FX-2DA SPECIAL FUNCTION BLOCK USER'S GUIDE

Similar documents
INTRODUCTION TERMINAL LAYOUTS FX2N-4AD SPECIAL FUNCTION BLOCK USER S GUIDE

LX3V-4AD User manual Website: Technical Support: Skype: Phone: QQ Group: Technical forum:

FX-4AD-TC SPECIAL FUNCTION BLOCK USER'S GUIDE

INTRODUCTION TERMINAL LAYOUTS FX2N-4AD-TC SPECIAL FUNCTION BLOCK USER S GUIDE

FX0N-3A SPECIAL FUNCTION BLOCK

USER S MANUAL. FX2N-8AD Analog input block

FX2N-2DA SPECIAL FUNCTION BLOCK

ANALOG I/O MODULES AD268 / DA264 / TC218 USER S MANUAL

FX2N-232IF RS232C INTERFACE BLOCK

FX2N-2AD SPECIAL FUNCTION BLOCK

SAFETY PRECAUTIONS. (Read these precautions before using this product.)

Vorne Industries. 87/719 Analog Input Module User's Manual Industrial Drive Itasca, IL (630) Telefax (630)

Industriefunkuhren. Technical Manual. IRIG-B Generator-Module for analogue / digital Signals of Type: IRIG-B / IEEE C / AFNOR NF S87-500

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

C200H-AD002/DA002 Analog I/O Units Operation Guide

Analogue output module DAO 081

R1MS-GH3 BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL THERMOCOUPLE & DC INPUT MODULE MODEL. (8 points; isolated)

Ocean Sensor Systems, Inc. Wave Staff, OSSI F, Water Level Sensor With 0-5V, RS232 & Alarm Outputs, 1 to 20 Meter Staff

Model Number Structure

MICROMASTER Encoder Module

Operating Instructions

PROGRAMMABLE DC SOURCE VIEW RECORDERS Programmable DC Source FEATURES

Ocean Sensor Systems, Inc. Wave Staff III, OSSI With 0-5V & RS232 Output and A Self Grounding Coaxial Staff

MELSEC-L Digital-Analog Converter Module User's Manual -L60DA4 -L60DAVL8 -L60DAIL8

User Manual CC DC 24 V 5A. Universal Control Unit UC-1-E. General Information SET. Universal Control Unit UC-1 Of Central Lubrication PAUSE CONTACT

LAUREL ELECTRONICS, INC.

Electrical connection

LED DRIVERS. LQC4D-V1 4 channels. User Manual FEATURES

AI-1204Z-PCI. Features. 10MSPS, 12-bit Analog Input Board for PCI AI-1204Z-PCI 1. Ver.1.04

32 Channel CPCI Board User Manual

Sensor module. Safety instructions. Function Correct use. Product characteristics. Structure of the device. Operation. Ref.No.

LED control gear Compact dimming. Uconverter LCAI 2x38 W 0500 K013 one4all ECO series. Ordering data

AD12-16U(PCI)EV. Features. High-Speed Analog Input Board for PCI AD12-16U(PCI)EV 1. Ver.1.01

Installation Guide VL-MV10. Model No.

MELSEC iq-f FX5 User's Manual (Analog Control - Intelligent function module)

Standard signal metering in wall-mounting case

ZU 251. Incremental Counter Module With Analogue Output and Serial Interface. Operating Instructions. control motion interface

K3NX Process Meter OPERATION MANUAL

K-BUS Dimmer Module User manual-ver. 1

IV 251. Signal Converter SSI => Analogue and SSI => Serial. Operating Instructions. control motion interface

AK-PVE4 Operating Instructions. Measuring of norm signals in wall-type units. Performance:

IV 251. Signal Converter SSI Analogue and SSI Serial. Operating Instructions. control motion interface

AD16-16U(PCI)EV. Features. High-Speed & Resolution Analog Input Board for PCI AD16-16U(PCI)EV 1. Ver.1.02

Digital Ratio Controller

NTB-500A. Medium Speed Network Terminal Box. Supports dynamic measurement at medium-speed synchronous sampling!

WECON LX3V-2PT2DA BD Board

PACSystems* RX3i Thermocouple Input Module, 12 Channels, IC695ALG412-CB

Special Applications Modules

MicroLogix 1200 Thermocouple/mV Input Module

Metal Electrode Meter

LED control gear Compact fixed output. Uconverter LCI 55 W 1400 ma O010 TOP series Ø4,4. Ordering data

MODEL: 40DPT. Digital Panel Meters 40 Series. [3] OPTIONS blank: none /Q: With options (specify the specification)

Multifunction Digital Timer

A/D and D/A convertor 0(4) 24 ma DC, 16 bits

Sentronic PLUS Electronic Pressure Regulator. Installation Manual

AD16-64(LPCI)LA. Non-isolated high precision analog input board for Low Profile PCI AD16-64(LPCI)LA 1. Ver.1.01

Troubleshooting. 1. Symptom: Status indicator (Red LED) on SSR is constant on. 2. Symptom: Output indicator (Yellow LED) on SSR is flashing.

Contact-Type Digital Displacement Sensor. HG-S Series. User's Manual WUME-HGS panasonic.net/id/pidsx/global

ZIRCONIA OXYGEN ANALYZER CONVERTER

CAMTO LTD. Arc detecting system DC/AC

Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module

L, LTC, LTM, LT are registered trademarks of Linear Technology Corporation. Other product

12months. on-site warranty. DZE ELECTRONIC PRESSURE SWITCH for detection of overload per EN 81 2 featuring two adjustable switching points

SCALE & WEIGHT DISPLAYS

Assembly. Front view. LEDs. Parametrization interface. Power Bus

(Cat. No IJ, -IK)

Kramer Electronics, Ltd. USER MANUAL. Model: FC Analog Video to SDI Converter

C8000. switch over & ducking

WECON LX3V-2TC2DA BD Board

On-screen display signal strength meter Version 1.02

MELSEC iq-r Channel Isolated Digital-Analog Converter Module User's Manual (Application) -R60DA8-G -R60DA16-G -RY40PT5B-AS

PACSystems* RX3i. Isolated Thermocouple Input Module, 6 Channels, IC695ALG306-EB Isolated Thermocouple Input Module, 12 Channels, IC695ALG312-EB

Automatic Transfer Switch Control PLC Operator s Manual

PicoScope 3000 Series Automotive User guide

MINI MCR-SL-F-UI-NC. Frequency transducers. Data sheet. 1 Description

2002 Martin Professional A/S, Denmark.

AE-341 SERIES PROCESS INDICATORS 2 TO 6 DIGITS 0-20 MA, 4-20 MA, 0-5V, OR 0-10V SCALED INPUT

V/L V/H H/L H/H. Satellite - Input. Programmable Cascadable switch. with 32 User Bands with Terrestrial input & 1 Legacy port

User s Manual TOS7200. Insulation Resistance Tester DANGER. 1. Preface Preparation Safety Precautions during Testing 19

Dimming actuators GDA-4K KNX GDA-8K KNX

Installation. SAPTF33xx-1xx in the Network. Standard Configuration

Manual. Analog (U/I) Sendix M3661 / M3681. Sendix M3661R. Sendix M5861. Absolute multiturn encoder. Order code: 8.M36X1.XXXX.XX12

Electronic Panel Meters DIGEM Preference Program Process control, automation & laboratory uses Class 0.01 to 1 Current, Voltage, Frequency,

Triple RTD. On-board Digital Signal Processor. Linearization RTDs 20 Hz averaged outputs 16-bit precision comparator function.

SIMATIC. ET 200S distributed I/O 2AO U HS analog electronic module (6ES7135-4FB52-0AB0) Preface. Properties 1. Parameters 2.

Safety Information. Camera System. If you back up while looking only at the monitor, you may cause damage or injury. Always back up slowly.

AI-1616L-LPE. Features. High-precision Analog input board (Low Profile size) for PCI Express AI-1616L-LPE 1. Ver.1.02 Ver.1.01

Foreword: The purpose of this document is to describe how to install and configure Neets 4 relay box

MBUS 10 RS232 TO MBUS LEVEL CONVERTER

SAFETY TERMS AND SYMBOLS

Dimming actuators of the FIX series DM 4-2 T, DM 8-2 T

Process Transmitter RMA 422

Operation Manual TX20 1/8 DIN Microcomputer Based ph/orp Controller with relays

Assembly Level Service Guide

COLOR TFT LCD MONITOR. Manual

CONVI104 SWITCHER & ANALOG TO SDI CONVERTER CONVI 104-M 15/03/2006

E6CP-A. An Absolute Encoder at About the Same Price as an Incremental Encoder. Ideal for robot limit signals. Low-cost Encoder with Diameter of 50 mm

Specifications. End-Point Linearity - ±5% F.S., when used with HACO SCR-speed control

Working with a Tektronix TDS 3012B Oscilloscope EE 310: ELECTRONIC CIRCUIT DESIGN I

Model IQ4-PC User Manual Revision Date:

Transcription:

FX-2DA SPECIAL FUNCTION BLOCK USER'S GUIDE JY992D52801C This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX-2DA special function block and should be read and understood before attempting to install or use the unit. Further information can be found in the FX PROGRAMMING MANUAL and FX SERIES HARDWARE MANUAL. 1 INTRODUCTION The FX-2DA analog special function block has two output channels. The output channels take a digital value and output an equivalent analog signal. This is called a D/A conversion. The FX-2DA has a maximum resolution of 12 bits. The selection of voltage or current based input/output is by user wiring. Analog ranges of -10 to 10V (resolution: 5mV), and/or 4 to 20mA (resolution: 20µA) maybe selected. FX programmable controllers versions 2.0 or later (those with serial number 13XXXX or larger) are required; as these units have the TO/FROM applied instructions in their instruction set. Data transfer between the FX-2DA and the FX base unit is by buffer memory exchange. There are 32 buffer memories (each of 16 bits) in the FX-2DA. The FX-2DA occupies 8 points of I/O on the FX, FX2C expansion bus. The 8 points can be allocated from either inputs or outputs. The FX-2DA draws 30mA from the 5V rail of the base unit or powered extension unit.

1.1 External dimensions Weight : Approx. 0.5kg (1.1 lbs) Dimensions : mm (inches) Extension cable and connector 24V LED D-A LED Any connection to these terminals may damage the FX-2DA. M3.5 (0.14) terminal screws 125 (4.92) 140 (5.51) Groove for 35mm (1.38) wide DIN rail 2-5.5mm (0.22) hole 63 (2.48) 73 (2.87) 10 (0.39) 95 (3.74) 2 Wiring DC24V ±10% 130mA *4 Class 3 Grounding (100 Ω or less) PC Extension cable +24V 0V DC/DC converter +15V AG -15V FX-2DA special function block CH1 CH2 V V I I V V I I + - + - + - + - Voltage output *2 Current output *1 *1 *2 *3 Inverter, etc. Recorder, etc. *1 Use a twisted pair shielded cable for the analog output. This cable should be wired away from power lines or any other lines which could induce noise. *2 Apply 1-point grounding at the load side of the output cable (class 3 grounding: 100 Ω or less). If electrical noise is caused from grounding, disconnect from grounding. *3 If electrical noise or a voltage ripple exists at the output, connect a smoothing capacitor of 0.1 to 0.47 µf, 25V. *4 Connect the ground terminal on the FX-2DA with the ground terminal on the base unit of the programmable controller. Use class 3 grounding on the base unit, if available. Caution; (a) The same output channel cannot drive current and voltage output loads at the same time! (b) Shorting the voltage output terminals may damage the unit!

3 INSTALLATION NOTES AND USAGE 3.1 Environment specification Item Environment specifications Specification Same as those for the FX base unit 3.2 Power supply specifications Item Analog circuits Digital circuits Specification 24V DC ±10% 130mA (external power supply) 5V DC, 30mA (internal power supply from base unit) 3.3 Performance specifications Item Max. convertible output range Digital input Voltage output Current output Voltage or current outputs can be individually selected with each output terminal. There are a total of 2 output points. DC -10V to +10V DC+4mA to +20mA (external load: 1kΩ to 1MΩ) (external load: 500 Ω or less) Voltage = -2048 to +2047 Current = 0 to +1000 Resolution 5mV (10V full scale 1/2000) 20µA (20mA full scale 1/1000) Overall accuracy Conversion speed ±1% full scale (10V range) ±1% full scale (20mA range) 18ms for 2 channels (normal speed), 3.5ms for 2 channels (high speed). Analog output continued... Factory Presets Load: = 10kΩ (voltage Output) = 250Ω (current Output) Analog output +10.235V +10V + 5V +2047-2000 -1000 0 +1000 +2000-5V -2048 Digital input -10V -10.24V +20mA Analog output + 4mA 0 1000 Digital input Gain and offset can be adjusted using the procedure described in chapter 4.

Miscellaneous Item Specification Photo-coupler isolation between analog and digital circuits. Isolation DC/DC converter isolation of power from FX base unit. No isolation between analog channels. Number of occupied I/O 8 points taken from the FX expansion bus points (can be either inputs or outputs) ATTENTION FOR WHEN SWITCHING SYSTEM ON/OFF Due to the inevitable timing difference of the DC24V for the analog circuits and other power lines of the base unit, the output of the FX-2DA special function block may behave erroneously before settling down to operational conditions in approximately 1sec. Therefore, ensure that this behavior is taken into account such that the end performance of the system is not degraded. (example) DC24V supply Power switch FX-2DA special function block cut analog lines before switching External analog machine

3.4 Allocation of buffer memories (BFM) BFM *# 0 *# 1 *# 2 # 3-# 4 *# 5 # 6 *# 7 # 8-#19 contents channel Initialization (Default = H00) channel 1 channel 2 Reserved Last data reset (Default = 0) Reserved selection of A-D When set to 0, normal conversion speed speed is selected 18ms see note When set to 1, high speed is selected 3.5ms Reserved In BFM's (buffer memory) with an *, data can be written from the programmable controller using the TO command. These BFM's should always be given when the programmable controller goes from STOP to RUN. Buffer memory (BFM's) are reset to their default settings upon power on. BFM *#20 *#21 *#22 *#23 *#24 #25-#28 #29 #30 #31 b3 b2 b1 b0 Reset all to default default value: 0 Gain/offset adjust prohibit Prohibit Permit Initial value (0,1) Offset/gain G2 O2 G1 O1 setting command Offset data (in mv or µa units) default value: 0 Gain data (in mv or µa units) default value: 5,000 Reserved Error status (See next page) Identification code K3010 (See next page) Reserved The buffer memory also handles information used to adjust the gain and offsets of the FX- 2DA unit. Status of the unit such as errors are also available. From BFM #29 and #30, data can be read via the FROM command. Offset value : the actual output value when the digital input is 0. Gain value : the actual output value when the digital input is +1000.

(1) Channel Selection Switching between voltage and current output modes. The value of BFM #0 switches the analog output between voltage and current on channels CH1 and CH2. It takes the form of a 2-character HEX number. The least significant character controls CH1 and the other controls CH2. Control of each O HEX character of HOO : O=0 : Voltage output (-10V to +10V) O=1 : Current output (+4mA to +20mA) Example : H10 CH1 : Voltage output CH2 : Current output (2) Last data reset If the programmable controller is changed to the STOP state, the FX-2DA will continue to output the last value. To reset the output to the offset value, set the HEX characters of BFM #5 to one of the appropriate settings below: H01 : CH2=Hold, CH1=Reset H10 : CH2=Reset, CH1=Hold H11 : CH2=Reset, CH1=Reset Both channels are held when BFM #5 = H00. (3) Digital to Analog conversion speed change By writing 0 or 1 into BFM #7 of the FX-2DA, the speed at which D-A conversion is performed can be changed. However the following points should be noted: Note : The conversion speed does not depend on the number of channels being used. On power up, the FX-2DA is set for normal speed conversion and BFM #7 contains 0. (4) Adjusting Gain and Offset Values (a) (b) (c) (d) When BFM #20 is set to, all settings in the buffer memory are reset to their default settings. This allows the buffer memory settings to be set from the beginning again when many settings have been corrupted. If (b1, b0) of BFM #21 is set to (1, 0), gain and offset adjustments are prohibited. This is to prevent inadvertent misuse by the operator. To adjust the gain and offset, (b1, b0) of BFM #21 must have the values (0, 1). The default is set at (0, 1). Each time a TO instruction is used to send data to BFM #22 (gain/offset setting command), the designated gain and offsets of each channel (G2 O2 G1 O1) are adjusted with the values in BFM #23 and #24. This action causes the adjustments to be written to internal non-volatile EEPROM memory. Limit this action to as little as possible to preserve the life of the EEPROM memory. Gain and offset values in BFM #23 #24 are set in units of mv or µa. Due to the resolution of the unit, the actual response will be in steps of 5mV or 20µA.

(5) Status information BFM #29 Bit b 0 : error b 1 : Offset/Gain error b 2 : Power abnormality ON When any of b1 to b3 is ON D/A conversion is stopped for the error channel Offset/Gain data in EEPROM is corrupted or adjustment error DC 24V power supply failure OFF No error Offset/Gain data normal Power supply normal b 3 : Hardware error b 8 : Not READY b10: Range error b12: Offset/Gain adjust prohibit Bits b4 to b7, b9, b11 and b13 are undefined. D/A converter or other hardware failure FX-2DA MODE switch is not set to READY. Digital input value or analog output is outside the specified range. Prohibit-(b1, b0) of BFM #21 is set at (1, 0). Hardware normal READY mode Analog output value is normal. Permit-(b1, b0) of BFM #21 is set at (1, 0). (6) Model code number BFM #30 The identification code for a Special Block is read using the FROM command. The identification code for the FX-2DA unit is K3010. The PC can use this facility in the program to identify the special block before commencing any data transfer from and to the special block. CAUTION Values of BFM #0, #5, #21, #23 and #24 are stored in EEPROM memory of the FX-2DA. BFM #23 and BFM #24 are only copied when the gain/offset setting command BFM #22 is used. Also, BFM #20 causes resetting of the EEPROM memory. The EEPROM has a life of about 10,000 cycles (changes), so do not use programs which frequently change these BFMs. Because of the time needed to write to the EEPROM memory, a delay of 300ms is required between instructions that cause a change to the EEPROM. Therefore, a delay timer should be used before writing to the EEPROM a second time.

4 DEFINING GAIN AND OFFSET GAIN Analog (a) (b) OFFSET Analog (d) (e) Gain value (c) Digital value 0 (f) 1000 Digital Gain is the angle or slope of the calibration line identified at a digital value of 1000. (a) Large gain low reading resolution (b) Zero gain - default 5V or 20mA (c) Small gain high reading resolution Digital Offset value Offset is the 'Potion' of the calibrated line, identified at a digital value of 0. (d) Positive offset (e) Zero offset default (4-20mA default is 4mA) ( f) Negative offset Offset and gain can be used independently or together. Reasonable offset ranges are -5V to +5V or -20mA to 20mA, and gain-offset difference 1V to 15V or 4mA to 32mA. Gain and offset can be adjusted by software in the FX base unit (see program example 2) or by the switches on the FX-2DA (with the aid of a voltmeter/ammeter). Bit device's b0, b1 of the gain/offset BFM (#21) should be set to 0, 1 to allow adjustment. Once adjustment is complete these bit device should be set to 1, 0 to prohibit any further changes. Channel initialization (BFM #0) should be set to the nearest range, i. e. voltage/current etc. 1. Power up the system the FX base unit can be in either RUN or STOP mode. 2. Connect the load and voltmeter or ammeter to the CH1 terminals. 3. Set the FX-2DA MODE switch to output CH1. 4. Press the OFFSET button once. The offset value is output. Use the UP/DOWN switch to reach the desired offset value. 5. Press the GAIN button once. The gain value is output. Use the UP/DOWN switch to reach the desired offset value. 6. Repeat operations 3 to 5 for each channel you wish to use. 7. Set the FX-2DA MODE switch to READY to complete gain and offset adjustment. NOTE : If the MODE switch is not set to a channel number, the FX-2DA is regarded as being in the READY status and no adjustments can be made.

5 EXAMPLE PROGRAM 5.1 Basic program In the following example, channel CH1 is set to voltage output, while CH2 is set to current output. The FX- 2DA unit is connected at the position of special function block No.1. If the programmable controller is changed to the STOP mode, the last data sent will remain and the outputs will hold. M8000 RUN monitor FROM(P) CMP K30 K3010 D4 D4 M0 The ID code for the special function block at position 1 is read from BFM #30 of that block and stored at D4 in the FX base unit. This is compared to check the block is an FX-2DA, if OK M1 is turned ON. These two program steps are not strictly needed to perform an analog output. They are however a useful check and are recommended as good practice. M1 K0 H10 The analog output channels (CH1, CH2) are set up by writing H10 to BFM #0 of the FX-2DA. Set CH1 setting to D0(-2,000 to +2,000) Set CH2 setting to D1( 0 to +1,000) TO D0 K2 (D0 BFM #1 (output to CH1)) (D1 BFM #2 (output to CH2)) FROM K29 K4M10 The operational status of the FX-2DA is read from BFM #29 and output as bit devices at the FX base unit. M10 NO error M18 READY M20 Output range normal M3 Output data normal

5.2 Using gain and offset in a program I/O characteristics of the FX-2DA can be adjusted by changing the gain and offset parameters. These can be changed by the switches of the FX-2DA with the aid of Voltage & Current meters or simply changed by writting these settings from the programmable controller. Only the gain and offset values in the memory of the FX-2DA need be adjusted. A voltmeter or an ammeter for the analog output is not needed. A program for the programmable controller will be needed however. The following is an example; changing the offset value to 0mA and gain value to 20mA on output channel CH2 of the FX-2DA connected as block No.1. Example: Adjusting gain/offset via software settings X010 M0 K0 K21 SET H10 M0 Adjustment start. (H10) BFM #0 (initialize input channels) In the program shown at left, the programmable controller should be in RUN status, and MODE switch of the FX-2DA in the READY position. () BFM #21 BFM #0 should be of HEX value H10, and (b1, b0) of BFM #21 should be (0, 1). TO K22 K0 (K0) BFM #22 (offset/adjust) Reset adjust bits. T0 K23 K24 K0 K20000 T0 K4 (K0) BFM #23 (offset) This statement may be omitted if BFM #23 is already at its default value. (K20000) BFM #24 (gain) T1 K22 HC RST M0 (HC) BFM #22 (offset/gain set) A delay of 300ms may be needed between setting BFM #0 and #22 (see section 3.4 caution ) Adjustment end. K21 K2 (K2) BFM #21 BFM #21 gain/offset adjust prohibit.

6 DIAGNOSTICS 6.1 Preliminary checks 1. Check whether the output wiring and/or expansion cables are properly connected on FX-2DA analog special function block. 2. Check that the FX system configuration rules have not been broken, i.e. the number of blocks does not exceed 8 and the total system I/O is equal or less than 256 I/O. 3. Ensure that the correct operating range has been selected for the application. 4. Check that the MODE switch on the FX-2DA panel is set to the READY position. 5. Check that there is no power overload on either the 5V or 24V power source, remember the loading on the FX base unit or a powered extension unit varies according to the number of extension blocks or special function blocks connected. 6. Pit the main processing unit into RUN. 6.2 Error checking If the FX-2DA special function block does not seem to operate normally, check the following items. Check the status of the POWER LED. Lit. : The extension cable is properly connected. Otherwise : Check the connection of the extension cable. Check the external wiring. Check the status of 24V LED (top right cover of the FX-2DA). Lit. : FX-2DA is OK, 24V DC power source is OK. Otherwise : Possible 24V DC power failure, if OK then possible FX-2DA failure. Check the status of th D/A LED (top right cover of the FX-2DA) Lit. : D/A conversion is proceeding normally Otherwise : Check buffer memory #29 (error status). If any bits (b2 and b3) are ON, then this is why the D/A LED is OFF.

Guidelines for the safety of the user and protection of the FX-2DA special function block This manual has been written to be used by trained and competent personnel. This is defined by the European directives for machinery, low voltage and EMC. If in doubt at any stage during the installation of the FX-2DA always consult a professional electrical engineer who is qualified and trained to the local and national standards. If in doubt about the operation or use of the FX-2DA please consult the nearest Mitsubishi Electric distributor. Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment. All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples. Manual number : JY992D52801 Manual revision : C Data : AUGUST 1996 HEAD OFFICE : MITSUBISHI DENKI BLDG MARUNOUCH TOKYO 100 HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN TELEX : J24532 CABLE MELCO TOKYO JY992D52801C Effective AUG. 1996 Specifications are subject to change without notice.