LIGHT SOURCE 3.5W/FT, 6W/FT, 11W/FT OPTICS COLOR TEMPERATURES (C.C.T.) 2700K 3000K 3500K 4000K CRI Standard: 83+ (Color tolerance = ±200) ELECTRICAL LUMENS & EFFICACY 3.5W IS ASHRAE COMPLIANT AND IS SUITABLE FOR TITLE 24 LUMEN MAINTENANCE LINE VOLTAGE DIMMING 4' - (4000K, 83CRI) WATTAGE OPTICS LUMENS EFFICACY 75,000 hrs L70 1535 2451 4249 INTEGRAL POWER SUPPLY, 120V OR 277V 0-10V, DMX, LUTRON ECO-SYSTEM 113.7 lm/w 108.0 lm/w 96.1 lm/w TOTAL POWER CONSUMPTION FIXTURE WATTAGE TOTAL POWER CONSUMPTION CONTROL 0-10V & DMX DIMMING DMX Dimming (Delivered Output Ratio =.75) PHYSICAL CERTIFICATION DIMENSIONS (HEIGHT X WIDTH) HOUSING LENS OPERATING TEMPERATURES RoHS COMPLIANT WITH FLAT LENS: 3/4" X 1-5/8" WITH WHITE DIRECT VIEW DOME LENS: 1-3/8" X 1-5/8" Aluminum extrusion with molded end caps, powder-coated finish, White Flat Clear Acrylic Lens is standard Optional "Flat White Acrylic Lens" is available with optics only. Allows for smooth light distribution, but does not remove diode images. Optional "White Direct View Lens" (DV) for direct view applications is available with optics only. The Direct View Lens option creates a crisp white illuminattion and eliminates all diode images. -25 C to 40 C ETL Listed for Dry Location WARRANTY 5 Year Limited Warranty 5 Year Limited All PILOT products are tested to IES LM-79 standards Page 1 of 5
PLC Prefix PLC Pilot Cove Series Wattage Watts /Ft LED Color/CCT 3.5 27K ORDERING INFORMATION Optics Mounting Length = X 3.5W IS ASHRAE COMPLIANT 3.5W IS SUITABLE FOR TITLE 24 6 27K 11 27K = X = X HM = Hinge FM = Fixed 24" 36" 48" Voltage/ Wiring Method ACV1 = 120V feed thru wiring for end-to-end fixture connection ACV2 = 277V feed thru wiring for end-to-end fixture connection Load not to exceed 16 amps See cable requirements below Control Options (Dimming) NO = No Dimming DIM = 0-10V Dimming DMXDM = DMX Dimming Resolution per power supply LES-LDE1 = Lutron Hi-Lume 1% EcoSystem dimming with Soft-on, Fade-to-Black (Available with 24" - 96" fixtures only) LES-L3D = Lutron Hi-Lume 1% EcoSystem /3--Wire dimming with Soft-on, Fade-to-Black (Available with 24" - 96" fixtures only) Finish W = Semi-Gloss White Contact factory for additional finishes Options WL = Flat diffusing lens (Available with optics only) DV = Direct view dome lens for direct view applications (Available with optics only) Contact factory for MRI applications INTERIOR LEADER CABLES An AC Leader Cable is required with each fixture run for connection from first fixture to the j-box. ACL-5-W 5 WHITE LEADER CABLE - For line voltage only, Used for connection to the start of each run. INTERIOR JUMPER CABLES ACV WIRING METHOD allows for end-to-end fixture connection without additional AC jumpers. If fixtures are not mounted in an end-to-end continuous manner, AC jumpers are required. CATALOG # DESCRIPTION CATALOG # DESCRIPTION ACJ-2-W 2 WHITE JUMPER CABLE - For line voltage only ACJ-10-W 10 WHITE JUMPER CABLE - For line voltage only ACJ-5-W 5 WHITE JUMPER CABLE - For line voltage only ACJ-25-W 25 WHITE JUMPER CABLE - For line voltage only Page 2 of 5
HM - HINGE MOUNT DIM 'A' FLAT CLEAR LENS IS STANDARD WITH HINGE MOUNT DIRECT VIEW LENS IS OPTIONAL 2-1/8" 2-1/8" DIM 'C' 3-1/8" 2-5/8" 3-7/8" 3-3/8" BOTTOM VIEW 100 2-3/8" 4-3/8" FIXTURE ROTATION DIM 'B' DIM 'D' DIM 'E' 2x clearance holes for #8 mounting hardware (by others, per hinge) MOUNTING BRACKET DETAIL 1-1/4" 2X Ø 1/8" FOR #6 MOUNTING FASTENERS (BY OTHERS) Static White, Dimming, RGBWWA, Dim DMX & RGB+W DIM -A- DIM -B- DIM -C- DIM -D- DIM -E- 24" 24-1/2" 4" 16-1/2" 1-1/4" to 6-1/4"< 4" to 14" 36" 36-1/2" 10" 16-1/2" 1-1/4" to 6-1/4"< 4" to 14" 48" 48-1/2" 16" 16-1/2" 1-1/4" to 6-1/4"< 4" to 14" Page 3 of 5
FM - FIXED MOUNT DIM "B" DIM "B" / 2 C L FLAT CLEAR LENS IS STANDARD 2 3/4" 2 5/8" 2 1/8" Ø1 1/8" Ø 1.25 THRU HOLE RECOMENDED DIM "A" 16 3/8" 3/8" DIM "B" DIM "B" / 2 C L DIRECT VIEW LENS IS OPTIONAL 2 1/8" DIM "A" 3 3/8" 3 3/8" Ø1 1/8" Ø 1.25 THRU HOLE RECOMENDED 16 3/8" 3/8" 2X Ø.188 THRU FOR #6 MOUNTING FASTENERS (BY OTHERS) 2 5/8" 1/2" DIM "A" DIM "B" 24" 24-1/2" 6" TO 15" 36" 36-1/2" 6" TO 15" 48" 48-1/2" 6" TO 15" Page 4 of 5
MAXIMUM FIXTURE RUN LENGTHS 16 AMP, 120V CIRCUIT, STATIC COLORS AND RGB APPLICATIONS 32 FIXTURES @ 15 WATTS PER FOOT 16 AMP, 277V CIRCUIT, STATIC COLORS AND RGB APPLICATIONS 32 FIXTURES @ 15 WATTS PER FOOT 32 FIXTURES MAX PER OUTPUT. 800' MAX. TOTAL CABLE LENGTH. WIRING DETAILS TYPICAL WHITE AND 0-10 ACV WIRING CONCEPT ACV WARNING: REMOVAL OF END CAP ON THIS FIXTURE VOIDS ALL WARRANTIES! CAPPED END OR INT 120-277 AC LINE ( BY OTHERS ) BY OTHERS, 24 AWG DATA PAIR IF APPLICABLE 0-10 SOURCE, IF APPLICABLE ( BY OTHERS ) ACL REQUIRED ( 4FT LEAD PROVIDED TYP. ) J-BOX BY OTHERS ( TYP. ) From Previous To From Previous Line Black Ground Green Neutral White To Next To Data In 0-10V DIMMING Line Black Ground Green Neutral White To Next Data + Yellow Data - Blue NON DIMMING 5/1/15 CAUTION: THIS IS AN ELECTRONIC DEVICE. CARE MUST BE TAKEN DURING STORAGE AND HANDLING. STORE IN CLEAN, COOL, AND DRY LOCATION. ELECTROSTATIC DISCHARGE (ESD) CAN HARM THIS PRODUCT. AVOID STATIC DISCHARGE WHILE HANDLING THIS PRODUCT. WARNING: ALL ELECTRICAL CONNECTIONS TO BE MADE BY A LICENSED ELECTRICIAN. WARNING: MAKE SURE ALL ELECTRICAL POWER IS OFF WHEN INSTALLING LUMINAIRES. NOTICE: SECONDARY CAUTION: INSIGHT LIGHTING IS NOT RESPONSIBLE FOR THE STRUCTURAL INTEGRITY CONNECTIONS SHALL BE MADE IN ACCORDANCE OF THE BUILDING TO SUPPORT THE LUMINAIRE. ADDITIONAL BACKING WITH NEC ARTICLE 725. MAY BE REQUIRED. 1 OF 1 Page 5 of 5