Automation Interface Requirements for J602 Basic I/O Interface of a DPC 4 Welding System

Similar documents
Sentinel I24 Digital Input and Output Configuration

This document describes the different ways to allow the automation system to close a gpi contact from the transmission list.

NX APPLICATION NOTE Led Guided Assembly Connector Pinning with Continuity

ENGR 1000, Introduction to Engineering Design

FOREST SHUTTLE S / L / M RECEIVER

TDEPD. Field-Programmable Pressure Switch/Transducer with Integrated LED Display. Programming Sequence Manual

Vorne Industries. 87/719 Analog Input Module User's Manual Industrial Drive Itasca, IL (630) Telefax (630)

013-RD

MAXTECH, Inc. BRC-1000 Series. C-Band Redundant LNB Systems. Technology for Communications. System Block Diagrams

FOM-9010, FOM-9011 and FOM-9012

ENGR 1000, Introduction to Engineering Design

ORM0022 EHPC210 Universal Controller Operation Manual Revision 1. EHPC210 Universal Controller. Operation Manual

(((((((((<<<<<<<<<<<<<<<<<<<<Q

SignalTap Plus System Analyzer

CARLO GAVAZZI Automation Components

Data Acquisition Using LabVIEW

Standard RS232 RS ma

Operating Instructions

Installing the FOREST SHUTTLE S / L

DM1624, DM1612, DM812

LAUREL ELECTRONICS, INC.

PRODUCT MANUAL. Product Description. Waterproof 4 Channel DMX to RGB-W LED Controller

(Cat. No IJ, -IK)

Instruction Manual. Series 3000 Model R-165A. Audio/Video IF/RF Relay Panel. CATV Switching and Control

X-Band Redundant LNB Systems

Ku-Band Redundant LNB Systems

C-Band Redundant LNB Systems

INSTRUCTION MANUAL. J800 Weld Controller. 3/25/2018 Revision

True Color Sensor with Analog and Digital Outputs

Yaesu FT-950 and FT-450D with KPA/KAT500 Power Combo

Advantys STB DATA SHEET. Advantys STB Output Module. Description. Features

Using SignalTap II in the Quartus II Software

TECHNICAL UPDATES. from by TeeJet Technologies. BoomPilot Kits Include: - BoomPilot Console - SmartCable - Lighter Adapter - RAM mount.

Special Specification 6083 Video Imaging and Radar Vehicle Detection System

Ku-Band Redundant LNB Systems. 1:1 System RF IN (WR75) TEST IN -40 db OFFLINE IN CONTROLLER. 1:2 System POL 1 IN (WR75) TEST IN -40 db POL 2 IN

16-BIT LOAD CELL/DUAL STATUS INPUT

In-process inspection: Inspector technology and concept

Model 4455 ASI Serial Digital Protection Switch Data Pack

DATA SHEET. The Advantys model STBDAI5260 Digital Input Module provides 2 isolated discrete input points that operate on a 115 VAC power source.

Foreword: The purpose of this document is to describe how to install and configure Neets 4 relay box

Migatronic Tig - Plasma Welding machine /Fanuc robot Interface. Adapted for RJ3 Controller: Adapted for RJ2 Controller:

TransitHound Cellphone Detector User Manual Version 1.3

C200H-AD002/DA002 Analog I/O Units Operation Guide

ProVu PD6000 Process Meter

Digital Feedback Eliminator

ACT 10 Digital Keypad Operating & Installation Instructions This manual is found at

Exercise 4-2. Counting of Actuator Cycles EXERCISE OBJECTIVE & & &

Connecting the Elecraft Power Combo to the Kenwood TS-2000 series Transceiver

SPX-5600 Series. Operations Manual. Suprex Reader Extender - RF Wireless Interface SPX-5600MAN. Page 1 of 20

DVI CAT-5 MS EXTREME EXT-DVI-CAT5-MS USER MANUAL.

Figure 1: Standard 906 Sensor and Pulser Disc. Figure 2: Standard 906 Sensor and Pulser Wrap

CLOCKAUDIO. MR88 Automatic Microphone Mixer. Version 4.2

STR 2000 Series Transceiver Programming Manual (V2) Table of Contents

Quick Reference Manual

SPECIAL SPECIFICATION Video Imaging and Radar Vehicle Detection System

DSIM-GI Installation Guide Revision P

SECU-16. Specifications Power: Input Voltage 9-12V DC or AC Input Current Max 200mA. 8 2-wire inputs, Analog (0 5VDC) or Supervised

Short Manual. ZX2 Short Manual.doc Page 1 of 12

CEDES. Functional description CEDES 7-Segment Double Digit Indicator (CAN) Functional description 7-Segment Double Digit Indicator (CAN)

QUICK START GUIDE FLEXSLICE MODULES

HS-509 VIBRATION TRIP MODULE

Analog Output for the TSI DUSTTRAK Aerosol Monitor Model 8520

WELDING CONTROL UNIT: TE 450 USER MANUAL

Logic Analyzer Auto Run / Stop Channels / trigger / Measuring Tools Axis control panel Status Display

GuardPLC Certified Function Blocks -- Basic Suite

LAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description

PSM-003. Micro Polarization Controller/Scrambler. User Guide

Digital Differential Pressure Gauge Switch 0.1 : 0.5 BAR USER GUIDE

Installation and Operation Manual

210E - 210ECL ECL ECL

Rotary Knife Controller

THE ASTRO LINE SERIES GEMINI 5200 INSTRUCTION MANUAL

AES-402 Automatic Digital Audio Switcher/DA/Digital to Analog Converter

DIVERSITY DVB-T RECEIVER (DDR)

PLASMA MONITOR (PT20 UVVis) USER GUIDE

RS232 settings are internally definable via jumper blocks, to accommodate interfacing with a wide range of control products.

HDRFI Series Tensolite High-Performance Cable & Interconnect Systems. High Density RF Interconnect

High-Definition Scaler. GTV-HIDEFS. User Manual

Intelligent Security and Fire Ltd

SCALE & WEIGHT DISPLAYS

STD-525T PRECISION TIMER

2 CHANNEL RECEIVER DISPLAY POTENTIOMETER COM2 NC2 NO2

MINI MCR-SL-F-UI-NC. Frequency transducers. Data sheet. 1 Description

CG-1 CAMERA-GUARD INSTRUCTION BOOK IB647501

MBUS 10 RS232 TO MBUS LEVEL CONVERTER

Installation. SAPTF33xx-1xx in the Network. Standard Configuration

DX-10 tm Digital Interface User s Guide

AUTOMATIC VIDEO LOSS A/B SWITCH

Special Applications Modules

Specification Type 1.1 Interface

LPX Platform LPX Platform

Wall-/Pipe-Mount Level Indicator

Installation & User s Manual

MICROSENS. Fast Ethernet Switch Modul 4x 10/100Base-TX, 1x 100Base-FX. Description. Features

Gordian. Multifunctional Power Distributor / Conditioner. v1.3

External Hardware Trigger Settings for RICOH Stereo Cameras

System Troubleshooting for

Safety Light Curtains GuardShield

Manual Version Ver 1.0

Security Escort SE3000 Series

Transcription:

- 1 - Automation Interface Requirements for J602 Basic I/O Interface of a DPC 4 Welding System The DPC 4 welding system offers several features that are intended to communicate with automation. These features allow the automation to control and respond to events that occur during the welding process. This document will provide guidelines that will help you interface automation to a DPC welding system per s requirements. Information within this document is intended to supplement the information in the DPC 4 manual (Dukane part # 403-557). Note: Early production models of the DPC IV welding system referred to J602 as the User I/O interface. The functionality of the Basic I/O Interface and the User I/O Interface are identical. Only the name has changed. Topics: The J602 Pin assignments The 200-1203 Basic Interface Cable Status Output Signal Descriptions Status Output Interface Examples System Signal Descriptions System Interface Examples Basic I/O Interface 11101 1

- 2 - J602 User Interface Connector The J602 User Interface connector is the primary communications link between the DPC IV and user automation equipment. This connector provides status signals that can be used to monitor DPC weld data analysis results as well as timing issues related to the processing of the weld sequence. It also provides the automation with dedicated communication lines that allows the automation to control the beginning and the end of a welding sequence. Pin Number DPC Signal Name DPC Signal Type 1 Power Supply +22 VDC (0.5 amp max) 2 Ground Power Supply Return 3 Bad Part Output 4 Suspect Part (see note #2) Output 5 Good Part Output 6 Ready (see note #1) Output 7 Isolated Output Common Common Pin for Output Signals 8 Automation 9 Automation Stop N/C 10 Automation Stop N/O 11 Hand Probe Press Inhibit 12 Common Common Pin for Signals 13 Ground Power Supply Return 14 15 Ground Detect Note #1: This input can be reconfigured in the DPC IV menu choices to activate during the following weld sequence event: In Cycle Sonics On In Hold Note #2: This input can be reconfigured in the DPC IV menu choices to activate during the following weld sequence event: Network Active Sonics On Note: Please refer to the Hardware Setup section of the DPC IV manual for details on reconfiguring pin 4 or pin 6 to the required status output signal. 22102 2

- 3 - Pin # Conductor Color 1 Red 2 Black 3 Blue / Black 4 Green / White 5 Blue / White 6 Red / Black 7 White / Black 8 White 9 Orange 10 Blue 11 Orange / Black 12 Red / White 13 Green Black 14 Black / White 15 Green Part Number Length 200-1203 10 FT 200-1203-15 15 FT 200-1203-20 20 FT 200-1203-25 25 FT 200-1203-30 30 FT Status Output signals for the J602 Connector: There are four status output signals available on the J602 connector. Each of these outputs are driven by a solid state relay that creates a switch closure between the specified output pin and the Output Common pin. These pins can be configured within the DPC software menus to provide a signal that accommodates the requirements of most automation interface equipment. The available configurations for these output signals are: Active High Outputs Active Low Outputs - Maintained Outputs - Pulsed Outputs - This setting will produce a closed switch condition between the specified output pin and the Output Common pin when the output signal is activated. (Factory default setting) This setting will produce an open switch condition between the specified output pin and the Output Common pin when the output signal is activated. This setting will produce an output signal that is maintained from the completion of a welding cycle until the beginning of the next welding cycle activation. (Factory default setting) This setting will produce an output signal that is pulsed a single time for 100 ms as the end of the welding cycle. Note: Please refer to the Hardware menu section of the DPC IV manual for further information on these features. 33103 3

- 4 - Status Output Signal Descriptions: Bad Part Output Good Part Output - Suspect Part Output - (J602 pin 3) This status output will activate when the data acquired during the welding sequence exceeds one of the user defined boundaries within the Bad Part Limits portion of the user setup. Please refer to the Process Limits section of the DPC IV manual for further details on selecting and setting up a Bad Part Limit window. (J602 pin 5) This status output will activate when the data acquired during the welding sequence does not exceed any of the user defined boundaries within the Bad Part Limits portion of the user setup. Please refer to the Process Limits section of the DPC IV manual for further details on selecting and setting up a Bad Part Limit window. (J602 pin 4) This status output will activate when the data acquired during the welding sequence exceeds one of the user defined boundaries within the Suspect Part Limits portion of the user setup. Please refer to the Process Limits section of the DPC IV manual for further details on selecting and setting up a Suspect Part Limit window. In Cycle (J602 pin 4 redefined) - This status output will activate when the welding cycle begins. If the status outputs have been set for maintained, In Cycle will deactivate when the Hold portion of the welding cycle has completed. Please refer to the Hardware Setup section of the DCP IV manual for further details on redefining J602 pin 4. Sonics On (J602 pin 4 redefined) This status output will activate when the DPC produces the ultrasound welding signal that creates motion in the transducer stack assembly. Activation of this signal will occur during the Weld, Scrub, and Afterburst portions of the weld cycle. Please refer to the Hardware Setup section of the DCP IV manual for further details on redefining J602 pin 4. In Hold (J602 pin 4 redefined) This status output will activate when the DPC is processing the Hold portion of the welding cycle. Please refer to the Hardware Setup section of the DCP IV manual for further details on redefining J602 pin 4. Ready Output - (J602 pin 6) This status output will activate at the completion of the Hold portion of the welding sequence. It should be noted that the activation of the Afterburst feature and the return of the pneumatic press to the home position will occur after the activation of the Ready Output status signal. Please refer to the Process Control section of the DPC IV manual for further information on the activation and use of the Afterburst feature. In addition please refer to the Hardware Setup section of the DCP IV manual for further details on redefining J602 pin 6. Network Active (J602 pin 6 redefined) This status output will activate when the DPC is an active node on a DPC network. Please refer to the Network section of the DPC IV manual for further details on setting up a DPC network. Please refer to the Hardware Setup section of the DCP IV manual for further details on redefining J602 pin 6. Sonics On (J602 pin 6 redefined) This status output will activate when the DPC produces the ultrasound welding signal that creates motion in the transducer stack assembly.. Please refer to the Hardware Setup section of the DCP IV manual for further details on redefining J602 pin 6. 44104 4

- 5 - The DPC status output pins can be configured to adapt to several types of automated devices. The ratings for the DPC Status output pins are: Maximum Voltage Rating = +24 VDC Maximum Current Rating = 100 ma Status Output Interface Examples: DPC IV + 24 VDC Bad Part 3 Suspect Part 4 Good Part 5 Ready Output Common 6 7 J602 PLC 200-1203 Cable DPC IV status output configuration for use with a PLC requiring sinking inputs. 55105 5

- 6 - DPC IV Bad Part 3 Suspect Part 4 Good Part 5 Ready 6 7 + 22 VDC Output Common Power Supply 1 Ground 2 J602 PLC 200-1203 Cable DPC IV status output configuration for use with a PLC requiring sourced inputs. 66106 6

- 7 - DPC IV Bad Part Suspect Part 3 4 Customer Customer Good Part Ready 5 6 7 Customer Customer + 22 VDC Output Common Power Supply 1 Ground 2 J602 200-1203 Cable DPC IV status output configuration for use when either isolation is required or the customer device exceeds the maximum ratings of the DPC outputs. 77107 7

- 8 - System signals for the J602 Connector: There are four system input signals available on the J602 connector. Each of these inputs are configured as sinking inputs ( Do not apply voltage to the J602 inputs). Automation - (J602 pin 8) This system input signal is activated by an external dry contact closure to the DPC Ground pin on J602 pin2). The minimum duration for the activation of this input is 100 ms. The maximum duration of this input is determined by the duration of the weld cycle. This input should be deactivated before the end of the weld cycle to avoid an error condition (Associated Error: # 212 Auto Active at Cycle Start). Please refer to the Initiate Mode section of the DPC IV manual for details on the activation and use of the Auto Initiate mode. Automation Stop N/O- (J602 pin 9) This system input signal is activated by an external dry contact closure to the DPC Ground pin on J602 pin2). The minimum duration for the activation of this input is 100 ms. Activation of this input will end the welding cycle and deactivate all valves in the press. This system response will continue until the contact closure to the DPC ground is removed. Weld cycles that have been stopped due to the activation of this input will not be counted in the part count value displayed on the DPC. Please refer to the Initiate Mode section of the DPC IV manual for details on the activation and use of the Automation Stop mode (Auto Abort). Automation Stop N/C- (J602 pin 10) This system input signal is activated by an removing an external dry contact closure to the DPC Ground pin on J602 pin2). The minimum duration for the activation of this input is 100 ms. Activation of this input will end the welding cycle and deactivate all valves in the press. This system response will continue until the contact closure to the DPC ground is replaced. Weld cycles that have been stopped due to the activation of this input will not be counted in the part count value displayed on the DPC. Please refer to the Initiate Mode section of the DPC IV manual for details on the activation and use of the Automation Stop mode (Auto Abort). Hand Probe Press Inhibit - (J602 pin 11) This system input is activated by an external dry contact closure to the DPC Ground pin on J602 pin2). The minimum duration for the activation of this input is 100 ms. Activation of this input is intended to configure the DPC for a probe system functionality. It will deactivate all valves for the press during a welding cycle. This system response will continue until the contact closure to the DPC ground is removed. 88108 8

- 9 - The DPC system inputs are configured for a dry contact closure activation. The following connection diagram indicates how to interface automation to the system inputs. System Interface Examples: PLC 200-1203 Cable + 24 VDC 8 Auto Initiate 9 Automation Stop N/O 10 11 2 Automation Stop N/C Hand Probe Press Inhibit Output Common J602 DPC IV DPC IV system input configuration for use when customer equipment provides contact closure signals with not voltage. 99109 9

- 10 - PLC + 24 VDC 200-1203 Cable + 24 VDC DPC IV 8 Auto Initiate 9 Automation Stop N/O 10 11 Automation Stop N/C 2 Hand Probe Press Inhibit Output Common J602 DPC IV system input configuration for use when customer equipment sources voltage to the DPC inputs. 10101010 10