Monash University. Communications Cabling Manual. (Sites running legacy PABXs)

Similar documents
UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

SECTION 7 -- CROSS-CONNECT SYSTEMS

Cable Installation Tips

Cable Installation Tips

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION

Target Interface / Construction Compliance Inspection Checklist

Follow The Leader In Shielded Technology

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus

African Development Bank Group

Enterprise Networks. Comms Room and Backbone. in DETAIL

Connectix Cabling Systems

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008

Compact Module. Category 6 FTP Cabling System

21.00 Communication & Data Services

1.0 GENERAL. 1.2 SUMMARY.1 Section Includes:

SPECIAL SPECIFICATION 8540 Telecommunication Cable

SECTION COMMUNICATIONS HORIZONTAL CABLING

Magic Patch Patch Leads & Accessories

Preparing a home for TransACT fibre-to-the-premise (FTTP) services

HighBand 25. TrueNet Category 6 Solutions

CABLING STANDARDS FOR

CATEGORY 6 CABLING SOLUTIONS

SPECIAL SPECIFICATION 6559 Telecommunication Cable

CAT6Plus System. Brand-Rex Limited

Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab*

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

Request for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE)

What really changes with Category 6

B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines.

btnet new products Modular and preloaded patch panels btnet

Best Friends General Trading FZE

Structured Cabling Introduction & Installation Guide

August " BLANK PATCH PANEL FOR STP KEYSTONE JACKS. 19" PATCH PANEL - 24x STP CAT6A PORTS 19" BLANK PATCH PANEL FOR STP KEYSTONE JACKS

A. All communications equipment rooms shall be installed in a neat and workmanlike manner.

RCIT Cable Certification Testing Revised 10/2017

جامعة مؤتة العطاءات املركزية توريد وتركيب وتشغيل أجهزة شبكات/كلية الزراعة. Central Tenders Mu tah University

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

CATEGORY 6A CABLING SOLUTIONS

APPENDIX A Verify All Part Numbers (Partial List of Approved Products)

A guide to Woolworths Limited additional requirements. for the testing of twisted pair and fibre installation.

CATEGORY 6A CABLING SOLUTIONS

SMART CLASSix 24/48 UTP Patch Panels -

Preferred ordering guide for NETCONNECT

UNM IT/Telecommunications Guide Specification Labeling 11/07/

Information Technology Services DESIGN AND INSTALLATION STANDARDS

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification

HI-DEX PRODUCT SET DATASHEET

MT-RJ SECURE Product Expansion Now 10 Variants of the MT-RJ SECURE Products

Brown University. Communications Standard Parts List

blackbox.com/connect The smart choice when price matters most. Need help? Talk to a Black Box cable expert 24/7 at

Connected Solutions. April $ Post, 19 Rack ELERK1FR BK

FTTH & FITH. Discreet optical fiber solutions from the network connection point to the set-top box.

STRUCTURED CABLE SYSTEM (SCS)

HELLERMANNTYTON DESCRIPTION DIMENSIONS PKG. PART NO. (HXWXD) QTY. RE18 Residential Enclosure Base: 18 H x 14.1 W x 4 D 1 Cover: 19.5 H x 15.

Section Communications Optical Fiber Backbone Cabling

Connectivity accessories by Nestor Cables

Gigabit Multi-mode SX to Single Mode LX Converter. User s Manual NGF-728 Series. Warning COPYRIGHT

LEGRAND CABLING SYSTEM 2 PERFORMANCE FROM TECHNICAL ROOM TO WORKSTATION

CATEGORY 5e CABLING SOLUTIONS

Peak Atlas IT. RJ45 Network Cable Analyser Model UTP05. Designed and manufactured with pride in the UK. User Guide

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project

STRUCTURED CABLING SYSTEMS (SCS)

CONNECT TO VALUE THE SMART CHOICE WHEN PRICE MATTERS MOST BLACK-BOX.EU/CONNECT

SECTION COMMUNICATIONS HORIZONTAL CABLING

BLACK-BOX.EU/CONNECT

City of Winter Springs, FL

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Robert Burén. Product Manager. Nexans Cabling Solutions. 10G Solutions

SPECIAL SPECIFICATION :1 Video (De) Mux with Data Channel

Standard Specification Data Communications Installations

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

Request for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling

Optimax Field Installable Connectors and Installation Tool Kits

Special Specification 6242 Special Fiber Optic Cable

How to Specify MTP Pre-terminated Optical Cabling. January White Paper. Published

QuickNet Copper Cabling in the Data Center

Copper Solution Contents Cabinets Fiber Optic Solution

GUXT. Mini-Breakout Cables (Distribution) Universal Indoor/ Outdoor A/I-VQ(ZN)BH Improved Rodent Protection. Ordering Information.

Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED.

CAT6 Cable Tester. Operating Manual. Part No TRIAX - your ultimate connection

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project

Michigan State University Construction Standards EXTERIOR FIBER OPTIC CABLE SYSTEM PAGE

ISS New Audio & Visual installations Design and Physical install guidelines v1.5

LAN / NETWORKING PRODUCTS

Product Line Reference Guide

Lab - Build and Test Network Cables

User Guide FA

Product Range Nexans Cabling Systems

Fiber Optics Redefined

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT

PREMIUM 5e F/UTP PRODUCTS

High Speed Data Connector (HSSDC) For 100 MBit/Sec Token Ring. John L. Hill AMP Incorporated July, 1998

SECTION INTERCOMMUNICATIONS AND PROGRAM SYSTEMS

AT&T January, 2012 Revised December, 2018 TABLE OF CONTENTS SECTION 1--INTRODUCTION...1-1

CUSTOM-LENGTH PATCH CABLES CUT-TO-LENGTH BULK FIBER PRE-TERMINATED FIBER MULTI-COLORED FIBER

Transcription:

Monash University Communications Cabling Manual (Sites running legacy PABXs) Communications & Networks Information Technology Services Monash University Monash Cabling Specifications (PABX sites)doc Page 1 of 15

Table of Contents 1 REVISION HISTORY 3 2 MINIMUM CABLING REQUIREMENTS 4 3 GENERAL SPECIFICATIONS CHECKLIST4 4 DATA CABLING6 5 BUILDINGS7 6 CABLES ENTERING A BUILDING7 7 RISER BACKBONE CABLES (UPLINKS) 7 8 CABLING IN CORRIDORS 8 9 MODULINE DUCTING IN OFFICES 8 10 STAFF OFFICES8 11 COMPUTER LABORATORIES 8 12 PLANT/MACHINERY ROOMS 9 13 LECTURE THEATRES 9 14 SEMINAR ROOM9 15 LAYOUT OF COMMUNICATIONS/DATA WIRING CUPBOARD 9 16 RACKS 11 17 UPLINKS14 18 MATERIAL SUMMARY14 19 TESTING15 20 CERTIFICATION15 21 DOCUMENTATION15 22 UTP PATCH LEAD COLOUR CODE FOR GIGABIT NETWORK15 Monash Cabling Specifications (PABX sites)doc Page 2 of 15

1 Revision History 1st Draft 26 August 1999 Update 20 February 2002 Update 06 September 2002 Update 25 September 2002 Update 19 June 2003 Update 30 September 2003 Update 10 March 2004 Update 30 August 2005 Update 06 October 2005 Update 01 May 2006 Update 07 June 2006 Update 22 August 2006 Update 17 November 2006 Update 29 November 2007 Update 30 May 2008 Update 03 July 2008 Formatting 03 June 2009 Robert Jamieson Robert Jamieson John Mitchell Tim Nightingale Note: This Manual and the ideas behind it have evolved over time It has not always been fruitful to update all the oldest sections to reflect changes Hence if there is inconsistency between two sections of the Manual, the newest section takes precedence Monash Cabling Specifications (PABX sites)doc Page 3 of 15

The following checklist represents the minimum requirements for the installation of cabling & equipment for telephones and data cabling in any buildings to be constructed or modified at Monash University Campuses These cabling specifications must to be complied with before any cabling is connected to the Monash University Data & Voice Network 2 Minimum cabling requirements A The Telecommunications cabling must meet the ACMA specifications as detailed in The Customer Premises Cabling Manual B The Data Cabling and termination shall be in accordance with Australian Standard, Premises Wiring AS3080 C All cable runs must be continuous and without splices D All skirting ducting shall be Moduline CFC 50150 or equivalent E Where cabling is to be enclosed in a solid wall, the cables should be installed in a conduit to facilitate the addition and or removal of cables in the future 3 General Specifications Checklist A Telephone cable 1 Cable: CAT6 UTP 2 Terminating method: PANDUIT CAT-6 RJ45 (grey) B Data cable 1 Cable: CAT6 - UTP 2 Terminating method: blue colored PANDUIT CAT-6 RJ45 socket with Green/White-1; Green-2; Orange/White-3; Blue-4; Bl/Wht-5; Orange-6; Br/Wht-7; Brown-8; 3 Each data point should have all four pairs assigned and terminated as per AS 3080 C Labeling of cables 1 Telephone & Data plates a On the face plate a unique number indicating for:- Data & Voice The location of cable termination on the Patch Panel ie A3, B24 b Frame records to reflect the same markings Monash Cabling Specifications (PABX sites)doc Page 4 of 15

D Fibre Optic Cable Installations 1 Grade of cable The cable shall conform to AS 3080 1034 2 Labeling Name of the Rack & location within the rack at other end eg <campus>-<building>-<room>-<rack number> CLAY-28-202-RK1 A1-A12mm, A13-A18sm 3 Terminations SC duplex connectors (SC-D) are to be used [AS 3080 94] Terminations to be housed in an approved enclosure A generous surplus of the Fibre cable is to be coiled up at the termination sites (minimum diameter of coil 600 mm) A five meter surplus is suggested Fibre to the desktop is to terminate on SC duplex connectors 4 Colour code of Terminations Panels 625 Micron Multimode Black OM3 50 Micron Multimode Green Single Mode Yellow All single mode O/F patch cords should be yellow 5 Components List Items Brand/Part No 36 Core Enclosure AFC (WBS27106-MU) OM3 50/125 6mm/6sm Tight Buffered Belden,General, Pirelli Composite Fibre OM3 50/125 6mm/6sm Loose Tube Belden,General, Pirelli Composite Fibre OM3 50/125 12mm/12sm Loose Tube Belden,General, Pirelli Composite Fibre OM3 50/125 24mm/24sm Loose Tube Belden,General, Pirelli Composite Fibre Patch Leads Andersons, AFC, Namlee Organiser for 36 Core Enclosure Organiser for 72 Core Enclosure Fibre splice Cassette Panduit CMPHF1 Krone 2RU Fibernet Types/Sizes of Cable to use Use Between Racks within the same building which are greater then 90 metres apart Incoming feed to small Building <20 Data Points Incoming feed to medium Building <200 Data Points Incoming feed to large building or Core network Location >200 Data Points Minimum Cable to Use OM3 50/125 12mm/12sm 6SM/6MM OM3 50/125 Loose Tube Composite Fibre 12SM/12MM OM3 50/125 Loose Tube Composite Fibre 24SM/24MM OM3 50/125 Loose Tube Composite Fibre Monash Cabling Specifications (PABX sites)doc Page 5 of 15

Figure 1: 36 Core Fibre Enclosure AFC Lightpaths Model AFC WBS27106-MU 4 Data Cabling A Unshielded Twisted Pair (UTP for 10BaseT, 100BaseX, ATM, 100VG) 1 Grade of cable Approved UTP CAT-6 cable 2 Terminations Internal cabling: segment of UTP Ethernet may not exceed 90 metres under any circumstances Approved UTP CAT-6 cable 3 Labeling As per 3 c B Coaxial cable Ethernet (10Base2) 1 Grade of cable Belden 9907 to be used for Coaxial cable 2 Terminations Use high quality 50 ohm crimp type BNC plugs eg HarTec type C53138 Total length of 10Base2 Ethernet may not exceed 184 metres under any circumstances; it is preferable to be less than 100 metres 3 Labeling As per 3 c Monash Cabling Specifications (PABX sites)doc Page 6 of 15

C Video Security Cable 1 Labeling As per 3 c 2 Terminations 75 ohm BNC crimp plugs 3 Internal Cabling Cable shall be installed in ducting or conduit as appropriate 4 Cable type The cable should be RG59/U 75 Ohm cable Commercial equivalents are acceptable 5 Buildings A Building to Building 1 Cabling connections between buildings shall be no less than composite fibre with 12 cores of multi-mode and 12 cores of single-mode Loose tube construction, eg OM3 50/125 12mm/12sm 2 The points of termination of the Fibre cable shall be made at a designated location and shall use the standard Fibre termination with SC style duplex (SC-D) connectors Enclosures for fibres are to be as per Material List 3 Fibre is to be laid in a white PVC conduit of not less than 50 mm internal diameter A draw wire is always to be retained in these conduits 4 Pits must be provided where the conduit changes direction by 30 degrees or more Pits are also to be provided at intervals of no more than 50 metres 5 The path of the conduit shall be completely documented and lodged with ITS and the Buildings and Premises Branch 6 Cables Entering a Building A The point of entry should be inaccessible to the public Where any such entry is at external ground level, it shall be appropriately protected 7 Riser Backbone cables (UPLINKS) A Supply and install six x single CAT-6 uplinks and OM3 50/125 12mm/12sm fibre cable to every floor distribution frame/rack, from the Main Building Rack Location indicated on drawings provided B All links must be clearly marked on both ends, including the link number and rack ID Eg: U/L 7-12 to CLAY-28-202-RK1 C Labeling See 3 c Monash Cabling Specifications (PABX sites)doc Page 7 of 15

8 Cabling in Corridors A All cables in corridors should be located on a tray that holds only telephone and data cables Data and telephone cable should be no closer than 100 mm from any power cabling distribution tray, as per AS 3084 B All cables not located on a cable tray shall be secured with catenary wires and may never foul ceiling tiles or other plant located in the ceiling space 9 Moduline ducting in offices A The preferred product is Moduline CFC50150 The cover panels shall be fixed in place with the maker s recommended hardware B Cabling Distribution to Offices from Corridors: The maximum length of UTP cables from the telecommunication rack to the outlet shall be 90 metres C The Moduline ducting placed around the exterior walls for office access must have entry points available, a maximum of ten cables (five data, five voice) in any section of duct is suggested to provide the shortest path and reduce congestion within the ducting D Moduline cover plates are not to be obscured or fouled by partition walls etc 10 Staff Offices A All Ethernet cables shall be UTP CAT-6 and shall be run in conjunction with the telephone cable B Every desk/workstation shall have a minimum of two data UTP cable and one telephone cable Open plan office environments shall have a minimum of two data UTP cables and one telephone UTP cable run to each anticipated position of desks or four for every 10m 2 C Printer locations should have a data UTP point D Photocopy rooms should have phone & data points E Power: It is highly recommended that each desk/workstation has two double GPO s for the exclusive use of IT equipment or one double GPO per data point 11 Computer Laboratories A A CAT6 UTP cable from each workstation is to be run to the appropriate communications wiring rack B All labs shall use Moduline ducting for Power and Data connections Monash Cabling Specifications (PABX sites)doc Page 8 of 15

12 Plant/Machinery Rooms A A minimum of one run of UTP Data and telephone wire shall be run between every plant/machinery room and the nearest appropriate Comms/Data Rack If a plant room be located on the roof level, it is acceptable to run the line to the uppermost level rack 13 Lecture Theatres Teleteaching Lecture Theatre A The front Comms/Data/Equipment Rack 4 x Basic Rate ISDN Points 2 x Telephone Points 2 x Data Points B Rear Control Room 2 x Telephone Points 2 x Data Points Standard Lecture Theatre A The front Comms/Data access Point 2 x Telephone Points 2 x Data Points B Rear Control Room 2 x Telephone Points 2 x Data Points 14 Seminar Room A Shall be wired with a minimum two data and one voice outlet 15 Layout of communications/data wiring cupboard A There should be one wiring rack [FD] for each floor They should be large enough to contain all termination hardware for telephone/data wiring, and computer networking equipment B One floor (usually ground) should be designated for a building distribution [BD] for a building switch and termination of inter-building fibres C Required minimum size for ground floor 2400mm wide, 1000mm deep Other floors 1500mm wide, 900mm deep Must extend from floor to ceiling with access to the ceiling space for that floor D The riser should be either one and the same or adjacent with easy access for cables E Two dedicated circuits with two standard double GPOs per circuit should be Monash Cabling Specifications (PABX sites)doc Page 9 of 15

included in each rack/cupboard F The telecommunications/data racks/cupboards shall be keyed alike with tamper proof latches G They shall be keyed differently from electrical cupboards H Every cupboard shall have a 20W fluorescent light fitted, unless a suitable light is located directly outside I Every communications cupboard shall be fitted with a minimum one 600 pair Krone profil frame (figs 2, 3 & 4) J The top and bottom entry points should be at the extreme left-hand side of the cupboard The entry ports should be sealed against fire with fire resistant pillows; they should not be sealed with cement Burndy APT cable tray of 300mm width to be secured to the left-hand back wall of the cupboard K All data cable including riser cables should be terminated on a RJ45 patch panel L Patch panels and computer equipment should be mounted in correctly sized racks M General power outlet (GPO) to be fitted at the lower left-hand corner Cable tray 100mm in width to be attached to the rear wall as shown in figs 2, 3 & 4; 600 pair Krone Profil Mount frames to be attached as shown in figs 2, 3 & 4 N All types of communication and data rack or frame, should be securely and rigidly mounted to it designated location To ensure frame stability the fitting of support bars and braces is recommended O Where there are two or more network racks on one level/floor, the data port identification shall be unique between racks P Do not use the letters O and I for data port identification Monash Cabling Specifications (PABX sites)doc Page 10 of 15

16 Racks Racks sizes A The racks should be Modempak lockable glass front door All racks should be keyed alike with "Modempak Monash Locks" i Supply and install two double GPOs into the bottom of each rack; Each GPO should be connected to a separate circuit breaker on the switchboard The rack itself should have a suitable protective earth connection B Cable tray size, minimum 200mm wide, should be provided to secure all incoming data cables C The customer data cables shall be terminated on a 48 way CAT-6 UTP RJ-45 Panduit patch panels, with a patch cord minder below each patch panel Customer voice cables shall be terminated on Krone modules Monash Cabling Specifications (PABX sites)doc Page 11 of 15

D Rack Layout B U IL D IN G R a ck Incom ing Fib re F ibreu p link s U T P U plinks K rone (P A B X ) patch p an el R J (d ata) F loo r O utlets p atch panels 210 0 200 0 130 0 gro wth B D S 1 B D S 2 F ES 1 F ES 2 grow th P LF & 2 40 V D ist U P S 300 200 100 0 Figure 2: BUILDING Distribution single equipment rack layout Monash Cabling Specifications (PABX sites)doc Page 12 of 15

F L O O R R ac k Fib re U T P U p link s U p link s K ro ne (P AB X ) patch pa nel R J (d ata) patch panel 21 00 20 00 13 00 g ro w th FE S1 FE S2 FE S3 g ro w th P LF & 24 0 V D ist U P S 30 0 20 0 10 0 0 Figure 3: FLOOR Distribution - single equipment rack layout B U IL D IN G R ac k 1 2R U C ab le M g Inco ming Fib re 21 00 20 00 B U IL D IN G R a ck 2 2 R U C able M g Switches 21 00 20 00 F ib re U plinks U T P U p links K rone (P A B X ) p atch panel 13 00 B D S 1 S tack 1 grow th 13 00 U T P Flo or O utlets B D S 2 S tack 2 G ro wth 30 0 grow th 30 0 20 0 10 0 0 P LF & 2 4 0V D ist U P S 20 0 10 0 0 Figure 4: FLOOR Distribution - equipment rack layout using two racks Monash Cabling Specifications (PABX sites)doc Page 13 of 15

E Rack Sizing Table Use Data points on floor Minimum rack size Model Ground Floor >120 800mm W, 45RU x 800mm D Modempak 11412095MMU Ground Floor <120 800mm W, 45RU x 800mm D x 2 Other Floors >20 800mm W, 45RU x 600mm D minimum Modempak 11414091MMU 17 Uplinks A Supply and install six single CAT-6 uplinks to every floor distribution rack, from the Main Building Rack Location indicated on drawings provided B All links must be clearly marked on both ends, including the floor number and the link number like 2-3 (second floor link number 3) 18 Material Summary Plates RJ45 Panels RJ45 Connectors (Data) - Cat 6 RJ45 Connectors (Comms)- Cat 6 Cable Organizer 800mm W Rack Clipsal 2000 Series (White Preferably) Panduit 48 Port 1RU (CPP48HDWBL) Panduit Smart Jack (Blue) Panduit Smart Jack (Grey) Panduit CMPHF1 Modempak 45RU X 600mm minimum with glass door & Monash Locks Floor Cable Data - Cat 6 Approved Cables covered by Panduit s Certification Plus Warranty Uplink UTP Data - Cat 6 Approved Cables covered by Panduit s Certification Plus Warranty Floor Cable Comms - Cat 6 Approved Cables covered by Panduit s Certification Plus Warranty ADC Patchpanel 50 Port Voice ADC Part No 7022 4 001-50 Communication Modules Krone modules (No6089 1 121-02) Fibre Enclosure (36 Cores) AFC WBS27106-MU Communications Rack Mounts Krone 19" rack mount (No 6450 1 008-00) Fibre Cables Small Building (<20Points)- Composite 6SM/6MM 50micron OM3 Medium Building(<200Points)-Composite 12SM/12MM 50micron OM3 Large Building(>200 Points) -Composite 24SM/12MM 50micron OM3 Monash Cabling Specifications (PABX sites)doc Page 14 of 15

19 Testing A Data Cables: All Data points and uplinks must be tested to CAT-6 specification with a Fluke DSP Cable tester with full detailed and summary test report provided in an electronic format B Communication Cables All terminated pairs to be continuity tested C Fibre All Fibre cores to be tested with DB loss results provided D All test results are to be supplied to the NIS Site Engineering Manager 20 Certification A All telephone, data and fiber optic cable installation should be certified So that the entire system meet the necessary level of performance specified in AS 3080 (clause 7) 21 Documentation A The telephone documentation should be completed as per standard practice It should include information pertaining to the unique identifier on each cable label A main frame (MDF) book shall be used and left within the Riser/Cupboard/Rack B The data documentation requires a floor plan showing the patch panel location for each of the data points and the test results from the Cat 6 testing in electronic format Contractor shall consult with ITS before commencing work to become familiar with ITS Documentation Standards 22 UTP Patch Lead Colour Code for Gigabit Network Colour Blue Red (Straight through) Use In the field: Basic 10/100/1000 Mb Ethernet user service (BDS or FES user) In a computer room: Dedicated 10/100/1000 Mb Ethernet service (BGS host) 1Gig Ethernet uplink (BDS to- FES) Monash Cabling Specifications (PABX sites)doc Page 15 of 15