GC61 Digital Pressure Gauge. Operation Manual

Similar documents
GC30 Digital Differential Pressure Gauge Operation Manual

E8Y. Micropressure Sensor with Easy-to-Read Digital Display. Differential Pressure Sensor. Ordering Information. Sensors

1 Output 1 operation. 3 Pressure unit display. 4 Main display Large 4-character LCD display. 5 Sub-display Small 4-character LCD display.

WIRING. Connection connector. NPN output type Standard type. Main circuit. High-function type. Main circuit. PNP output type.

Pressure Sensor. PSAN Series. Compact Digital Pressure Sensors. Features Pressure Measurement Range (Negative, Standard, Compound)

AP-40. AP-40 Series Features Industry s smallest-sensor head Ultra lightweight High-speed response Two-color LED digital pressure display

Weekly Time Switch. Rated time Time setting range Time division 24 hrs x 7 days 00:00 to 23:59 1min

Pressure Sensor. Ordering Information. Mini-Cube Pressure Sensor with Easy-to-Read LED Display

1.5mm amplitude at 10 to 55Hz frequency in each X, Y, Z direction for 2 hours 500m/s² (approx. 50G) in each X, Y, Z direction for 3 times

Slot-type Photomicrosensor with connector or pre-wired models (Non-modulated) *1. configuration. Dark-ON/Light-ON

Installation and Maintenance Instructions for GC51 Rangeable Pressure Transmitter

E6CP-A. An Absolute Encoder at About the Same Price as an Incremental Encoder. Ideal for robot limit signals. Low-cost Encoder with Diameter of 50 mm

K3NX Process Meter OPERATION MANUAL

Digital Gap Checker to 0.15 mm (Displayable/Settable range: 10 to 300) G type Rated distance range. Workpiece. Large gap. Workpiece.

Multifunction Digital Timer

Digital Flow Switch for Large Flow

Digital Indicating ORP Meter AER-101-ORP. Instruction Manual

Electromagnetic Type Digital Flow Switch

How to Order. Flow rate (l/min) Applicable models PFA710, PFA750. Nil

Electromagnetic Type Digital Flow Switch

Cylindrical Photoelectric Sensor CY-100 SERIES

UV Power Monitor. incident light 200 to 370 nm 300 C (Use at temperatures below the Fiber Unit s rated operating

Installation Guide VL-MV10. Model No.

DMP 335 DMP 335. Industrial Pressure Transmitter. Welded, Dry Stainless Steel Sensor. Pressure Transmitter. Industrial

SCALE & WEIGHT DISPLAYS

Solid-State Digital Timer

DMP 335. Industrial Pressure Transmitter. Welded, Dry Stainless Steel Sensor. accuracy according to IEC 60770: 0.5 % FSO.

Ordering Information. Absolute 60-mm-dia. Rotary Encoder E6F-A. High Accuracy and Durability for Automatic Equipment.

Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment

3-color/ 2-screen display 1

DS 200 P DS 200 P. Electronic Pressure Switch with Flush Process Connection

Digital Flow Switch for Water

Quick Start Function Summary Instructions for ASHCROFT GC52 Differential Pressure Transmitter Version 6.03 Rev. B

Weekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N

Hybrid Chart Recorder 250 mm (10")

Electromagnetic Digital Flow Switch

Model Number Structure

OWNER S MANUAL MOTORIZED 7 WIDE TFT LCD COLOR MONITOR CNT-701

DS 400 P. Intelligent Electronic Pressure Switch in Hygienic Stainless Steel Ball Housing. on hygienic process connections

Instructions for Use P.154-UP (9/4) P.155-UP (9/8) P.150-UP-12 (9/12) P.150-UP-16 (9/16)

Self--powered Time Counter

Signet 2250 Hydrostatic Level Sensor

HPX-T Series. Auto-tuning Fiber Optic Photoelectric Control. Specifications CLICK FEATURES AMPLIFIER UNIT ORDER GUIDE. No.

USER S MANUAL. FX2N-8AD Analog input block

Fiber-Optic Sensor Amplifiers E3S-X3, E3X-NL and E3X-NM Discontinued March 2012; Revised Replacements

Contact-Type Digital Displacement Sensor. HG-S Series. User's Manual WUME-HGS panasonic.net/id/pidsx/global

AK-PVE4 Operating Instructions. Measuring of norm signals in wall-type units. Performance:

User s Manual. LG Industrial Systems G3F AT4A. LG Programmable Logic Controller

Instructions for Use P.160-AP-8 (13/8) P.160-CP-8 (13/8) P.160-CP-12 (13/12) P.160-CP-16 (13/16)

Single Point Flow Monitor SW118 SW119

Digital Flow Switch for Water 3 -color/2-screen display

Digital Flow Monitor PFG3#0

Separate Thin Amplifier type. AP-V40AW Series

DMP 339. Pressure Transmitter. with G ¼" flush diaphragm. Pressure Transmitter. Industrial. accuracy according to IEC 60770: 0.

Digital Fiber Amplifier E3X-DA51. Ordering Information. Digital Fiber Amplifier Provides High Performance and Ease of Use

Safety Information. Camera System. If you back up while looking only at the monitor, you may cause damage or injury. Always back up slowly.

TPHADA TRANSMITTER FOR HIGH PRESSURE WITH DIGITAL AUTO-ZERO & SPAN

Flow Monitor PF3W3##

Figure 1: Standard 906 Sensor and Pulser Disc. Figure 2: Standard 906 Sensor and Pulser Wrap

Digital Flow Switch for Air/Water

ZN-PD. Smallest Air Particle Sensor in the Industry for In-line Measurement. Air Particle Sensor. Features

XS_-EU. M8 and M12 Sensor Connectors. Ordering Information

Hygrotest 600. Instruction manual WH / WHT -20/+70 C DH / DHT -20/+70 C / DHT -20/+120 C PHT -20/+70 C / PHT -20/+120 C

DMP 331 DMP 331. Industrial Pressure Transmitter. for Low Pressure. Stainless Steel Sensor. Pressure Transmitter. Industrial. tri-matic.

Photoelectrics Through-beam Type PA18C.T..., DC

F90 Series (Rate Indicators / Controllers) INSTRUCTION MANUAL

Ordering Information. Self -P owered Count Totalizer H7EC. Subminiature Total Counters With Improved Appearance and Features

Scanning Laser Range Finder Smart-URG mini UST-10LX (UUST003) Specification

Type Contact form Model PCB SPDT G6E-134P-ST-US G6E-134PL-ST-US. Type Contact form Model

Thank you for purchasing SEIKO SHOOTING TIMER KT-401. Before using your SEIKO SHOOTING TIMER, please read this manual carefully for its proper use

Standard signal metering in wall-mounting case

LED Driver Linear / area fixed output

Read and understand this manual for safely usage.

Sentronic PLUS Electronic Pressure Regulator. Installation Manual

Operating Instructions

FX2N-2AD SPECIAL FUNCTION BLOCK

LAUREL ELECTRONICS, INC.

Photoelectric Sensors E3F2

UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load Cell

AF-300 E11 Adjustable Frequency Drive

RK-2 ENVIRONMENTAL DATA CONTACTLESS MAGNETOSTRICTIVE LINEAR POSITION TRANSDUCER WITH FLANGED HEAD. Main characteristics

Absolute Rotary Encoder E6CP

LCD VALUE SERIES (32 inches)

Digital pressure sensor PPX series

02/11/2015

Voltage inputs: High and low signal voltages (count, reset, short, counter No. selection, I/O inhibit) No-contact outputs: RUN, forecast

TRF STEP-DOWN TRANSFORMER USER MANUAL

Type Contact form Model Ag (Au clad) Standard DPDT G6A-274P-ST-US Low-sensitivity DPDT G6A-274P-ST40-US

- special pressure ranges - variety of electrical and mechanical. Characteristics. - other versions on request

Digital Gap Checker to 0.15 mm (Displayable/Settable range: 10 to 300) G type Rated distance range. Workpiece. Large gap. Workpiece.

Digital Gap Checker. Workpiece. Large gap. Workpiece. Workpiece. Small gap. Detection surface Detection nozzle. Air STEP 2 STEP 3

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

FlexiScan. Impro FlexiScan 4-Channel Controller INSTALLATION MANUAL

LMP 305. Slimline Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO.

SA1J-F: Full Color Fiber Optic Sensors

USER S Manual NGLT104WPD NGLT150WPD LCD TV / Monitor (IP67 Grade)

20 mm Beam Pitch General Purpose Area Sensor. Distance between parts shelf and sensor can be shortened (Enables miniaturization of equipment)

LMP 331 LMP 331. Screw-In Transmitter with piezoresistive Stainless Steel Sensor

Voltage inputs: High and low signal voltages (count, reset, short, counter No. selection, I/O inhibit) No-contact outputs: RUN, forecast

CSM Color sensors. Color sensors for the detection of a single color in restricted space conditions

Transcription:

TY-GC61-009A エ GC61 Digital Pressure Gauge Operation Manual 2016. 3

TY-GC61-009A 1/24 For proper and safe operation GC61 Digital Pressure Gauge is a compact digital pressure gauge which complies with the EMC Directive. In order to safely and properly utilize this device, please read this operation manual carefully. Incorrect operation may cause malfunction, damage, or an accident. Warning Caution Warning Indicates that incorrect use may result in severe injury or loss of life. Indicates that incorrect use may result in risk of injury or property damage. 1. Do not apply pressure greater than the maximum allowable pressure. This may cause damage or burst of the pressure element and also injury or damage to the surroundings. 2. Use of a non-designated power source may cause a fire or electrical shock. 3. Do not apply excessive weight, vibration or shock. This may cause damage or burst of the unit and release of the measurement fluid. It will result in injury or damage to the surroundings. 4. This device is not explosion-proof. Do not use this device in the areas where flammable or explosive gases or liquids are located. 5. Perform wiring according to the wiring faceplate or the wiring instructions of this operation manual. Incorrect wiring may cause injury or a fire. 6. Use this device within the operating temperature range. Using outside the range of operating temperature may cause malfunction or damage of the unit and also injury or damage to the surroundings. 7. Perform installation carefully according to the installation instructions of this operation manual. 8. Do not disassemble or alter this device. Also, do not remodel this device by adding new functions. Contact the manufacturer for repairs. 9. Perform operation of the switches carefully according to the operation instructions of this operation manual. Incorrect operation may cause malfunction. 10. Since this device is a precision electronic instrument, keep this device as far away from noise source as possible. Also, remove noise from power source of this device by using noise filter, etc. Please do not use this device if its breakdown or malfunction may threaten human life directly or it may harm human body.

TY-GC61-009A 2/24 Warranty If the delivered products within the warranty period (within one year from the delivered date) are determined to be non-conforming products according to Defects due to the design or manufacturing by NAGANO KEIKI, they are repaired or replaced with conforming products free of change. However, note that the following cases are excluded: (1) Where the delivered products are disassembled, altered or where their parts are replaced or new function is added by the customer or any third party. (2) Where directions described in the operation manual or catalog are not observed. (3) Where the non-conformance is caused by deterioration due to use, natural disaster, fire or other force majeure events. (4) The secondary damage caused by non-conformance of the products including the above. Whether the customer has recognized a miss handling by the customer himself/herself, where any apparent evidence of deformation, abrasion, burnout, etc. is seen on parts, they shall be excluded from the warranty scope and the cost shall be paid by the customer.

TY-GC61-009A 3/24 Contents 1. Specifications 4 2. Outline drawing 7 3. Mounting 8 4. Connection 8 5. Noise Prevention 11 6. Storage Location 12 7. Maintenance 12 8. How to Move to Each Mode 13 9. Function Setting Mode 14 10. Comparator Setting Mode 17 11. Comparator Operation 19 12. Other Functions 21 13. Trouble Shooting 23

TY-GC61-009A 4/24 1. Specifications GC61-7 4:Standard Sensor assembly : SUS630(17-4PH) G: Sensor assembly : SUS316L 1: Vertical mounting 3: Horizontal mounting Diaphragm material : SUS630(17-4PH) Joint material : SUS316 in use Pressure range Max. pressure display 0 to 0.5 MPa 0.500 0 to 1 MPa 1.000 0 to 2 MPa 2.000 0 to 3.5 MPa 3.50 0 to 5 MPa 5.00 0 to 10 MPa 10.00 0 to 20 MPa 20.00 0 to 35 MPa 35.0 0 to 50 MPa 50.0-0.1 to 0.5 MPa 0.500-0.1 to 1 MPa 1.000-0.1 to 2 MPa 2.000 *:For positive pressure side span (full scale) Resisting pressure 2 times 1.5 times 2 times* Diaphragm material : SUS316L Joint material : SUS316L in use Pressure range Max. pressure display 0 to 0.5 MPa 0.500 0 to 1 MPa 1.000 0 to 2 MPa 2.000 0 to 3.5 MPa 3.50 0 to 5 MPa 5.00 0 to 10 MPa 10.00 0 to 20 MPa 20.00 0 to 35 MPa 35.0-0.1 to 0.5 MPa 0.500-0.1 to 1 MPa 1.000-0.1 to 2 MPa 2.000 *:For positive pressure side span (full scale) Resisting pressure 2 times 1.5 times 2 times*

TY-GC61-009A 5/24 Display range -10 to 110%F.S. of pressure range or -1999 to 6000 of display value Measurement Gas, fluid (water or oil) (Non-corrosive gas/liquid) fluid Contact us for other measurement fluids. Operating Free from combustible gas or liquid causing fire/explosion under condition normal condition Connection R1/4 screw Accuracy Display accuracy : ±(1.0%F.S. + 1digit) Temperature coefficient : ±0.1%F.S./ (Both zero and span) Power supply 12 to 24VDC±10% Ripple voltage 10% (P-P) or less (4 to 20 ma output: 15 to 24VDC±10%) Consumption NPN specifications : 30mADC or less current PNP specifications : 40mADC or less (Not include analog output and comparator output) Display Pressure representation 4-digit LED(Height of characters 8mm) Operation display lamp Red LED 2(Lit with ON) Display period 0.2s Output Comparator output Output : NPN Open collector 2 Output form PNP Open collector 2 Output Select at factory Response : 5ms or less speed (Filter off) Output :NPN specifications : 30VDC 80mA or less capacitance PNP specifications : Supply voltage or less 80mA or less Dead : Hysteresis : Variable band Window comparator : 1%F.S. Fixed Delay : 0 2.00s(Both ON,OFF) Analog output (Option at factory shipment) Output : 4 to 20mADC or 1 to 5VDC Output : ±1.0%F.S. accuracy Response : 50ms or less speed (Filter off) Resolution: 0.04mADC or less (4 to 20mADC Output ) 12mVDC or less (1 to 5VDC Output ) Load : 400Ω 以下 (4 20mADC Output) resistance 10kΩmin. (1 to 5VDC Output ) Heat run time 5 minutes or more

TY-GC61-009A 6/24 Operating -10 to 50 (no condensation, no freezing) temperature limits Operating 35 to 85%RH (no condensation) humidity limits Storage -20 to 60 (no condensation, no freezing) temperature range Storage 35 to 85%RH (no condensation) humidity range Withstand 300VAC 1 minute voltage Case structure IP65(with vent hole) Case material Front case PC/ABS (UL-94, V-0) Rear case ADC12 Cable length 2m (Standard) Conductor : 0.18sq(7/0.18), Insulation diameter 0.86(mm) Sheath : Outer diameter 4 mm, Material : PVC Mass Vertical mounting approx. 175g (incl. cable 2m) Horizontal mounting approx. 170g (incl. cable 2m) EMC Directive*1 Applicable standards : EN61326-1: 2006, EN61326-2-3: 2006 RoHS Directive Applicable standards : EU RoHS Directive compliant *1 Please connect supply of indoor electric grid that doesnʼt receive the influence of the excess voltage by the thunder, etc. Application as safe accessories cannot be performed.

TY-GC61-009A 7/24 2. Outline Drawing * Diaphragm : When SUS316L is selected, LC is engraved on one side of hexagon part. Vertical mounting Horizontal mounting

TY-GC61-009A 8/24 3. Mounting Install in a location where vibration, shock, direct sunlight, humidity and dust can be minimized and free from oil and water. This device is waterproof equivalent to IP65. However, it should be used outdoors, after measures such as rain-cover are taken and a tube of 4 mm of outer diameter and 2 mm of inside diameter is connected to the vent hole with the tube end letting in no water in case. During the installation, use wrench (22mm) on the hexagon (metal) while ensuring no excess force is applied to the unit (resin). Installation torque shall be 10 N m or less. And apply seal tape on the R1/4 screw to prevent leakage of the pressure media. Caution Caution When installing the unit to the pressure line, do not install while the line is filled with a liquid. Because liquid is incompressible, when the connection screw is tightened, a high pressure may be generated thus causing a damage to the unit. When mounting on the existing pressure line or replacing the existing unit, drain the fluid on the pipe connection side to allow 15 to 20 mm of air before tightening. Do not touch the pressure port with sharp object as it will cause damage to the diaphragm that may result in abnormal operation of the unit. 4. Connection Wire connection The cable wiring colors are indicated as follows. Check the wire connection first and turn on the power supply. Also, wait at least 5 minutes for warming up after power-on. After that confirm the steady state, implement zero point adjustment and measurement. (1) Standard (Without analog output) Brown Power supply (+) Blue Power supply (-) Black Open collector output OUT 1(+) White Open collector output OUT 2(+) (2) With 4 to 20 ma DC output or 1 to 5 VDC output Brown Power supply (+) Blue Power supply (-), Analog output (-) Common Orange Analog output (+) (when option specified) Black Open collector output OUT 1(+) White Open collector output OUT 2(+)

TY-GC61-009A 9/24 Internal form Output forms include open collector output as a comparator output and 4 to 20 ma DC current output or 1 to 5 V DC voltage output as an analog output. Open collector enables the collector of an output transistor to be opened to the user for various applications. With what connection to use the open collector output can be freely determined by the user but three kinds of usage example are shown below. Caution Since the rating of output transistor is NPN: 30 V DC, 80 ma and PNP: 24 V DC (supply voltage range), 80 ma, please be careful not to exceed the rating including rush current etc. 1Usage example of NPN open collector 1(Wiring to relay ) 2Usage example of NPN open collector 2(Wiring to photo coupler) 3 Usage example of NPN open collector 3(Voltage output)

TY-GC61-009A 10/24 4 Usage example of PNP open collector 1(Wiring to relay ) 5 Usage example of PNP open collector 2(Wiring to photo coupler) 6 Usage example of PNP open collector 3(Voltage output)

TY-GC61-009A 11/24 Example of analog output wiring (4 to 20mA DC) Since it is only for source, be careful not to connect or short to power supply (+). (1 to 5V DC) 5. Noise Prevention Noise issues are complicated and many of them cannot be solved easily. If measured values often fluctuate or differ, they may be affected by noise. In this case, take noise prevention measures described below. Power line If noise remains in the power line, it may cause malfunctions such as fluctuation of pressure display. Take care not to tangle the DC power line. Also use a power supply which is of high noise rejection rate or stable enough for keeping ripple voltage from remaining.

TY-GC61-009A 12/24 Output routing In the open collector output circuit, since output line and internal circuit are connected directly, pay attention not to tangle lines. Also, make connection cables as short as possible. Inductive noise Induction noise from outside sources may cause malfunctions. In this case, separate the device from the noise source, change direction, and use a magnetic shield or an electrostatic shield. Lightning surge Lightning surge may cause malfunctions. Please connect this unit to indoor distribution network which is free from influence of lightning surge. 6. Strage Location Do not store this device in the following places as it may cause malfunction and damage. Caution Water splashing places Any place where there can be negative influence of atmosphere, temperature, humidity, draft, sunlight, dust, salt or sulphuric air. Any places where there is inclination, vibration or shock (including during transportation). Any place where chemicals are stored or where there are releases of gas. In direct sunlight or inside a hot vehicle etc. 7. Maintenance In this unit, there are no moving parts in the sensing element and circuit components so basically there will be no maladjustment. However, depending on the use condition, aging may occur so biannual regular check is recommended. For the zero point adjustment, please refer to Section of zero point adjustment. Since plastic molding material is used for the case part of this device, make sure not to touch it with soldering iron, etc. Also, chemicals may have an adverse effect on the case so ensure that none come in contact.

TY-GC61-009A 13/24 8. How to Move to Each Mode Each mode and its function Comparator setting mode Function setting mode Setting of Hysteresis Selection of comparator operation Setting of set point and dead band Selection of display Setting of ON, OFF delay time Scaling of etc. display Setting of Window Comparator Selection of filter Setting of output range Scaling of analog output Setting of ON, OFF delay time 3 seconds or more Below 3 seconds 3 seconds or more 3 seconds or more Power on Measurement mode 3 seconds Pressure display Comparator output or more Zero point adjustment mode Zero adjustment of display Analog output End value, analog output Peak or Bottm 3 seconds or more Peak hold display mode + Peak hold display Below 3 seconds Display of applied pressure maximum Loop check mode Pressure display, comparator output Bottom hold display and analog output are manually Display of applied pressure tested regardless of applied pressure. minimum key is pressed, thereby is displayed. For returning to measurement mode by each setting mode, when pressed for 3 seconds or longer, display will blink.

TY-GC61-009A 14/24 Name and functions of panel part Comparator (OUT1,OUT2) Operation display LED (Red) It lights when the output is ON with the monitor of comparator output. ADJ. Key Use for zero adjustment Setting mode (SET) operation display LED (orange) Pressure setting value display LED It lights during setting. It blinks with loop check and peak and bottom displayed. Otherwise, it goes out. MODE Key DOWN Key UP Key MODE key is used for Use for setting of values Use for setting of values changeover of each and selection of items and selection of items operation mode and each submode. In measurement mode, In measurement mode, bottom hold value is peak hold value is displayed. displayed. Since a hole opens on the panel, please do not carry out key operation with a sharp object. 9. Function Setting Mode Setup steps In measurement mode, key is pressed, thereby is displayed. When pressed for 3 seconds or longer, SET LED will blink. x key is released, thereby the function setting mode is active. It performs selection of comparator operation, selection of display, setting of display scaling, selection of filter time constant, and scaling setting of analog output. Edit of the setting value in function setting mode recalculates all of the setting values including the comparator. Please note that when the recalculated setting values are out of the display range, they will be the upper or lower limit value that can be processed internally.

TY-GC61-009A 15/24 Measurement mode More than 3 sec ON More than 3 sec ON Function setting mode (Selection of comparator operation) key is used for selection or Message display Current setting Hysteresis Window comparator key is used for selection (Selection of display) Pa or kpa Message display Current setting Pressure display by SI unit (when SI etc display. unit is selected) under display scaling (only when etc. display scaling function is selected) (Display scaling) Decimal point placement key is used to select between 0 & 3 Message display (Display scaling) key to select between -1999 & 6000 Min. pressure indicated value Message display (Display scaling) Max. pressure indicated value Message display key to select between -1999 & 6000 key is used for selection Filter off (Setting of filter) Message display TC 25ms TC 250ms TC 2.5s TC 5s (only when analog output option is selected) TC 10s (Analog scaling) Analog output pressure key to select between -100 & 200% at zero point Message display (Analog scaling) key to select between -100 & 200% Analog output pressure Message display at span point

TY-GC61-009A 16/24 Selection of comparator operation key is used to display Selection of comparator operation. is displayed for 1 second and then the current setting is displayed. key is used to select either hysteresis or window comparator operation mode. As this unit is equipped with two comparator outputs option, both comparators will be in the same operation mode. Selection of display key is used to display Selection of display. is displayed for 1 second and then the current setting is displayed. key is used to select either pressure representation under SI unit (kpa or MPa) or representation under display scaling (etc.). Scaling of LED display In Selection of display, is selected, thereby LED indicated value will be arbitrarily scaled based on the applied pressure. This feature can scale LED indicated value based on the minimum and maximum pressures and will not affect the relation between applied pressure and analog output. key is used to set [Decimal point placement] of [Display scaling] [Minimum pressure indicated value] [Maximum pressure indicated value] 1. is displayed for 1 second and then decimal point placement for current display setting is displayed. key is used to select the decimal point placement. 2. is displayed for 1 second and then minimum pressure indicated value for the current setting is displayed. key is used to set the display value. 3. is displayed for 1 second and then maximum pressure indicated value for the current setting is displayed. key is used to set the display value. The above enables the user to set the scaling of LED display. Example) Pressure range 0.00 to 5.00 MPa (0 to 100%F.S.) corresponding scaled output 1.0 to 100.0 displayed value. Decimal point placement : 0.02 0.1 (Least significant digit) Min. pressure indicated value : 0.00 (0.0) 1.0 Max. pressure indicated value : 5.00 (50.0) 100.0 (Actual display) Selection of filter This device is equipped with 5 internal time constant filters. key is used to display Selection of filter. is displayed for 1 second and then the current setting is displayed. key is used to select Filter time constant -----Filter off -----Time constant 25ms -----Time constant 250ms -----Time constant 2.5s -----Time constant 5s -----Time constant 10s Use of the function is recommended when the pressure fluctuation is so intense that display, comparator output, analog output do not stabilize. The selected time constant filter is reflected on comparator/analog output as well.

TY-GC61-009A 17/24 Analog output scaling (only when output option is selected) This function sets analog output pressure corresponding to zero point (4 ma DC or 1 V DC) and span point (20 ma DC or 5 V DC) in percentage figure (when pressure range is set to 0.0 to l00.0%f.s.) key is used to set [Analog output pressure at zero point] [Analog output pressure at span point] 1. is displayed for 1 second and then the current analog output under zero point (4 ma DC) value in percentage figure (when pressure range is set to 0.0 to 100.0%F.S.) is displayed. key is used to set pressure value in percentage figure. 2. is displayed for 1 second and then the current analog output under span point (20 ma DC) value in percentage figure (when pressure range is set to 0.0 to 100.0%F.S.) is displayed. key is used to set pressure value in percentage figure. The above enables the user to set the scaling of analog output. Example) Pressure range 0.00 to 5.00 MPa (0.0 to 100.0%F.S.) corresponding to analog output of 1 to 5 V DC is scaled to pressure range 0.00 to 4.91 MPa (0.00 to 98.1%F.S.) corresponding to analog output of 1 to 5 V DC. Pressure value for analog output zero point 0.0 0.0 (%F.S.) Pressure value for analog output span point 100.0 98.1 (%F.S.) 10. Comparator Setting Mode Setup steps In measurement mode, key is pressed, thereby is displayed. When the key is released within 3 seconds, the comparator setting mode is active. Comparator setting mode enables the user to change settings on the two comparator outputs provided by the unit. The available settings of this mode varies based on the selected operation common to outputs 1 and 2 in [Selection of comparator operation] of Function setting mode. For Hysteresis, settings of comparator operation point (A) and dead band (b) can be done independently with outputs 1 and 2. For Window Comparator, settings of comparator operation point (A) and comparator operation point (b) can be also done independently with outputs 1 and 2. The dead band setting for Window Comparator is fixed at 1 %F.S. in the comparator OFF direction. Also, as common parameters between comparator operations, comparator ON delay time and comparator OFF delay time can be selected in the range of 0.00 to 2.00 seconds independently with outputs 1 and 2.

TY-GC61-009A 18/24 Measurement mode Below 3 secondson More than 3 sec ON Comparator setting mode (Output 1. Comparator setting value A) (Output 1. Comparator setting value b) (Output 1. Comparator ON delay time) (Output 1. Comparator OFF delay time) (Output 2. comparator setting value A) (Output 2. comparator setting value b) (Output 2. Comparator ON delay time) (Output 2. Comparator OFF delay time) key to select between Message display -1999 & 6000 key to select between Message display -1999 & 6000 key to select between Message display 0 & 2.00s key to select between Message display 0 & 2.00s key to select between Message display -1999 & 6000 key to select between Message display -1999 & 6000 key to select between Message display 0 & 2.00s key to select between Message display 0 & 2.00s Comparator setting value A (Output 1, output 2) key is used to display [Comparator setting value A]., is displayed for 1 second and then the current setting value is displayed. key is used to set comparator setting point (A). Comparator setting value b (Output 1, output 2) key is used to display [Comparator setting value b]., is displayed for 1 second and then the current setting value is displayed. key is used to set dead band (b) in Hysteresis and comparator setting point (b) in Window Comparator. Note) In the setting of dead band (b) in Hysteresis, if the set value is too small, there will be a fear of chattering occurrence. Be careful when setting dead band (b). (For dead band (b), the value more than 1%F.S. of pressure range is recommended).

TY-GC61-009A 19/24 Comparator ON delay time (Output 1, output 2) key is used to set [Comparator ON delay time]., is displayed for 1 second and then the current setup time appears on the LED display. key is used to set delay time where comparator operation is ON. Comparator OFF delay time (Output 1, output 2) key is used to set [Comparator OFF delay time]., is displayed for 1 second and then the current setup time appears on the LED display. key is used to set delay time where comparator operation is OFF. Note) Comparator output setting values are always checked and recalculated when a setting related to comparator operation is changed so that there will be no inconsistency in comparator operation. However, please note that when comparator output setting value is recalculated, if the calculation result is beyond setting range, the comparator output setting value will be changed automatically so that it will be within the setting range. Also, please not that when comparator output setting value is recalculated, calculational error at ±1 digit may be observed at comparator output setting value. 11. Comparator Operation When the comparator output conditions shown below are met, each output becomes ON status and Comparator display LED (OUT 1, OUT 2) is lit. Operation of Hysteresis Setting the upper limit When the setting value (A) is the upper limit, the comparator operates. The upper limit setting is determined when you select a positive number (including 0) for setting value (b) Setting the lower limit When the setting value (A) is the lower limit, the comparator operates. The lower limit setting is determined when you select a negative number for setting value (b).

TY-GC61-009A 20/24 Operation of Window Comparator (A) (b) (A)>(b) Dead band of 1%F.S. is automatically set inside the set points (A) and (b).

TY-GC61-009A 21/24 12. Other Functions Basic key operations For setting up in each setting mode, use keys. key is used to increase value, key is used to decrease value. A repeat state occurs in three phases of speed when key is pressed for more than 0.5 seconds to increase or decrease value. For settings of comparator operation mode, unit, and filter in the function setting mode, when each setting is selected, key is used. Zero adjustment mode In measurement mode, after releasing pressure from the pressure port, key is pressed for 3 seconds or longer until blinks. Approximately 1 second later an automatic zero adjustment takes place and the pressure displays as zero. When the zero adjustment is successful, appears on the LED display. When applied pressure was outside the range of -10 to 10% F.S, The error displays for one second; zero adjustment does not happen. In order to perform zero point adjustment properly, filter setting for zero point adjustment is temporarily a fixed value. For user setting of the filter, re-calculation of a setting value needs to reset power or to shift to function setting mode and perform operation to return to measurement mode. (It is not necessary to set the filter again) Loop Check mode In Loop Check mode, without actually applying pressure to the unit, key enables the user to vary pressure display value. As a result, comparator(s) and analog outputs will vary based on the pressure display value chosen. This function allows the user to confirm outputs or output settings manually. This function is also useful in checking proper wiring and other simulations. In measurement mode, key + is pressed, thereby is displayed for 1 second. Then, the loop check mode is active and SET LED is blinking. The indicated value in the measurement mode just before it changes to the loop check mode is displayed as an initial value. key is used to change the indicated value and thereby check comparator output operation and analog output operation. key is pressed for 3 seconds or longer, enabling to return to measurement mode. Peak hold display mode The GC61 unit keeps the maximum and minimum pressure level applied to the pressure port as peak and bottom values respectively, in the internal memory. The peak and bottom values are displayed as long as key and key are pressed and held, respectively. When you select this operation, is displayed for one second and selected Peak value is displayed. While the peak value is indicated, SET LED blinks. Peak and bottom values are reset when you reset power to the unit, or by following procedure. Resetting peak value: key is held, key is pressed. Resetting bottom value: key is held, key is pressed.

TY-GC61-009A 22/24 Key lock Key operations can be nullified to prevent inadvertent overwriting of setting values. Once the key lock state is set, the mode cannot be shifted to the one other than the peak hold display mode. The key lock mode cannot be reset by restoring power. It is reset by the following release operation of a key lock. In measurement mode, key + key is pressed, thereby is displayed for 1 second until key lock state. Release of key lock : Press key + key. is displayed for one second and key lock is released. Error display An error message is alternately displayed when one of the following errors occurs in the measurement mode. Check the content of error message and take the action below immediately. Error Contents Actions Out of pressure display range (Upper limit) A pressure above 110% F.S. of pressure range is applied, or when indicated value Adjust the applied exceeds 6000. pressure within the Out of pressure display range (Lower limit) rated pressure. A pressure less than -10% F.S, of pressure range is applied, or when indicated value Open the unit to the During zero point adjustment, applied atmosphere and pressure is outside the range of ±10% F.S. Comparator 1 is overloaded. Comparator 2 is overloaded. Comparators 1 and 2 are overloaded. perform zero point adjustment again. Use the unit with a load current, set to 80 ma DC or less. Reset power to the unit for error reset. Backup of setting values The unit has an internal EEPROM and settings and the key lock state are maintained even after the power is turned OFF. However, peak / bottom values are not maintained. Items which can be backed up Items which cannot be backed up Setting values in function setting mode Setting values of comparator Zero adjustment Key lock & unlock Peak hold Error display

TY-GC61-009A 23/24 13. Trouble Shooting Error Probable cause Actions No display Wiring Please carry out wiring correctly according to the connection No output Supply_voltsagse procedure. After applying Pressure leak Please pipe correctly according to the pressure, pressure attachment procedure. display and output Too low pressure applied Please check applied pressure and linked to the applied use the pressure gauge with suitable pressure do not pressure range. change. (It remains zero point) Pressure display and Zero point shift Please perform zero point adjustment output linked to the according to [zero point adjustment applied pressure mode] conflict with the Pressure indication mode Please select a pressure indication. value of actual [Function setting mode] => applied pressure. [Selection of display] (Output does not Analog scaling mode Please check an analog output scaling match) setup. [Function setting mode] => [Analog scaling] Setting values of Please check setting values of comparator output comparator operating point and delay time. [Function setting mode] => [Selection of comparator operation], [Comparator setting mode] Foreign material Clean/remove obstruction in piping. (blockage)

TY-GC61-009A 24/24 The contents of this operation manual are subject to change without notice due to revisions or other reasons. For more information or inquiries, please contact the closest sales office or please access the website shown below. NAGANO KEIKI CO.,LTD. URL : http://www.naganokeiki.co.jp/ HEAD OFFICE & OVERSEAS SALES DEPT. 1-30-4, Higashimagome, Ohota-ku, Tokyo, Japan. Phone +81-3-3776-5328 Fax +81-3-3776-5447 E-mail :overseas_sales_dept@naganokeiki.co.jp