This is defined by the European directives for machinery, low voltage and EMC. If in doubt at any stage during the installation of the FX-4AD-TC always consult a professional electrical engineer who is qualified and trained to the local and national standards. If in doubt about the operation or use of the FX-4AD-TC please consult the nearest Mitsubishi Electric distributor. Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment. All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples. Manual number : JY992D55901 Manual revision : A Data : February 1996 HEAD OFFICE : MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100 HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN TELEX : J24532 CABLE MELCO TOKYO JY992D55901A Effective FEB. 1996 Specifications are subject to change without notice.